Service chart "H"
SCBA Numbers
Global Fire and Safety, Inc.
THE PROFESSIONALS IN WORLDWIDE SERVICE
No. Of Sheets
Sheet No.
Inspection Year
Working
Pressure Manufacturer
Date
Latest Test
Date
6000 11‐2016 6000 11‐2016 6000 11‐2016 6000 11‐2016 6000 11‐2016 6000 11‐2016 6000 11‐2016 6000 11‐2016
6000psi Cascade System Cylinders
Deck Training Locker 010 Steel, Due for Hydro Test/ RC Deck Training Locker 016 Steel, Due for Hydro Test/ RC
Deck Training Locker 005 Steel, Due for Hydro Test/ RC Deck Training Locker 007 Steel, Due for Hydro Test/ RC
Damage Control Lkr. 1 015 Steel, Due for Hydro Test/ RC Damage Control Lkr. 1 017 Steel, Due for Hydro Test/ RC
Damage Control Lkr. 1 013 Steel, Due for Hydro Test/ RC Damage Control Lkr. 1 014 Steel, Due for Hydro Test/ RC
SCBA / Medical Oxygen
RECORD OF CYLINDER WEIGHTS
Name Of Installation T/S Golden Bear 1
Pressure Shown in PSI
Location Cylinder Serial
Number Cylinder Type/ Comment
Owner or Operator MARAD 1
Signature of Inspector 2021
2001 Peralta St., Suite "F" Tel: (510) 834‐2323 Oakland, CA 94607 Fax (510) 834‐2326 United States of America Email: sales@globalfireandsafety.com
Service Chart "O"
Portable/Semi Portable Service Chart
Global Fire and Safety, Inc.
THE PROFESSIONALS IN WORLDWIDE SERVICE
IMO # PO #
8834407 691PE19P000069
DC Dry Chemical 1 = Inspection WC Water Chemical 2 = Recharge CO2 Carbon Dioxide 3 = Six Year Maintenance Halon Halon 1211 4 = Hydrostatic Test
PKP Purple K 5 = Repair
Foam Foam 6 = Condemned Cart Cartridge Operated Dry Chemical 7 = New Extinguisher
8 =
Station No Location Serial No Type Rating Capacity Hydro Date Work code
FE 0401 Cascade Room 64910 CO2 BC 15lb. 3‐2016 1‐4‐2 FE 0404 Feed Pump Room 64601 Co2 BC 15lb. 3‐2016 1‐4‐2 FE 0307 Officer's Laundry 64609 CO2 BC 15lb. 3‐2016 1‐4‐2 FE 0107 Aft house STBD Passway AFT 33121986 DC ABC 10lb. 2015 1‐3 FE 103 Galley 76807 Co2 BC 15lb. 3‐2016 1‐4‐2 N/A Galley 376024 WC K 2.5gal. 2019 1‐7 N/A Galley 899005 WC K 2.5gal. 2016 1‐7 FE 108 Port Side Of Passageway 367364 DC ABC 10lb. 2015 1‐3 N/A Tool Room Spare 76808 Co2 BC 15lb. 3‐2016 1‐8 FE 116 Just Inside Engine Room 585377 DC ABC 10lb. 2009 1‐4‐2 FE 121 Supply Office (Across DC 2) 3249336 DC ABC 10lb. 2015 1‐3 FE 203 Lower Berthing 480041 DC ABC 10lb. 2015 1‐3 FE 212 E/R O/S Elec Shop 00396672 DC ABC 10lb. 2015 1‐3 FE 222 E/R EOS 591142 DC ABC 10lb. 2009 1‐4‐2 FE 302 Classrm Flat Pway 33121993 DC ABC 10lb. 2015 1‐3 LB‐2 Lifeboat #2 480057 DC ABC 10lb. 2015 1‐3 LB‐4 Lifeboat #4 33121991 DC ABC 10lb. 2015 1‐3 LB‐6 Lifeboat #6 7220791 DC ABC 10lb. 2015 1‐3 Spare DC #2 396667 DC ABC 10lb. 2015 1‐3 Spare DC #2 733686 CO2 BC 15lb. 3‐2016 1‐5 Spare 2nd Deck by Halon Rm 03249825 DC ABC 10lb. 2015 1‐3 Spare 2nd Deck by Halon Rm 321852 DC ABC 10lb. 2015 1‐3 Spare 2nd Deck by Halon Rm 01482 CO2 BC 15lb. 3‐2016 1‐4‐2 Spare 2nd Deck by Halon Rm 65035 CO2 BC 15lb. 3‐2016 1‐4‐2
New Hose & Horn
Portable Fire Extinguishers Due for Service Next Annual Inspection in 2021
Name of Installation
April 15, 2020 26339 TS Golden Bear
Type Description Work Code Description
Date GFS #
PORTABLE FIRE EXTINGUISHERS
2001 Peralta St., Suite "F" Tel: (510) 834‐2323
Service Chart "K"
Galley System
Global Fire and Safety, Inc.
THE PROFESSIONALS IN WORLDWIDE SERVICE
IMO # GFS# PO #
8834407 25915 691PE19P000069
Total Bottles Capacity
1.00 2.5 QTS
TECHNICAL DESCRIPTION
Galley System
DATE Name of Installation
March 31, 2020 TS Golden Bear
Agent bottle(s) weighed and pressure checked Carried Out
Make/Type Pilot Cartridge(s) Capacity
Range Guard 1.00 300 PSI
Protecting The following Spaces: Cooking Surfaces
Test/Inspection Type: Complete Testing/Inspection
Tested operation of remote pull(s) and local control of bottle release(s) Carried Out
Pilot bottle(s) weighed and pressure checked Carried Out Tested fusible link(s) release cable. Carried Out Fusible link(s) Quanitity 3
Tested operation of microswitch(es) Not Applicable Inspected bottle(s) and bracket(s) Carried Out
Inspected piping and fitting(s) Carried Out Inspected nozzle(s) Carried Out Nozzle Quantity 3
Inspected nozzle cap(s) Replaced Nozzle Cap Quantity 3
Inspected remote pull station(s) Carried Out
Comments:
Replaced (2) Foil Seals for nozzles
Inspected operation and warning label signs Carried Out
Sealed, tagged, and left in ready to use condition Carried Out
2001 Peralta St., Suite "F" Tel: (510) 834‐2323
Service Chart "T"
Action summary
Global Fire and Safety, Inc.
THE PROFESSIONALS IN WORLDWIDE SERVICE
IMO # GFS# PO #
8834407 26339 691PE19P000069
SCBA: (8) 6000psi Cascade cylinders due for hydrostatic testing and recharge.
Range Guard Galley Wet Chemical System: The Range Guard system is obsolete and no longer UL listed. There are no support or maintenance parts available. In the event of an activation, leak or next hydro test the cylinder cannot be refilled without rebuild parts. GFS recommends that the system be replaced.
The following items are due for service during the next annual fire equipment inspection for 2021:
Portable Fire Extinguishers: (8) 15lb Co2 hydrostatic testing and recharge, (2) 10lb DC ABC hydrostatic testing and recharge. (12) 10lb DC ABC 6 year internal maintenance and recharge, For (2) Wet Chemical Fire extinguishers: Fire extinguisher manufacturers matching industry standards have made USCG approved version of portable fire extinguishers and this now includes wet chemical type fire extinguishers. GFS recommends (2) existing older model wet chemical extinguishers "not bearing marine type label" be replaced to be in accordance with NFPA 10 Portable Fire Extinguishers and 46 CFR 162.028‐4.
Actions Summary
DATE Name of Installation
April 15, 2020 TS Golden Bear
SUMMARY OF ACTION
2001 Peralta St., Suite "F" Tel: (510) 834‐2323