2.2.1 Attachment F 201.24-NM3.1 (202).pdf
PDF 3 MB Posted
- Attached to
- Replace the outdated HVAC system in the Federal Regional Center (FRC) building in Denton, TX
- Solicitation number
- 70FBR622Q00000046
- Issued by
-
Federal Emergency Management Agency
About this file
This is a combined synopsis/solicitation for a contractor to replace the HVAC system in the Federal Regional Center building in Denton, Texas. The project requires labor, materials, supplies and equipment to replace the outdated HVAC system. A site visit is scheduled for August 30th between 9AM and 1PM CDT; interested parties must contact the named individual at least 24 hours in advance to arrange attendance. The solicitation is 100% set aside for small businesses. The Federal Emergency Management Agency is the issuing agency. Responses are due based on standard FAR contracting terms and conditions.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
89 TONS THROUGH 209 TONS
313 kW THROUGH 735 kW
60Hz
STYLE A
HFC-407C
FORM 201.24-EG3 (308)
YCWS
WATER COOLED LIQUID CHILLER
2 JOHNSON CONTROLS
FORM 201.24-EG3 (308)
Table of Contents Introduction Specifications MicroComputer Control Center Accessories & Options Nomenclature Design Parameters Refrigerant Flow Diagram Pressure Drop Curves Selection Data Ratings (HFC-407C English) Ratings (HFC-407C SI) Ratings- Brine (30 % Ethylene Glycol) (R-22 English) Ratings- Brine (30 % Ethylene Glycol) (R-22 SI) Ratings- Brine (30 % Propylene Glycol) (R-22 English) Ratings- Brine (30 % Propylene Glycol) (R-22 SI) Brine Correction Factors Part Load Ratings Physical Data Isolator Selection Data Isolator Details Sound Data Dimensions (English) Electrical Data Incoming Wire Range Selections Customer Wiring Data Typical Control Panel Wiring Application Data Guide Specifications
Table of Contents
FORM 201.24-EG3 (308)
3JOHNSON CONTROLS
YORK YCWS Water-Cooled models provide chilled water for all HFC air conditioning applications that use central station air handling or terminal units. They are completely self-contained and are designed for indoor (new or retrofit) installation. Each unit includes accessible semi-hermetic screw compressors, a liquid cooler, water cooled condenser, and a user-friendly, diagnostic Microcomputer Control Center all mounted on a rugged steel base. The units are produced at an ISO 9001 regis-tered facility. The YCWS chillers have certified ratings in accordance with the latest version of ARI Standard 550/590.
Introduction
York YCWS Water Cooled Screw Chillers
4 JOHNSON CONTROLS
GENERAL
The Liquid Chiller will be completely assembled with all interconnecting refrigerant piping and internal wiring, ready for field installation. The unit can be covered with an optional coat of Caribbean Blue enamel.
There will be an operational test, with water flowing through the cooler, to check that each control device op-erates correctly. The chiller will be shipped with 10 lbs of HFC-407C refrigerant and York ‘L’ (POE) synthetic oil.
Units are designed in accordance with NFPA 70 (National Electric Code), U.L. and cU.L. Standards, ASHRAE/ANSI 15 Safety Code for Mechanical Refrigeration. All units are produced at an ISO 9001 registered facility. All YCWS chillers are rated and certified in accordance with ARI Standard 550/590 at ARI conditions.
SEMI-HERMETIC YORK SCREW COMPRESSORS
• Continuous function, microprocessor controlled, 3- way proportional Capacity Control Valve provides regulated output pressure independent of valve input pressure for a stable, smooth, and precise match of compressor capacity to cooling load to 10% of chiller capacity.
• Automatic spring return of capacity control valve to minimum load position ensures compressor starting at minimum motor load. Internal discharge check to prevent rotor backspin upon shutdown.
• Acoustically tuned, internal discharge gas path elimi-nates objectionable noise at the source, while optimizing flow for maximum performance.
• Reliable suction gas cooled, high efficiency, accessible hermetic motor with APT2000 type magnet wire and redundant overload protection using both thermistor and current overload protection.
• Suction gas screen and serviceable, 0.5 micron full flow oil filter within the compressor housing.
• Cast iron compressor housing precisely machined for optimal clearances and superb efficiency. Entire com-pressor, from suction to discharge has a Design Working Pressure of 450psig (31 bar).
• 350W compressor body cartridge heater.
• Each compressor will be mounted on isolator pads to reduce transmission of vibration to the rest of the unit.
COOLER
The dual-circuit cooler will be the direct-expansion type, with refrigerant in the tubes and chilled liquid flowing through the baffled shell. The design working pressure of the shell (liquid) side will be 150 PSIG (10.3 bar), and 300 PSIG (26.7 bar) for the tube (refrigerant) side.
The cooler will be constructed and tested in accordance with the applicable sections of the ASME Pressure Vessel Code, Section VlII, Division (1). The water side will be exempt per paragraph U-1, (c)(6).
The water baffles will be constructed of galvanized steel to resist corrosion. The removable heads will allow access to the internally enhanced, seamless, copper tubes. Vent and drain connections will be included.
The cooler will be covered with 3/4" (19.1 mm ) flexible, closed-cell, foam insulation (K = 0.25).
CONDENSER
The condenser is a cleanable through-tube type with steel shell, copper tubes, removable water heads, and includes integral subcooling. Refer to PHYSICAL DATA for design working pressures. The shell will be constructed and tested in accordance with section Vll, division 1 of the ASME pressure-vessel code. The water side is exempt per paragraph U-1 (c) of section VlII, division 1 of the ASME pressure-vessel code. The condenser is equipped with relief valves and will hold the full refrigerant charge for pumpdown.
REFRIGERANT CIRCUIT
Two independent refrigerant circuits will be furnished on each unit. All piping will be copper with brazed joints. The liquid line will include: a shutoff valve with charging port;
sightglass with moisture indicator; thermal expansion valve; solenoid valve; and high-absorption removable-core filter drier. The entire suction line and the liquid line be-tween the expansion valve and the cooler will be insulated with flexible, closed-cell, foam insulation.
Specifications
5JOHNSON CONTROLS
POWER AND CONTROL PANELS
All controls and motor starting equipment necessary for unit operation shall be factory wired and function tested.
The panel enclosures shall be designed to NEMA 1 (IP
32) and manufactured from powder-painted galvanized steel.
The Power and Control Panel shall be divided into a power section for each electrical system, a common input section and a control section.
Each power panel shall contain:
Compressor starting contactors, control circuit serv-ing compressor capacity control, compressor contactor coils and compressor motor overloads. The compressor motor overloads contain current transformers which sense each phase, as an input to the microprocessor, to protect the compressor motors from damage due to: low input current, high input current, unbalanced current, single phasing, phase reversal, and com-pressor locked rotor.
The common input section shall contain:
The control supply transformer providing 115V, cus-tomer relay board and control circuit switch disconnect/ emergency stop device.
The control section shall contain:
On/Off rocker switch, microcomputer keypad and dis-play, microprocessor board, I/O expansion board, relay boards, and 24V fused power supply board.
MICROPROCESSOR CONTROLS
Fuzzy Logic control will be incorporated in the YCWS range of chillers. Fuzzy Logic allows the control system to monitor several key variables to provide tighter, more stable chilled water temperature control. The control system monitors the leaving chilled water temperature to track where it has been, where it is now, how fast it is moving, and accurately adjusts the chiller operation in anticipation of expected performance to minimize hunting and save energy.
The microprocessor shall have the following functions and displays:
• A liquid crystal 40 character display with text provided on two lines and light emitting diode backlighting for outdoor viewing.
• A color-coded, 35 button, sealed keypad with sections for Display, Entry, Setpoints, Clock, Print, Program, and
Unit On/Off Switch.
The standard controls shall include: brine chilling or ther-mal storage, automatic pumpdown, run signal contacts, demand load limit from external building automation system input, remote reset liquid temperature reset input, unit alarm contacts, chilled liquid pump control, automatic reset after power failure, automatic system optimization to match operating conditions, software stored in nonvolatile memory (EPROM) to eliminate chiller failure due to AC power failure.
The microprocessor can be directly connected to a Johnson Controls ISN Building Automation System via the standard onboard RS485 communications port. This option also provides open system compatibility with other communications networks.
Programmed Setpoints shall be retained in a lithium bat-tery backed RTC with a memory of five years.
Display - In Imperial (°F and PSIG) or SI (°C and BAR) units, and for each circuit:
• Return and leaving chilled liquid
• Day, date and time. Daily start/stop times. Holiday and
Manual Override status.
• Compressor operating hours and starts. Automatic or manual lead/lag. Lead compressor identification.
• Run permissive status. No cooling load condition.
Compressor run status.
• Anti-recycle timer and anti-coincident start timer status per compressor.
• Suction (and suction superheat), discharge, and oil pressures and temperatures per System.
• Percent full load compressor motor current per phase and average per phase. Compressor capacity control valve input steps.
• Cutout status and setpoints for: supply fluid tempera-ture, low suction pressure, high discharge pressure and temperature, high oil temperature, low and high current, phase rotation safety, and low leaving liquid temperature.
• Unloading limit setpoints for high discharge pressure and compressor motor current.
• Liquid pulldown rate sensitivity (0.5°F to 5°F [0.3°C to 3.0°C]/minute in 0.1°F [0.05°C] increments).
• Status of: evaporator heater, load and unload timers, chilled water pump.
• Out of range message.
• Up to 6 fault shut down conditions.
• Standard Display Language is English, with an Option for Spanish.
MicroComputer Control Center
6 JOHNSON CONTROLS
Entry - Enter set point changes, cancel inputs, advance day, change AM/PM.
Set Points - Chilled liquid temperature, chilled liquid range, remote reset temperature range.
Clock - Time, daily or holiday start/stop schedule, manual override for servicing.
Print - Operating data or system fault shutdown history for last six faults. Printouts through an RS-232 port via a separate printer (by others).
Program -
• Low leaving liquid temperature cutout, 300 to 600 sec-ond anti-recycle timer, lag compressor start time delay, and average motor current unload point. Liquid tem-perature setpoint reset signal from Johnson Controls ISN or building automation system (by others) via:
• Pulse width modulated (PWM) input for up to 40°F (22°C) total reset as standard.
Specifications – continued
• Optional Building Automation System interface input card for up to 20°F (11.1°C) reset using a: 4 to 20 mA, 0 to 10 Vdc input, or discrete reset input.
NOTE: The Standard MicroPanel can be directly connected to a Johnson Controls ISN Building Automation System via the standard onboard RS485 communication port. This Option also provides open system compatibility with other communications networks (BACnet™ & LONMARK™ via interface through standard onboard 485 or 232 port and an external YorkTalk Translator.
• Additional functions (password protected) for pro-gramming by a qualified service technician:
Cutouts for low suction pressure, high dis-charge pressure, high oil temperature.
Refrigerant type.
High discharge pressure unload setpoint.
Compressor motor current percent limit.
7JOHNSON CONTROLS
ELECTRICAL OPTIONS:
MULTIPLE POINT POWER SUPPLY CONNECTION -
Standard field power wiring connection on all models is Multiple Point Power Connection to factory provided Ter-minal Blocks. Two field supplied electrical power circuits with appropriate branch circuit protection provide power to each of two motor control center cabinets, located on either side of the Control panel on the front of the chiller. Each cabinet contains starter elements for one compressor.
Optional to the Terminal Blocks for field power connection are Non-Fused Disconnects or Circuit Breaker Switches with external, lockable handles.
SINGLE POINT POWER CONNECTION - (Factory Mounted) An optional configuration for field connection of a single electrical circuit to: either Terminal Block or Non-Fused Disconnect Switch with lockable external handle (in compliance with Article 440 of N.E.C., to isolate unit power supply for service). Factory wiring is provided from the Terminal Block or Disconnect Switch to Factory supplied individual system Circuit Breakers, Non-Fused Disconnect switch with external, lockable handle or J Class Fuses/Fuse Block in each of the two compressor motor control centers. (Note: Single Point Non-Fused Disconnect Switch will not be supplied with individual system Non Fused Disconnect Switches with external, lockable handles in each of the two compressor motor control centers).
65 Ka HIGH VOLTAGE PROTECTION - Non-Fused Disconnect Switch with fuses (200 & 575V) or Circuit Breakers (230, 380, & 460V) are used for applications where customers have a requirement for single point wiring with high “fault current” withstanding capability.
This option provides between 50Ka and 65Ka withstand protection to the equipment.
BUILDING AUTOMATION SYSTEM INTERFACE (Fac-tory Mounted) – Provides means to reset the leaving chilled liquid temperature or percent full load amps (current limiting) from the BAS (Factory Mounted):
• Printed circuit board to accept 4 to 20 milliamp, 0 to 10 VDC, or dry contact closure input from the BAS.
• A YORK ISN Building Automation System can provide a Pulse Width Modulated (PWM) signal direct to the standard control panel via the standard onboard RS485 port.
FLOW SWITCH – The flow switch or its equivalent must be furnished with each unit. 150 PSIG (10.5 bar) DWP
– For standard units. Johnson Controls model F61MG- 1C Vapor-proof SPDT, NEMA 4X switch (150 PSIG [10.5 bar] DWP), -20°F to 250°F- (29°C to 121°C), with 1" NPT connection for upright mounting in horizontal pipe.
(Field mounted)
DIFFERENTIAL PRESSURE SWITCH - Alternative to the above mentioned Flow Switch. Pretemco Model DPS 300A-P4OPF-82582-S (20.7bar max working pressure).
SPDT 5 amp 125/250 VAC switch. Range: 0 - 2.8bar, deadband: 0.003 - 0.005bar, with 1/4 NPTE pressure connections.
LANGUAGE LCD AND KEYPAD - Standard display language and keypad is in English. Spanish is available as an option.
PRINTER KIT - Printer for obtaining printout of unit oper-ating and history data. (Field Mounted)
MULTIPLE UNIT SEQUENCE CONTROL (Field Mount-
ed) - Sequencing Control with automatic unit sequencing.
Necessary items for operation and control of up to eight units with parallel water circuits. Includes software and mixed liquid temperature sensor (interconnecting wiring by others).
PRESSURE VESSEL CODES - Coolers and condensers can be supplied in conformance with the following pres-sure codes: A.S.M.E. (Standard)
FINAL PAINT OVERSPRAY - The unit can be sprayed with an optional coat of Caribbean Blue paint. (Factory)
CHICAGO CODE RELIEF VALVES (Factory Mounted)
- Unit will be provided with relief valves to meet Chicago Code requirements.
OPTIVIEW REMOTE CONTROL CENTER - Graphically displays all operational and historical data, provides indoor control of unit setpoints and scheduling, and com-municates with up to eight (8) chiller units from an indoor location. (Field mounted)
ACCESSORIES:
FLANGES (Weld Type) – Consists of 150 PSI (10.5 bar ) standard cooler (150 lb) R.F. flanges to convert to flanged cooler-connections and includes companion flanges.
(Field mounted)
FLANGES (Victaulic Type) – Consists of (2) Flange adapter for grooved end pipe (standard 150 PSI [10.5 bar] cooler). Includes companion flanges. (Field mounted)
VIBRATION ISOLATION:
• Neoprene Isolators – Recommended for normal in-stallations. Provides very good performance in most applications for the least cost. (Field mounted)
• 1" Spring Isolators – Level adjustable, spring and cage type isolators for mounting under the unit base rails. 1" nominal deflection may vary slightly by appli-cation. (Field mounted)
• 2" Seismic Spring Isolators – Restrained Spring-Flex Mountings incorporate a rugged welded steel housing with vertical and horizontal limit stops. Housings de-signed to withstand a minimum 1.0g accelerated force in all directions to 2". Level adjustable, deflection may vary slightly by application. (Field-mounted)
Accessories & Options
8 JOHNSON CONTROLS
ALTERNATIVE CHILLED FLUID APPLICATIONS -
Standard water chilling application range is 40°F to 50°F (4.4°C to 10°C) Leaving Chilled Water Temperature. To protect against nuisance safety trips below 40°F (4.4°C) and reduce the possibility of cooler damage due to freezing during chiller operation, the unit microprocessor automatically unloads the compressors at abnormally low suction temperature (pressure) conditions , prior to safety shutdown.
• Process Brine Option – Process or other applications requiring chilled fluid below 40°F (4.4°C) risk water freezing in the evaporator, typically overcome by using antifreeze. For these applications, the chiller system incorporates brine (ethylene or propylene glycol solu-tion), and the system design Leaving Chilled Fluid Temperature must be provided on the order form to ensure proper factory configuration.
• Thermal Storage Option – Thermal Storage requires special capabilities from a chiller, including the ability to ‘charge’ an ice storage tank, then possibly automatically reset for operation at elevated Leaving Chilled Fluid Temperatures as required by automatic building con-trols. The Thermal Storage Option provides Ice Storage duty Leaving Chilled Fluid setpoints from 25°F to 15°F ( -4°C to -10°C) minimum during charge cycle, with a Reset range of 36°F (20°C) supply fluid temperature.
Accessories & Options - continued
9JOHNSON CONTROLS
Nomenclature
YC W S 0140 46 Y A
YC= York Chiller
W= Water cooled
S= Screw Compressor
Nominal Capacity in Tons Refrig B = HFC-407C
Voltage Code:
Type Start: Y = Star-Delta
Design Series: A
S= Standard Efficiency
17 = 200-3-60
28 = 230-3-60
40 = 380-3-60
46 = 460-3-60
58 = 575-3-60
BS
Nomenclature
10 JOHNSON CONTROLS
Design Parameters
SI
English
YCWS 0100SB 0120SB 0140SB 0180SB 0200SB 0220SB 0240SB
Min. Cooler Water Flow - GPM 200 200 200 260 260 300 300 Max. Cooler Water Flow - GPM 506 506 506 695 695 830 830 Min. Cond. Water Flow - GPM 193 193 193 330 330 330 330 Max. Cond. Water Flow - GPM 645 645 645 1050 1050 1050 1050 Min. Lvg. Liquid Temp. - °F 40 40 40 40 40 40 40 Max. Lvg. Liquid Temp. - °F 50 50 50 50 50 50 50 Min. Ent. Cond. Water Temp - °F 75 75 75 75 75 75 75 Max. Ent. Cond. Water Temp - °F 95 95 95 95 95 95 95 Min. Equipment Room Temp. - °F 40 40 40 40 40 40 40 Max. Equipment Room Temp. - °F 115 115 115 115 115 115 115
YCWS 0100SB 0120SB 0140SB 0180SB 0200SB 0220SB 0240SB
Min. Cooler Water Flow - l/sec 12.6 12.6 12.6 16.4 16.4 18.9 18.9 Max. Cooler Water Flow - l/sec 31.9 31.9 31.9 43.8 43.8 52.4 52.4 Min. Cond. Water Flow - l/sec 12.2 12.2 12.2 20.8 20.8 20.8 20.8 Max. Cond. Water Flow - l/sec 40.7 40.7 40.7 66.2 66.2 66.2 66.2 Min. Lvg. Liquid Temp. - °C 4.4 4.4 4.4 4.4 4.4 4.4 4.4 Max. Lvg. Liquid Temp. - °C 10 10 10 10 10 10 10 Min. Ent. Cond. Water Temp - °C 23.8 23.8 23.8 23.8 23.8 23.8 23.8 Max. Ent. Cond. Water Temp - °C 35 35 35 35 35 35 35 Max. Equipment Room Temp. - °C 46.1 46.1 46.1 46.1 46.1 46.1 46.1 Min. Equipment Room Temp. - °C 4.4 4.4 4.4 4.4 4.4 4.4 4.4
11JOHNSON CONTROLS
Low-pressure liquid refrigerant enters the cooler tubes and is evaporated and superheated by the heat energy absorbed from the chilled liquid passing through the cooler shell. Low-pressure vapor enters the compressor where pressure and superheat are increased. High-pressure vapor is passed through the oil separator where heat is rejected to the con-denser water passing through the tubes. The fully condensed and subcooled liquid leaves the condenser and enters the expansion valve, where pressure reduction and further cooling take place. The low pressure liquid refrigerant then returns to the cooler. Each refrigerant circuit utilizes liquid injection, maintaining efficient oil temperature operation within the compressor.
Refrigerant Flow Diagram
12 JOHNSON CONTROLS
100 1000 10000
100 1000
Pressure Drop Curves
FIGURE 1 - COOLER WATER PRESSURE DROP CURVES (ENGLISH)
FIGURE 3 - CONDENSER WATER PRESSURE DROP CURVES (ENGLISH)
Pr es su re
D ro p (H
2O
Flow (GPM)
Pr es su re
D ro p (H
2O
Flow (GPM)
U
S
O
P
Q
YCWS Model Number Cooler
0100SB, 0120SB, 0140SB O
0180SB, 0200SB P
0220SB, 0240SB Q
YCWS Model Number Condenser
0100SB, 0120SB, 0140SB S
0180SB, 0200SB
0220SB, 0240SB U
13JOHNSON CONTROLS
10 100
10 100
FIGURE 2 - COOLER WATER PRESSURE DROP CURVES (SI)
FIGURE 4 - CONDENSER WATER PRESSURE DROP CURVES (SI)
Pr es su re
D ro p (k
Pa
Flow (l/s)
S
U
Pr es su re
D ro p (k
Pa
Flow (l/s)
Q
PO
YCWS Model Number Cooler
0100SB, 0120SB, 0140SB O
0180SB, 0200SB P
0220SB, 0240SB Q
YCWS Model Number Condenser
0100SB, 0120SB, 0140SB S
0180SB, 0200SB
0220SB, 0240SB U
14 JOHNSON CONTROLS
GUIDE TO SELECTION
Complete water chilling capacity ratings for YORK YCWS chillers are shown on the following pages to cover the majority of job requirements. For any application beyond the scope of this Engineering Guide, consult your nearest YORK Office.
SELECTION RULES
1. RATINGS - YCWS 200, 230 380, 460 & 575-3-60 rating are certified in accordance with ARI standard 550/590, at the ARI standard condition. Rating not at standard ARI conditions are rated in accordance with ARI rating procedures. These ratings may be interpolated but should not be extrapolated.
2. COOLING WATER QUANTITY - Ratings are based on 10ºF chilled water range. Use the chilled water correc-tion factors (below) for other ranges except as limited by water pressure drop, minimum or maximum water flows for the cooler.
3. CONDENSER WATER QUANTITY – Rating are ap-plicable from 2 to 4 gpm/ton as limited by water pres-sure drop or minimum or maximum water flows for the condenser. Using the tabulated MBH, the Cond. GPM is calculated as follows:
MBH x 2 Cond. Water Range (ºF)
4. FOULING FACTORS – Rating are based on 0.0001 evaporator and 0.00025 condenser fouling factor. For other fouling factors, consult the table below or contact your YORK representative.
EVAP FOULING FACTORS
Selection Data
COND FOULING FACTORS
Temp Split
0.0001
X
0.00025 Tons Comp.
Kw Tons Comp. Kw 6 0.9692 1.0015 0.9972 1.0001 8 0.9849 1.0008 0.998 1.0001
10 1 1 0.9982 1.0001 12 1.0133 0.9993 0.9978 1.0001 14 1.0248 0.9986 0.9979 1.0001
Temp Split
0.00025
X
0.0005 Tons Comp. Kw Tons Comp. K
8 0.9998 1.0004 0.9957 1.0072 10 1 1 0.9959 1.0068 12 1.0001 0.9998 0.9961 1.0065 14 1.0001 0.9998 0.9965 1.006
GPM=
Note: Temperature split factors @ 44ºF Leaving Chilled Liquid Temp
(LCLT)
Note: Temperature split factors @ 95ºF Leaving Condenser Water Temp (LCWT).
METHOD OF SELECTION
If the duty requires a 10ºF range on both the cooler and condenser, see “Ratings”. For water ranges other than 10ºF, use the following procedure.
1. Determine capacity required from the following for-mula
GPM x Chilled Water Range (ºF) Capacity (tons) = 24
2. After applying any fouling factor corrections, the actual condenser heat rejection may be determined as fol-lows:
Heat Rejection (Btuh) = (Tons x 12,000) + (kW x 3415)
Heat Rejection (Btuh)Heat Rejection (MBH) =
= (Tons x 12) = (kW x 3.415)
3. Determine condensing water requirements for water cooled models as follows:
Heat Rejection (MBH) x 1000 Condenser Tons = 15,000
Condenser Tons x 30 Cond. Water GPM = Condenser Water Range (ºF)
Or combine the two formulas:
MBH x 2 Cond. Water GPM = Condenser Water Range (ºF)
15JOHNSON CONTROLS
SAMPLE SELECTION
Water Cooled Condenser (YCWS)
GIVEN – Chill 200 GPM of water from 56ºF to 44ºF and
0.0001 evaporator fouling factor with 85ºF to 95ºF con-densing water available. Fouling factor of 0.0005 special field for the condenser.
FIND – The required unit size capacity, kW, EER, and water pressure drop.
SOLUTION:
1. Chilled water range = 56ºF - 44ºF = 12ºF and correction factors are 1.0133 for Tons and 0.9993 for kW for the cooler.
GPM x Chilled Water Range2. Capacity (tons) =
= 200 x 12 = 100TR
2. From the rating, a model YCWL0120SB has a capacity range required. For the cooler leaving water tempera-ture of 44ºF and a condenser leaving water temperature of 95ºF, the unit capacity rating table indicates:
Tons = 106.2
KW = 96.7
EER = 13.2
Correcting for the 12ºF chilled water range and the 0.0005 condenser-fouling factor:
Tons = 106.2 x 1.0133 x 0.9961 = 107.2TR KW = 96.7 x 0.9993 x 1.0065 = 97.3
The unit is suitable.
3. Determine the average full load kW and EER at 95.0 Tons
95.0 X (97.3) = 86.2KW
107.2
Tons x 12 = 95.0 X 12 = 13.2 EER = Kw 86.2
4. Determine the cond. Heat rejection as follows:
Heat Rejection (MBH) = (Tons x 12) + (kW x 3.415) = (95.0 x 12) + (86.2 x 3.415) = 1140 + 294 = 1434
5. Determine GPM condensing water as follows:
GPM Condenser Water = MBH x 2
Cond Water Range
6. From curves on pages 10 and 11, the pressure drops with 200GPM through the cooler and 288 through the condenser of the Model YCWS120SB
Cooler Pressure Drop at 200 GPM = 2.9ft Condenser Pressure Drop at 288 GPM = 5.5ft
16 JOHNSON CONTROLS
Ratings (HFC-407C English)
NOTES:
1. Tons = Unit Cooling Capacity Output
2. kW = Compressor Input Power
3. MBH = Condenser heat rejection
4. EER = Chiller Energy Efficiency Ratio (Capacity [Tons x 12] ÷ kW)
5. LCWT = Leaving Chilled Water Temperature
6. Ratings based on 2.4 GPM cooler water per ton
7. Ratings certified in accordance with ARI Standard 550/590-98 up to 200 tons.
MODEL: YCWS0100SC IPLV= 18.8
LEAVING CONDENSER WATER TEMPERATURE (F)
LCWT
(F)
85.0 95.0 105.0
TONS KW MBH EER TONS KW MBH EER TONS KW MBH EER
40.0 89.5 63.3 1289.0 17.0 84.2 71.5 1254.0 14.1 78.7 80.7 1220.0 11.7
42.0 93.1 63.4 1334.0 17.6 87.7 71.8 1297.0 14.7 82.1 80.9 1261.0 12.2
44.0 96.9 63.5 1380.0 18.3 91.3 72.0 1342.0 15.2 85.6 81.1 1304.0 12.7
45.0 98.9 63.6 1403.0 18.7 93.2 72.2 1364.0 15.5 87.4 81.2 1326.0 12.9
46.0 100.8 63.6 1426.0 19.0 95.1 72.3 1388.0 15.8 89.2 81.4 1348.0 13.2
48.0 104.8 63.5 1474.0 19.8 99.0 72.5 1435.0 16.4 92.9 81.7 1394.0 13.7
50.0 108.9 63.4 1523.0 20.6 102.9 72.7 1483.0 17.0 96.7 81.9 1440.0 14.2
MODEL: YCWS0120SC IPLV= 18.2
LEAVING CONDENSER WATER TEMPERATURE (F)
LCWT
(F)
85.0 95.0 105.0
TONS KW MBH EER TONS KW MBH EER TONS KW MBH EER
40.0 108.0 75.6 1554.0 17.1 101.7 85.6 1513.0 14.3 95.3 96.7 1473.0 11.8
42.0 112.4 75.8 1607.0 17.8 106.0 85.9 1564.0 14.8 99.4 96.9 1523.0 12.3
44.0 116.9 76.0 1662.0 18.5 110.3 86.2 1618.0 15.4 103.5 97.2 1574.0 12.8
45.0 119.2 76.0 1689.0 18.8 112.5 86.3 1645.0 15.6 105.7 97.3 1600.0 13.0
46.0 121.5 76.0 1717.0 19.2 114.8 86.5 1672.0 15.9 107.8 97.5 1626.0 13.3
48.0 126.3 76.0 1775.0 19.9 119.4 86.7 1728.0 16.5 112.2 97.8 1680.0 13.8
50.0 131.2 75.9 1833.0 20.7 124.1 86.9 1785.0 17.1 116.8 98.1 1736.0 14.3
MODEL: YCWS0140SC IPLV= 19.3
LEAVING CONDENSER WATER TEMPERATURE (F)
LCWT
(F)
85.0 95.0 105.0
TONS KW MBH EER TONS KW MBH EER TONS KW MBH EER
40.0 127.9 88.1 1835.0 17.4 120.5 99.9 1787.0 14.5 113.0 112.9 1741.0 12.0
42.0 133.0 88.3 1898.0 18.1 125.5 100.2 1848.0 15.0 117.8 113.1 1799.0 12.5
44.0 138.3 88.5 1962.0 18.8 130.6 100.5 1910.0 15.6 122.7 113.4 1859.0 13.0
45.0 141.1 88.6 1995.0 19.1 133.2 100.7 1942.0 15.9 125.2 113.6 1890.0 13.2
46.0 143.8 88.6 2028.0 19.5 135.9 100.8 1975.0 16.2 127.8 113.7 1922.0 13.5
48.0 149.4 88.6 2095.0 20.2 141.3 101.1 2040.0 16.8 133.0 114.1 1985.0 14.0
50.0 155.0 88.5 2162.0 21.0 146.7 101.3 2106.0 17.4 138.2 114.4 2049.0 14.5
MODEL:YCWS0180SC IPLV= 20.8
LEAVING CONDENSER WATER TEMPERATURE (F)
LCWT
(F)
85.0 95.0 105.0
TONS KW MBH EER TONS KW MBH EER TONS KW MBH EER
40.0 156.8 97.9 2215.0 19.2 147.8 111.5 2154.0 15.9 138.6 126.2 2094.0 13.2
42.0 163.2 98.0 2293.0 20.0 154.0 111.8 2229.0 16.5 144.5 126.5 2165.0 13.7
44.0 169.7 97.9 2371.0 20.8 160.4 112.0 2306.0 17.2 150.7 126.8 2240.0 14.3
45.0 173.1 97.9 2410.0 21.2 163.7 112.2 2347.0 17.5 153.8 126.9 2278.0 14.5
46.0 176.4 97.8 2450.0 21.6 166.9 112.2 2386.0 17.8 157.0 127.1 2317.0 14.8
48.0 183.6 97.5 2536.0 22.6 173.6 112.4 2467.0 18.5 163.4 127.4 2396.0 15.4
50.0 190.7 97.2 2620.0 23.6 180.5 112.5 2550.0 19.3 170.1 127.7 2476.0 16.0
17JOHNSON CONTROLS
YCWS0200SB
YCWS0220SB
YCWS0240SB
IPLV = 18.5
IPLV = 17.6
IPLV = 18.1
NOTES:
1. Tons = Unit Cooling Capacity Output
2. kW = Compressor Input Power
3. MBH = Condenser heat rejection
4. EER = Chiller Energy Efficiency Ratio (Capacity [Tons x 12] ÷ kW)
5. LCWT = Leaving Chilled Water Temperature
6. Ratings based on 2.4 GPM cooler water per ton
7. Ratings certified in accordance with ARI Standard 550/590-98 up to 200 tons.
40.0 210.9 151.5 3048.0 16.7 191.6 173.3 2891.0 13.3 182.6 185.6 2825.0 11.8 174.1 199.0 2768.0 10.5
42.0 220.2 151.5 3159.0 17.4 200.1 173.2 2992.0 13.9 190.8 185.5 2923.0 12.3 182.0 198.8 2862.0 11.0
44.0 229.6 151.3 3271.0 18.2 208.8 173.0 3096.0 14.5 199.2 185.2 3022.0 12.9 190.0 198.5 2957.0 11.5
45.0 234.3 151.1 3327.0 18.6 213.3 172.8 3149.0 14.8 203.4 185.1 3073.0 13.2 194.1 198.3 3006.0 11.7
46.0 239.1 150.9 3384.0 19.0 217.7 172.6 3202.0 15.1 207.7 184.8 3124.0 13.5 198.2 198.0 3055.0 12.0
48.0 248.9 150.3 3500.0 19.9 226.8 172.1 3309.0 15.8 216.5 184.3 3227.0 14.1 206.7 197.5 3154.0 12.6
50.0 258.9 149.6 3618.0 20.8 236.1 171.4 3418.0 16.5 225.5 183.7 3332.0 14.7 215.3 196.8 3255.0 13.1
40.0 177.4 124.7 2554.0 17.1 161.0 142.7 2419.0 13.5 153.4 152.9 2363.0 12.0 146.2 163.9 2313.0 10.7
42.0 185.2 124.6 2648.0 17.8 168.2 142.6 2505.0 14.2 160.3 152.7 2445.0 12.6 152.8 163.7 2392.0 11.2
44.0 193.2 124.4 2743.0 18.6 175.6 142.3 2593.0 14.8 167.4 152.5 2529.0 13.2 159.6 163.4 2473.0 11.7
45.0 197.3 124.2 2791.0 19.1 179.3 142.2 2637.0 15.1 171.0 152.3 2572.0 13.5 163.1 163.2 2514.0 12.0
46.0 201.4 124.0 2839.0 19.5 183.1 142.0 2682.0 15.5 174.6 152.1 2615.0 13.8 166.6 163.0 2555.0 12.3
48.0 209.7 123.5 2937.0 20.4 190.8 141.5 2772.0 16.2 182.0 151.6 2702.0 14.4 173.7 162.4 2639.0 12.8
50.0 218.1 122.8 3037.0 21.3 198.7 140.8 2865.0 16.9 189.6 150.9 2790.0 15.1 181.0 161.8 2724.0 13.4
40.0 193.0 138.0 2787.0 16.8 175.3 157.9 2642.0 13.3 167.1 169.1 2582.0 11.9 159.2 181.3 2529.0 10.5
42.0 201.5 138.0 2889.0 17.5 183.0 157.8 2735.0 13.9 174.5 169.0 2671.0 12.4 166.4 181.1 2615.0 11.0
44.0 210.1 137.7 2992.0 18.3 191.0 157.5 2830.0 14.6 182.1 168.7 2761.0 13.0 173.8 180.8 2702.0 11.5
45.0 214.5 137.6 3044.0 18.7 195.1 157.4 2878.0 14.9 186.1 168.5 2808.0 13.2 177.5 180.6 2746.0 11.8
46.0 219.0 137.4 3096.0 19.1 199.2 157.2 2927.0 15.2 190.0 168.3 2855.0 13.5 181.2 180.4 2790.0 12.1
48.0 228.0 136.8 3202.0 20.0 207.6 156.6 3025.0 15.9 198.1 167.8 2949.0 14.2 189.0 179.8 2882.0 12.6
50.0 237.2 136.1 3311.0 20.9 216.1 156.0 3125.0 16.6 206.3 167.2 3046.0 14.8 196.9 179.2 2974.0 13.2
LEAVING CONDENSER WATER TEMPERATURE (°F)
| LCWT | 85.0 | 95.0 | 100.0 | 105.0 | |||||||||||||||
| (°F) | TONS | KW | MBH | EER | TONS | KW | MBH | EER | TONS | KW | MBH | EER | TONS | KW | MBH |
18 JOHNSON CONTROLS
Ratings (HFC-407C SI)
NOTES:
1. KWo = Unit kW Cooling Capacity Output
2. KWi = Compressor kW Input
3. COP = Coefficient of Performance
4. LCWT= Leaving Chilled Water Temperature
5. Ratings based on 0.047 l/s cooler water per kW.
YCWS0120SB
YCWS0140SB
YCWS0180SB
YCWS0100SB
5.0 314.9 71.5 386.0 4.4 288.7 80.3 369.0 3.6 264.7 90.9 355.0 2.9 242.8 103.1 346.0 2.4
6.0 327.3 70.9 398.0 4.6 300.2 79.7 380.0 3.8 275.4 90.1 365.0 3.1 252.8 102.2 355.0 2.5
7.0 340.0 70.4 410.0 4.8 312.0 79.1 391.0 4.0 286.4 89.4 375.0 3.2 263.1 101.3 364.0 2.6
8.0 352.8 69.8 422.0 5.1 324.0 78.4 402.0 4.1 297.6 88.7 386.0 3.4 273.5 100.5 374.0 2.7
9.0 365.9 69.1 435.0 5.3 336.2 77.8 414.0 4.3 309.0 87.9 396.0 3.5 284.2 99.6 383.0 2.9
10.0 379.3 68.4 447.0 5.5 348.6 77.1 425.0 4.5 320.6 87.2 407.0 3.7 295.0 98.8 393.0 3.0
5.0 378.1 86.5 464.0 4.4 347.1 97.4 444.0 3.6 318.6 110.3 428.0 2.9 292.6 125.0 417.0 2.3
6.0 392.7 86.3 479.0 4.6 360.8 97.2 458.0 3.7 331.4 109.9 441.0 3.0 304.6 124.5 429.0 2.5
7.0 407.7 86.0 493.0 4.7 374.7 96.8 471.0 3.9 344.5 109.5 454.0 3.2 316.8 124.0 440.0 2.6
8.0 422.9 85.6 508.0 4.9 388.9 96.4 485.0 4.0 357.7 109.0 466.0 3.3 329.3 123.4 452.0 2.7
9.0 438.5 85.2 523.0 5.2 403.4 96.0 499.0 4.2 371.2 108.5 479.0 3.4 341.9 122.8 464.0 2.8
10.0 454.2 84.7 539.0 5.4 418.2 95.5 513.0 4.4 385.0 108.0 493.0 3.6 354.8 122.2 477.0 2.9
5.0 551.0 111.9 662.0 4.9 504.8 126.3 631.0 4.0 462.6 143.1 605.0 3.2 424.4 162.4 586.0 2.6
6.0 572.8 111.8 684.0 5.1 525.0 126.2 651.0 4.2 481.3 142.9 624.0 3.4 441.9 162.1 604.0 2.7
7.0 595.0 111.5 706.0 5.3 545.6 126.0 671.0 4.3 500.5 142.7 643.0 3.5 459.6 161.7 621.0 2.8
8.0 617.7 111.2 728.0 5.6 566.7 125.6 692.0 4.5 520.2 142.3 662.0 3.7 477.8 161.3 639.0 3.0
9.0 640.6 110.8 751.0 5.8 588.2 125.2 713.0 4.7 540.1 141.9 682.0 3.8 496.5 160.8 657.0 3.1
10.0 664.3 110.2 774.0 6.0 610.1 124.7 734.0 4.9 560.3 141.4 701.0 4.0 515.6 160.2 675.0 3.2
5.0 447.1 101.5 548.0 4.4 410.8 114.6 525.0 3.6 377.5 129.7 507.0 2.9 347.0 147.0 494.0 2.4
6.0 464.2 101.6 565.0 4.6 426.8 114.6 541.0 3.7 392.5 129.6 522.0 3.0 361.1 146.8 508.0 2.5
7.0 481.7 101.5 583.0 4.7 443.2 114.5 557.0 3.9 407.8 129.5 537.0 3.2 375.4 146.6 522.0 2.6
8.0 499.5 101.4 601.0 4.9 459.8 114.4 574.0 4.0 423.4 129.3 552.0 3.3 390.0 146.3 536.0 2.7
9.0 517.7 101.2 618.0 5.1 476.7 114.2 590.0 4.2 439.2 129.1 568.0 3.4 404.9 146.0 551.0 2.8
10.0 536.2 100.9 637.0 5.3 494.1 113.9 608.0 4.3 455.4 128.8 584.0 3.5 420.1 145.7 565.0 2.9
LEAVING CONDENSER WATER TEMPERATURE (°C)
| LCWT | 30.0 | 35.0 | 40.0 | 45.0 | ||||||||||||||||
| (°C) | KWo | KWi | KW | COP | KWo | KWi | KW | COP | KWo | KWi | KW | COP | TONS | KW | MBH | EER |
IPLV= 4.8 COP
IPLV= 4.6 COP
IPLV= 4.9 COP
IPLV= 5.2 COP
19JOHNSON CONTROLS
NOTES:
1. KWo = Unit kW Cooling Capacity Output
2. KWi= Compressor kW Input
3. COP = Coefficient of Performance
4. LCWT= Leaving Chilled Water Temperature
5. Ratings based on 0.047 l/s cooler water per kW.
YCWS0200SB
YCWS0220SB
YCWS0240SB
IPLV= 5.4 COP
5.0 741.7 153.8 895.0 4.8 680.3 173.6 854.0 3.9 623.8 196.6 820.0 3.2 573.1 222.9 796.0 2.6
6.0 770.8 153.8 924.0 5.0 707.3 173.5 880.0 4.1 649.2 196.5 845.0 3.3 596.3 222.6 819.0 2.7
7.0 800.4 153.6 954.0 5.2 734.9 173.3 908.0 4.2 674.9 196.2 871.0 3.4 620.0 222.2 842.0 2.8
8.0 830.7 153.2 984.0 5.4 763.0 173.0 936.0 4.4 701.2 195.8 897.0 3.6 644.8 221.7 866.0 2.9
9.0 861.5 152.7 1014.0 5.6 791.8 172.5 964.0 4.6 727.9 195.3 923.0 3.7 669.8 221.1 891.0 3.0
10.0 892.7 152.1 1044.0 5.9 821.1 172.0 993.0 4.8 755.2 194.7 950.0 3.9 695.4 220.4 915.0 3.2
5.0 623.8 126.6 750.0 4.9 571.6 142.9 714.0 4.0 524.3 161.9 686.0 3.2 481.2 183.7 664.0 2.6
6.0 648.4 126.5 775.0 5.1 594.5 142.8 737.0 4.2 545.2 161.7 707.0 3.4 500.9 183.3 684.0 2.7
7.0 673.5 126.3 799.0 5.3 617.9 142.6 760.0 4.3 567.0 161.5 728.0 3.5 520.9 183.0 703.0 2.9
8.0 699.1 125.9 825.0 5.6 641.6 142.3 783.0 4.5 589.2 161.1 750.0 3.7 541.4 182.5 724.0 3.0
9.0 725.2 125.5 850.0 5.8 666.0 141.8 807.0 4.7 611.8 160.6 772.0 3.8 562.5 182.0 744.0 3.1
10.0 751.9 124.9 876.0 6.0 690.7 141.3 832.0 4.9 634.9 160.1 795.0 4.0 584.1 181.4 765.0 3.2
5.0 678.5 140.1 818.0 4.8 622.2 158.2 780.0 3.9 570.1 179.2 749.0 3.2 523.8 203.2 727.0 2.6
6.0 705.3 140.1 845.0 5.0 647.0 158.1 805.0 4.1 593.6 179.0 772.0 3.3 545.2 202.8 748.0 2.7
7.0 732.5 139.8 872.0 5.2 672.0 157.9 829.0 4.3 617.2 178.7 796.0 3.5 566.8 202.4 769.0 2.8
8.0 760.3 139.5 899.0 5.5 697.9 157.5 855.0 4.4 641.2 178.3 819.0 3.6 589.5 201.9 791.0 2.9
9.0 788.6 139.0 927.0 5.7 724.4 157.1 881.0 4.6 665.5 177.8 843.0 3.7 612.4 201.4 813.0 3.0
10.0 817.4 138.4 955.0 5.9 751.3 156.5 907.0 4.8 690.7 177.3 868.0 3.9 635.8 200.8 836.0 3.2
LEAVING CONDENSER WATER TEMPERATURE (°C)
| LCWT | 30.0 | 35.0 | 40.0 | 45.0 | ||||||||||||||||
| (°C) | KWo | KWi | KW | COP | KWo | KWi | KW | COP | KWo | KWi | KW | COP | TONS | KW | MBH | EER |
IPLV= 5.1 COP
IPLV= 5.3 COP
20 JOHNSON CONTROLS
LEAVING CONDENSER WATER TEMPERATURE (°F)
| LCWT | 85.0 | 95.0 | 105.0 | ||||||||||||
| (°F) | TONS | KW | MBH | EER | TONS | KW | MBH | EER | TONS | KW | MBH | EER |
YCWS0120SC
YCWS0140SC
YCWS0180SC
YCWS0100SC
16.0 43.1 69.0 753.0 7.5 38.9 82.2 746.0 5.7 34.9 98.4 755.0 4.3
20.0 48.7 70.6 825.0 8.3 43.9 82.8 809.0 6.4 39.5 98.0 808.0 4.8
24.0 55.0 71.5 904.0 9.2 49.7 83.1 880.0 7.2 44.9 97.3 870.0 5.5
28.0 62.5 72.0 995.0 10.4 56.5 82.9 961.0 8.2 51.1 96.4 942.0 6.4
32.0 71.3 72.0 1101.0 11.9 64.6 82.4 1056.0 9.4 58.5 95.2 1026.0 7.4
36.0 81.0 71.6 1216.0 13.6 73.5 81.6 1161.0 10.8 66.7 93.9 1121.0 8.5
40.0 88.5 70.8 1303.0 15.0 80.5 80.5 1240.0 12.0 73.1 92.4 1193.0 9.5
16.0 52.0 77.9 890.0 8.0 47.0 92.6 879.0 6.1 42.3 110.4 884.0 4.6
20.0 58.7 80.6 979.0 8.7 53.0 94.6 958.0 6.7 47.8 111.6 954.0 5.1
24.0 66.3 82.6 1077.0 9.6 60.0 96.0 1047.0 7.5 54.2 112.3 1033.0 5.8
28.0 75.1 84.0 1188.0 10.7 68.0 96.9 1147.0 8.4 61.6 112.6 1123.0 6.6
32.0 85.5 85.0 1316.0 12.1 77.7 97.5 1264.0 9.6 70.4 112.7 1229.0 7.5
36.0 97.1 85.5 1456.0 13.6 88.3 97.7 1392.0 10.8 80.2 112.5 1346.0 8.6
40.0 106.0 85.4 1563.0 14.9 96.5 97.4 1490.0 11.9 87.8 111.8 1435.0 9.4
16.0 61.8 87.0 1038.0 8.5 55.8 103.3 1021.0 6.5 50.2 122.8 1021.0 4.9
20.0 69.6 90.7 1144.0 9.2 62.7 106.4 1116.0 7.1 56.8 125.4 1109.0 5.4
24.0 78.5 93.7 1262.0 10.1 71.1 109.1 1225.0 7.8 64.3 127.4 1206.0 6.1
28.0 88.9 96.1 1395.0 11.1 80.6 111.1 1346.0 8.7 73.0 129.0 1317.0 6.8
32.0 101.2 98.0 1548.0 12.4 91.9 112.7 1487.0 9.8 83.4 130.2 1445.0 7.7
36.0 114.7 99.3 1715.0 13.9 104.4 113.8 1641.0 11.0 94.9 131.1 1586.0 8.7
40.0 125.1 100.0 1842.0 15.0 114.0 114.3 1758.0 12.0 103.9 131.3 1694.0 9.5
16.0 75.7 97.6 1241.0 9.3 70.5 116.5 1243.0 7.3 61.4 137.0 1205.0 5.4
20.0 85.5 101.5 1372.0 10.1 77.1 118.9 1331.0 7.8 69.5 139.7 1311.0 6.0
24.0 96.0 104.5 1508.0 11.0 87.3 121.5 1462.0 8.6 78.8 141.8 1429.0 6.7
28.0 109.8 107.1 1683.0 12.3 100.0 123.7 1622.0 9.7 89.4 143.3 1562.0 7.5
32.0 125.3 108.8 1874.0 13.8 113.5 125.0 1788.0 10.9 102.7 144.4 1725.0 8.5
36.0 142.6 109.9 2086.0 15.6 129.2 125.9 1980.0 12.3 117.2 145.0 1901.0 9.7
40.0 155.9 110.2 2246.0 17.0 141.5 126.1 2128.0 13.5 128.4 144.9 2036.0 10.6
Ratings- Brine (30 % Ethylene Glycol) (R-22 English)
NOTES:
1. Tons = Unit Cooling Capacity Output
2. kW = Compressor Input Power
3. MBH = Condenser heat rejection
4. EER = Chiller Energy Efficiency Ratio (Capacity [Tons x 12] ÷ kW)
5. LCWT = Leaving Chilled Water Temperature
6. Ratings based on 2.4 GPM cooler water per ton.
7. Rated in accordance with ARI Standard 550/590-98 up to 200 tons.
8. For ratings other than 30% glycol, refer to the Design 03 dxchill program.
21JOHNSON CONTROLS
LEAVING CONDENSER WATER TEMPERATURE (°F)
LCWT 85.0 95.0 105.0
(°F) TONS KW MBH EER TONS KW MBH EER TONS KW MBH EER
YCWS0200SC
YCWS0220SC
YCWS0240SC
16.0 85.8 110.1 1406.0 9.4 77.4 130.4 1374.0 7.1 69.6 154.8 1364.0 5.4
20.0 96.7 114.5 1551.0 10.1 87.4 134.2 1507.0 7.8 78.8 157.9 1484.0 6.0
24.0 109.0 118.0 1710.0 11.1 98.9 137.3 1655.0 8.6 89.3 160.3 1618.0 6.7
28.0 124.4 121.0 1905.0 12.3 112.6 139.7 1827.0 9.7 101.5 162.0 1770.0 7.5
32.0 142.0 123.0 2123.0 13.8 128.5 141.3 2025.0 10.9 115.9 163.2 1948.0 8.5
36.0 161.4 124.3 2361.0 15.6 146.4 142.4 2243.0 12.3 132.8 164.0 2153.0 9.7
40.0 176.4 124.7 2542.0 17.0 160.2 142.7 2410.0 13.5 145.5 163.9 2306.0 10.7
16.0 93.6 121.6 1538.0 9.2 84.4 144.0 1504.0 7.0 75.9 170.9 1494.0 5.3
20.0 105.7 126.7 1701.0 10.0 95.3 148.3 1649.0 7.7 85.9 174.3 1625.0 5.9
24.0 119.4 130.6 1878.0 11.0 107.8 151.7 1811.0 8.5 97.3 177.0 1772.0 6.6
28.0 135.4 133.7 2081.0 12.2 121.9 154.2 1989.0 9.5 110.6 179.0 1938.0 7.4
32.0 154.6 136.0 2319.0 13.6 139.9 156.3 2212.0 10.7 126.8 180.5 2137.0 8.4
36.0 175.7 137.5 2577.0 15.3 159.4 157.5 2450.0 12.1 144.6 181.3 2353.0 9.6
40.0 192.0 138.0 2774.0 16.7 174.4 157.9 2631.0 13.3 157.8 181.3 2513.0 10.4
16.0 102.4 133.2 1683.0 9.2 92.3 157.7 1646.0 7.0 83.1 187.3 1636.0 5.3
20.0 114.9 138.4 1851.0 10.0 104.3 162.5 1806.0 7.7 94.0 191.0 1780.0 5.9
24.0 130.6 143.1 2055.0 10.9 117.8 166.2 1980.0 8.5 106.5 194.0 1940.0 6.6
28.0 148.1 146.6 2278.0 12.1 134.0 169.2 2185.0 9.5 121.1 196.3 2123.0 7.4
32.0 169.0 149.1 2536.0 13.6 153.1 171.4 2422.0 10.7 138.7 197.9 2340.0 8.4
36.0 191.9 150.8 2818.0 15.3 174.3 172.8 2681.0 12.1 158.1 198.9 2576.0 9.5
40.0 209.6 151.5 3032.0 16.6 190.6 173.3 2878.0 13.2 173.3 199.0 2758.0 10.4
NOTES:
1. Tons = Unit Cooling Capacity Output
2. kW = Compressor Input Power
3. MBH = Condenser heat rejection
4. EER = Chiller Energy Efficiency Ratio (Capacity [Tons x 12] ÷ kW)
5. LCWT = Leaving Chilled Water Temperature
6. Ratings based on 2.4 GPM cooler water per ton
22 JOHNSON CONTROLS
Ratings- Brine (30 % Ethylene Glycol) (R-22 SI)
LEAVING CONDENSER WATER TEMPERATURE (°C)
| LCWT | 30.0 | 35.0 | 40.0 | ||||||||||||
| (°C) | KWo | KWi | KW | COP | KWo | KWi | KW | COP | KWo | KWi | KW | COP |
YCWS0120SC
YCWS0140SC
YCWS0180SC
YCWS0100SC
-8.0 157.5 70.9 228.0 2.2 143.4 82.5 225.0 1.7 130.4 96.6 227.0 1.4 -6.0 175.7 72.0 247.0 2.4 160.3 83.0 243.0 1.9 145.9 96.2 242.0 1.5 -4.0 196.5 72.7 269.0 2.7 179.4 83.0 262.0 2.2 163.6 95.6 259.0 1.7 -2.0 220.4 72.9 293.0 3.0 201.4 82.8 284.0 2.4 183.9 94.8 278.0 1.9
0.0 248.2 72.9 321.0 3.4 227.2 82.4 309.0 2.8 207.8 93.8 301.0 2.2
2.0 279.6 72.6 352.0 3.9 256.2 81.7 338.0 3.1 234.8 92.8 327.0 2.5
4.0 303.0 71.8 374.0 4.2 278.0 80.7 358.0 3.4 255.0 91.4 346.0 2.8
-8.0 190.0 80.4 270.0 2.4 173.3 93.5 266.0 1.9 157.8 109.1 266.0 1.5 -6.0 211.8 82.5 294.0 2.6 193.3 95.0 288.0 2.0 176.3 110.0 286.0 1.6 -4.0 236.5 84.1 320.0 2.8 216.1 96.2 312.0 2.3 197.4 110.6 308.0 1.8 -2.0 264.9 85.3 350.0 3.1 242.4 97.0 339.0 2.5 221.7 111.0 332.0 2.0
0.0 297.9 86.1 384.0 3.5 273.1 97.5 370.0 2.8 250.1 111.0 361.0 2.3
2.0 335.2 86.6 421.0 3.9 307.6 97.7 405.0 3.2 282.2 110.9 393.0 2.5
4.0 362.9 86.5 449.0 4.2 333.4 97.5 430.0 3.4 306.2 110.4 416.0 2.8
-8.0 225.5 90.0 315.0 2.5 205.8 104.6 310.0 2.0 187.4 121.8 309.0 1.5 -6.0 251.1 93.1 344.0 2.7 229.4 107.3 336.0 2.1 209.3 124.0 333.0 1.7 -4.0 280.1 95.6 375.0 2.9 256.3 109.5 365.0 2.3 234.2 125.8 360.0 1.9 -2.0 313.6 97.7 411.0 3.2 287.1 111.3 398.0 2.6 262.8 127.3 390.0 2.1
0.0 352.3 99.3 451.0 3.6 323.2 112.7 435.0 2.9 296.2 128.4 424.0 2.3
2.0 395.9 100.6 496.0 3.9 363.7 113.8 477.0 3.2 333.9 129.2 463.0 2.6
4.0 428.4 101.2 529.0 4.2 393.9 114.3 508.0 3.5 362.2 129.5 491.0 2.8
-8.0 276.6 100.8 377.0 2.7 252.0 116.9 368.0 2.2 229.4 135.9 365.0 1.7 -6.0 308.6 104.1 412.0 3.0 281.7 119.8 401.0 2.4 256.3 138.2 394.0 1.9 -4.0 343.1 106.6 449.0 3.2 314.8 122.0 436.0 2.6 287.1 140.0 427.0 2.1 -2.0 386.9 108.8 495.0 3.6 354.4 123.8 478.0 2.9 322.7 141.4 464.0 2.3
0.0 436.3 110.3 546.0 4.0 398.9 125.0 524.0 3.2 364.7 142.3 507.0 2.6
2.0 492.0 111.3 603.0 4.4 450.2 125.9 576.0 3.6 412.3 142.9 555.0 2.9
4.0 533.4 111.7 645.0 4.8 488.6 126.1 614.0 3.9 447.9 142.9 590.0 3.1
NOTES:
1. KWo = Unit kW Cooling Capacity Output
2. KWi = Compressor kW Input
3. COP = Coefficient of Performance
4. LCWT= Leaving Chilled Water Temperature
5. Ratings based on 0.047 l/s cooler water per kW.
6. For ratings other than 30% glycol, refer to the Design 03 dxchill program.
23JOHNSON CONTROLS
LEAVING CONDENSER WATER TEMPERATURE (°C)
| LCWT | 30.0 | 35.0 | 40.0 | ||||||||||||
| (°C) | KWo | KWi | KW | COP | KWo | KWi | KW | COP | KWo | KWi | KW | COP |
YCWS0200SC
YCWS0220SC
YCWS0240SC
-8.0 313.6 113.8 427.0 2.8 285.6 132.0 417.0 2.2 259.9 153.5 413.0 1.7 -6.0 349.7 117.5 467.0 3.0 319.0 135.2 454.0 2.4 290.5 156.1 446.0 1.9 -4.0 387.5 120.3 507.0 3.2 356.5 137.8 494.0 2.6 325.5 158.2 483.0 2.1 -2.0 438.6 122.9 561.0 3.6 400.0 139.8 539.0 2.9 365.1 159.7 524.0 2.3
0.0 494.3 124.7 619.0 4.0 451.9 141.3 593.0 3.2 412.7 160.9 573.0 2.6
2.0 557.1 125.9 683.0 4.4 510.1 142.4 652.0 3.6 467.3 161.6 629.0 2.9
4.0 603.7 126.3 730.0 4.8 553.5 142.7 696.0 3.9 507.4 161.7 669.0 3.1
-8.0 341.6 125.7 467.0 2.7 311.4 145.8 457.0 2.1 283.4 169.5 453.0 1.7 -6.0 381.1 129.9 511.0 2.9 347.6 149.4 497.0 2.3 316.6 172.4 489.0 1.8 -4.0 424.2 133.1 557.0 3.2 387.9 152.2 540.0 2.6 354.6 174.8 529.0 2.0 -2.0 477.6 135.9 613.0 3.5 436.4 154.6 591.0 2.8 395.4 176.4 572.0 2.2
0.0 533.9 137.7 671.0 3.9 489.6 156.2 645.0 3.1 450.6 177.9 628.0 2.5
2.0 606.2 139.3 745.0 4.4 555.3 157.5 712.0 3.5 508.6 178.7 687.0 2.9
4.0 657.0 139.8 796.0 4.7 602.4 157.9 760.0 3.8 552.5 178.9 731.0 3.1
-8.0 373.8 137.7 511.0 2.7 340.8 159.7 500.0 2.1 310.2 185.7 496.0 1.7 -6.0 415.7 142.1 557.0 2.9 380.2 163.7 543.0 2.3 346.6 189.0 535.0 1.8 -4.0 466.0 146.0 612.0 3.2 425.4 166.9 592.0 2.6 387.9 191.5 579.0 2.0 -2.0 522.4 148.9 671.0 3.5 477.4 169.4 646.0 2.8 436.2 193.6 629.0 2.3
0.0 588.4 151.2 739.0 3.9 538.3 171.4 709.0 3.1 492.5 195.0 687.0 2.5
2.0 662.5 152.8 815.0 4.3 607.2 172.7 780.0 3.5 556.3 196.1 752.0 2.8
4.0 717.5 153.4 871.0 4.7 658.5 173.2 831.0 3.8 604.2 196.3 800.0 3.1
NOTES:
1. KWo = Unit kW Cooling Capacity Output
2. KWi= Compressor kW Input
3. COP = Coefficient of Performance
4. LCWT= Leaving Chilled Water Temperature
24 JOHNSON CONTROLS
Ratings- Brine (30 % Propylene Glycol) (R-22 English)
YCWS0120SC
YCWS0140SC
YCWS0180SC
YCWS0100SC
LEAVING CONDENSER WATER TEMPERATURE (°F)
| LCWT | 85.0 | 95.0 | 105.0 | ||||||||||||
| (°F) | TONS | KW | MBH | EER | TONS | KW | MBH | EER | TONS | KW | MBH | EER |
16.0 42.9 68.9 750.0 7.5 38.7 82.1 744.0 5.6 34.8 98.4 753.0 4.2
20.0 48.4 70.5 821.0 8.2 43.7 82.8 807.0 6.3 39.4 98.0 807.0 4.8
24.0 54.7 71.5 900.0 9.2 49.5 83.1 877.0 7.1 44.7 97.4 868.0 5.5
28.0 62.1 71.9 990.0 10.4 56.2 82.9 957.0 8.1 50.8 96.4 939.0 6.3
32.0 70.8 72.0 1095.0 11.8 64.2 82.4 1052.0 9.3 58.2 95.3 1023.0 7.3
36.0 80.5 71.6 1210.0 13.5 73.1 81.7 1156.0 10.7 66.4 94.0 1117.0 8.5
40.0 87.9 70.8 1297.0 14.9 80.0 80.6 1234.0 11.9 72.7 92.5 1188.0 9.4
16.0 42.9 68.9 750.0 7.5 38.7 82.1 744.0 5.6 34.8 98.4 753.0 4.2
20.0 48.4 70.5 821.0 8.2 43.7 82.8 807.0 6.3 39.4 98.0 807.0 4.8
24.0 54.7 71.5 900.0 9.2 49.5 83.1 877.0 7.1 44.7 97.4 868.0 5.5
28.0 62.1 71.9 990.0 10.4 56.2 82.9 957.0 8.1 50.8 96.4 939.0 6.3
32.0 70.8 72.0 1095.0 11.8 64.2 82.4 1052.0 9.3 58.2 95.3 1023.0 7.3
36.0 80.5 71.6 1210.0 13.5 73.1 81.7 1156.0 10.7 66.4 94.0 1117.0 8.5
40.0 87.9 70.8 1297.0 14.9 80.0 80.6 1234.0 11.9 72.7 92.5 1188.0 9.4
16.0 61.3 86.7 1031.0 8.5 55.4 103.0 1016.0 6.4 49.9 122.6 1017.0 4.9
20.0 69.0 90.4 1136.0 9.2 62.4 106.2 1111.0 7.0 56.4 125.2 1104.0 5.4
24.0 77.9 93.5 1253.0 10.0 70.5 108.9 1218.0 7.8 63.8 127.3 1200.0 6.0
28.0 88.1 95.9 1384.0 11.0 80.0 111.0 1338.0 8.6 72.5 128.9 1310.0 6.7
32.0 100.2 97.8 1537.0 12.3 91.1 112.6 1478.0 9.7 82.8 130.2 1438.0 7.6
36.0 113.7 99.2 1702.0 13.7 103.5 113.8 1630.0 10.9 94.2 131.0 1577.0 8.6
40.0 124.1 99.9 1829.0 14.9 113.1 114.3 1747.0 11.9 103.1 131.3 1685.0 9.4
16.0 75.4 97.4 1237.0 9.3 68.0 115.3 1209.0 7.1 61.1 136.9 1200.0 5.4
20.0 85.1 101.4 1368.0 10.1 77.0 118.8 1329.0 7.8 69.2 139.7 1307.0 5.9
24.0 96.3 104.6 1513.0 11.1 87.0 121.5 1458.0 8.6 78.5 141.8 1425.0 6.6
28.0 109.4 107.0 1678.0 12.3 98.9 123.5 1608.0 9.6 89.4 143.3 1562.0 7.5
32.0 124.9 108.8 1870.0 13.8 113.1 125.0 1783.0 10.9 102.3 144.4 1721.0 8.5
36.0 142.1 109.9 2080.0 15.5 128.8 125.9 1975.0 12.3 116.7 145.0 1895.0 9.7
40.0 155.3 110.2 2240.0 16.9 141.0 126.1 2123.0 13.4 127.8 144.9 2028.0 10.6
NOTES:
1. Tons = Unit Cooling Capacity Output
2. kW = Compressor Input Power
3. MBH = Condenser heat rejection
4. EER = Chiller Energy Efficiency Ratio (Capacity [Tons x 12] ÷ kW)
5. LCWT = Leaving Chilled Water Temperature
6. Ratings based on 2.4 GPM cooler water per ton
25JOHNSON CONTROLS
YCWS0200SC
YCWS0220SC
YCWS0240SC
16.0 85.5 109.9 1401.0 9.3 77.0 130.2 1368.0 7.1 69.3 154.7 1359.0 5.4
20.0 96.7 114.5 1551.0 10.1 87.0 134.1 1502.0 7.8 78.5 157.8 1481.0 6.0
24.0 109.2 118.1 1713.0 11.1 98.6 137.2 1651.0 8.6 89.0 160.2 1614.0 6.7
28.0 123.9 120.9 1900.0 12.3 112.1 139.6 1821.0 9.6 101.3 162.0 1768.0 7.5
32.0 141.4 122.9 2116.0 13.8 128.1 141.3 2020.0 10.9 116.0 163.2 1949.0 8.5
36.0 160.8 124.3 2353.0 15.5 145.9 142.4 2237.0 12.3 132.4 164.0 2148.0 9.7
40.0 175.6 124.7 2533.0 16.9 159.7 142.7 2403.0 13.4 145.1 163.9 2300.0 10.6
16.0 93.2 121.4 1532.0 9.2 84.0 143.8 1498.0 7.0 75.6 170.7 1489.0 5.3
20.0 105.2 126.5 1693.0 10.0 94.2 147.9 1635.0 7.6 85.5 174.2 1621.0 5.9
24.0 118.9 130.5 1873.0 10.9 107.4 151.6 1806.0 8.5 97.0 176.9 1767.0 6.6
28.0 135.0 133.6 2076.0 12.1 122.1 154.3 1991.0 9.5 110.4 179.0 1935.0 7.4
32.0 154.0 136.0 2312.0 13.6 139.5 156.2 2207.0 10.7 126.4 180.4 2132.0 8.4
36.0 175.0 137.5 2569.0 15.3 158.9 157.5 2444.0 12.1 144.2 181.3 2349.0 9.5
40.0 191.2 138.0 2765.0 16.6 173.8 157.9 2624.0 13.2 158.0 181.3 2514.0 10.5
16.0 102.0 133.0 1678.0 9.2 91.9 157.5 1641.0 7.0 82.7 187.1 1631.0 5.3
20.0 115.1 138.5 1854.0 10.0 103.9 162.3 1801.0 7.7 93.6 190.9 1774.0 5.9
24.0 130.1 143.0 2049.0 10.9 117.5 166.1 1977.0 8.5 106.1 193.9 1935.0 6.6
28.0 147.6 146.5 2271.0 12.1 133.6 169.1 2180.0 9.5 120.4 196.2 2115.0 7.4
32.0 168.3 149.1 2528.0 13.5 152.6 171.3 2415.0 10.7 138.3 197.9 2334.0 8.4
36.0 191.1 150.8 2807.0 15.2 173.6 172.8 2673.0 12.1 157.6 198.9 2570.0 9.5
40.0 208.6 151.5 3020.0 16.5 189.8 173.2 2869.0 13.1 172.7 199.0 2751.0 10.4
LEAVING CONDENSER WATER TEMPERATURE (°F)
| LCWT | 85.0 | 95.0 | 105.0 | ||||||||||||
| (°F) | TONS | KW | MBH | EER | TONS | KW | MBH | EER | TONS | KW | MBH | EER |
NOTES:
1. Tons = Unit Cooling Capacity Output
2. kW = Compressor Input Power
3. MBH = Condenser heat rejection
4. EER = Chiller Energy Efficiency Ratio (Capacity [Tons x 12] ÷ kW)
5. LCWT = Leaving Chilled Water Temperature
6. Ratings based on 2.4 GPM cooler water per ton
26 JOHNSON CONTROLS
LEAVING CONDENSER WATER TEMPERATURE (°C)
| LCWT | 30.0 | 35.0 | 40.0 | ||||||||||||
| (°C) | KWo | KWi | KW | COP | KWo | KWi | KW | COP | KWo | KWi | KW | COP |
YCWS0200SC
YCWS0220SC
YCWS0240SC
-8.0 312.2 113.7 425.0 2.8 284.3 131.8 416.0 2.2 258.6 153.4 412.0 1.7 -6.0 348.5 117.4 465.0 3.0 317.8 135.1 453.0 2.4 289.2 156.0 445.0 1.9 -4.0 389.6 120.5 510.0 3.2 355.5 137.7 493.0 2.6 324.2 158.1 482.0 2.1 -2.0 437.1 122.8 560.0 3.6 400.5 139.8 540.0 2.9 364.6 159.7 524.0 2.3
0.0 492.4 124.6 617.0 4.0 450.5 141.3 591.0 3.2 412.0 160.9 572.0 2.6
2.0 554.8 125.8 680.0 4.4 508.3 142.3 650.0 3.6 465.5 161.6 627.0 2.9
4.0 601.2 126.3 727.0 4.8 551.5 142.7 694.0 3.9 505.8 161.7 667.0 3.1
-8.0 340.3 125.5 465.0 2.7 310.4 145.7 456.0 2.1 282.1 169.4 451.0 1.7 -6.0 379.6 129.7 509.0 2.9 346.2 149.2 495.0 2.3 315.3 172.3 487.0 1.8 -4.0 424.5 133.1 557.0 3.2 387.4 152.2 539.0 2.6 353.4 174.7 528.0 2.0 -2.0 476.0 135.8 611.0 3.5 435.0 154.5 589.0 2.8 396.6 176.5 573.0 2.3
0.0 536.2 137.8 674.0 3.9 490.5 156.2 646.0 3.1 448.2 177.8 626.0 2.5
2.0 603.9 139.2 743.0 4.3 553.5 157.4 711.0 3.5 507.1 178.7 685.0 2.8
4.0 654.3 139.8 794.0 4.7 600.4 157.9 758.0 3.8 550.7 178.9 729.0 3.1
-8.0 373.2 137.6 510.0 2.7 339.4 159.5 499.0 2.1 308.7 185.6 494.0 1.7 -6.0 415.5 142.1 557.0 2.9 379.2 163.6 542.0 2.3 345.2 188.8 534.0 1.8 -4.0 464.4 145.9 610.0 3.2 423.9 166.8 590.0 2.5 386.3 191.4 577.0 2.0 -2.0 520.5 148.8 669.0 3.5 475.9 169.4 645.0 2.8 434.9 193.5 628.0 2.3
0.0 586.0 151.1 737.0 3.9 536.5 171.3 707.0 3.1 491.0 195.0 686.0 2.5
2.0 659.5 152.7 812.0 4.3 604.9 172.7 777.0 3.5 554.5 196.0 750.0 2.8
4.0 714.2 153.4 867.0 4.7 655.9 173.2 829.0 3.8 602.1 196.3…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .