400 Hz Workorder Material List.docx

DOCX document 45 KB Posted

Attached to
120 KVA 400 Hz Vertical Solid State Frequency Converter
Solicitation number
70Z03426QHONO0071
Issued by

About this file

This is a material list and technical specification document for a 400 Hz electrical system repair and installation project at USCG Air Station Barbers Point. The project requires procurement and installation of a 120 KVA 400 Hz vertical solid state frequency converter (input: 480VAC 3-phase 60Hz; output: 115/200VAC 3-phase 400Hz) with dimensions not exceeding 80" height by 5'-10" width to fit through doorways, mounted on an 18" minimum steel stand. The converter must be fully compatible with U.S. Coast Guard C-130J aircraft per MIL-STD-704E power quality standards. Known compliant manufacturers include Unitron, ITW, and FCX; other manufacturers must provide signed compliance letters from their representatives. The specification also details three motorized 400 Hz cable reels (two for HH-65 helicopters, one for C-130J), one 28V DC cable reel, three 400 Hz power cables with pushbutton controls (100 feet of 260 amp phased balanced cable with molded connectors and electronic level wind controls), one 28VDC cable assembly, three Load Point Control Units (LPCU) for monitoring voltage and overload conditions, and one 175-amp enclosed circuit breaker (600V NEMA 1).

All cable reels and assemblies must arrive pre-assembled with cables and plugs installed and factory-tested. The vendor must provide on-site commissioning including startup, personnel training, resistive load bank testing, and final verification testing with an actual C-130J aircraft, with warranty commencing upon startup completion. Three copies of written documentation and CD/DVD format materials plus four copies of operations and maintenance manuals are required upon project completion. The related solicitation (70Z03426QHONO0071) is a 100% small business set-aside (NAICS 335311, 800 employee threshold) issued by USCG Regional Support Team Oceania as a Request for Quotation with a closing date of February 20, 2026, at 12:00 p.m. Hawaiian Standard Time. Delivery is required to USCG Air Station Barbers Point in Kapolei, Hawaii (Building 1669), with FOB Destination pricing on a firm fixed-price basis.

View the file

Other files

File Type Posted
SF1449.pdf PDF
400 hz specs.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Repair Circuits 400 Hz- ASBP 1790 - Material List with Salient Characteristics

Material List with Salient Characteristics (Refer to Drawing and Specs for more detailed requirements)

1. Quantity (1) one -120 KVA 400 Hz Vertical Solid State Frequency Converter.

Input: 480VAC, 3-phase, 60 Hz. 135 amps max. Output: 115/200 VAC, 3-phase, 400 Hz, 347 amp. Must be < 80” H x 5’-10” W to fit through door way. Unit shall be floor mounted on a min. 18” high steel stand. Provide live on-site commissioning of the unit upon completion of the 400 hz system replacement. Final test shall include connecting to C-130J aircraft for power acceptance.

This 400 Hz Frequency must be fully compatible with the U.S. Coast Guard C-130J aircraft. Known compliant manufacturer’s include Unitron, ITW and FCX. Other manufacturer’s submitting bids which are not approved, must submit a signed letter from the manufacturer’s rep stating their unit is specifically compliant with the U.S. Coast Guard’s C-130J.

2. Quantity (3) three- 400 Hz motorized cable reel with floor stand.

(2) for HH 65, (1) for C-130J.

Cable reels shall have 100’ of the new 400 hz cable and plug installed and tested on the new cable reels at the factory and not done on-site. Operates on 120VAC, 60 Hz.

Known compliant motorized cable reels include Gleason Reel Model P32-420/53-1612-75 200V/35A, Counterclock wise, 150 f.p.m. Hannay Reel Model ECR-6626-33-34-15/5 RT, 400 Hz.

3. Quantity (1) one- 28V DC motorized cable reel with floor stand.

(1) for HH hangar side.

Cable reel shall have 100’of the new DC cable and plug installed and tested on the new cable reel at the factory and not done on-site. Operates on 120VAC, 60 Hz.

4. Quantity (3) three- 400 Hz cable, plug w/ pushbutton controls for cable reels.

(3) 100’ of long phased balanced 260 amp single jacket 400 Hz power cable with molded on head and cable relief. Single piece molded (yellow) nose contact section, orange scuff jacket installed on the entire length of the cable sealed on both ends. Standard termination on the other end. Installed on the new cable reels. 4 push buttons for control on/off, up and down to cable reel. With level wind and electronic payout and rewind via momentary level switch.

6-#4 Awg Class M, stranding, neutral 1-#1 Awg Class M, stranding, Control Wires 18-#18, Note: Drawings indicate 90’ of net cable length on cable reel. 100’ of gross cable length is ordered to account for splicing and wiring losses to the cable reel which the manufacturer still charges.

5. Quantity (1) one 28 VDC cable, plug w/ pushbutton controls for cable reels.

(1) 100’ of two (2) #4/0 AWG single conductor power wires. All conductors to comply with MIL-C-5756 power cable capability, MIL-C-7974D. Strain relief. Silver plated contacts. Non-metallic bonds. Hypalon Material. Provide a 28.5 VDC connector.

6. Quantity (3) three Load Point Control Unit (LPCU) for 400 Hz cable reels.

Controls power delivered to a 115/200 volt, 3-phase, 400 Hz load up to 90 kva. Monitors over voltage, under voltage and overload for each phase. Enclosure door equipped with lamp test switch and LED indicators for all fault types, power available and contactor closed.

Known compliant product is Page JB900PSSU and Unitron RCCU-ACDC 28-64-100.

7. Quantity (1) Enclosed circuit breaker, 175 amps , 600 V, NEMA 1, min. 65K AIC. Surface mtd.

8. Commissioning. Start up, training, Load Bank testing, Actual C-130J load testing.

After equipment that have been installed by U.S. Coast Guard Personnel, qualified vendor personnel shall provide start up, training and resistive load bank testing of all the equipment and insure that everything is working properly. The final test will be connecting to a C-130J to verify the 400 hz power is not rejected. Commission the starting date of the warranty. Three (3) copies in written and CD/DVD format shall be submitted to the U.S. Coast Guard upon completion of this line item. Four (4) copies of the O&M manuals shall also be submitted.

P/N 10879119