This is a Third Floor Life Safety Plan architectural drawing for the Reconstruction of USCG Integrated Support Command facility in New Orleans, Louisiana. The plan details exit capacity calculations, occupancy loads, and safety provisions for the third floor. The third floor has an occupancy load of 50 people, with required exit capacity of 25 people distributed across multiple exits. Exit capacity calculations are provided using both NFPA and IBC standards, with stair exit capacities ranging from 176 to 265 people and door exit capacities from 170 to 226 people, depending on the applicable code standard. Travel distances to exits are specified as 145 feet, 135 feet, and 161 feet maximum.
The plan indicates the presence of 1-hour rated partitions, illuminated exit signs, fire extinguishers (referenced on sheets A631 and A633), and smoke detectors as required by code. The drawing references additional code data on Sheet G101 and includes a lighting plan reference (E103). The document is prepared by BROADMOOR/BOH BROS., Broadmoor Tower, Metairie, Louisiana, and bears the seal of the U.S. Coast Guard Facilities Design and Construction Center (LANT). The drawing is dated April 1, 2010, with an approval date of January 23, 2009, and is designated as Sheet 6 of 40 pages in the construction document set (Drawing Number 32-L02001, A32L020101G4).
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TRAVEL DISTANCE 135'-0"TRAVEL DISTANCE 145'-0"
NFPA
STAIR EXIT CAPACITY
53/.3= 176 PEOPLE
IBC
STAIR EXIT CAPACITY
53/.2= 265 PEOPLE
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
NFPA
STAIR EXIT CAPACITY
53/.3= 176 PEOPLE
IBC
STAIR EXIT CAPACITY
53/.2= 265 PEOPLE
IBC
DOOR EXIT CAPACITY
34/.2 = 170 PEOPLE
NFPA
DOOR EXIT CAPACITY
34/.15 = 226 PEOPLE
REQ'D. EXIT CAPACITY
25 PEOPLE
REQ'D. EXIT CAPACITY
25 PEOPLE
THIRD FLOOR OCCUPANY LOAD: 50
REFER TO SHEET G101 FOR ADDITIONAL CODE DATA
1 HR. RATED PARTITION
ILLUMINATED EXIT SIGN
RE: (LIGHTING PLAN/E103)
F.E.
FIRE EXTINGUISHER
PER CODE
A631 & A633 (SMOKE)
T R
A V
E L
D
I S
T A
N C
E