AMENDMENT A00001 SOLICIATION 70Z080-18-Q-P45044-00

REQUEST FOR SPECIFICATION CLARIFICATION

USCGC KISKA DRYDOCK

WORK ITEM NO: D-006

WORK ITEM TITLE: Cradle Assembly, Transport PARAGRAPH NO: 3.4.3 States: “Certification. The Contractor shall complete a cradle inspection IAW SFLC Std. Spec 8634 and complete a load test IAW with the checklist found in Std. Spec 8634. Upon completion of the inspection and load test, KTR shall submit all paperwork, certified by a Professional Engineer, to the US Coast Guard and COR.

QUESTION: SFLC Std. Spec 8634 Paragraph C2.2.2 indicates the weight test portion of the cradle certification is only required upon original fabrication or modification.

RESPONSE: A weight test will be required for the cradle after assembly during this availability.

WORK ITEM NO: D-002

WORK ITEM TITLE: Tank (Potable Water), Preserve “100%” QUESTION: Request Government to clarify if a Contractor Furnished NACE Inspector is required for this Work Item.

RESPONSE: A NACE inspector is required for WI 2, Tank (Potable Water), Preserve “100%”.