QA 3.docx

DOCX document 15 KB Posted

Attached to
Base ECity Ultrasonic Testing
Solicitation number
70Z08124QELIZ0013
Issued by

About this file

This document appears to be a set of questions and answers related to a federal solicitation for an ultrasonic thickness inspection of above-ground storage tanks at the USCG Base in Elizabeth City, North Carolina. The key details are:

The Solicitation Number is 70Z08124QELIZ0013 for the "Base ECity Ultrasonic Testing" requirement. The Contractor shall provide all labor, transportation, supervision, equipment, and materials to perform the ultrasonic thickness inspection in accordance with the detailed Statement of Work. The procurement is 100% set-aside for Small Businesses under NAICS code 541380. All quotes must be submitted by noon Eastern Time on September 5, 2024 via email to the Contracting Specialist. A site visit is required, and questions about the solicitation must be submitted in writing by July 21, 2024. The Government contemplates award of a Firm-Fixed Price contract resulting from this solicitation.

View the file

Other files

File Type Posted
Questions Base ECity Ultrasonic Testing.xlsx XLSX spreadsheet
Ultrasonic QA 1.docx DOCX document
70Z08124QELIZ0013- 1442.pdf PDF
Map Location Photos.pdf PDF
DOL Eciyt.pdf PDF
Data Plate Photos.pdf PDF
B365 Tank UT Inspections SOW.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. Is there structural steel on top of the tanks for rope anchorage points?

Answer… There is a fixed ladder along with a platform/catwalk on the roof of each fuel tank. The SOW states….. The Contractor shall provide ALL equipment to reach any area, which cannot be inspected/analyzed from the ground.

2. Are tank drawings available to determine UTT points and quadrants, or will you provide this information based on previous inspections?

Answer… No! There are no drawings available to be provided or information based on a previous inspection.

1. Will we need to provide AutoCAD drawings of the tanks?

Answer… No!

1. What is the USCG policy on the use of drones during inspections?

Answer… No! There will be NO use of drones due to an active airfield adjacent to where the work is being completed.