Provide 3,700 feet of 2 AWG 3/C 15KV type MP-GC power cable with class B copper conductors, Ethylene Propylene Rubber (EPR) 133% insulation level, copper tape shield, with ground and ground check, and mold cured Chlorinated Polyethylene (CPE) jacket (jacket color Orange).

Cable must be MSHA approved and meet the following specifications:

• ASTM B3 Soft or Annealed Copper Wire

• ASTM B8 Concentric-Lay-Stranded Copper Conductors

• ASTM B496 Compact Round Concentric-Lay-Stranded Copper Conductors

• ICEA S-75-381/NEMA WC 58 Portable and Power Feeder Cables for use in Mines and Similar

Applications

Prior to receiving a notice to proceed, provide the cable manufacturer’s catalog data and drawing for the cable being offered, for acceptance.

Cable is to be tested in accordance with ICEA S-75-381 section 4.10 and applicable sections of section 6.

Provide the manufacturer’s test reports and a certificate of cable testing.

Cable is intended to be used for underwater service in shallow water (max 36 foot depth).

Cable to be provided as one continuous length on one spool, with an acceptable length variance of +/-5%.