This document appears to be the technical specifications for a CANARIIS Corporation variable speed booster pump system. The system is designed to provide 400 GPM of water flow at 71 PSIG of pressure, with a minimum suction pressure of 20 PSIG and a maximum of 65 PSIG. The system includes three variable speed pumps, manifolds, and a hydro-pneumatic tank. Standard system features are listed, as well as available options. Details on the control panel, sequence of operation, and available enclosure types are provided. This specification is referenced in the related federal contract opportunity, Solicitation 36C25725B0005 issued by the Department of Veterans Affairs, Veterans Health Administration, VISN 17, to install a new water booster pump system at the VA Hospital in El Paso, TX. The estimated cost of the project is $698,034.76, with a period of performance from 12/31/2024.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

fjj Accepted fjj Rectangle fjj Line fjj Line fjj Typewritten Text

OUTLET

fjj Typewritten Text

INLET

VHAELPMoralA Text Box

SPECIFICATIONS FOR BRAND NAME OR EQUAL

CANARIIS CORPORATION page 2.23 VS* Form FS020 Rev. 12 MAR/2020

UL LISTED PACKAGED PUMPING SYSTEMS

www.canariis.com

VARIABLE SPEED BOOSTER SYSTEM DATA SHEET

JOB NAME VA Hospital DATE 10/18/2023

LOCATION El Paso, TX

ENGINEER

CONTRACTOR

DISTRIBUTOR James, Cooke & Hobson, Inc.

SYSTEM INFORMATION SYSTEM MODEL NO. TM-400-60-3VS

SYSTEM CAPACITY 400 GPM

SYSTEM PRESSURE 71 PSIG

MINIMUM SUCTION PRESSURE 20 PSIG

MAXIMUM SUCTION PRESSURE 65 PSIG

SYSTEM DIFFERENTIAL PRESSURE 51 PSI

SYSTEM POWER 460 VOLTS 3 PHASE 60 HERTZ

PUMP INFORMATION PUMP NO. 1 PUMP NO. 2 PUMP NO. 3

PUMP TYPE MULTISTAGE EQUAL TO #1 EQUAL TO #1

PUMP SIZE CR32-2-1

VARIABLE / CONSTANT SPEED VARIABLE

MOTOR HP / FLA 7-1/2

MOTOR ENCLOSURE TEFC

DESIGN RPM 3500

DUTY POINT GPM 133

TDH 130

PRV OR CHECK VALVE SIZE 2-1/2”

PUMP SHUTOFF PSIG 72

MAX WORKING PRESS PSIG 137

MAX. WORKING PRESSURE IS THE TOTAL OF THE MAXIMUM SUCTION PRESSURE PLUS PUMP SHUT OFF HEAD AT MAX.

SPEED AND MUST NOT EXCEED THE ALLOWABLE WORKING PRESSURE OF THE COMPONENTS.

STANDARD SYSTEM FEATURES SYSTEM OPTIONS

COMPLETELY PREFABRICATED PRV’S IN PLACE OF CHECK VALVES

304L STAINLESS STEEL MANIFOLDS PUMP PRESSURE GAUGES

INDIVIDUAL PUMP ISOLATION VALVES Match Discharge H Dimension (JCH to Provide)

CHECK VALVE ON EACH PUMP

THERMAL PURGE VALVES

SYSTEM AND SUCTION PRESSURE GAUGES

FACTORY TEST

SYSTEM CONSTRUCTION

MANIFOLD SIZE 4" CONNECTIONS GROOVED FLANGED

CONFIGURATION RIGHT HAND LEFT HAND CUSTOM

SYSTEM DIMENSIONS AND DRY WEIGHT L 60 " x W 70 " x H 67 " WT 2500 #

HYDRO-PNEUMATIC TANK TANK LOCATION

MODEL FX300V 80 GALLONS 150# ADJACENT TO SYSTEM

MODEL FX500V 132 GALLONS 150# ON PUMP SKID

MODEL FX750V 198 GALLONS 150# REMOTE MOUNTED

MODEL FXA300 79 GALLONS 125# ASME

MODEL FXA400 106 GALLONS 125# ASME

MODEL FXA500 132 GALLONS 125# ASME FOR UL LISTING TANK ON PUMP SKID MUST BE ASME

MODEL FXA600 158 GALLONS 125# ASME

MODEL FXA800 211 GALLONS 125# ASME TANK CONNECTED PER PAGE

MODEL FXA700 185 GALLONS 200# ASME TANK STORAGE CAPACITY GAL.

Not Included *NOTE: ALSO PAGE 9.60.05 OF I.O.& M. MANUAL page 2.24 VS* CANARIIS CORPORATION MAR/2020 Form FS020 Rev. 10

UL LISTED PACKAGED PUMPING SYSTEMS

www.canariis.com

PUMP OPERATING AND SEQUENCE CONTROLS PUMP SEQUENCE

INTERMITTENT LEAD PUMP OPERATION 0 to 125 GPM PUMP Any One CONTINUOUS RUN LEAD PUMP 125 to 250 GPM PUMPS Any Two SUCTION & DISCHARGE PRESSURE SENSORS 250 to 375 GPM PUMPS All Three FLOW SENSOR(REMOTE MOUNTED) to GPM PUMPS

VARIABLE FREQUENCY DRIVES

MANUFACTURER / MODEL ABB / ACH580 QUANTITY 3

NEMA 1 ENCLOSURE NEMA 12 ENCLOSURE NEMA 3R ENCLOSURE

FULL SPEED ELECTRICAL BYPASS (MANUAL)

STANDARD CONTROL PANEL FEATURES

UL LISTED ENCLOSED INDUSTRIAL CONTROL PANEL

NEMA 1 ENCLOSURE

INDIVIDUAL DISCONNECTS WITH EXTERNAL HANDLES

FUSE BLOCKS WITH FUSES

CONTROL POWER (ON-OFF) SWITCH AND LIGHT

PROGRAMMABLE LOGIC CONTROLLER (PLC) with Touchscreen Display

PUMP RUNNING LIGHTS

H/O/A SELECTOR SWITCHES

115 VOLT FUSED CONTROL CIRCUIT TRANSFORMER

PUMP MINIMUM RUN TIMING

AUTO ALTERNATE EQUAL PUMPS

MOUNTED AND WIRED ON SKID

PUMP OPERATING AND SEQUENCE CONTROLS

PUMP RUNTIME INDICATION

CONTROL PANEL OPTIONS

NEMA 12 ENCLOSURE NEMA 3R ENCLOSURE NEMA 4 ENCLOSURE

LOW SUCTION PRESSURE ALARM AND SHUTDOWN WITH AUTO RESET AND INDICATION

LOW SYSTEM PRESSURE ALARM WITH MANUAL RESET AND INDICATION

HIGH SYSTEM PRESSURE ALARM AND SHUTDOWN WITH MANUAL RESET AND INDICATION

LOW SUCTION LEVEL ALARM AND SHUTDOWN WITH AUTO RESET AND INDICATION – (SIGNAL BY OTHERS)

HIGH SUCTION PRESSURE SHUTDOWN WITH AUTO RESET AND INDICATION

AUDIBLE ALARM WITH SILENCE PUSH BUTTON

24 HOUR TIME CLOCK - ALTERNATE EQUAL PUMPS

7 DAY TIME CLOCK FOR CONTINUOUS SYSTEM OPERATION

FLOW SWITCH TO LIMIT LEAD PUMP ON-OFF CYCLING

REMOTE ALARM PANEL WITH SILENCE PUSH BUTTON AND LIGHT

AUXILIARY RELAY ALARM CONTACTS

AUXILIARY RELAY PUMP STATUS CONTACTS

LOCKABLE ENCLOSURE

LIGHTNING ARRESTER

EMERGENCY POWER ALARM TO PREVENT LAG PUMP(S) OPERATION (SIGNAL BY OTHERS)

EMERGENCY POWER ALARM TO PREVENT SYSTEM OPERATION (SIGNAL BY OTHERS)

NOTES & COMMENTS:

NOTE: ALSO PAGE 9.60.06 & 9.60.07 OF I.O.& M. MANUAL