This document is a detailed product specification sheet for Kohler's KCS/KCP/KCC Model Automatic Transfer Switches (ATS), which are standard any breaker rated switches designed for emergency and standby power applications. The switches are available in three transition types (standard, programmed, and closed-transition) with current ratings from 30-4000 amps, compatible with 208-600 VAC and 50/60 Hz systems. Key features include UL 1008 listing, CSA certification availability, IBC and OSHPD seismic certification, and configurations in 2, 3, or 4 pole options with integral solid neutral monitoring.
The document provides comprehensive technical specifications, including two available controllers (Decision-Maker® MPAC 1200 and MPAC 1500), detailed withstand and close-on ratings for various circuit breaker manufacturers, weights and dimensions for different models, and an extensive list of optional accessories. The transfer switches can be customized through a complex model designation system that allows selection of mechanism, transition type, controller, voltage/frequency, poles, enclosure, current rating, and connection type. Accessories include digital meters, surge protection devices, extended warranties, seismic certifications, and communication modules, making these switches adaptable to various industrial and commercial power infrastructure requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Model - KCS/KCP/KCC
Automatic Transfer Switches Standard Any Breaker Rated
G11-142_9/24l
Discovery Energy, LLC
200 Twin Oaks Road, Kohler, WI 53044 USA For the nearest sales and service outlet in the US and
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 1/16
Available Controllers
• Decision-Maker® MPAC 1200
• Decision-Maker® MPAC 1500
Ratings Model Current Voltage, Frequency
KCS 30-4000 amps
208-600 VAC
50/60 Hz KCP 150-4000 amps
KCC 150-4000 amps
Transfer Switch Standard Features
• UL 1008 listed file #E58962 (automatic), #E86894 (nonautomatic)
• CSA certification available
• IBC and OSHPD seismic certification available
• Available in 2, 3, or 4 pole configurations
• Integral solid neutral provides line-to-neutral monitoring
• Electrically operated, mechanically held mechanism
• High withstand and close-on ratings
• Design suitable for emergency and standby applications on all classes of load, 100% tungsten rated through 400 amps
• Silver alloy main contacts
• Gold-flashed engine start contacts rated 2 amps
@ 30 VDC/250 VAC
• Front-accessible contacts for easy inspection
• Front-replaceable main and arcing contacts (800-4000 amps)
• Reliable, field-proven solenoid mechanism
• Switching mechanisms lubricated for the expected life of the transfer switch
• Internal manual operating handle
• Main shaft auxiliary position-indicating contacts rated 10 amps @ 32 VDC/250 VAC
• NEMA type 1, 12, 3R, 4, and 4X enclosures available
• Standard one-year limited warranty. Extended limited warranties are available.
Standard-Transition Models (KCS)
• Standard-transition operation with either automatic or non-automatic control
• Standard-transition transfer time less than 100 milliseconds (6 cycles @ 60 Hz)
• Double-throw, mechanically interlocked design (break-before-make power contacts)
• Solid, switched, or overlapping (make-before-break) neutral
Programmed-Transition Models (KCP)
• Programmed-transition operation with either automatic or non-automatic control
• Programmed-transition operation provides a center OFF position that allows residual voltages in the load circuits to decay
• Programmable OFF time
• Double-throw, mechanically interlocked design (break-before-make power contacts)
• Solid or switched neutral
Closed-Transition Models (KCC)
• Closed-transition transfer switches operate with no power interruption during transfer and retransfer between two live sources
• Source parallel times are less than 100 milliseconds (6 cycles @ 60 Hz)
• Adjustable extended transfer time relay (ensure that the setting complies with applicable codes)
• Solid or switched neutral
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 2/16
Available Automatic Transfer Switch Controllers Select one of the following controllers for your automatic transfer switch.
Decision-Maker® MPAC 1200 Controller Decision-Maker® MPAC 1500 Controller
• LCD display, 4 lines x 20 characters, backlit • LCD display, 4 lines x 20 characters, backlit
• Complete programming and viewing capability at the door using the keypad and LCD display
• Complete programming and viewing capability at the door using the keypad and LCD display
• LED indicators: Source available, transfer switch position, service required (fault), and “not in auto”
• LED indicators: Source available, transfer switch position, service required (fault), and “not in auto”
• Programmable voltage and frequency pickup and dropout settings
• Programmable voltage and frequency pickup and dropout settings
• Programmable time delays • Programmable time delays
• Programmable generator exerciser • Programmable generator exerciser
• Time-based load control • Time-based load control
• Two programmable inputs and two programmable outputs • Current-based load control (current-sensing kit required)
• Up to four I/O extension modules available • Two programmable inputs and two programmable
• Modbus communication standard outputs
• RS-485 communication standard • Up to four I/O extension modules available
• Ethernet communication optional • Modbus communication standard
• For more information about Decision-Maker® MPAC 1200 features and functions, see specification sheet G11-127.
• RS-485 communication standard
• Ethernet communication standard
• Three-source system
• Prime power
For more information about Decision-Maker® MPAC 1500 features and functions, see specification sheet G11-128.
Codes and Standards The ATS meets or exceeds the requirements of the following specifications:
• IEEE 472 (ANSI C37.90A) Ring Wave Test
• NEMA Standard ICS 10-2005, Electromechanical AC
• CSA C22.2 No. 178 certification available, file #LR58301 Transfer Switch Equipment
• EN61000-4-4 Fast Transient Immunity Severity Level 4 • NFPA 70, National Electrical Code
• EN61000-4-5 Surge Immunity Class 4 (voltage sensing and programmable inputs only)
• NFPA 99, Essential Electrical Systems for Health Care Facilities
• IEC Specifications for EMI/EMC Immunity: • NFPA 110, Emergency and Standby Power Systems o CISPR 11, Radiated Emissions • Seismic certification in accordance with the International Building Code is available. (Accessory kit is required for seismic certification.)
o IEC 1000-4-2, Electrostatic Discharge o IEC 1000-4-3, Radiated Electromagnetic Fields o IEC 1000-4-4, Electrical Fast Transients (Bursts) o IBC 2000, referencing ASCE 7-98 and ICC AC-156 o IEC 1000-4-5, Surge Voltage o IBC 2003, referencing ASCE 7-02 and ICC AC-156 o IEC 1000-4-6, Conducted RF Disturbances o IBC 2006, referencing ASCE 7-05 and ICC AC-156 o IEC 1000-4-8, Magnetic Fields o IBC 2009, referencing ASCE 7-05 and ICC AC-156 o IEC 1000-4-11, Voltage Dips and Interruptions o IBC 2012, referencing ASCE 7-10 and ICC AC-156
• IEEE Standard 446, IEEE Recommended Practice for • California OSHPD approval is available.
(Accessory kit required.) Emergency and Standby Power Systems for Commercial and Industrial Applications • Underwriters Laboratories UL 1008, Standard for Automatic Transfer Switches for Use in Emergency Standby Systems file #E58962 (automatic), #E86894 (nonautomatic)
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 3/16
Application Data
Environmental Specifications
Operating Temperature - 20°C to 70°C (- 4°F to 158°F)
Storage Temperature - 40°C to 85°C (- 40°F to 185°F)
Humidity 5% to 95% noncondensing
Input and Output Connection Specifications
Component Wire Size Range
Main board I/O terminals #12-24 AWG
I/O module terminals #14-24 AWG
Auxiliary Position Indicating Contacts (rated 10 amps @ 32 VDC/250 VAC)
Switch Rating, Amps
Number of Contacts Indicating Normal, Emergency
KCS KCP KCC
30-230 2, 2 N/A N/A
260-600 8, 8 — —
150-600 — 8, 8 7, 7
800-1200 8, 8 8, 8 7, 7
1600-4000 8, 8 7, 7 6, 6
Extended Transfer Time Adjustable Relay (Model KCC only)
Power 12 or 24 VDC (customer-supplied)
Connections 12-20 AWG
Output type Relay contacts, DPDT (2 form C)
Rating 10 amps max. resistive at 240 VAC
Note:
Customer-supplied shunt trip on emergency source circuit breaker is required.
Source Synchronization Settings (Model KCC)
Parameter Default Adjustment
Range
Voltage differential 5% 0-5%
Frequency differential 0.1 Hz 0-0.3 Hz
Phase angle 10 deg. 0-10 deg.
Cable Sizes Note:
Cable size data is subject to change. Refer to the transfer switch dimension drawings and wiring diagrams for planning and installation.
UL-Listed Solderless Screw-Type Terminals for External Power Connections
Range of Wire Sizes, Copper or Aluminum‡
Model Switch Rating, Amps Normal, Emergency, and Load
(per phase) Neutral (3-pole) Ground
KCS
30-150 (1) #14 AWG to 4/0 AWG (3) #14 to 4/0 AWG (3) #6 to 3/0
(1) #14 AWG to 4/0 AWG Cu only (3) #14 to 4/0 AWG Cu only (3) #6 to 3/0
230 (208-480 V)
230 (600 V) (1) #4 AWG to 600 KCMIL or
(2) 1/0 to 250 KCMIL
(3) #4 AWG to 600 KCMIL or
(6) 1/0 to 250 KCMIL
(3) #4 AWG to 600 KCMIL or
(6) 1/0 to 250 KCMIL 260-400
KCP
KCC
150-400
(1) #4 AWG to 600 KCMIL or
(2) 1/0 to 250 KCMIL
(3) #4 AWG to 600 KCMIL or
(6) 1/0 to 250 KCMIL
(3) #4 AWG to 600 KCMIL or
(6) 1/0 to 250 KCMIL
KCS
KCP
KCC
600 (2) #2 AWG to 600 KCMIL (6) #2 AWG to 600 KCMIL
(3) #4 AWG to 600 KCMIL or
(6) 1/0 to 250 KCMIL 800-1000
(4) 1/0 AWG to 750 KCMIL (12) 1/0 AWG to 750 KCMIL
1200 (NEMA 3R)
1200 (NEMA 1) (4) 1/0 AWG to 750 KCMIL (12) 1/0 AWG to 750 KCMIL (3) #4 to 500 KCMIL
1600-2000 F †
(NEMA 3R)
(6) 1/0 AWG to 750 KCMIL (18) 1/0 AWG to 750 KCMIL
(3) #4 AWG to 600 KCMIL or
(6) 1/0 to 250 KCMIL
1600-2000 (6) 1/0 AWG to 750 KCMIL (18) 1/0 AWG to 750 KCMIL
(3) #4 to 500 KCMIL
2600-3000 (12) 1/0 AWG to 750 KCMIL (36) 1/0 AWG to 750 KCMIL
4000 (12) 1/0 AWG to 750 KCMIL (36) 1/0 AWG to 750 KCMIL (18) 1/0 AWG to 750 KCMIL
† F = Front connected ‡ Use 75ºC minimum Cu/Al wire for power connections.
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 4/16
Withstand and Close-On Ratings (WCR)
Standard, Programmed, and Closed-Transition Models
Maximum current in RMS symmetrical amperes when coordinated with customer-supplied fuses or circuit breakers. All values are available symmetrical RMS amperes and tested in accordance with the withstand and close-on requirements of UL 1008. Application requirements may permit higher withstand ratings for certain size switches. Contact the factory for assistance.
Model
Switch Rating, Amps
Withstand Current Ratings in RMS Symmetrical Amperes Short Time Ratings (sec.) ‡
Current-Limiting Fuses Time-Based Rating * 480 V Max. 600 V Max.
480 V Max.
600 V Max.
Amps, Max.
Fuse Class
Time, sec.
240 V, Max
480 V, Max
600 V, Max .13 .2 .3 .5 .1 .13 .3 .5
KCS
100kA — 300 J
0.025 10kA 10kA 10kA
200kA 35kA 200 J — —
35kA 35kA 200 RK1 — —
200kA 35kA 200 J 0.025 10kA 10kA 10kA — —
35kA 35kA 200 RK1 0.025 10kA 10kA 10kA — —
200kA 35kA 200 J
0.025 10kA 10kA 10kA
35kA 35kA 200 RK1 — —
(480V)
100kA — 300 J 0.025 10kA 10kA — — —
(600V)
200kA 200kA 600 J
0.05 65kA 42kA † 35kA 7500A
800 L — —
KCP
KCC
150 200kA 200kA 600 J 0.05 65kA 42kA † 35kA 7500A — —
800 L 0.05 65kA 42kA † 35kA 7500A — —
KCP 225 200kA 200kA 600 J 0.05 65kA 42kA † 35kA 7500A — —
800 L 0.05 65kA 42kA † 35kA 7500A — —
KCS
KCP
KCC
200kA 200kA 600 J 0.05 65kA 42kA † 35kA 7500A — —
800 L 0.05 65kA 42kA † 35kA 7500A — —
600 200kA 200kA 600 J 0.05 65kA 42kA † 35kA — — —
800 L 0.05 65kA 42kA.† 35kA — — —
800-
200kA 200kA 1600 L 0.05 50kA 50kA 50kA 36kA — 36kA —
1600- 2000 F
200kA 200kA 2500 L 0.05 85kA 85kA 85kA 42kA 36kA —
1600- 2000 S
200kA 200kA 3000 L 0.05 100kA 100kA 100kA 42kA 36kA 42kA —
200kA 200kA 4000 L 0.05 100kA 100kA 100kA 42kA 36kA 42kA —
4000 200kA 200kA 5000 L 0.05 100kA 100kA 100kA 85kA 65kA 65kA
* Applicable to breakers with instantaneous trip elements.
† Applicable to 2-pole, 3-pole, and conventional 4-pole switches only. Overlapping neutral switches have “any” breaker ratings of 35kA, 0.050 seconds at 480 V.
‡ Short time ratings are provided for applications involving breakers that utilize trip delay settings for system selective coordination.
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 5/16
Ratings with Specific Manufacturers’ Circuit Breakers
The following charts list power switching device withstand and close-on ratings (WCR) in RMS symmetrical amperes for specific manufacturers’ circuit breakers. Circuit breakers are supplied by the customer.
Model
Switch Rating, amps
WCR,
amps
RMS
Volts, Max.
Molded-Case Circuit Breakers
Manufacturer Type or Class Max. Size, amps
KCS
22,000
GE THED 40
25,000 Siemens/ITE ITE CED6 125
150,000
240 Square D
HR 250
125,000 HL 150
100,000 BJ, HJ 125
65,000 BG, HG 125
42,000 QG, QJ 90
25,000 HD 150
25,000 BD 125
22,000
GE THED 90
85,000
Square D
HL, HR 150
50,000 BJ 125
35,000
HG, HJ 150
BG 125
18,000 BD, HD 125
25,000
600 Square D
HJ, HL, HR 150
BJ 125
18,000
HG 150
BG 125
14,000
HD 150
BD 125
KCS 104
150,000
240 Square D
HR 250
125,000 HL 150
100,000 BJ, HJ 125
65,000 BG, HG 125
42,000 QG, QJ 125
25,000
HD 150
BD 125
22,000
GE THED 150
85,000
Square D
HL, HR 150
50,000 BJ 125
35,000
HG, HJ 150
BG 125
18,000 BD, HD 125
25,000
600 Square D
HJ, HL, HR 150
BJ 125
18,000
HG 150
BG 125
14,000
HD 150
BD 125
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 6/16
Rating, amps
WCR, amps
RMS
Volts, Max.
Molded-Case Circuit Breakers
Manufacturer Type or Class Max. Size, amps
KCS 150
150,000
240 Square D
HR 250
125,000 HL 150
100,000 BJ, HJ 125
65,000
JG, JJ, JL, JR 200
BG, HG 125
42,000 QG, QJ 200
25,000
HD 150
BD 125
22,000
GE THED 150
85,000
Square D
HL, HR 150
50,000 BJ 125
35,000
HG, HJ 150
BG 125
25,000 JG, JJ, JL 200
18,000 BD, HD 125
25,000
600 Square D
HJ, HL, HR 150
BJ 125
18,000
HG 150
BG 125
14,000
HD 150
BD 125
KCS
200,000
240 Square D
JR 250
125,000 JL 250
100,000 JJ 250
65,000 JG 250
42,000 QG, QJ 225
25,000 JD 250
85,000
Square D JL, JR 250
30,000 JG, JJ 250
18,000 JD 250
200 14,000 600 Square D JD, JG, JJ, JL, JR 250
42,000
Eaton/Cutler Hammer
JGU, JGX, JGH 250
KDC 400
LDC, CLDC 600
GE
TBC4 400
SGL1, SGL4, SGL6, SGP1, SGP4, SGP6, FGP 600
Siemens/ITE
HJD, CFD6 250
HHJD6, HHJXD6, CJD6, SCJD6 400
HHLD6, HHLXD6, CLD6, SCLD6, LNG, LPG, LGC*,LGU*,
LGX*
Square D
HJ, HL, HG 150
KI, JJ, JL, JR, CF250L 250
CK400H, CK400HH, CJ400L 400
CK800H, CK800HH, MasterPact STR 28D, PK 800
50,000 LL (current limiting) 600
100,000 LR (current limiting) 600
65,000 Eaton/Cutler Hammer
PD3 (current limiting) 600
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 7/16
Rating, amps
WCR, amps
RMS
Volts, Max.
Molded-Case Circuit Breakers
Manufacturer Type or Class Max. Size, amps
KCP
KCC
225 §
65,000
GE
THQMV 225
SGL1, SGL4, SGL6, SGP1, SGP4, SGP6 600
Eaton/Cutler Hammer
LDC, CLDC, HLD, CHLD 600
Siemens/ITE HLD6, HLXD6 600
Square D QG, QJ 250
100,000
Square D
LJ (current limiting) 600
125,000 LL (current limiting) 600
200,000
LR (current limiting) 600
Eaton/Cutler Hammer
PD2 (current limiting) 225
PD3 (current limiting) 600
50,000
Eaton/Cutler Hammer
HFDE, FDC, FDCE 225
NHH 250
JDC, JGU, JGX 350
HKD, CHKD, KDC, HKDB, CHKDB, LHH 400
HLD,CHLD, LDC, CLDC, LGH*, LGC*, LGU*, LGX* 600
HMDLB, CHMDLB 800
GE
SEL, SEP 150
SFL, SFP, FEN, FEH 250
TBC4 400
FGN, FGH, FGL, FGP, SGL1, SGL4, SGL6, SGP1, SGP4,
SGP6. TJL4V, TJL1S- 6S, TBC6
TB8 800
Siemens/ITE
HDG, LDG 150
HFD, HFD6, HFXD, HFXD6, HHFD6, HHFXD6, CFD6, HFG,
LFG
HJD, HJD6, HJXD, HJXD6, SHJD, SHJD6, HHJD6, HHJXD6,
CJD6, SCJD6, HJG, LJG, LLG
HLD6, HLXD6, HHLD6, HHLXD6, CLD6, SHLD6, SCLD6, HLG 600
Square D
HJ, HL 150
KC, KI, CF250L, NSF250 250
CK400N, CK400NN, CK400H, CK400HH, CJ400L, NSJ400 400
LC, DJ, DL, LI, NSJ600 600
MasterPact STR 28D, PK, PJ, PL 800
65,000 JJ (current limiting) 250
LJ (current limiting) 600
100,000
JL (current limiting) 250
LL (current limiting) 600
Eaton/Cutler Hammer
PD2 (current limiting) 225
PD3 (current limiting) 600
200,000 Square D JR (current limiting) 250
LR (current limiting) 600
42,000
Eaton/Cutler Hammer
JGU, JGX, JGH 250
KDC 400
LDC, CLDC 600
GE
TBC4 400
SGL1, SGL4, SGL6, SGP1, SGP4, SGP6, FGP 600
Siemens/ITE
HJD, CFD6 250
HHJD6, HHJXD6, CJD6, SCJD6 400
HHLD6, HHLXD6, CLD6, SCLD6, LNG, LPG, LGC*, LGU*,
LGX*
Square D
HJ, HL, HG 150
KI, JJ, JL, JR, CF250L 250
CK400H, CK400HH, CJ400L 400
LI, MasterPact STR 28D, PK 600
50,000 LL (current limiting) 600
65,000 Eaton/Cutler Hammer
PD3 (current limiting) 600
100,000 Square D LR (current limiting) 600
* With Digitrip 310+ LS or LSG Inst. Override set to 12X.
§ KCP only
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 8/16
Rating, amps
WCR, amps
RMS
Volts, Max.
Molded-Case Circuit Breakers
Manufacturer Type or Class Max. Size, amps
KCS
KCP
KCC
65,000
GE
THQMV 225
SGL1, SGL4, SGL6, SGP1, SGP4, SGP6 600
Eaton/Cutler Hammer
LDC, CLDC, HLD, CHLD 600
65,000 Siemens/ITE HLD6, HLXD6 600
Square D
QG, QJ 250
100,000 LJ (current limiting) 600
125,000 LL (current limiting) 600
200,000
LR (current limiting) 600
Eaton/Cutler Hammer
PD2 (current limiting) 225
PD3 (current limiting) 600
50,000
Eaton/Cutler Hammer
HFDE, FDCE, HFD, FDC, LHH 225
JDC, JGH, JGC, JGU, JGX 250
HKD, HKDB, CHKD, CHKDB, KDC 400
HLD,CHLD, LDC, CLDC, LGH*, LGC*, LGU*, LGX*, NHH 600
MDL, CMDL, HMDL, CHMDL, NGS, NGH, NGC, MDLB,
CMDLB, HMDLB, CHMDLB
GE
SFL, SFP, FEN, FEH 250
TBC4 400
TBC6, TJL4V, TJL1S- 6S, SGL1, SGL4, SGL6, SGP1, SGP4,
SGP6, FGN, FGH, FGL, FGP
TBC8, TKL4V, TKH8S- 12S, TKL8S- 12S, SKH8, SKL8, SKP8,
TB8
Siemens/ITE
HFD6, HFXD6, HHFD6, HHFXD6, CFD6, HFG, LFG 250
HJD6, HJXD6, SHJD6, HHJD6, HHJXD6, CJD6, SCJD6, HJG,
LJG, LLG
HLD6, HLXD6, SHLD6, HHLD6, HHLXD6, CLD6, SCLD6, HLG 600
LMD, LMD6, LMXD, LMXD6, HLMD, HLMD6, HLMXD,
HLMXD6, MD, MD6, MXD6, HMG, HMD6, HMXD6, SMD6,
SHMD6, CMD6, SCMD6, LMG, MG
Square D
KI, KC, CF250L, NSF250 250
CK400N, CK400NN, CK400H, CK400HH, CJ400L, NSJ400 400
LC, DJ, DL, LJ, LL, LR, LI, NSJ600 600
CK800N, CK800NN, CK800H, CK800HH, MasterPact STR
28D, MJ, PK, PJ, PL
CK1000HL 1000
CK1200NN, CK1200HH 1200
65,000 JJ (current limiting) 250
LJ (current limiting) 600
100,000 JL (current limiting) 250
LL (current limiting) 600
200,000
JR (current limiting) 250
LR (current limiting) 600
Eaton/Cutler Hammer
PD2 (current limiting) 225
PD3 (current limiting) 600
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 9/16
Rating, amps
WCR, amps
RMS
Volts, Max.
Molded-Case Circuit Breakers
Manufacturer Type or Class Max. Size, amps
KCS
KCP
KCC
42,000
Eaton/Cutler Hammer
JGU, JGX 250
KDC 400
LDC, CLDC 600
GE
TBC4 400
TBC6, SGL1, SGL4, SGL6, SGP1, SGP4, SGP6, FGP 600
TBC8, TKL4V, TKL8S- 12S, SKL8, SKP8 800
Siemens/ITE
HJD, CFD6 250
HHJD6, HHJXD6, CJD6, SCJD6 400
HHLD6, HHLXD6, CLD6, SCLD6 600
HLMD6, HLMXD6, HMXD6, SHMD6, HMD6, CMD6, SCMD6,
LMG, LNG, LPG, LGC*, LGU*, LGX*
Square D
KI, JL, JR, JJ, CF250L 250
CK400H, CK400HH, CJ400L 400
LI 600
CK800H, CK800HH, MasterPact STR 28D, PK 800
50,000 LL (current limiting) 600
65,000 Eaton/Cutler Hammer
PD3 (current limiting) 600
100,000 Square D LR (current limiting) 600
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 10/16
Rating, amps
WCR,
amps RMS
Volts, Max.
Molded-Case Circuit Breakers
Manufacturer Type or Class Max. Size, amps
KCS
KCP
KCC
65,000
GE
THQMV 225
SGL1, SGL4, SGL6, SGP1, SGP4, SGP6 600
Eaton/Cutler Hammer
LDC, CLDC, HLD, CHLD 600
200,000 PD2 (current limiting) 225
PD3 (current limiting) 600
65,000 Siemens/ITE HLD6, HLXD6 600
Square D
QG, QJ 250
100,000 LJ (current limiting) 600
125,000 LL (current limiting) 600
200,000 LR (current limiting) 600
50,000
Eaton/Cutler Hammer
JGH, JGC, NHH 250
HKD, CHKD, KDC, HKDB, CHKDB, LHH 400
CHLD, LDC, CLDC, LGH*, LGC*, LGU*, LGX* 600
MDL, CMDL, HMDL, CHMDL, NGS, NGH, NGC, MDLB, CMDLB,
HMDLB, CHMDLB
NGU 1600
GE
TBC4 400
TBC6, TJL4V, TJL1S- 6S, SGL1, SGL4, SGL6, SGP1, SGP4,
SGP6, FGN, FGH, FGL, FGP
TBC8, TKL4V, TKH8S- 12S, TKL8S- 12S, SKH8, SKL8, SKP8,
TB8
Siemens/ITE
HFD6, HFXD6, HFG, LFG 250
HJD6, HJXD6, SHJD6, HHJD6, HHJXD6, CJD6, SCJD6, HJG,
LLG, LJG
HLD6, HLXD6, SHLD6, HHLD6, HHLXD6, CLD6, SCLD6, HLG 600
LMD6, LMXD6, HLMD6, HLMXD6, MD6, MXD6, HMD6, HMXD6,
SMD6, SHMD6, CMD6, SCMD6, HMG, LMG
Square D
CK400N, CK400NN, CK400H, CK400HH, CJ400L, NSJ400 400
LC, DJ, DL, LJ, LL, LR, LI, NSJ600 600
CK800N, CK800NN, CK800H, CK800HH, MJ 800
CK1000HH 1000
PK, PJ, PL, MH, MasterPact STR 28D, CK1200HH 1200
65,000 LJ (current limiting) 600
100,000 LL (current limiting) 600
200,000 LR (current limiting) 600
100,000 Eaton/Cutler Hammer
PD3 (current limiting) 600
42,000
Eaton/Cutler Hammer
KDC 400
LDC, CLDC, LGC*, LGU*, LGX* 600
65,000 PD3 (current limiting) 600
42,000
GE
TBC4 400
TBC6, SGL1, SGL4, SGL6, SGP1, SGP4, SGP6, FGP 600
TBC8, TKL4V, TKL8S- 12S, SKL8, SKP8 800
Siemens/ITE
HHJD6, HHJXD6, CJD6, SCJD6 400
HHLD6, HHLXD6, CLD6, SCLD6 600
HLMD6, HLMXD6, HMXD6, SHMD6, HMD6, CMD6, SCMD6,
LMG
LNG, LPG 1200
Square D
CK400H, CK400HH, CJ400L 400
LI 600
CK800H, CK800HH 800
MasterPact STR 28D, PK 1200
50,000 LL (current limiting) 600
100,000 LR (current limiting) 600
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 11/16
Rating, amps
WCR,
amps RMS
Volts, Max.
Molded-Case Circuit Breakers
Manufacturer Type or Class Max. Size, amps
KCS
KCP
KCC
65,000
GE
THQMV 225
SGL1, SGL4, SGL6, SGP1, SGP4, SGP6 600
Siemens/ITE HLD6, HLXD6 600
Eaton/Cutler Hammer
LDC, CLDC, HLD, CHLD 600
Square D
QG, QJ 250
100,000 LJ (current limiting) 600
125,000 LL (current limiting) 600
200,000
LR (current limiting) 600
Eaton/Cutler Hammer
PD2 (current limiting) 225
PD3 (current limiting) 600
50,000
Eaton/Cutler Hammer
JGH, JGC, HFG, LFG 250
HLD, CHLD, LDC, CLDC, LGH*, LGC*, LGU*, LGX* 600
MDL, CMDL, HMDL, CHMDL, NGS, NGH, NGC, NGU, MDLB,
CMDLB, NF
50,000
GE
TBC6, TJL4V, TJL1S- 6S, SGL1, SGL4, SGL6, SGP1, SGP4,
SGP6, FGN, FGH, FGL, FGP
TBC8, TKL4V, TKH8S- 12S, TKL8S- 12S, SKH8, SKL8, SKP8,
TB8
SKL12, SK12P 1200
Siemens/ITE
HLD6, HLXD6, SHLD6, HHLD6, HHLXD6, CLD6, SCLD6, HLG,
LLG
LMD6, LMXD6, HLMD6, HLMXD6, MD6, MXD6, HMD6,
HMXD6, SMD6, SHMD6, CMD6, SCMD6, HMG, LMG
HND6, HNXD6, SND6, SHND6, ND6, NXD6, HNG, LNG, CND6 1200
Square D
LC, DJ, DL, LI, NSJ600 600
CK800N, CK800NN, MJ 800
MH, CK1200N, CK1200NN, CK1200H, CK1200HH, NT- H, NT-
L1, NT- L, NT- LF, PK, PJ, PL
CM2000HH 2000
CM2500HH 2500
85,000 PL1200 1200
65,000 LJ (current limiting) 600
100,000 LL (current limiting) 600
200,000 LR (current limiting) 600
100,000 Eaton/Cutler Hammer
PD3 (current limiting) 600
42,000
Eaton/Cutler Hammer
JGC 250
TBC4 400
LDC, CLDC 600
42,000
GE
TBC6, SGL1, SGL4, SGL6, SGP1, SGP4, SGP6, FGP 600
TBC8, TKL4V, TKL8S- 12S, SKL8, SKP8 800
SKL12, SKP12 1200
Siemens/ITE
HHLD6, HHLXD6, CLD6, SCLD6 600
HLMD6, HLMXD6, HMXD6, SHMD6, HMD6, CMD6, SCMD6,
LMG
HND6, HNXD6, HNG, LNG, SHND6 1200
Square D
LI 600
CK800H, CK800HH 800
CK1000HL 1000
CK1200H, CK1200HH, NT- H, NT- L, NT- LF, NT- L1,
MasterPact STR 28D, PK
50,000 LL (current limiting) 600
65,000 Eaton/Cutler Hammer
PD3 (current limiting) 600
100,000 Square D LR (current limiting) 600
* With Digitrip 310 + LS or LSG Inst. Override set to 12X.
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 12/16
Rating, amps
WCR,
amps RMS
Volts, Max.
Molded-Case Circuit Breakers
Manufacturer Type or Class Max. Size, amps
KCS
KCP
KCC
65,000 480
Eaton/Cutler Hammer
HLD, CHLD, LGH, LGC, LGU, LGX, LDC, CLDC 600
HMDL, CHMDL, HMDLB, CHMDLB 800
HND, CHND, NDC, CNDC, NF 1200
NGH, NGC, NGU 1600
RGH, RGC 2500
GE
TBC6, TJL4V, SGL, SGP6 600
TBC8, SKL8, SKP8 800
SKL12, SKP12, TKL4V 1200
Siemens/ITE
HLXD6, HHLXD6, HHLD6, CLD6, SHLD6, SCLD6, HLG, LLG 600
HMXD6, HMD6, SHMD6, HMG, LMG, CMD6, SCMD6 800
SHND6, CND6, HNXD6, HNG, LNG 1200
HPG, LPG, HPD, HPD6, CPD6, HPXD, HPXD6, SHPD, SHPD6 1600
HRD6, HRXD6 2000
Square D
LI, LE LSI, LE LI, LX, LXI, LJ, LL, LR 600
MJ, ME, MX, CK800H, CK800HH 800
CK1000HL 1000
NT- L1, NT- L, NT- LF, NE, NX, CK1200H, CK1200HH, PJ, PL 1200
NW, RJ, RL, MTZ 1600
PE, PX 2500
SES, SE, SEH (LS or LSI TRIP) 3000
SE (LI, LSI- E, and LI- E TRIP) 4000
MasterPact STR 28D 6300
65,000 600
Eaton/Cutler Hammer
Tri-Pac NB 800
RDC 2500
Siemens/ITE CND 1200
KCS
KCP
KCC
150,000 480 Square D
MTZ2-LF 2000
200,000 MTZ2-L1/L1F 2000
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 13/16
Weights and Dimensions
Note: Always use the transfer switch dimension drawing for planning and installation. Weights and dimensions may vary for different configurations. See your local distributor for dimension drawings.
Weights and dimensions are shown for NEMA Type 1 enclosures, NEMA Type 3R enclosures and open units. See the transfer switch dimension drawings for other enclosure types.
Model Amps
NEMA
Type Poles Wires
Dimensions mm (in.) Weight kg (lb.) Dimension Drawing Height Width Depth 2-Pole 3-Pole 4-Pole
KCS
30-200
1, 3R
2,3,4 3, 4 791 (31) 450 (18) 314 (12.4)‡ 28 (62) 30 (65) 31 (68) ADV-8566
(208-480V)
2,3,4 3, 4 1223 (48) 560 (22) 362 (14.3)‡ 52 (115) 56 (123) 59 (131) ADV-8568
230 (600 V) 260-600
2,3,4 3, 4 1702 (67) 610 (24) 514 (20.2)‡ 179 (395) 183 (403) 188 (414) ADV-8570
800 2,3,4 3, 4 1932 (76)* 864 (34) 515 (20.3)‡ 220 (485) 231 (510) 238 (525) ADV-8572
1000 3,4 4 1932 (76)* 864 (34) 515 (20.3)‡ — 231 (510) 238 (525) ADV-8572
1200 1 3,4 4 2286 (90) 963 (38) 688 (27.1) — 356 (785) 379 (835) ADV-8574
3R 3,4 4 2286 (90) 940 (37) 717 (28.2) — 356 (785) 379 (835) ADV-8575
1600-2000F† 1 3,4 4 2286 (90) 963 (38) 688 (27.1) — 472 (1040) 494 (1090) ADV-8577
3R 3,4 4 2286 (90) 940 (37) 869 (34.2) — 356 (785) 379 (835) ADV-8578
1600-2000 1 3,4 4 2286 (90) 963 (38) 1220 (48) — 472 (1040) 494 (1090) ADV-8579
3R 3,4 4 2286 (90) 940 (37) 1434 (56.4) — 472 (1040) 494 (1090) ADV-8580
2600-3000 1 3,4 4 2286 (90) 963 (38) 1524 (60) — 649 (1430) 679 (1495) ADV-8581
3R 3,4 4 2286 (90) 940 (37) 1738 (68.4) — 649 (1430) 679 (1495) ADV-8582
4000 1 3,4 4 2311 (91) 1524 (60) 1836 (72.3) — 975 (2149) 1056 (2328)
ADV-8583
3R 3,4 4 2529 (100) 1606 (63) 2310 (91) — 1436 (3165) 1523 (3357)
KCS
30-200
Open Unit §
2,3,4 3, 4 787 (31) 445 (18) 296 (11.6) 8 (17) 9 (20) 11 (23)
ADV-7182
(208-480V)
2,3,4 3, 4 1219 (48) 457 (18) 330 (13.0) 17 (37) 21 (45) 24 (53)
230 (600V) 260-600
2,3,4 3, 4 1422 (56) 610 (24) 362 (14.3) 31 (68) 34 (74) 36 (80)
800 2,3,4 3, 4 1829 (72) 864 (34) 508 (20) 68 (150) 78 (170) 90 (196)
1000 3,4 4 1829 (72) 864 (34) 508 (20) — 78 (170) 90 (196)
1200 3,4 4 2210 (87) 965 (38) 584 (23) — 78 (170) 90 (196)
1600-2000F† 3,4 4 2210 (87) 965 (38) 635 (25) — 190 (420) 213 (470)
1600-2000 3,4 4 2286 (90) 965 (38) 1219 (48) — 190 (420) 213 (470)
2600-3000 3,4 4 2286 (90) 965 (38) 1524 (60) — 213 (470) 243 (535)
KCP
KCC
150-600 1, 3R 2,3,4 3, 4 1702 (67) 610 (24) 514 (20.2)‡ 179 (395) 183 (403) 188 (414) ADV-8570
800 1, 3R 2,3,4 3, 4 1932 (76)* 864 (34) 515 (20.3)‡ 220 (485) 231 (510) 238 (525) ADV-8572
1000 1, 3R 2,3,4 4 1932 (76)* 864 (34) 515 (20.3)‡ 220 (485) 231 (510) 238 (525) ADV-8572
1200 1 3,4 4 2286 (90) 963 (38) 688 (27) — 463 (1020) 485 (1070) ADV-8574
3R 3,4 4 2286 (90) 940 (37) 717 (28.2) — 463 (1020) 485 (1070) ADV-8575
1600-2000F† 1 3,4 4 2286 (90) 963 (38) 688 (27) — 533 (1175) 556 (1225) ADV-8577
3R 3,4 4 2286 (90) 940 (37) 869 (34.2) — 533 (1175) 556 (1225) ADV-8578
1600-2000 1 3,4 4 2286 (90) 963 (38) 1220 (48) — 533 (1175) 556 (1225) ADV-8579
3R 3,4 4 2286 (90) 940 (37) 1434 (56.4) — 533 (1175) 556 (1225) ADV-8580
3000 1 3,4 4 2286 (90) 963 (38) 1524 (60) — 735 (1620) 765 (1685) ADV-8581
3R 3,4 4 2286 (90) 940 (37) 1738 (68.4) — 735 (1620) 765 (1685) ADV-8582
4000 1 3,4 4 2311 (91) 1524 (60) 1836 (72.3) — 975 (2149) 1056 (2328) ADV-8583
3R 3,4 4 2528 (100) 1606 (63) 2310 (91) — 1436 (3165) 1523 (3357) ADV-8583
KCP
150-600
Open Unit §
2,3,4 3, 4 1422 (56) 610 (24) 362 (14.3) 38 (84) 41 (90) 44 (96)
ADV-7182
800 2,3,4 3, 4 1829 (72) 864 (34) 508 (20) 80 (175) 94 (205) 108 (235)
1000 2,3,4 4 1829 (72) 864 (34) 508 (20) 80 (175) 94 (205) 108 (235)
1200 2,3,4 4 2210 (87) 965 (38) 584 (23) 80 (175) 94 (205) 108 (235)
1600-2000F† 3,4 4 2210 (87) 965 (38) 635 (25) — 252 (555) 274 (605)
1600-2000 3,4 4 2286 (90) 965 (38) 1219 (48) — 252 (555) 274 (605)
2600-3000 3,4 4 2286 (90) 965 (38) 1524 (60) — 300 (660) 329 (725)
2600-3000 3,4 4 2286 (90) 965 (38) 1524 (60) —
(660)
329 (725)
* Includes mounting feet † F = Front connected
‡ On 30-1000 amp models, the NEMA type 3R enclosures have a security cover on the controller that extends 54 mm (2.1 in.) beyond the door.
§ Dimensions shown for open units are the minimum required enclosure size. Open unit weights are shipping weights for the contactor only.
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 14/16
Controller Accessories See the controller specification sheets for more information.
❑ Accessory Modules
• Alarm Module
• External Battery Supply Module
• Input/Output Module
• High-Power Input/Output Module
❑ Controller Disconnect Switch
❑ Ethernet Communications (Standard with MPAC1500 controller)
❑ Current Sensing Kit
❑ Padlockable User Interface Cover
❑ Supervised Transfer Control Switch
Transfer Switch Accessories Accessories are available either factory-installed or as loose kits, unless otherwise noted.
❑ CSA Certification
❑ Digital Meter
• Measure and display voltage, current, frequency, and power
• 35 programmable alarms
• LCD display, 67 x 62.5 mm (2.65 x 2.5 in.)
• Pushbutton operation
• Password- protected programming menus
• Two digital inputs
• Two digital outputs and two Form A relay outputs
• Serial port for optional network connections
• Data logging
• Factory-installed
❑ Engine Start Circuit Monitor
See Specification Sheet G6-165.
❑ Export Packaging
❑ Extended Limited Warranties
• 2-year basic
• 5-year basic
• 5-year comprehensive
• 10-year major components
❑ Heater, Anti-Condensation
• Hygrostat-controlled 120 VAC strip heater (customer-supplied voltage source required)
• 100 or 250 watts (sized for enclosure)
• Protective 15 Amp circuit breaker
❑ Literature Kits
• Production literature kit (one set of literature is included with each transfer switch)
• Overhaul literature kit
❑ Load Shed Kit
• Forced transfer from Emergency to OFF for programmed-transition or closed- transition models
• Customer-supplied signal (contact closure) is required for the forced transfer to OFF function
• Factory-installed and loose kits available
❑ RSA III Remote Serial Annunciator
• Monitors the generator set
• Monitors Normal and Emergency source status and connection
• Monitors ATS common alarm
• Allows remote testing of the ATS
• For more information, see specification sheet G6-139
❑ Surge Protection Device (SPD)
• SPD available for the normal source supply
• Reduces transient voltages to harmless levels
• Protection modes: L-L/L-N/L-G/N-G
• Replaceable phase and neutral cartridges for service
• Frequency: 50-60 Hz
• Operating Temperature Range: - 40 to 176°F (- 40 to 80°C)
• Remote contacts for customer-supplied status indicators:
Contacts: 1 NO, 1 NC Min Load: 12VDC/10 mA Max. Load: 250 VAC/1 A Wire Size (max.): 16AWG
• Fuse protection: 30 amps/600 V
• UL 1449, 3rd Edition for Type 2 applications
• IEC 61-643-1, 2nd Edition T2/11
• See additional SPD specifications below
Seismic Certification ❑ California OSHPD Pre-Approval
• Available for KC model transfer switches with NEMA 1 and NEMA 3R enclosures.
❑ IBC Seismic Certification
• Certification depends on application and geographic location.
Contact your distributor for details.
• Available for the KC model transfer switches with enclosures shown below:
ATS Size, Amps
Enclosure, NEMA Type:
1 3R 4 4X 12
30-1200 • • • • •
1600-4000 • •
SPD Specifications
Nominal Voltage
Max.
Discharge
Current UL VPR 3rd Ed (L-N/N-G/L-G)
Limiting Voltage, (L-N/N-G/L-G) (kV) Short Circuit
Withstand
Maximum Continuous Operating at 3kAmps at 10kAmp (V±15%) (kA) Phase Poles (kV) Current (kA) Voltage (VAC)
240/120 40 Split 3 0.6/1.2/ 0.7 0.6/0.4/0.6 0.8/0.7/0.8 200 175/350
208/120 40 Wye 4 0.6/1.2/ 0.7 0.6/0.4/0.6 0.8/0.7/0.8 200 175/350
480/277 40 Wye 4 1.0/1.2/ 1.1 1.0/0.4/1.0 1.2/0.7/1.2 200 320/640
240/120 40 HLD 4 1.0/1.2/ 1.1 1.0/0.4/1.0 1.2/0.7/1.2 200 320/640
600/347 40 Wye 4 1.3/1.2/ 1.4 1.3/0.4/1.3 1.5/0.7/1.5 200 440/880
Canada, phone 1‐800‐544‐2444 - powersystems.rehlko.com © 2024 Discovery Energy, LLC - All rights reserved. 15/16
Model Designation
Record the transfer switch model designation in the boxes. The transfer switch model designation defines characteristics and ratings as explained below.
Sample Model Designation: KCS-DNTA-0400S
Model Number of Poles/Wires K: Kohler N: 2 Poles/3 Wires, Solid Neutral
T: 3 Poles/4 Wires, Solid Neutral
Mechanism V: 4 Poles/4 Wires, Switched Neutral C: Standard (Time-Based) W: 4 Poles/4 Wires, Overlapping Neutral
Transition Enclosure S: Standard A: NEMA 1 D: NEMA 4 P: Programmed B: NEMA 12 F: NEMA 4X C: Closed C: NEMA 3R G: Open Unit
Controller Current, Amps 0030 0230 1200 A: Decision-Maker® MPAC 1200, Automatic 0070 0260 1600 B: Decision-Maker® MPAC 1200, Non-Automatic 0104 0400 2000 D: Decision-Maker® MPAC 1500, Automatic 0150 0600 2600 F: Decision-Maker® MPAC 1500, Non-Automatic 0200 0800 3000
0225 1000 4000
Voltage/Frequency
C: 208 Volts/60 Hz K: 440 Volts/60 Hz Connections D: 220 Volts/50 Hz M: 480 Volts/60 Hz S: Standard F: 240 Volts/60 Hz N: 600 Volts/60 Hz F: Front (1600 and 2000 amp only) G: 380 Volts/50 Hz P: 380 Volts/60 Hz H: 400 Volts/50 Hz R: 220 Volts/60 Hz J: 416 Volts/50 Hz S: 400 Volts/60 Hz Note: Some selections are not available for every model.
Contact your authorized distributor for availability.
Model Mechanism Transition Controls Voltage Poles Enclosure MechanismTransition Current
Current Rating Miscellaneous