21. SF 30 - A-0002- Amendment of Solicitation - Pico del Este HVAC.pdf
PDF 7 MB Posted
- Solicitation number
- 697DCK-21-R-00327
About this file
This is a request for proposal for HVAC replacement services at the Pico del Este radar facility in Carolina, Puerto Rico. The Federal Aviation Administration seeks to award a firm fixed price contract for HVAC replacement with an estimated cost between $325,000 to $375,000. The 120-day period of performance is anticipated to begin in late 2021. The solicitation is set aside for socially and economically disadvantaged, service-disabled veteran-owned small, woman-owned small, and historically underutilized business zone small business firms. Interested parties must submit technical and cost proposals by August 4, 2021 responding to the statement of work and drawings attached to the solicitation. A site visit is scheduled for July 21, 2021 to familiarize offerors with the facility. The FAA will provide responses to requests for information submitted by July 28, 2021 and holds the right to communicate with offerors throughout the solicitation process.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 21. SF 30 - Amendment of Solicitation - Pico del Este HVAC.pdf | ||
| 16. 697DCK-21-R-00327 & attchs v3.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OMB Control No. 2120-0595 (SF-30) FAA Template No. 11 (Reverse) (8/97)
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES
1 1
2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)
A-0002 08/09/2021 WS-21-01451
6. ISSUED BY 7. ADMINISTRATED BY (If other than Item 6)
DOT/FEDERAL AVIATION ADMINISTRATION
SOUTHERN REGION, AAQ-570
1701 COLUMBIA AVENUE
COLLEGE PARK, GA 30337
DOT/FEDERAL AVIATION ADMINISTRATION
SOUTHERN REGION, AAQ-570
1701 COLUMBIA AVENUE
COLLEGE PARK, GA 30337
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)
All Prospective Offerors.
9A. AMENDMENT OF SOLICITATION NO.
697DCK-21-R-00327
9B. DATED (SEE ITEM 11)
07/07/2021
10A. MODIFICATION OF CONTRACT/ORDER NO.
*TO BE COMPLETED BY VENDOR IF NOT COMPLETE 10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended is not extended.
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation on as amended, by one of the following methods:
(a) By completing Item 8 and 15, and returning 1 copies of the amendment; (b) acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDG- MENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hours and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS, IT MODIFIES THE CONTRACT/ORDER NO.
AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT/ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
Reference: 697DCK-21-R-00327 – Amendment –A – 0001 – Pico del Este (QJQ) HVAC Replacement, Carolina, PR
This amendment is being issued to answer the RFIs related to this project. See attached. Friendly reminder the proposals are due on August 18, 2021, 3:00pm Eastern Daylight Time (EDT)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING SPECIALIST(Type or print)
James E. Love 15B. CONTRACTOR/OFFEROR 15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 16C. DATE SIGNED
(Signature of person authorized to sign)
BY
(Signature of Contracting Specialist)
8/9/2021
U.S. Department of Transportation
Federal Aviation Administration
RFI’S
Solicitation: 697DCK-21-R-00327 – HVAC Replacement, Pico Del Este, PR.
General questions:
1. Can you clarify which areas were found with lead containing paints or surfaces?
See attached report.
2. Can we re-use existing refrigeration copper piping?
All copper piping shall be replaced.
3. Can we re-use recuperated R-410A refrigerant?
All refrigerant for new equipment must be new.
4. What do you mean by low ambient control?
Low ambient control is a standard option for HVAC equipment that provides refrigerant head pressure control during low ambient conditions. This is intended to maintain system pressure at normal levels should cooling be required when outdoor temperatures are low.
5. How long would the FAA ID take?
Obtaining FAA ID will not be required. FAA will provide escort for all contractors.
6. What is considered temporary services?
Any services required for construction, but not available on site (e.g. compressed air).
7. Should we provide temporary air for shutdown work?
Yes, Contractor is responsible for providing temporary conditioned air for areas impacted by construction.
SOW Questions:
General:
Section 4:
•What is the requirements construction for temporary offices/staging?
The site is not occupied, so temporary offices are not required. Contractor must provide access to any FAA personnel, as requested, throughout the project.
•Can FAA Second floor offices be used for these purposes?
See above. Temporary offices are not required.
Section 5:
•During site visit we saw water service provision at condensing unit’s pad. Can we use this provision for general cleaning purposes?
Contractors may use on-site water for general cleaning; however, Contractor is responsible to remove all debris.
•We will be requiring power at condensing unit location for refrigerant recovery and vacuum dehydration of refrigerant circuits. Can we use power from existing disconnect switches?
Contractor may use readily available power at the facility; however, the FAA is not responsible for any delays caused by any potential loss of power.
Section 8:
•Please clarify which areas were found with lead containing coatings or lead contaminated surfaces. Please provide report if possible.
See attached report.
Design:
•Please provide list of all existing electrical equipment for both the first and second floor, with quantities and heat rejection load.
Contractor is responsible for compiling this list. FAA expects to review the calculated heat loads during the design portion of this project.
Section 3:
Once we conduct heat load calculations chances are that we could used existing Air handling units. Can Air handling units be re-use?
Existing air handling units are to be replaced during this project.
Are low ambient control applicable to weather conditions on site?
Low ambient controls are required for new HVAC equipment.
Same goes with second floor duct system, can it be re-use? Section 5:
Second floor ductwork may be re-used, depending on new HVAC system equipment selection. Contractor will be expected to ensure any portions to be re-used will be compatible with new HVAC equipment/airflow.
Can we get information GFE OAS HVAC System controller prior to bid date? Section 6:
See attached documentation.
Please confirm that the handrail at mechanical yard area, (condensing units pad), needs to be considered to be replace?
Contractor shall evaluate this area to ensure new equipment installed in this location will have all required clearances and meet all required standards. If the handrail does not require any modifications to meet the applicable codes, then the handrail will not be replaced.
Please confirm that mechanical yard structure can be re-use? Section 6a:
Contractor shall evaluate this area to ensure new equipment installed in this location will have all required clearances and meet all required standards. If the area does not require any modifications to meet the applicable codes, then the handrail will not be replaced.
Can we use existing condensing unit yard (base) supports and just add requested fence to it?
This is one potential solution. Contractor would need to evaluate supports to ensure this solution is acceptable. Debris is also blown under the facility into the condensing unit area, so this would also need to be addressed to protect the HVAC equipment.
Demolition:
Section 1d:
Who will be performing the commissioning of the HVAC systems?
Contractor is responsible for performing and documenting all commissioning of the HVAC systems.
Is it a combination of Contractor/CO/Cor and FAA RE, or do we need to hire and independent commissioning Engineering Company?
Contractor is responsible for hiring the appropriate personnel to perform commissioning.
FAA will not be providing these services.
Do we need to provide temporary HVAC system?
Yes, Contractor is responsible for providing temporary conditioned air for areas impacted by construction.
Installation:
Section 1a:
Can we get GEF OAS HVAC Controller information prior to bid date?
See attached documentation.
Section 1b:
What type of stainless steel is required for exterior hardware? SST 316, 304?
304 stainless steel is the minimum standard.
Section 2:
Is CAI and FAA will be conducted concurrently?
FAA will be working with the Contractor to perform the CAI.
Electrical:
Section 3d:
During site visit heavy duty disconnect switches were in good conditions. Are they NEMA3R? If so, can we re-use them?
Existing heavy duty disconnect switches can be re-used.
In the event that temporary HVAC units are required to avoid interruptions to FAA operations while construction, Will FAA/Government provided temporary power for these temporary units?
Contractor shall plan for this during the design portion of the project. FAA power may be used, if available, however, Contractor is responsible for providing any new breakers, conductors, labor, etc.
to make the connections available.
Testing and balance:
Section d:
On facilities second floor, whether we used existing ductwork or replace it with a new one, and that the duct system will be inside the air-conditioned space thus any leak of air will not affect system operation. Please clarify.
Need more information to properly address this question.
1. Scope of Work asks for a full heat load analysis of the facility to determine all HVAC requirements (e.
g. heating, cooling, dehumidification, etc.). The set of drawings provided have a Mechanical Equipment Schedule with specifications of the Air Handling and Condensing Units to be installed. Is a full heat load analysis of the facility really required?
The set of drawings being referenced are from the previous HVAC project and are provided to detail the existing system. These drawings do not specify any mechanical equipment to be replaced during this project. HVAC equipment at the site has been failing at a very rapid rate. A full heat load analysis is required to ensure proper loading.
2. If a full heat load analysis of the facility is required additional information is needed from the FAA.
The following information is needed:
a. Drawings with dimensions of the structure as it is at present.
See drawing SO-D-103405-C03 for details. Facility has recently added approximately 1-1/2” thick closed-cell insulation to the interior side of all exterior walls (see attached product information).
b. Construction details of the exterior walls of the structure as they are at present.
c. See drawing SO-D-103405-C03 for details. Facility has recently added approximately 1-1/2” thick closed-cell insulation to the interior side of all exterior walls (see attached product information).
c. Heat produced by existing equipment and lighting inside the building on each floor level.
Contractor is responsible for determining all heat loads at the facility. FAA expects to review the calculated heat loads during the design portion of this project.
d. Desired Temperature and Per Cent of Relative Humidity parameters on first and second level.
Desired temperature: 73 deg F +/- 2 deg F Desired relative humidity: 35% to 50%
Please confirm if the above requested information will be made available to the Contractor or an As Built of the existing structure and further investigation of all the equipment inside the structure shall be considered as part of the total cost of our Proposal.
3. Drawing M001 shows Detail 2/M00 “New Grating Layout” with New Concrete Supports. The existing structure where the new condensing units will be installed have already concrete supports. And there are no instructions to build a new structure or repairs required to the structure where the new condensing units will be installed. Please clarify.
Drawing M001 is from a previous HVAC project and is provided to show the existing system installation.
Contractor shall evaluate this area to ensure new equipment installed in this location will have all required clearances and meet all required standards.
4. Item Number 1 of the Key Installation Notes on Drawing M003 asks to supply and install grating platform per Appendix “A” in the Specifications. Appendix “A” was not found on the provided documents. Can the Appendix “A” or specifications of the required grating be provided?
Drawing M003 is from a previous HVAC project and is provided to show the existing system installation, not detail work to be accomplished on this project.
5. Drawing M006 shows detail 1/M004 “Duct Layout” connected to AHU Units 1,2 and 3. It looks as if the drawing is illustrating the Second Level in which the AHU to install there are Numbers 3,4 and 5.
Please clarify.
Drawing M006 is from a previous HVAC project and is provided to show the existing system installation, not detail work to be accomplished on this project.
6. Drawing M006 shows detail 1/M004 “Duct Layout” shows air distribution ductwork where new diffusers will be installed. Actually, the second level have air distribution ductwork installed. Will the existing ductwork be reused, or the existing ductwork needs to be removed and new ductwork be installed?
Drawing M006 is from a previous HVAC project and is provided to show the existing system installation, not detail work to be accomplished on this project. Second floor ductwork may be re-used, depending on new HVAC system equipment selection. Contractor will be expected to ensure any portions to be re-used will be compatible with new HVAC equipment/airflow.
7. Scope of work asks to: “ design an install a wind fence to protect any outdoor equipment from high winds and debris.”
a. Are the new condensing units the only equipment to protect with the requested fence?
The intent of the fence is to protect any HVAC equipment placed outdoors.
b. There is no Basis of Design or Guideline for the requested fence. Is the Puerto Rico Building
Cod requirement for wind velocity the only parameter to consider in the fence design?
Code requirements will depend on size and location of fence. FAA will need to review design to fully answer this question.
c. What type of mesh (Perforated Metal, Wire Mesh, Expanded Metal, opening of mesh, etc.)
is desired?
Contractor shall specify the type of mesh that will work best for this application. FAA will review Contractor’s fence design.
d. Please define the height of the fence (A sketch of a possible fence alternative is included for your convenience.).
Contractor shall determine the height of the fence required. FAA will review Contractor’s fence design.
8. We would like to request that the proposed date to submit the proposal of August 4, 2021, be changed to at least 10 days after all the questions and or clarifications are received.
9. Please provide Plans of existing HVAC conditions and Proposed work to be done.
This is a design-build project. Contractor will submit the design for FAA review.
Height Above Pllatform ??
Height Above Platform ??
Height Above Platform ??
10. What Standard should the Anti corrosive treatment comply with?
The FAA will not specify a specific anti-corrosion treatment for the coils to avoid directing the Contractor to a sole source. Anti-corrosion treatments for coils is a standard option for several equipment manufacturers with similar results.
11. Please clarify if bid bond or payment and performance bond is required for this solicitation. Payment
& performance bond is required.
12. Please provide details of the disconnect switch to be replaced.
Existing heavy-duty disconnects can be re-used.
13. Please clarify the linear distance between the disconnect location of each HVAC equipment and the HVAC Equipment it feeds.
This shall be determined by the Contractor during the design portion of the project.
14. Please indicate the linear distance between the disconnect switches and the Main Distribution panel.
15. Can we relocate the thermostat?
It is unclear which thermostat this is referencing. Contractor shall install FAA provided OAS HVAC controller for all HVAC systems supporting an equipment space.
16. Can we change the base of the capacitors or it needs to be replaced?
17. We are considering in reusing the cooling pipe or refrigeration. Is this acceptable?
Refrigerant and copper piping shall be replaced.
Additionally, if you may be so kind to clarify; the SOW only states that the contractor shall design and install (part C. Design, #8 ). I would like to be clear if the designs need to be certified by an engineer or a local designer?
All drawings, specifications, etc. issued for construction shall be signed and sealed by a licensed professional engineer practicing within the applicable discipline for each signed and sealed item.
Professional licensing specifically for Puerto Rico is not required.
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
PR
MEK
JBB
RCS 03/15/2019
A
JC03/15/2019A
ENGINEERING SERVICES
INFRASTRUCTURE
ARSR
FACILITY DRAWINGS
PICO DEL ESTE
PROJECT ENGINEER
NDP
QJQ-D-ARSR-A002
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
SCALE: 3/8" = 1'-0"
4' 6'2'02'
N
NUMBERED LEGEND:
UP
PLATFORM
RADOME
MPG (TYP.)
SPG (TYP.)
MAIN GROUND
MDPC
ERMS P18
ERMS P1 PANEL
TVSS
HVAC PANEL
ERMS J-BOX
FIRE ALARM
HOIST CONTROL
FIRE EXSTINGUISHER
TRANSIET GROUND
ALARM
RADIOS
AHU #1
AHU #2
REHEAT COIL 2 DISCONNECT
AHU #1 DISCONNECT
RCAG/RCO
REHEAT COIL DISCONNECT
AHU #2 DISCONNECT
PANEL A
CAP RACK
MDPB
PANEL
NDAG PANEL
S
M
ARGORP ESNEF
E
D
M E
T S
Y
S
ECAPSRIA LA
N
OI
T
A N
AS-BUILT FOR FACILITY DRAWINGS
RADOME BUILDING FIRST FLOOR
02/26/2020
LAYOUT PLAN
KEY MAP
NOT TO SCALE
ELEVATION KEY PLAN
NOT TO SCALE
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X
BLDG
E/G
PLATFORM
ANTENNA
RADOME
(BLDG NO. 311)
FOUNDATION
(NO. 3012)
FND
NO. 3036)
(BLDG
FOUNDATION
N O
1ST LEVEL
2ND LEVEL
ANTENNA DECK
NDP RESOURCE MANAGERRADOME BUILDING FIRST FLOOR LAYOUT PLAN
SCALE: 3/8" = 1'-0"
28 ANTENNA J-BOX
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
DATE
REDLINE
APVD
qjq-d-arsr-a002.dgn 3/18/2021 1:19:10 PM
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
$W
ATERMARK$
E D
M
IS
S
U E
D F
O R
PR
MEK
JBB
RCS 03/15/2019
JC03/15/2019A
SCALE: 3/8" = 1'-0"
4' 6'2'02'
N
ENGINEERING SERVICES
INFRASTRUCTURE
ARSR
FACILITY DRAWINGS
PICO DEL ESTE
PROJECT ENGINEER
QJQ-D-ARSR-A003
q jq
-d -a rs r-a .d g n
THIS DRAWING PRODUCED ON ASO REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
S
-B U
IL
T
NUMBERED LEGEND:
MPG (TYP.)
SPG (TYP.)
ERMS P5
FIRE EXSTINGUISHER
FIRE PULL ALARM
HVAC CONTROL
REMOTE UPS ALARM
RMC CABINET
OVERHEAD CABLE TRAY (TYP.)
ACE CABINET
AHU #3
DISCONNECT AHU #3
REHEAT COILS 1
TVSS
ATCBI-6 PANEL
REHEAT COIL 2
AHU #5 DISCONNECT
COMPRESSOR/DEHYDRATORS
AHU #5
CODEX MODEM
ANCILLARY POWER PANEL
CARSR PANEL
AHU #4
AHU #4 DISCONNECT
REHEAT COIL DISCONNECT 3
CARSR SECONDARY BREAKERS SCB 1&2 W/ EMI FILTERS
CARSR TRANSFORMERS T1 & T2
ALARM
FIRE ALARM
LP PANEL
FTI RACKS
RMMS CONTROL
P4A ERMS & FIRE ALARM
COMMUNICATIONS INTERFACE CABINET (U7)
TRANSDMITTER POWER INTERFACE CABINET (U4)
TRANSFMITTER CABINET (U3)
MODE-S LIGHTNING PROTECTION
CARSR WAVEGUIDE
RCAG
ATCBI-6 CABINETS
TMCT A/B WORKSTATION (U8/U9)
LPU1155 LPU10
APU (INDUCTOSYN) CABINET
ANTENNA REMOTE LIGHT (ARL)
UP VENTS
OLD CLOSED
ABANDENED DUCT
DOOR
ABANDENED
SEALED EXIST DOOR
VENT
HATCH
HOIST
LADDER
DOWN
S
M
ARGORP ESNEF
E
D
M E
T S
Y
S
ECAPSRIA LA
N
OI
T
A N
AS-BUILT FOR FACILITY DRAWINGS02/26/2020
LAYOUT PLAN
RADOME BUILDING SECOND FLOOR
KEY MAP
NOT TO SCALE
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X
BLDG
E/G
PLATFORM
ANTENNA
RADOME
(BLDG NO. 311)
FOUNDATION
(NO. 3012)
FND
NO. 3036)
(BLDG
FOUNDATION
N O
RADOME
ELEVATION KEY PLAN
NOT TO SCALE
1ST LEVEL
2ND LEVEL
ANTENNA DECK
N
NDP RESOURCE MANAGERRADOME BUILDING SECOND FLOOR LAYOUT PLAN
SCALE: 3/8" = 1'-0"
F
IL
E
S
D
A T
E
T
IM
E
N
A M
E
A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
DATE
REDLINE
APVD
C03 NOT TO SCALE
INSTALLATION SECTION
BOTTOM PVC SIDING
T
Y P
T
Y P
SELF-DRILL W/BONDED SEALING WASHER
EXIST. METAL SIDING
SELF-DRILL W/BONDED SEALING WASHER
EXIST. CHANNEL
CORRUGATED SIDING PANEL
4.2X1-1/16"X3/16" PVC
C03 NOT TO SCALE
CORNER SIDING DETAIL
CORRUGATED SIDING PANEL
4.2X1-1/16"X3/16" PVC
GALV PLATE
WELDED CORNER
ALUM FLASHING
1/8 "X12"
SEAL FASTENERS
S/S GROMMENT
SEALING WASHER
SELF-DRILL W/BONDED
EXIT METAL SIDING
INSULATION ("STEREO FOAM")
CONTINUOUS 2" RIGID
EXTERIOR
INTERIOR
CHANNEL
WELDED TO
GALV ANGEL
3/16 "X2"X2"
C03 NOT TO SCALE
HATCH
FLOOR
STALL
SHOWER
HEATER
WATER
REFRIGERATOR
PANEL LP
INSTALL
AHU #3
UL-301
RATED WALL
2 HOUR FIRE
BR #1
BR #2
ROOM
QUIET
STAIRS
QUIET ROOM
BEDROOMS &
TO RESTROOM,
DUCT ROUTED
10"X12" A/C
COMPRESSOR
ROTARY
ROOM
BATH-
WALLBOARD
5/8" GYPSUM
PLATES
2-2"X4"
(SEE DETAIL BELOW)
16 O.C.
2-2"X4"
WALLBOARD
5/8" GYPSUM
WALLBOARD
5/8" GYPSUM
WALLBOARD
5/8" GYPSUM
FIRESTOPPED
2"X4"
BATTS
MINERAL WOOL
4LB/CU FT
MIN-3-1/2",
16" O.C.
WOOL BATTS
WITH 4LB MINERAL
CAVITIES FILLED
O.C. FIRESTOPPED
2"X6"X12"
C03 NOT TO SCALE
SECTION 7
C03 NOT TO SCALE
SECTION
WALLBOARD
5/8" GYPSUM
PLATES
2-2"X4"
(SEE DETAIL BELOW)
16 O.C.
2-2"X4"
WALLBOARD
5/8" GYPSUM
WALLBOARD
5/8" GYPSUM
WALLBOARD
5/8" GYPSUM
BATTS
MINERAL WOOL
4LB/CU FT
MIN-3-1/2",
16" O.C.
WOOL BATTS
WITH 4LB MINERAL
CAVITIES FILLED
O.C. FIRESTOPPED
2"X6"X12"
2"X4"
C03 NOT TO SCALE
SECTION
WALLBOARD
5/8" GYPSUM
BATTS
MINERAL WOOL
4LB/CU FT
MIN-3-1/2",
16" O.C.
2"X4" FIRESTOPPED
WALLBOARD
5/8" GYPSUM
WOOL BATTS
WITH 4LB MINERAL
CAVITIES FILLED
O.C. FIRESTOPPED
2"X6"X12"
PLATES
2-2"X4"
(SEE DETAIL BELOW)
16 O.C.
2-2"X4"
WALLBOARD
5/8" GYPSUM
13'-0"
C03
C03 NOT TO SCALE
DETAIL 4
CORRUGATED SIDING PANEL TYP
4.2 X 1-1/16"X3/16" PVC
EXTERIOR CORRUGATED SIDING PANEL PLAN
WELDED TO EXIST. METAL SIDING
CONTINUOUS GALV PLATE 3/16 "X 2" DIA 24"
SECOND FLOOR LAYOUT PLAN
C03
C03
C03
WELDED TO EXIST. METAL SIDING
3/16"X2" DIA 24"
CONTINUOUS GALV PLATE
FASTENERS
S/S GROMMENT SEAL
ARSR
ARCTIC TOWER REFURBISHMENT
WALL DETAILS
PICO DEL ESTE (QJQ) PR
John M. Taylor IV
SENIOR ENGINEER, SURVEILLANCE/WEATHER PLATFORM
Jeffrey A. Jones
MANAGER, PLATFORM OPERATIONS, SURVEILLANCE/WEATHER
04-28-2003
SO-D-103405-C03 .
JNB
NXS
CB
S0049896 SP036000 July 24, 2003 - 2:05 PM
CENTER
IMPLEMENTATION
ATLANTA NAS
Reflects FAA MicroStation Drawing Standards for DMS2000
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
SOUTHERN REGION ATLANTA, GEORGIA 30320
DESCRIPTION CHECKED APPROVEDREV.LTR. DATE
REVIEWED BY
SUBMITTED BY APPROVED BY
DESIGNED BY
DRAWN BY
CHECKED BY
DRAWING NO.
DATE -
LTR.
REV.ISSUED BY
(ORIGINAL SIGNED BY) (ORIGINAL SIGNED BY)
OAS
2.5 Version 2/19/2018
OAS
2.5
User’s Guide
OAS
2.5 User’s Manual
Table of Contents
General Information
Manufacturer
Definitions
Quick Reference
Installation
5.1 Physical Installation
5.2 Electrical Requirements
5.3 Connections
Operation
6.1 Introduction
6.2 User Inputs
6.3 System Status Lights
6.4
Operational States
6.5
Sequence of Operations
Troubleshooting
Parts List
Schematics
Appendixes
A Thermostat Setup
B
OAS
Functional Test
OAS
2.5 User’s Manual
Table of Contents
General Information
Manufacturer
Definitions
Quick Reference
Installation
5.1 Physical Installation
5.2 Electrical Requirements
5.3 Connections
Operation
6.1 Introduction
6.2 User Inputs
6.3 System Status Lights
6.4
Operational States
6.5
Sequence of Operations
Troubleshooting
Parts List
Schematics
Appendixes
A Thermostat Setup
B
OAS
Functional Test
OAS
2.5 User’s Manual
General Information:
This user manual is intended to accompany the
OAS
2.5
HVAC
Controller.
The
OAS
HVAC
controller is a
FAA
designed
HVAC
controller for use at critical
FAA
facilities that require reliable redundant
HVAC
control.
The
OAS
is a simple yet robust control system which captures specific operational criteria important to
NAS
equipment.
Some of these features are listed below:
1. Redundant control of
HVAC
Units
2. Primary Unit Selection
3. Adjustable Set Points
4. Automatic Unit Switch Over
5. System Status Lights
6. Audible and Visual Alarms
7. Audible Alarm Silence
8. Simplified Troubleshooting
9. Commercially Available Replacement Parts
10. Ease of Use and Reparability
11. ERMS
compatibility
Manufacturer Information:
The
OAS
2.5 was designed by
NDP
Infrastructure Engineering (Jonathan Salter, 202.744.1408) and manufactured by:
The
FAA
National Staging Area
(AJW-‐2C15P)
S.
Geospace Dr
Independence, MO
64056
Ph:
(816) 329-‐3970 http://stagingarea.faa.gov
OAS
2.5 User’s Manual
Definitions:
Dehumidify
The mechanical process of reducing the air humidity.
OAS
Overtemp Automated System
FAA
specific controller that provides control to a Unit, fully redundant
HVAC
system.
These systems are typically associated with unoccupied electrical equipment rooms.
Overtemp Condition where the room temperature becomes greater than what is considered acceptable for a normally operating
HVAC
Unit.
An Overtemp situation indicates that the selected
HVAC
Unit is not functioning properly.
Set Point
The manually inputted temperature setting for an associated thermostat.
Relay
Electronic device that when activated, allows current to pass through.
Room Temperature Actual Current Temperature of the Equipment Room as measured by the
OAS.
OAS
2.5 User’s Manual
OAS
Quick Reference:
Figure 1:
OAS
Quick Reference
Alarm:
Red Visual
Alarm Light and
Audible Alarm
System Status Lights
Indicate the presence of Control Power and a call for operation for both
HVAC
Units
Room Temperature
Control Thermostat
(T1) Provides Control to the Active
HVAC
Unit.
Setpoint input for the desired room temperature
Room Overtemp
Thermostat (T2)
Setpoint input for the overtemp switchover
Primary Unit Selector
Switch Manual control point for the selection of the desired primary Unit
Audible Alarm Silence
When the controller is in Alarm, this button silences the audible alarm tone.
Overtemp Reset
Button Resets the
Controller from an
Alarm
OAS
2.5 User’s Manual
Installation:
5.1 Physical Installation:
The
OAS
is contained within a 10”x16”x5” electrical box.
The box contains mounting holes for attaching the box to a supporting wall or stand.
The controller should be mounted at chest level in a central location where the ambient temperature is representative of the room.
Locating the unit on an uninsulated outside wall, near equipment exhaust, or in a stagnant air area may cause the system to operate inefficiently.
If space is not available for the
OAS
in a preferred location, a separate remote temperature sensor option can be added.
of these sensors are required, one for each thermostat on the
OAS.
The sensors must be setup within the thermostat settings.
Use of remote sensors should be limited to the greatest extent possible.
Buttons, thermostats and switches shall be accessible and warning light shall be generally visible within the associated room.
Allow for 3’ of clearance from the face of the control box per the latest revision of the
NEC.
5.2 Electrical Requirements:
All requirements of the most current revisions of
FAA-‐STD-‐19
and
FAA-‐C-‐1217
shall be followed.
All associated control wires run between the Controller and
HVAC
Units shall be contained within conduits.
Any outdoor conduit runs shall be rigid type with threaded connections or liquid-‐tite flexible conduit.
The
OAS
is powered by low voltage
24VAC,
supplied by the associated
HVAC
Units.
To fully isolate power from the controller, each
HVAC
must be electrically disconnected.
The
OAS
does not require a separate power circuit and the only energized power within the controller will be the
24VAC
provided from the
HVAC
Units.
Warning:
When attaching or changing wired connections within the
OAS,
ensure power is electrically isolated from
BOTH
HVAC
Units.
Failure to do so may cause sparks, damage to the
OAS,
damage to the
24VAC
Transformers in the
HVAC
units, and/or personal injury.
OAS
2.5 User’s Manual
Installation:
5.1 Physical Installation:
The
OAS
is contained within a 10”x16”x5” electrical box.
The box contains mounting holes for attaching the box to a supporting wall or stand.
The controller should be mounted at chest level in a central location where the ambient temperature is representative of the room.
Locating the unit on an uninsulated outside wall, near equipment exhaust, or in a stagnant air area may cause the system to operate inefficiently.
If space is not available for the
OAS
in a preferred location, a separate remote temperature sensor option can be added.
of these sensors are required, one for each thermostat on the
OAS.
The sensors must be setup within the thermostat settings.
Use of remote sensors should be limited to the greatest extent possible.
Buttons, thermostats and switches shall be accessible and warning light shall be generally visible within the associated room.
Allow for 3’ of clearance from the face of the control box per the latest revision of the
NEC.
5.2 Electrical Requirements:
All requirements of the most current revisions of
FAA-‐STD-‐19
and
FAA-‐C-‐1217
shall be followed.
All associated control wires run between the Controller and
HVAC
Units shall be contained within conduits.
Any outdoor conduit runs shall be rigid type with threaded connections or liquid-‐tite flexible conduit.
The
OAS
is powered by low voltage
24VAC,
supplied by the associated
HVAC
Units.
To fully isolate power from the controller, each
HVAC
must be electrically disconnected.
The
OAS
does not require a separate power circuit and the only energized power within the controller will be the
24VAC
provided from the
HVAC
Units.
Warning:
When attaching or changing wired connections within the
OAS,
ensure power is electrically isolated from
BOTH
HVAC
Units.
Failure to do so may cause sparks, damage to the
OAS,
damage to the
24VAC
Transformers in the
HVAC
units, and/or personal injury.
OAS
2.5 User’s Manual
5.3 Connections:
The
OAS
controller has connections identical to most modern thermostats, and therefore wiring the controller is similar.
Each installation may vary slightly, however the basic premise remains the same.
Inside the box, there are separate terminal strip areas, one for each unit.
They should appear similar to the picture below:
Figure 2:
OAS
Wiring Terminals
These connections are in accordance with industry standard, and are compatible with the vast majority of
HVAC
equipment.
The symbols are defined below for reference:
Symbol Description Standard Wire Color
R Control Power
(24VAC)
from associated
HVAC
Unit Red
Y1 Stage Cooling, control point Yellow
Y2 Stage Cooling, control point Blue
W Heat, control point White
G Fan (Supply Air Blower) Green
C Common or Neutral Brown
Wire colors and symbols may vary slightly depending on manufacturer
A single line diagram is shown on the next page for a simple packaged unit installation.
Each facility should be provided with a site specific control drawing that depicts the actual configuration.
The diagram contained in this manual shall be used for reference only.
Unit
Connections
Unit
Connections
OAS
2.5 User’s Manual
Figure 3:
Typical Control Wiring
OAS
2.5 User’s Manual
Operation:
6.1 Introduction:
The
OAS
is delivered configured, tested, and ready for the operation of a Unit, fully redundant, dual stage, cooling only, HVAC
System.
However, if a thermostat is replaced or for some other reason the thermostat needs to be reset, the required parameters are provided in “Appendix A” to assist in reprograming.
The
OAS
utilizes the Honeywell VisionPro Thermostat.
This model has a touch screen, and provides various capabilities that allow the
OAS
to be more robust and flexible while also providing a simple operational interface.
The diagram below explains the basic operation of this thermostat:
Figure 4:
Thermostat Quick Reference
Heating:
If the associated
HVAC
system includes heat, the
SYSTEM
setting on T1 (upper thermostat) only can be changed to “Auto”.
In this setting, the
OAS
will provide automatic switchover from cooling and heating as needed on the active unit.
The T2
(lower thermostat)
SYSTEM
setting must always be set to “Cool” regardless of the system configuration.
Current
Temperature
FAN
Menu Sets fan mode.
Set to
“On”
SYSTEM
Menu
Sets System
Setting.
Default is
“Cool”
Current System
Mode
Set Point
Adjusted with Up
Down Arrows
OAS
2.5 User’s Manual
6.2 User Inputs:
The
OAS
Controller has basic inputs:
Room Set Point The Desired Room Temperature To set, adjust the set point of the T1 (upper) thermostat.
This will be the temperature that the
OAS
will try to maintain the room at within a few degrees.
Recommended Set Point:
70°
Overtemp Set Point The Unit Failure Temperature To set, adjust the set point of the T2 (lower) thermostat.
This will be the temperature where the controller assumes the selected primary unit has failed, and will switch to the back-‐up unit.
Recommended Set Point:
80°
Primary Unit Selection The Unit that will operate as Primary To set, move the selector switch to the desired unit number.
Whichever unit is selected will be the operational unit unless the
OAS
is in Alarm.
To ensure similar run times on both
HVAC
Units, this selector switch should be toggled at regular intervals.
Recommended Interval:
Monthly
Care should be taken in selecting the Room and Overtemp Set Points.
Selecting a Room Temperature that is too low may result in Unit failure.
Additionally, selecting an Overtemp Temperature that is too close to the Room Temperature set point may cause the
OAS
to alarm during normal operation.
To prevent these issues, do no set the Room Temperature below 68°, and ensure the Overtemp Set Point is at least 6° higher than the Room Set Point.
6.3 System Status Lights:
There are status lights on the
OAS
which are intended to provide quick visual information to the user.
The lights are split up by
HVAC
Units so there are statuses shown per unit.
An illuminated power light indicates that the associated
HVAC
Unit is providing control voltage.
An illuminated Run Light indicates that the associated
HVAC
unit is active.
This light does not indicate that the unit is actually cooling, only that if cooling is called for, this is the unit that should cool.
Under normal operation, the Power lights for each unit should be illuminated, and the
Run light for the selected primary unit should be illuminated.
UNIT
UNIT
POWER
RUN
OAS
2.5 User’s Manual
6.4 Operational States:
Normal Operation:
The T1 (upper) thermostat will control the selected primary unit directly.
Only the primary unit will be allowed to run and maintain the room at the Room Set
Point.
Unit Failure:
If the primary unit fails for any reason, it will not be able to maintain the Room
Set Point.
Once the room temperature climbs above the Overtemp Set Point, the
OAS
will alarm.
During alarm, a red light will illuminate on top of the controller, the Alarm
Silence button will illuminate, and a loud alarm tone will sound from the controller.
When in alarm, the
OAS
will shutdown the selected primary unit, and T1 will begin controlling the back-‐up unit directly.
Only the back-‐up unit will be allowed to operate.
Since T1 is now controlling the back-‐up unit, the room temperature should return back to the Room Set Point.
Alarm Silence
To silence the audible alarm, press the Alarm Silence button once.
The red alarm light on the top of the controller and the light in the Alarm Silence button will remain illuminated.
Reset:
To reset the
OAS
controller from an alarm condition, press the Reset Button.
This will resume normal operation of the
OAS
controller.
If the room temperature is above the Overtemp Set Point, the Reset button will not function.
The room temperature must be below the Overtemp Set Point to reset.
Note:
The
OAS
does not monitor specific conditions in each
HVAC
unit and an alarm only indicates that the
Temperature in the room exceeded the Overtemp Set Point while the selected primary unit was active.
Upon an alarm, a technician should perform a deeper evaluation into why the selected unit was not able to maintain the Room Set Point.
OAS
2.5 User’s Manual
6.4 Operational States:
Normal Operation:
The T1 (upper) thermostat will control the selected primary unit directly.
Only the primary unit will be allowed to run and maintain the room at the Room Set
Point.
Unit Failure:
If the primary unit fails for any reason, it will not be able to maintain the Room
Set Point.
Once the room temperature climbs above the Overtemp Set Point, the
OAS
will alarm.
During alarm, a red light will illuminate on top of the controller, the Alarm
Silence button will illuminate, and a loud alarm tone will sound from the controller.
When in alarm, the
OAS
will shutdown the selected primary unit, and T1 will begin controlling the back-‐up unit directly.
Only the back-‐up unit will be allowed to operate.
Since T1 is now controlling the back-‐up unit, the room temperature should return back to the Room Set Point.
Alarm Silence
To silence the audible alarm, press the Alarm Silence button once.
The red alarm light on the top of the controller and the light in the Alarm Silence button will remain illuminated.
Reset:
To reset the
OAS
controller from an alarm condition, press the Reset Button.
This will resume normal operation of the
OAS
controller.
If the room temperature is above the Overtemp Set Point, the Reset button will not function.
The room temperature must be below the Overtemp Set Point to reset.
Note:
The
OAS
does not monitor specific conditions in each
HVAC
unit and an alarm only indicates that the
Temperature in the room exceeded the Overtemp Set Point while the selected primary unit was active.
Upon an alarm, a technician should perform a deeper evaluation into why the selected unit was not able to maintain the Room Set Point.
OAS
2.5 User’s Manual
6.5 Sequence of Operation:
OAS
2.5 User’s Manual
Troubleshooting:
Problem
Check Condition Potential Cause Corrective Action
Power light is not illuminated for a unit.
(If power light is not illuminated for the backup unit, make the backup unit the primary and perform these steps.
If the power light illuminates in only one mode, perform the
System Test in App B)
• 24VAC
present at the R terminal for the associated
Unit?
• 24VAC
is present at R terminal
• Lose Connection
Check
Connections within the
OAS
to ensure there are no loose wires or short circuits
• Tighten and/or secure loose connections as needed.
• Bad Relay
Perform System
Test in Appendix B to ensure all
Relays are operational
• Replace Defective
Relay (see parts list)
• Bad
LED
Check
LED
operation by applying
24VAC
across contacts.
• Replace
LED
bulb
(see parts list)
• 24VAC
is not present at R terminal
• Unit is electrically isolated.
• Check breakers and disconnects for the associated Unit.
• Check Associated
Unit Control
Power
24VAC
output
Measured between terminals R and C terminals in the
Unit.
• Check control transformer for a fuse or built in circuit breaker.
If no
CB
or fuse are present, and transformer is not outputting
24VAC,
Replacement of the transformer may be required.
Run light is not illuminated for the selected unit.
• Is
OAS
is in Alarm?
OAS
is in Alarm.
• When in Alarm, the “Run Light” should be illuminated for the back-‐up Unit and not the selected Unit.
• Reset
OAS
and troubleshoot the selected unit.
• Is the
FAN
setting on T1 set to “On”?
• FAN
Setting set to
“Auto”.
• The Run light is tied directly to the call for indoor fan.
In “Auto” setting, the Run light will only illuminate during a call for cooling.
• It is recommended that the fan be run continuously on the active Unit.
Change
T1
FAN
Setting to
“On”.
FAN
Setting set to
“On”
• Bad
LED
Check
LED
operation by applying
24VAC
across contacts.
• Replace
LED
bulb
(see parts list)
OAS
2.5 User’s Manual
Problem Check Condition Potential Cause Corrective Action
Sporadic clicking sounds while opening the
OAS
Panel
N/A
• Relays are engaging/disengaging randomly as
OAS
door is moving.
• Short or loose connection in
Wiring Bundle between panel door and relay board
• Inspect for loose connections and repair as needed.
• Request
Replacement
Controller from
Staging Area.
OAS
is in Alarm and will not reset
Is Room
Temperature above
Overtemp Setpoint
(T2)?
• Room Temperature is above Overtemp
Setpoint.
• OAS
Alarm cannot be reset when the conditions would immediately put it back into Alarm.
• Alternate Units, ventilate, and/or add temporary cooling to bring down the room temperature.
• Room Temperature is below Overtemp
Setpoint.
• T2 may be in a time delay function
• Allow some time for T2 to reset (5 minutes max) and retry.
Upper thermostat
(T1) isn’t functioning.
Is the Power Light illuminated for the selected unit?
• Power Light is On
• Bad Thermostat or other
OAS
Component
Perform System
Test in Appendix B to ensure all components are operational
• Replace Defective part (see parts list)
• Power Light is Off
• OAS
is not receiving control power from the selected unit.
• Perform troubleshooting steps for “Run light is not illuminated for the selected unit.”
above.
Lower thermostat
(T2) isn’t functioning.
Is the Power Light illuminated for the back-‐up unit?
• Power Light is On
• Bad Thermostat or other
OAS
Component
Perform System
Test in Appendix B to ensure all components are operational
• Replace Defective part (see parts list)
• Power Light is Off
• OAS
is not receiving control power from the backup unit.
• Perform troubleshooting steps for “Run light is not illuminated for the selected unit.”
above.
OAS
2.5 User’s Manual
Problem Check Condition Potential Cause Corrective Action
Sporadic clicking sounds while opening the
OAS
Panel
N/A
• Relays are engaging/disengaging randomly as
OAS
door is moving.
• Short or loose connection in
Wiring Bundle between panel door and relay board
• Inspect for loose connections and repair as needed.
• Request
Replacement
Controller from
Staging Area.
OAS
is in Alarm and will not reset
Is Room
Temperature above
Overtemp Setpoint
(T2)?
• Room Temperature is above Overtemp
Setpoint.
• OAS
Alarm cannot be reset when the conditions would immediately put it back into Alarm.
• Alternate Units, ventilate, and/or add temporary cooling to bring down the room temperature.
• Room Temperature is below Overtemp
Setpoint.
• T2 may be in a time delay function
• Allow some time for T2 to reset (5 minutes max) and retry.
Upper thermostat
(T1) isn’t functioning.
Is the Power Light illuminated for the selected unit?
• Power Light is On
• Bad Thermostat or other
OAS
Component
Perform System
Test in Appendix B to ensure all components are operational
• Replace Defective part (see parts list)
• Power Light is Off
• OAS
is not receiving control power from the selected unit.
• Perform troubleshooting steps for “Run light is not illuminated for the selected unit.”
above.
Lower thermostat
(T2) isn’t functioning.
Is the Power Light illuminated for the back-‐up unit?
• Power Light is On
• Bad Thermostat or other
OAS
Component
Perform System
Test in Appendix B to ensure all components are operational
• Replace Defective part (see parts list)
• Power Light is Off
• OAS
is not receiving control power from the backup unit.
• Perform troubleshooting steps for “Run light is not illuminated for the selected unit.”
above.
OAS
2.5 User’s Manual
Parts List:
QTY
Description Make/Model Part No
EA
Thermostat Honeywell VisionPro
HW-‐TH8321-‐R1001
AS
Selector Switch Eaton Switch
EA
10250T3011
Contact
EA
10250T1
EA
Indicator Lights Grainger 24M067
AS
Push Button (Alarm Silence)
ABB
Button
EA
MP1-‐31R
Contact
EA
MCBH-‐01
LED
EA
MLBL-‐01R
AS
Push Button (Reset)
ABB
Button
MP1-‐30R
Contact
MCBH-‐01
EA
Relay
IDEC
RH-‐4B-‐UL
AC24V
Optional Parts:
QTY
Description Make/Model Part No
EA
Wireless Remote Sensors Honeywell C7189R
OAS
2.5 User’s Manual
Schematics:
OAS
2.5 User’s Manual
OAS
2.5 User’s Manual
Appendix A
Appendix A
T1 (Top):
Installer Setup:
Application Commercial Thermostat Name Thermostat Zoned No Equipment Module No Connect Redlink No Installer Setup
NEXT
Thermostat Type Non-‐ Programmable Temperature Scale Fahrenheit Outdoor Air Sensor No Heating System None (Cool Only) Cooling Stages A-‐L/A Terminal None Control Options Basic Cool/Compressor
CPH
Stg Cool/Compressor
CPH
Stg Compressor Off time Off Extended Fan Run Time in Cool Off Min Cool Setpoint Keypad Lockout Unlocked Wired Sensor on S Terminal No Filter Type:
Media Number of Filters Air Filter Reminder Off Humidifier Type None Humidifier Pad Reminder Off Dehumidifier None Defumidifier Filter Reminder Off Ventilation Type None Ventilation Filter Reminder Off Number of
UV
Devices None Custom Reminder
NEXT
Backlighting On Demand Clock Format 12hr Daylight Savings Time Off Indoor Temp Offset Indoor Humidity Offset Alert Light Indicator On Dealer Name
NEXT
Dealer Phone
NEXT
Dealer Email
NEXT
Dealer Website
NEXT
Dealter Message
NEXT
DONE
Exit Installer Setup
YES
T2 (Bottom):
Installer Setup:
Application Commercial Thermostat Name Thermostat Zoned No Equipment Module No Connect Redlink No Installer Setup
NEXT
Thermostat Type Non-‐ Programmable Temperature Scale Fahrenheit Outdoor Air Sensor No Heating System None (Cool Only) Cooling Stages A/L/A Terminal Off Control Options Basic Cool/Compressor
CPH
Stg Compressor Off time Off Extended Fan Run Time in Cool Off Min Cool Setpoint Keypad Lockout Unlocked Wired Sensor on S Terminal No Filter Type:
Media Number of Filters Air Filter Reminder Off Humidifier Type None Humidifier Pad Reminder Off Dehumidifier None Defumidifier Filter Reminder Off Ventilation Type None Ventilation Filter Reminder Off Number of
UV
Devices None Custom Reminder
NEXT
Backlighting On Demand Clock Format 12hr Daylight Savings Time Off Indoor Temp Offset Indoor Humidity Offset Alert Light Indicator On Dealer Name
NEXT
Dealer Phone
NEXT
Dealer Email
NEXT
Dealer Website
NEXT
Dealter Message
NEXT
DONE
Exit Installer Setup
YES
Main Screen Settings:
SYSTEM:
COOL
FAN:
ON
OAS
2.5 User’s Manual
B
Appendix B
Relay Operation Check:
Note:
This test confirms the proper operation of the
OAS
controller.
This test is best performed using isolated
24VAC
power sources as shown below.
Test can be performed using control power from the
HVAC
Units, but this test will cause non-‐continuous operation of the units, so care must be taken to ensure the equipment space remains at a desirable temperature.
During Test, note any inconsistencies from the expected checks and utilize this information for troubleshooting faulty components or other issues.
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
OAS
2.5 User’s Manual
B
Forma P GC-009
GOBIERNO DE PUERTO RICO
OFICINA DEL GOBERNADOR
JUNTA DE CALIDAD AMBIENTAL
Área de Calidad de Agua
CERTIFICACION DE NO PRESENCIA DE ASBESTO
EN ESTRUCTURAS A DEMOLERSE
(Deberá completarse en letra de molde o impresa)
PGC-_____________________
PARA USO OFICIAL
(Nombre) (Estado Civil) (Municipio)
Dirección Postal__________________________________ _________________________________________________ demolición se encuentra libre de asbesto.
2. La información antes indicada es cierta y correcta.
3. Afirmo y reconozco las consecuencias de incluir y someter información falsa en este documento.
(Municipio)
Firma y Sello del Profesional o
Firma del Inspector de Asbesto registrado por la JCA (Original)
Nota: Ingenieros o Arquitectos deberán someter evidencia de que se encuentra al día en el pago de sus cuotas de colegiación e Inspectores de Asbesto deberán someter evidencia de la tarjeta de registro provista por la JCA.
Dirección Física: Ave. Ponce de León 1308, Carr. Estatal 8838, Sector el Cinco, Río Piedras, PR 00926
Dirección Postal: Apartado 11488, Santurce, PR 00910-
Elme Rivera Casado Yo, ______________________________, mayor de edad,______________, y vecino de__ _______________________ Vega Baja
Vega Baja Lakes Calle 11 L31 00693
(Pueblo) (Zip Code)
Vega Baja
787 724 5788
969 1311 787 722 0220
4. Para que así conste, firmo la presente certificación en ___________________ __________________ de Puerto Rico, Tel. (787) 767-8181 • Fax (787) 767-1962 hoy día ____ de ____________________ de ________
Teléfonos: Residencial (______) ______- ________ Oficina (______) ______- ________ Ext.________ Fax (______) ______- ________
Certifico que:
1. La estructura localizada en__________________________________________________, la cual será objeto de una
* Esta certificacion es exclusivamente para las areas muestreadas.
San Juan
8 abril 2021
Appendix I
Appendix II
TESTING
ANALYTICAL ENVIRONMENTAL SERVICES INTERNATIONAL, INC.
POLARIZED LIGHT MICROSCOPY (PLM) BULK SAMPLE ANALYSIS REPORT
REPORT NUMBER
RP21040702
Comments:
FOR ALL HETEROGENEOUS AND LAYERED SAMPLES EASILY SEPARATED INTO SUBLAYERS, EACH COMPONENT IS ANALYZED AND REPORTED SEPARATELY.
SAMPLE WAS ANALYZED BY PLM USING DISPERSION STAINING TECHNIQUES IN ACCORDANCE WITH US EPA METHOD: 600/M4-82/020 of Dec. 1982 and 600/R-93/116 OF JULY 93.
EPA - 40 CFR APPENDIX E TO SUBPART E OF PART 763,INTERIM METHOD OF THE DETERMINATION OF ASBESTOS IN BULK INSULATION SAMPLES.
MICROANALYST:
PLM IS NOT CONSISTENTLY RELIABLE IN DETECTING SMALL CONCENTRATION OF ASBESTOS IN FLOOR TILES AND SIMILAR NONFRIABLE MATERIALS. QUANTITATIVE TEM IS CURRENTLY THE ONLY METHOD THAT CAN BE USED TO GET THE CONCLUSIVE ASBESTOS CONTENT. THIS REPORT RELATES ONLY TO THE ITEMS TESTED. THIS REPORT SHALL NOT BE REPRODUCED EXCEPT IN FULL AND NOT WITHOUT WRITTEN APPROVAL OF THE LABORATORY. THIS REPORT SHALL NOT BE USED TO CLAIM ENDORSEMENT BY NVLAP OR ANY AGENCY OF OF THE US GOVERNMENT. METHOD IS USED FOR DETERMINATION OF ASBESTOS IN BULK SAMPLES IS INTERIM METHOD FOR DETERMINATION OF ASBESTOS IN BULK INSULATION SAMPLES (EPA 600/M4-82-020) AS FOUND IN 40 CFR,PART 763, APPENDIX E TO SUBPART E.
[Elme Rivera]
Appendix III
Client Name: FAA/ESA Engineering Services 4/1/21
Project Name: Exterior Building Restoration on FAA Long Range Radar, Pico del Este Elme Rivera
Address: Rio Grande, Puerto Rico 2222
Reading # Structure Room Substrate Color Component & Location
XRF
Reading
Laboratory
Result (% or mg/cm
1 Calibration 1.0
2 Calibration 1.1
3 Calibration 1.1
4 South Exterior Building PVC Green Corrugated Panel 0.1
5 South Exterior Building Metal Green Inside Panel 0.2
6 South Exterior Building Metal Green Exterior Staircase Column 0.8
7 South Exterior Building Metal Green Exterior Staircase Handrail 0.6
8 South Exterior Building Concrete Green/Gray Exterior Staircase Base 0.4
9 South Exterior Building Metal Gray Exterior Ladder Rung 2.1
10 South Exterior Building Metal Gray Exterior Ladder Rail 2.3
11 South Exterior Building Concrete White Staircase Riser 0.1
12 South Exterior Building Concrete White Staircase Tread 0.3
13 Calibration 1.0
14 Calibration 1.0
15 Calibration 1.0
16 Radar Interior 1st Floor Metal Gray Lower Column 1.7
17 Radar Interior 1st Floor Metal White…