CONSTURCTION DRAWINGS QVR ARSR-1400365-ROOF.pdf
PDF 2 MB Posted
- Solicitation number
- 6973GH-19-R-00292
About this file
CONSTURCTION DRAWINGS QVR ARSR-1400365-ROOF (pdf)
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H
G
F
E
D
C
B
A
8 7
�'\ Of
TR411;
(5',.o
L...w a
C
1; <)
S14T£S 0�
Av1
DRAWING NO.
QVR-1 400368-G001
QVR-1400368-G002
QVR-1400368-G003
OVR-1400368-G004
QVR-1400368-A001
QVR-1400368-A002
OVR-1400368-E004
OVR-1400368-E005
Qp .,;A z:
G
-1 )'
,z, REV.
6 5 4 3 2 1
��r0¢-_, 44)
/ -----_j/__A, ii!I BEACH BL VO
Ed/ --- ----u
QVR/ ARSR - OCEAN A, VIRGINIA
ARSR-4 QVR
ROOF REPLACEMENT
DRAWING LIST
DATE
08/01/2017
08/01/2017
08/01/2017
DESCRIPTION
ARSR-4
ARSR-4
ARSR-4
ARSR-4
QVR
OVR
QVR
OVR
OCEANA ROOF REPLACEMENT
OCEANA ROOF REPLACEMENT
OCEANA ROOF REPLACEMENT
OCEANA ROOF REPLACEMENT
COVER SHEET AND DRAWING INDEX
ABBREVIATIONS
SYMBOLS AND LEGENDS
GENERAL NOTES
ARSR-4
ARSR-4
OVR OCEANA ROOF REPLACEMENT ROOFING PLANS - REMOVAL AND NEW WORK
QVR OCEANA ROOF REPLACEMENT ROOFING DETAILS
ARSR-4
ARSR-4
OVR
OVR
OCEANA ROOF
OCEANA ROOF
REPLACEMENT
REPLACEMENT
ROOF LIGHTNING PROTECTION
ELECTRICAL AIR TERMINAL DETAILS
5 4
PTSI Managed Services Inc.
3800 Camp Creek Pkwy Building" 2400, Suite 106
Atlanta, GA 30331
404. 766.1693
404.559.1715 (Fax)
APPROVED
DATE
VICINITY MAP
f�OT TO SCALE
CESCR!PT'ON JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
RED;...INE
DATE
ATO - TECHNICAL OPERATIONS EASTERN SERVICE
1--RE-L-EA-SE_D_F_O_R _, ------------1
CONSTRUCTION - osio1i2011
ARSR
ARSR-4 QVR OCEANA ROOF REPLACEMENT
COVER SHEET
AND DRAWING INDEX
OCEANA
RC:VIEWED BY
1----l-----'_ Bryan_ Pe
PROJECT ENGINEER MGR, ENGINEERING · CENTER A
/.l.PVD
AREA
VA
ISSUED BY DATE JCN
1----+--+0-R.I\-WN ___ ....,,D�
L
ENGINEERING srnv1cEs ..... DR-A,-V,N -G --"-2!= 1--"-0
12=0=17-'-----'1'-'-'40=0=3
R 6"-= Ee
OESIG�ED
1----1--��c------"-'RC""-IL NAV�DS CHECKED
QVR-1400368-G001
H
G
F
E
D
C
B z
0 ::> z
A
0 >
G
F
I::_
D
C
B
A
7 6 5
7 6 5
A, AMP
ABV
ADJ
AF
ALS
ALSF
APPROX
ARP
ATCT
AVG
BJ
BLDG
BOT
BOC
BSC
BSDC
C
CAB
CAP
CCM
CET
CL
CJ
CND
COMM
CONC
CONN
CONSTR
CONT
CONTR
CP
CTR
CBA
DEB
DIA
DIAG
DIM
DISTR
DME
ON
DWG
DS1
EA
EJ
EL, ELEV
EES
E/G
ELEC
EMERG
EMT
EQUIP
EXIST
EXP
EXT
FAA
FF
FFM
FL
FRANG
FT
FVC
FOP
F/0
A
AMPERES
ABOVE
ADJACENT, ADJUSTABLE
AIRWAY F AGILITY
AMBIENT LIGHT SENSOR
HIGH INTENSITY APPROACH
LIGHTING SYSTEM WITH
SEQUENCED FLASHING LIGHTS
APPROXIMATELY
AIRPORT REFERENCE POINT
AIRPORT TRAFFIC CONTROL
TOWER
AVERAGE
B
BONDING JUMPER
BUILDING
BOTTOM
BOTTOM OF CONDUIT
BARE STRANDED COPPER
BARE SOFT DRAWN COPPER
C
COMMUNICATION DUCT OR LINE
CABINET
CAPACITY
CONCRETE CABLE MARKER
CONSTRUCTION ENGINEERING
TECHNICIAN
CENTERLINE
CONTROL JOINT
CONDUIT
COMMUNICATIONS
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUE, CONTINUATION,
CONTINUOUS
CONTRACTOR
CONTROL PANEL
CENTER
CHANNEL BANK
D
DIRECT EARTH BURIAL
DIAMETER
DIAGONAL
DIMENSION
DISTRIBUTION
DISTANCE MEASUREMENT
EQUIPMENT
DOWN
DRAWING
DIGIT AL SIGNAL 1
E
EACH
EXPANSION JOINT
ELEVATION (HEIGHT)
EARTH ELECTRODE
SYSTEM (COUNTERPOISE)
ENGINE-GENERATOR
ELECTRIC
EMERGENCY
ELECTRICAL METALLIC TUBING
EQUIPMENT
EXISTING
EXPOSED, EXPANSION
EXTERIOR, EXTERNAL
F
FEDERAL AVIATION
ADMINISTRATION
FINISH FLOOR
FAR FIELD MONITOR
FLOOR, FLOW LINE
FRANGIBLE
FOOT, FEET
FIRE VAL VE CABINET
FIBER DISTRIBUTION PANEL
FIBER OPTIC
GA
GALV
GFM
GFCI
GND
G.P.S.
GEC
GL
GS
H
HC
HD
HORIZ
HT
HH
HV
ICC
!LS
IM
J
KV
KVA
KW
LOIN
LF
LHA
LOC
LOM
MALSF
MALSR
MH
MAX
MECH
MIN
MSL
MTL
MUX
3 2
ABBREVIATIONS
G
GAUGE
GALVANIZED
GOVERNMENT FURNISHED
MATERIALS
GROUND FAULT CIRCUIT
GROUND
GLOBAL POSITIONING SYSTEM
GROUNDING ELECTRODE
CONDUCTOR
GLASS
GLIDE SLOPE
H
HIGH
HANDICAPPED
ACCESSIBLE
HEAVY DUTY
HORIZONTAL
HEIGHT
HANDHOLE
HIGH VOLT AGE
INDIVIDUAL CONTROL CABINET
INSTRUMENT LANDING SYSTEM
INNER MARKER
J
JOULES
K
KILO-VOLT
KILO-VOLT AMPERES
KILO-WATT
L
NAD
NAVO
NIC
NDB
NGVD
OA
oc
OD
OH
OM
OPNG
OPP
P, PWR
PAPI
PCF
PL
PLBG
PNL
POI
POB
POS
pp
PSF
PSI
PT
PVC
PVMT
NORTH AMERICAN DATUM
NORTH AMERICAN VERTICAL
NOT IN CONTRACT
NON-DIRECTIONAL BEACON
NATIONAL GEODETIC
VERTICAL DATUM
OVERALL
ON CENTER
OUTSIDE DIAMETER/
OVERFLOW DRAIN
OPPOSITE HAND
OUTER MARKER
OPENING
OPPOSITE
p
POWER
PRECISION APPROACH PATH
INDICATOR LIGHTS
POUNDS PER CUBIC FOOT
PROPERTY LINE, PLATE
PLUMBING
PANEL
POINT OF INTERCEPT
POINT OF BEGINNING
POINT OF ST ART
POWER POLE
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
SA
DATUM SSALR
SCHED
SHT
SIM
SP
SPEC
SQ
ss
SSC
ST
STO
SW
TEL
TCH
TD
THK
TOC
TOD
TOFA
TOS
TSA
TS
TXWY
TYP
UON
UPS
PRESSURE TREATED, P�NT
POLYVINYL CHLORIDE CONDUIT UP
UTIL PAVEMENT
Q
QTY QUANTITY
s
SURGE ARRESTOR
SIMPLIED SHORT APPROACH
LIGHTING SYSTEM W/
RUNWAY ALIGNMENT
INDICATOR LIGHTS
SCHEDULE
SHEET
SIMILAR
SPACE
SPECIFICATIONS
SQUARE
STAINLESS STEEL
SYSTEM SUPPORT CENTER
STAIN
STORAGE
SWITCH
T
TELEPHONE
THRESHOLD CROSSING HEIGHT
TOUCHDOWN
THICK/THICKNESS
TOP OF CONCRETE
TOP OF DUCT
TAXIWAY OBJECT FREE AREA
TOP OF STEEL
TAXIWAY SAFETY AREA
TUBE STEEL
TAXIWAY
TYPICAL
u
UNLESS OTHERWISE NOTED
UNINTERRUPT ABLE POWER
SUPPLY
UTILITY POLE
UTILITY
V
VISUAL APPROACH
SLOPE INDICATOR
H
G
F
E
LEAD-IN LIGHTS
LINEAR FEET
LAMP HOUSING
ASSEMBLY
LOCALIZER
R
VASI
VERT
VIF
VERTICAL
VERIFY IN FIELD
VOLTS
RAIL RUNWAY ALIGNMENT
INDICATOR LIGHTS
V
VISUAL SENSOR
LOCATOR - OUTER MARKER RCP REINFORCED CONCRETE PIPE
vs
VTR VENT THROUGH ROOF
M
RCVR RECEIVER
RE RESIDENT ENGINEER w D
MEDIUM INTENSITY APPROACH
LIGHTING SYSTEM W /
SEQUENCED FLASHING LIGHTS
MEDIUM INTENSITY APPROACH
LIGHTING SYSTEM W/ RUNWAY
ALIGNMENT INDICATOR LIGHTS
MANHOLE
REF REFERENCE
REIL RUNWAY END IDENTIFICATION
LIGHTS
REINF REINFORCEMENT, REINFORCED
REQD REQUIRED
REV REVISION
RSA RUNWAY SAFETY AREA
WI
W/0
WH
WR
WT
WWF
WITH
WITHOUT
WATER HEATER
WATER RESIST ANT
WEIGHT
WELDED WIRE FABRIC
MAXIMUM
MECHANICAL
MINIMUM
MEAN SEA LEVEL
METAL
MULTIPLEXER
RSC/RGS RIGID STEEL CONDUIT/
RIGID GALVANIZED STEEL
RO ROLLOUT
ROFA RUNWAY OBJECT FREE AREA
RVR RUNWAY VISUAL RANGE
RWY RUNWAY
R/W RIGHT-OF-WAY
XMTR
XFMR
X
TRANSMITTER
TRANSFORMER
C
PARSONS�-� ...... -.. �-------������=�=�
PTSI Managed Services Inc. , 0. ;,�
3800 Camp Creek Pkwy !:';,ff&.'< ·i �'·• ·· · · -····· Building" 2400, Suite 106 t ti�///�(*.!'.( �{t�
, REV AP
l;���ED ' ··· -·- · · ··-··- -�- E
-s-cR -.1F
TIO
-N-------+-J�CN -l----Ri',-�L.-1�l-.1.-,1P---1vo B Atlanta, GA 30331 !Ii I ,Fd.�� ,;, J)ilt--'---"-..;;..__.______________ ..1-_ __i:.._..:;:;.:.:;,_...J...-I
404.766.1693 �,� 1 �J DEPARTMENT OF TRANSPORTATION z 404.559,1715 (Fax) '-� lC:: YA FEDERAL A VIA Tl ON ADMINISTRATION
0�
RELE/\SED FOR:
� · ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA =>
CONSTRUCTION - 08/01/2017 �
ARSR
ARSR-4 OVR OCEANA
ABBREVIATIONS �
OCEANA . /'}
REVEWED BY SLBMIT TE
D BY
·=·d-�AA/'"7P"' < ---1-�
BY /'///
,::;,rv,=·- • - n r,-,2� .. '-.. "(,,/ 7_ �-)p
_ __ _ _ _ _ Bryan P nnamon ..
PROJECT ENGINEER MGR•ENG�EEmNG - CENTER A
DESIGNED
VA
ISSUED BY DATE '') IJC,
1----l --+D� RA�IV-N ___ Ck/'AK!tl.j ENGINEERING SERVICES f,-D�RA-IVl l�IG-'�""o8"-'10=1
1 =0.J.!.17-'-------.C:14""'0-"'0 ""��"'-'�
1----l--+C-HE�CK-ED _ __ H!]bL�G NAY AIDS
QVR-1400368 G002
G
F
E
D
C
B
A
GENERAL
DETAIL NUMBER ---, --
A 3
DETAIL TITLE REFERENCE
A, 12 A003
SHEET ON WHICU' ,_ ·,
DETAIL IS DRAW
OR SCHEDULED
SHEET FROM WHICH DETAIL
IS TAKEN OR FIRST REFERENCED -1
SECTION LETTER-�,,--
r, A
SECTION TITLE REFERENCE Ab1Q AQQS
SHEET ON WHICH /·
SECTION IS DRAWN_/
SHEET WHERE
SECTION CUT
PARTIAL SECTION CUT
ELEVATION REFERENCE
NORTH ARROW
ROOM/AREA NUMBER
DEMOLITION
SECTION
/A'\ ..
\.AD10,'
IS CUT
.., A '"
\_A010
_i_
REVISION
,.I -v " " '-... r .. ...-- CLOUD TO
ENCOMPASS
REVISION DESIGNATION
GENERAL SYMBOLS
• NUMBER.POUNDS
---{c----- CENTERLINE
II
FEET OR MINUTES
INCHES OR SECONDS
DEGREE
AT
REVISED AREA
EXISTING WORK TO BE REMOVED
EXISTING WORK
NEW WORK
GLIDE SLOPE CRITICAL AREA
RUNWAY SAFETY AREA
--------- RUNWAY OBJECT FREE AREA
_____ ft, _____ _
FENCE
PROPERTY LINE
SITE ACCESS ROUTE
STAGING AREA
6 5 .. 4 3 2 1
SYMBOLS AND LEGENDS
CIVIL
EXISTING NEW
FAA POWER CABLE
FAA LINES POWER CONTROL FLPC/F AA LINES POWER CONTROL
HANDHOLE/PULLBOX
AVN FUEL LINE
FUEL M SHP
GAS LINE
CONDENSATE RETURN
INDUSTRIAL COLD WATER
BUILDING
ELECTRICAL MANHOLE CEMH)
STORM WATER LINE
WATER LINE
FIRE WATER
WATER M SHP
CONCRETE CABLE MARKER
ELECTRIC POWER LINE:
OVERHEAD
UNDERGROUND
ELECTRIC LINES
ELECTRICAL CONTROL
D
AFL/ A\/N FUEL LNE
FUEL M SHP
-G-
-CR -
-1w-
D
SWL/STORM WATER LINE
WL/WATER LINE
-FW-
WATER M SHP
D
-P-.-
-POWER-
EL/ELECTRIC LINES
AF
IMDC ELEC M SHP
ELECTRIC DUCT BANK LINE
IMDC ELEC M SHP
EDL/ELECTRIC DUCT BANK LINE
TELEPHONE LINE:
OVERHEAD
UNDERGROUND
TELECOM LINE
BURIED DUCT BANK
CONDUIT
OVERHEAD ELECTRICAL
UTILITY POLE
UNDERGROUND DUCT BANK
ELECTRIC BUSS DUCT SUPPORT
TRANSFORMER
STREET LIGHT
LIGHTCAN
-T-
-T UG
TELECOM LINE
UG -D-
-OE-
-u.�-- 1---------lf.--------1
[jl o---¢
-6-
SANITARY SEWER LINE SSL/SANITARY _SEWER _Ll�JE
SAN M SHP
STORM DRAIN LINE
PROPERTY LINE
EASEMENT LINE
SIGN
TREES
ASPHALT PAVING
PCC
(PORTLAND CEMENT
CONCRETE)
GRAVEL AREA
LEASE AREA
COMMUNICATIONS
SPOT ELEVATION
CONTOUR
FENCE
STRUCTURE/SHELTER
SWALE/DITCH
HORIZONTAL DIRECTIONAL
BORE (HOB)
SAi--:_ M SHP
SD
______ tj;_ _____ _
I
I
E3
I l
I '
I ---------"
X 9.50
---s---
DCM
C---J
1 •• .
X 10.25
--5--
-111:-X-K-
ELECTRICAL
---- ELECTRICAL CONDUIT AND WIRING
BRANCH CIRCUIT, SURFACE MOUNTED 3/4"C,
WITH 2"12 WIRES PLUS 1*12 GROUND
CROSS MARKS DENOTE NUMBER OF 4112 WIRES
WHEN MORE THAN 3 IN 3/ 4" CONDUIT
-"" / ' SAME AS BRANCH CIRCUIT - BUT CONCEALED
DP, 1
HOME RUN TO PANEL DP CIRCUIT 1, SHOWN
SOLID WHETHER CONCEALED OR EXPOSED
� CONDUIT, CAPPED
� CONDUIT, FLEXIBLE
� CONDUIT DOWN
� CONDUIT UP
[D OR , • 'j '., TRANSFORMER
·----- EXOTHERMIC WELD
�1 5A FUSE, 15A
GROUND ROD 3/ 4"x 10'-011
WITH EXOTHERMIC WELD
GJ GROUND ACCESS WELL
• ABOVE GROUND JUNCTION
D UNDERGROUND HANDHOLE
BOX
CONTROL CABLE COLOR CODE CHART H
100 PAIR CONTROL CABLE
FOUR BUNDLES - 25 PAIR PER BUNDLE - CODED WITH TWINE
BUNDLE COLOR CODED TWINE PAIR NOS.
1 ST BLUE 1 THRU 25
2ND ORANGE 26 THRU 50
3RD GREEN 51 THRU 75 G
4TH BROWN 76 THRU 1 00
COLOR CODE PER BUNDLE
PAIR NO. TRACER COLOR
1 • WHITE BLUE
2. WHITE ORANGE
3. WHITE GREEN
4. WHITE BROWN
5. WHITE SLATE
F 6 . RED BLUE
7. RED ORANGE
8. RED GREEN
9. RED BROWN
1 0, RED SLATE
1 1 • BLACK BLUE
1 2. BLACK ORANGE
1 3. BLACK GREEN
1 4. BLACK BROWN
1 5, BLACK SLATE
1 6. YELLOW BLUE
1 7. YELLOW ORANGE
1 8, YELLOW GREEN
1 9. YELLOW BROWN
E 20. YELLOW SLATE
21 • PURPLE BLUE
22. PURPLE ORANGE
23. PURPLE GREEN
24. PURPLE BROWN
25. PURPLE SLATE
PAR SD NSl---l--------1---------1----+----+---I PTSI Managed Services Inc. �� 3800 Camp Creek Pkwy #/.!;:f u z � 1----1--- -----J.-------- - ------l-------"e-----1-----1 Building" 2400, Suite 106 'fj,·'(;� ·"5M � , '",. REV t.P�1�to 01cscR1PT10N JCN Rfi';}1�E
APVD
Atlanta, GA 30331 �I� �� ,,;)J J)il--.J.-_;;,;..;.......1. __ D_E_ P_A_R_T _M_E_ N_T_O_F_T _R _A _N _S_PO_ R_ T_ A_ T_I.._O_N _ ___.'"--...,;,;,,;.,;.,_--'---t 404-766·1693 ::;;u r4t1 ' °
FEDERAL A VIA TI ON ADMINISTRATION 404.559.1715 (Fax) �� � �·
"<! ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
RELEASED FOR:
CONSTRUCTION - 08/01/2017
ARSR
ARSR-4 QVR OCEANA
SYMBOLS AND LEGENDS
OCEANA
Bryan Pennamon : M noJ , ' ,u -
PROJECT ENGINEER MGR: ENGINEERING - CENTER /1.
VA
DESIGNED ISSUED BY DATE IJCN
DRAWN CAK ENGINEERING SERVICES �DR-AW- IN-G--"2=
o
8'-'10'-"'11'-=2"'-01'"-7J__- --'-'14-"'00,::.;,3"" R
�"'-le l----+--1------=HL"'-JG NAY AIDS CHECKED
• QVR-1400368-G003
D
C z
V) z
V)
F
E
D
C
B
A
8 7 6
GENERAL NOTES
1. DURING PERIODS WHEN CONSTRUCTION EQUIPMENT AND VEHICLES ARE WORKING
ADJACENT TO ROADWAYS HAVE EQUIPMENT ON-SITE IN ORDER TO CLEAN SUCH
PAVEMENTS. THE CLEANING MEASURES SHALL BE ACCEPTABLE TO THE RE AND
AIRPORT MANAGEMENT.
2, ALL CONSTRUCTION ACTIVITIES SHALL BE CONDUCTED IN A MANNER ACCEPTABLE
TO THE FEDERAL AVIATION ADMINISTRATION (FAA), THE RE WILL ATTEND A
WEEKLY CONSTRUCTION COORDINATION MEETING TO COORDINATE THIS WORK. THE
SUBCONTRACTOR SHALL COOPERATE FULLY TO ALLOW ORDERLY PROGRESSION OF
ONGOING OPERATIONS AND TO MAINTAIN ACCEPTABLE LEVELS OF SAFETY.
3. REVIEW ALL UTILITIES PRIOR TO BEGINNING WORK, THE SUBCONTRACTOR IS
RESPONSIBLE FOR OBTAINING INFORMATION ON THE UNDERGROUND CABLING
AND FACILITIES FROM AIRPORT AND FAA.
4. ENSURE THAT ALL TRAFFIC OVER EXISTING OR CONSTRUCTED IMPROVED ROADWAYS
ARE WITHIN THE DESIGN WEIGHT RANGE OF SAID ROADS AND IS RESPONSIBLE FOR
REPAIRS OF ANY DAMAGE OR DETERIORATION TO SAID ROADS.
5. CONTROL DUST, WASTE AND DEBRIS RESULTING FROM OPERATIONS AT ALL TIMES.
THE SUBCONTRACTOR SHALL HAVE AVAILABLE THE MEANS TO CLEAN AND REMOVE
ANY DEBRIS OR EARTH MATERIAL THAT MAY BE DROPPED ON ANY ROADWAY AT ALL
TIMES. OPERATIONS THAT RESULT IN THE SPILLAGE OF DEBRIS ON ROADS, OR THE
FAILURE TO PROPERLY REMOVE ANY SPILLED MATERIAL MAY RESULT IN THE
STOPPING CONSTRUCTION ACTIVITY UNTIL THE OPERATION JS CORRECTED.
6. PRIOR TO BEGINNING OF CONSTRUCTION, INSPECT THE CONDITION OF THE
EXISTING PAVEMENT, GRAVEL ROAD(S). SUBCONTRACTOR SHALL PROVIDE A REPORT
TO THE RESIDENT ENGINEER AND THE PROJECT MANAGER, THIS REPORT SHALL
CONTAIN THE LOCATION AND THE DESCRIPTION OF ANY ITEM(SJ ALREADY DAMAGED.
7, ANY DAMAGE TO THE EXISTING SITE CONDITIONS CAUSED BY THE SUBCONTRACTOR'S
PERSONNEL OR EQUIPMENT DURING CONSTRUCTION SHALL BE REPAIRED BY THE
SUBCONTRACTOR AT NO COST TO THE OWNER.
SECURITY AND SAFETY NOTES
1. SUBCONTRACTOR'S SECURITY CLEARANCE: THE SUBCONTRACTOR'S EMPLOYEES SHALL
COMPLY WITH ALL SECURITY CLEARANCE REQUIREMENTS OF THE CONSTRUCTION
CONTRACT AND WITH LOCAL AUTHORITIES. THE SUBCONTRACTOR SHALL NOT PERMIT
ANY UNAUTHORIZED PERSONNEL OR TRAFFIC ON THE SITE.
2. GENERAL SAFETY CRITERIA - ALL PROVISIONS OF THE FAA AC 150/5370-2F
uOPERATIONAL SAFETY ON AIRPORTS DURING CONSTRUCTION,u AND THE
CONSTRUCTION CONTRACT APPLY.
3. ADHERE TO REQUIREMENTS AS SET FORTH IN THE FAA SAFETY RISK MANAGEMENT
(SRMJ DOCUMENT AND SUBCONTRACTORS APPROVED RISK MANAGEMENT PLAN (RMP).
4. THE CONSTRUCTION SITE ACCESS AND HAUL ROADS: ACCESS TO THE JOB SITE
SHALL BE VIA SPECIFIC ROUTE SHOWN ON THE ATTACHED PLAN AND VERIFIED
AT THE PRE-CONSTRUCTION MEETING, ACCESS AND HAUL ROUTES MAY CHANGE
DURING CONSTRUCTION AS DIRECTED BY THE RE, THE SUBCONTRACTOR SHALL LOCK
GATE AFTER EACH INGRESS/EGRESS. THE SUBCONTRACTOR SHALL REPAIR ANY DAMAGE
TO HAUL ROADS, RESULTING FROM EXECUTING THIS CONTRACT, AT NO ADDITIONAL
COST TO THE GOVERNMENT. ALL SUBCONTRACTOR VEHICLES AND TRAFFIC SHALL
REMAIN WITHIN THE LIMITS OF CONSTRUCTION AREA, STAGING AREA, OR
HAUL ROUTES. STAGING AREA WILL BE PLACED CLEAR OF RSA AND TSA, AS WELL
AS ANY CRITICAL OPERATIONAL AREAS FOR FUNCTIONING FAA FACILITIES,
5, STAGING AREA - THE SUBCONTRACTOR'S STAGING AREA WILL BE AS SHOWN ON THE
PLAN AND VERIFIED DURING THE PRE-OFFER MEETING. THE SUBCONTRACTOR SHALL
MAKE PROVISIONS FOR ANY REQUIRED UTILITIES. UPON COMPLETION OF THE
PROJECT, THE SUBCONTRACTOR SHALL RESTORE THE STAGING AREA; INCLUDING THE
REPAIR OF EXISTING FACILITIES, REMOVAL OF UTILITIES, REGRADING, THE TOP
SOILING, AND THE PLANTING OF SOD COMPLETE TO THE SATISFACTION OF THE RE
AND AIRPORT DIRECTOR.
6. CONSTRUCTION LIMITS - ALL SUBCONTRACTOR VEHICLES AND CONSTRUCTION TRAFFIC
ARE REQUIRED BY FAA RULES TO STAY WITHIN THE LIMITS OF CONSTRUCTION WHILE
ON THE CONSTRUCTION SITE, THESE LIMITS ARE STRICTLY ENFORCED. LIMITS
SHALL BE DEFINED AT THE PRE-CONSTRUCTION MEETING AND MAY CHANGE DURING
CONSTRUCTION AS DIRECTED BY THE RE. TRAFFIC ASSOCIATED WITH CONSTRUCTION
IS TO USE ONLY AREAS SHOWN FOR CONSTRUCTION USE. FAILURE TO DO SO COULD
RESULT IN OFFENDERS BEING REMOVED FROM THE CONSTRUCTION SITE, A FINE OF
$1 MILLION CAN BE ADMINISTERED IN THE EVENT OF A RUNWAY INCURSION.
7, HAVE ON HAND EMERGENCY CONTACT INFORMATION FOR THE COTR, RE, SSC, ATCT,
AND AIRPORT OPERATIONS IN THE EVENT OF A CONSTRUCTION ACTIVITY THAT
ADVERSELY IMPACTS THE OPERATIONAL SAFETY OF THE AIRPORT.
SURVEY CONTROL NOTE
1. PROTECT ALL EXISTING MONUMENTS UNLESS NOTED OTHERWISE ON THE DRAWINGS,
ANY MONUMENTS THAT ARE DAMAGED OR DISTURBED SHALL BE RESET BY A
PROFESSIONAL SURVEYOR LICENSED IN THE STATE AT NO ADDITIONAL COST TO
THE GOVERNMENT.
7 6
5 • 4
SEQUENCE AND COORDINATION OF CONSTRUCTION
1. WITHIN 10 DAYS OF NOTICE OF AWARD THE SUBCONTRACTOR SHALL PREPARE A
SEQUENCE OF CONSTRUCTION FOR REVIEW AND APPROVAL BY THE FAA, AIRPORT,
AND PARSONS, THAT IS COORDINATED WITH ALL OTHER PROJECTS IN THE WORK
AREA SUCH THAT THERE ARE NO KNOWN INTERFERENCES.
2. ANY SCHEDULE/SEQUENCE INTERFERENCE SHALL BE IMMEDIATELY BROUGHT TO
THE ATTENTION OF THE RE IN WRITING.
3, THE SCOPE OF WORK INCLUDES:
REPLACE EXISTING HVAC UNITS FOR THE EQUIPMENT ROOM WITH LIKE
TONNAGE AND ELECTRIC HEATING OPTIONS. REPLACE EXISTING EXTERIOR
DUCTING CONFIGURATION WITH NEW RECTANGULAR DUCT WITH INTERNAL
INSULATION, ADD NEW MOTORIZED DAMPERS. REPLACE EXISTING HVAC
CONTROL SYSTEM WITH NE CONTROL PANEL THAT WILL AUTOMATICALLY
ALTERNATE PRIMARY/STANDBY UNIT BASED ON A PREDETERMINED SCHEDULE.
INSTALL TEMPORARY COOLING UNITS TO MAINTAIN REDUNDANCY DURING
CONSTRUCTION PERIOD. REMOVE 3
X6
OPENING USED AS THE ECONOMIZER.
REPLACE BREAKERS 8 AND 9 WITH NEW BREAKERS AND WIRING TO THE NEW
HVAC UNITS. INSTALL NEW LIGHTNING PROTECTION SYSTEM AFTER THE NEW
ROOF HAS BEEN INSTALLED,
GRADING NOTE
1. HAUL ALL EXCESS MATERIAL OFF SITE AND DISPOSE OF PROPERLY,
3 2 1
H
G
F
E
5 4
EMERGENCY CONTACT INFO
FIRE AND RESCUE: 911
PARSDNS������-i.=-=---"='------""'-"'="---""==--�=-=""""---1---l--------aC---- - - --- --- -- - -
PTSI Managed Services Inc. &�� 3800 Camp Creek Pkwy , �� , Jc, REDLINE
'APVlJ i DATE
Building* 2400, Suite 106 & j
:1»wM-tr��
1- -
I--R -EV+- A- P-6�-��-,[D--+-- - - - -D-ES-CR-PT-IO_N
Atlanta, GA 30331 11(1 "' �--..\, 1) 1) l---'--..,...:.....;;___,, ______________ ..1.-_-..J_..;;;..;;;;...__...--1 �,&\L - @1///W DEPARTMENT OF TRANSPORTATION 404·766·1693 \��v � FEDERAL AVIATION ADMINISTRATION 404.559.1715 (Fax) �� '--,,-, AREA � _ -- ATO - TECHNICAL OPERATIONS EASTERN SERVICE
1---'---:;__:;c.;;.;;.:_;:__;_::__:_=__.:_:=-===-=-=-=-----==.::.:=:_:___=:::__:_:=�==-i
ARSR RELEASED FOR:
CONSTRUCTION - 08/01/2017
ARSR-4 QVR OCEANA HVAC REPLACEMENT
GENERAL NOTES
OCEANA
REVIEWED BY oUBMlr-ED 82,/1;
PPR
OV ,
----� !�t..-fett-,,v_, V ..____ '' /).; ...__,,__,,., Bryan Pennamon t:JI """u
- --.J
1-------+--IPROJECT ENGINE�f< MGR: ENGINEERING - CENTER A
VA
DESIGNED ISSUED BY DATE 1Jrn
DR A WN CAK ENGINEERING SERVICES >-D-R.A- W N-G���0
8�10 �11�2=0�17
�--�14�0-"-'03=,�=�
CHECKEC
HLG NAVAJOS
QVR-1400368-G004
2 1
D
C
B z
0::
(I) z ii uJ (I)
!!l
F
E
D
C
B
A
LL
8 7 6
43'-4" V.I.F.
5 ... 4 I 3
' 7'-8" ' 17'-0" ' 7'-8" ' 6'-8" I I _Ji.. I I-
( 3 ',,.
�o, �
0' 0
11, __ -
D I'-.. ' • / ' �/ ______ _,/ r ---------_ _j ____ ---------- ------- - ----------------- -- -------------- -- --------
! ,---------------------------------------------------------1 �----------------- -------- - --- 1 I
I I I I I I I I I I I I
I I I I l ! j !
I I I I I I I ! ! !
I I I I I I I ! l !
I I I I I I I I ! !
II
I I I I ! I ! !
II
I I I I i r i i II I
I I I i i i i I I I I I I
- 'k-------'"'------------------------------lf-------------_____g- I l I I I :, 'I I I I I I I I I I : ---- -- ----- -·--- ----·------ -- �------------------------______________ _! 1-------,----,-------1 ! : :
, i TECH ROOM i i RADIO ROOM i !
1 I I I ! I I !
J !
I I I I
I : l ! II I I I I
I I I I I I I I : j ! II I I I I
I I I I I I I
I I I t
I I I I I I I I I I I
: STORAGE ROOM I
: w f--'. : I I, I ,' 1 1 o...w.. 'I I I I I
I I I Q I 1 il
1 :l ...JO::: ![
I I I I I I I (/) W I I I I I I I 0... I I i I I ! l I 1 ! I
' : : : . EQUIPMEf�T F;OO_M
: 1 1 : t; =co : I I , '' wt- ' , x- ' I I ' , ' o...w.. , ', 10 : ' w_;: , : , : s et'. : , ., , 1 I
� � ffi6 :, l _______ l _______________________________ j [ ___________________________________! 1
1 I I I (I) - I I ' I _ Cl) I I I I 'I x--.... I I ,1
I 1 1 wn 1 1 I
I : : 7 8 : : : I I I ffi I I I
I I I I I 1 , I I I I I
I I I I I ( 1 ', I II I I I SIMILAR I
I : [___________________________________________ : : 00 , 1
I : f
-----1 i-------�: : l l I
I I I I I I I I I I UPS ROOM : I ! I I i !
I I I ! ! I I I I I : I I I
I I I ! : ! . ! I I I I I : I : : : : : I :
t : :
!i I • I TELCO ROOM :RESTROOM: I ....___ I I : I I : i i
2 ! : / 1
?J}
\ SIMILAR i ! i I
I
I I I I I I QQ I I I
! I t J
I l !
I I I I I I I I I I I I l L : L : J L _ ______ ___________________________________ J L _____________________________________________________________________________ J I L_ ------- -------------------- - ------------------- - J
LL-
tj-
2 1
SHEET NOTES
1 . PLAN WORK FOR CLEAR SKY AND NO RAIN FORECAST; PREPARE
FOR THE WORST AND HAVE A PLAN IN PLACE TO DEAL WITH
UNEXPECTED INCLEMENT WEATHER,
2. REVIEW MECHANICAL & ELECTRICAL DRAWINGS FOR EXTENT OF
WORK PERTAINING TO EACH TRADE.
3. PHASE WORK TO ALLOW USER/OCCUPANTS USE OF BUILDING EXITS.
4. COORDINATE WORK WITH OTHERS UNDER SEPARATE CONTRACT WITH
THE GOVERNMENT, WHICH OCCUR IN THE SAME TIME SCHEDULE AS
THE RENOVATION AND REROOFING.
KEYED NOTES
G G
0)
G
G
G
G
G
REMOVE VTR COUNTER-FLASHING,
REMOVE GUTTER SYSTEM, INCLUDING ROOF LEADERS AND WALL
TIES.
REMOVE EXISTING ROOFING COUNTER-FLASING AND ROOFING
MEMBRANE ONCE ALL ELECTRICAL WIRING, ANCHORS AND
PENETRATION HAVE BEEN REMOVED.
REMOVE ROOFING INSULATION SYSTEM AND COVER BOARDS AS
APPLICABLE DOWN TO ROOF DECK.
PATCH AND REPAIR ROOF DECKING WITH SIMILAR METAL
DECKING SYSTEM; COVER ABANDONED PENETRATION WITH
18-GA. GALVANIZED STEEL SHEET AS REQUIRED PRIOR TO NEW
ROOFING INSULATION.
PROVIDE FULLY ADHERED 45-MIL KEE ROOFING MEMBRANE
SYSTEM WITH 1/2" DENS-DECK PRIME OVER METAL DECK,
2-LAYERS 3" RIGID POLYISOCYANURATE WITH STAGGERED
JOINTS AND 1/2" DENS-DECK PRIME COVER BOARD; PROVIDE
ADDITIONAL CONTINUOUS PT 2X6 WOOD BLOCKING AT
PERIMETER, REFER TO ROOFING DETAILS ON A002.
PROVIDE 6" X 6" MEMBRANE STRIPS, HEAT WELDED TO FIELD
MEMBRANE AT LIGHTNING ROD BASE. SET BASES ON STRIPS
IN DOW 799 SILICONE SEALANT, TYPICAL,
H
G
F
E
D / � - - �---------( I, - ------------------------ �- -- - --- --�" ----- -
WHERE ADDITIONAL MEMBRANE STRIPS ARE REQUIRED TO SECURE
BONDING OR GROUNDING WIRE TO ROOFING, PROVIDE 2" X 8"
MEMBRANE STRIPS, HEAT WELDED TO FIELD MEMBRANE 4" ON
EITHER SIDE OF WIRE.
I/ /
� ---9_ '_-;;._·'_' ---,J� ___ 6 _'-_8 _" _ ____,,-_ __ _ _ _____ 2_4 _'-_0_" _______________ 10_'_-2_'_' ____ i ___ 7_'-_2_" _______ 1_0_'- _2_" ___ -->-1-' __________ 2_1'_-8_'_' ---------to-j
G
DENOTES BUILDING OUTLINE BELOW ROOF.
DENOTES PLAN LAYOUT OF ROOMS BELOW.
REFER TO GUTTER DETAIL 3/A002. PROVIDE ROOF LEADERS
IN QUANTITY AND SIZE TO MATCH EXISTING, IN ADDITION TO
CONCRETE SPLASH BLOCKS, UNLESS CONNECTING TO BUILDING
PERIMETER STORM DRAIN PIPING,
r I 1--------1 ! I l I I I I I
89'-0" V.1.F.
! I ! l
-o ----� -----------4-----
----o -,---------------0---------1 : 2 I
I I
I : __ " _____________________________________________ " I Ir ________________________ J I I I I I I I I I I �t ex) �[: I I S Ct'. S Ct'.
I I (/)W (/)W I I o.. o.. I �- f-_ I (/) - (/) ro I _CX)
I Q;;:; CJ� I
I I
I 8
I l_ _____________ "---------- _______________________ J
L _ ________ _
2 ROOF PLAN - REMOVAL WORK
A001 SCALE: 1/8" = 1'-0"
8 7 6
1 ROOF PLAN - NEW WORK
4'
8'
A001 SCALE: 1/4" = 1'-0"
0 4' 8'
SCALE: 1/4" = 1'-0"
0 8' 16' i..-------SCALE: 1/8" = 1'-0"
5 •
J
I -N-, KEY PLAN
NOT TO SCALE
@ PROVIDE ROOFING MEMBRANE MANUFACTURER PREFABRICATED
VENT THROUGH ROOF (VTRl PIPE FLASHING, HEAT WELDED TO
ROOFING MEMBRANE.
PAR SD NS----���----�·
PTSI Managed Services Inc.
� c,�
C
3800 Camp Creek Pkwy £:'�m, -, Building" 2400, Suite 106 r_i�V,�i?M
REV AP���ED DESCRIPTION JCN Rii�l�E APVD 6 Atlanta, GA 30331 1
[11( [�'�'--- I )f t---'-----"-----------------'----..1.--------f
11, � DEPARTMENT OF TRANSPORTATION 404·766·1693
'5\ -- " (fl� FEDERAL AVIATION ADMINISTRATION z
404.559.1715 (Fox) '\� -� , �
, , ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA �
>--�� �� �������--I ARSR �z RELEASED FOR:
CONSTRUCTION - 08/01/2017
OCEANA
I-R_E_V1E_w�ED _a_Y--I
S UBlflT
ED
��t-•---';iv •. r>�;7r"----+-�pp;P'///� -r;@
Bryan Pennamon M6nifi DI w(JJ,I
PROJECT ENGINEER MGR: ENGINEERING - CENTER A
ISSUED BY DATE IJCN
� -- -==; ENGINEERING SERVICES DRAY/ING
J!10112017
DESIGNED
JAE
DRAVIN
NAVAIDS JPE
CHECKED QVR-1400368-A001
2 1
VA
1400368
REV
ARSR-4 QVR OCEANA � REROOFING PLANS -
REMOVAL AND NEW WORK
w �0
F
E
D
C
B
A
PROVIDE PT 5/8"
PL YWOOO, SCREW
ATTACHED TO
CONTINUOUS PT
2X6 BLOCKING
FLUSH WITH
INSULATION
PROVIDE FIBER CLAD-'
MET AL FASCIA
FLASHING
PROVIDE 3/8" TOGGLE
BOLTS, THROUGH METAL
DECKING @ 36" O.C.
COUNTERSINK INTO PT
BLOCKING WITH 1" HD
GLAV. WASHER, TYPICAL
EXISTING METAL
FASCIA TO REMAIN
EXISTING MET AL SOFFIT
CLOSURE SYSTEM TO
REMAIN
PROVIDE 112"
RADIUSED,
TYPICAL OUTER
EDGE
EXISTING MASONRY EXTERIOR _ _.WALL
ROOFING & FASCIA
SCALE: 11/2" = 1'-0"
PROVIDE FIBERTITE 50-MIL THERMAL
TAN KEE ROOFING MEMBRANE SYSTEM,
FULLY ADHERED TO 1/ 2" DENS-DECK
COVER BOARD, ADHERED TO RIGID
INSULATION
PROVIDE 2-LAYERS OF 3"
POL YISOCY ANURATE RIGID
INSULATION, FULLY ADHERED
SYSTEM WITH STAGGERED
JOINTS
_J �<( wW
PROVIDE 1/2" DENS-DECK
PRIME OVERLAYMENT
BOARD,FULLY ADHERED
TO TOP OF EXISTING
FLUTED STEEL DECK
ROOF STRUCTURE
EXISTING PT 2X6 WD
BLOCKING TO REMAIN
��LIGHTNING ROD BASE, SET IN
DOvl 799 SILICONE
2" X 6" MEMBRANE STRIP, HEAT __ __,,
WELDED TO FIELD MEMBRANE 4"
ON EITHER SIDE OF BASE. INSTALL
ADDITIONAL MEMBRANE STRIPS AT
48" O.C. TO NEXT TERMINAL.
ANTENNA BASE
SCALE: 1/ 4" = 1'-0"
8 7 6
PROVIDE PT 5/8" _PLYWOOD,
SCREW ATTACHED TO
CONTINUOUS PT BLOCKING @
8" O.C. ALTERNATING SIDE
PROVIDE FIBERCLAD -.__
MET AL FASCIA
FLASHING
1'
PROVIDE FIBERTITE 50-MIL THERMAL-TAN KEE
ROOFING MEMBRANE SYSTEM, FULLY ADHERED
TO 1/2" DENS-DECK COVER BOARD, ADHERED
TO RIGID INSULATION
6" !AIN.
4"
PROVIDE
MEMBRANE
FLASHING STRIP
WITH HOT AIR
WELD
PROVIDE PT ----t---t-4U:.BLOCKING WITH
TOGGLE BOLTS @
3'-0" O.C. THRU
MET AL DECKING
PROVIDE S.S. OR
HOG TOGGLE BOLTS
@ 3'-0" O.C. THRU
BLOCKING DOWN
THRU METAL
DECKING
PROVIDE CONTINUOUS --1
GALVANIZED MET AL
CLEAT FASTENED
WITH GALVANIZED
ANNULAR RING SHANK
NAILS @ 3" O.C.
PROVIDE
CONTINUOUS
I I I I! I l !
------ l _ _r __ t-_' I I I I
I
! I I I I I I I I . I I , I I I I I I : I I I I I I
I I I I I I
I I I I I I I I I I I I
I I I I I I I I
I I I I I I I I I I I I I I I I I I I I I I I I
BUTYL SEALANT-------++--'
TAPE
I I I -- I l ---
--- I
- ., 1----
EXISTING PT 2X6
BLOCKING WITH TOGGLE
SOL TS @ 3'-0" O.C. EXISTING MET AL
FASCIA TO REMAIN
1 I II II __ J
EDGE FLASHING DETAIL
SCALE: 6" = 1'-0"
4' 0 4'
SCALE: 1/4" = 1'-0"
1' 9" 6" 3" 0
SCALE: 1 1/2" • 1' -0"
3" 0 3" 6" i------
SCALE: 3" • 1'-0"
2" 0 2"
SCALE: 6" = 1'-0"
8'
1'
9"
4"
I .
I ' I !
I i
I I I I I I I t
I t
PROVIDE FIBERCLAD ----.
MET AL FASCIA FLASHING
PROVIDE CONTINUOUS BUTYL
SEALANT TAPE
OVERLAP ROOFING MEMBRANE
@ ROOF EDGE BY 10"MIN. TRIM
EXCESS BELOW GUTTER
SYSTEM
PROVIDE CONTINUOUS
ALUMINUM GUTTER AND
ROOF LEADER
<DOWNSPOUT) SYSTEM,
TYPICAL
I I I ---- t-1-rJ
I I I
I II
I I - -�-..1 l ,r
PROVIDE MEMBRANE
FLASHING STRIP, HOT AIR
WELD, TYPICAL
I I I I I I • I I I I I I I I I I I ' I I I I I
I I I I I I ' I I I I I I I I I I I I I I I I I I I
EXISTING PT 2X6
BLOCKING TO REMAIN
PROVIDE CONTINUOUS
BUTYL SEAL��T TAPE
EXISTING MET AL FASCIA
& SOFFIT SYSTEM TO
REMAIN
I I I I I I r . T
I I I I . I I I I
_.c>
GUTTER SECTION DETAIL
SCALE: 3" • 1'-0"
A:;,PROVED
DATE DESCRIPT·Q:,J JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
RECLINE
DATE APVD
L�����-=�- -����:__jATO - TECHNICAL OPERATIONS EASTERN SERVICE
ARSR
(Fax)
AREA
RELEASED FOR:
CONSTRUCTION - 08/01/2017
ARSR-4 OVR OCEANA ROOFING DETAILS
OCEANA VA
1- R
E v, :w
ED
OY
-j
SUBMITTED
��,,-¥-2/Tr'...--I
Bryan Pennamon
PROJECT ENGINEER MGR: ENGINEERING - CENTER A
DESIGNED ISSLED BY DATE 08/01/2017 JCN 1400368
1-- -+- --+-DR_A _w,-, - - --'"JAEeo:.; ENGINEERING SERVICES f--D-RA-w-,N-G -'N"'c "--"-'-'-=-"-'-'_,_ ___ -2-""'-;"-'RE'-"-lv
NAVAIDS JAE
QVR-1400368-A002 CHECKED
2 1
H
G
F t--
D
C
B z u z u
F
E
D
C
B
AC 'C
�o n ..
. ro "' ... 0 ..
w-
"'"o_ Oo 0 N -, 0:: ;;;
OCs
STRAP TYPE PIPE CLAMP
CROSS RUN CONNECTOR
BlMETAL
CONNECTOR
BRONZE
1 BOLT PARALLEL CLAMP
T[NNED BRONZE
BONDlNG PLATE u
TINNED BRONZE
U-BOLT TYPE PIPE CLAMP
BRONZE
CABLE TO FLAT METAL CLAMP
BRONZE
SECONDARY BONDING LUG
1/2
X 60"
SOLID COPPER AIR TERMINAL
GALVANIZED
STEEL TRIPOD BRACE 48• HIGH-
COPPER
UNIVERSAL BASE
COPPER
ADHESIVE CABLE e
FASTENER EVERY 3' ""e�,dg,/MAX. ------_
NO. 32R, CLASS II COPPER
LIGHTNING CONDUCTOR
(32 STRANDS OF 16 AWG WIRES)----'
1 TYPICAL BONDING/SPLICING DETAILS 2 AIR TERMINAL DETAIL
005 NOT TO SCALE
TO LIGHTNING DOWN
CONDUCTOR ON ROOF
32R CLASS II COPPER
LJGHTNlNG CONDUCTOR
1 11 SCH 80 Pvc-��11
12•x12•x6"
JUNCTION BOX-�
EXOTHERMIC
WELD BUTT SPLICE
111 SCH 80 PVC ----1..i1 z
<.O I z
I -
BUTT SPLICE DOWN
CONDUCTOR TO 4/0
BSC IN JUNCTION
BOX .
FINISHED GRADE
oz I -
- 2
GROUND ROD ON
EXISTING EES-�
4/0 BARE � STRANDED COPPER
4 DOWN CONDUCTOR DET�L
005 NOT TO SCALE
8 7 6
005 NOT TO SCALE
1 /2
X 2 4
BULLET TIPPED SOLID
COPPER AIR TERMINAL- --
BRONZE
UNIVERSAL BASE MOUNTED
WITH STAINLESS STEEL
FASTENERS
CLASS II COPPER
LIGHTNING CONDUCTOR (32
STRANDS OF 16 AWG WIRES
COPPER CABLE CLIP
\ WITH STAINLESS STEEL
FASTENER - EVERY 3 1 MAX
A'�ff!�
3 2 1
NOTES
1. ALL BENDS IN ROOF AND DOWN CONDUCTORS SHALL HAVE A MINIMUM 8
11 RADIUS.
2. MOUNT BASE PLATES TO BU[LDING ROOF WITH COPPER ADHESIVE AS RECOMMENDED
BY THE ROOFING MANUFACTURER. DO NOT PENETRATE ROOFING W[TH MECHANICAL
FASTENERS. TYPICAL FOR ALL BASE PLATES.
3 AIR TERMINAL DETAIL
005 NOT TO SCALE
RELEASED FOR:
CONSTRUCTION - 08/01/2017
APPROVED
DATE DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL A VIA TI ON ADMINISTRATION
REDLINE
DATE
- TECHNICAL OPERATIONS EASTERN SERVICE
ARSR
ARSR-4 OVR OCEANA ELECTRICAL AIR
TERMINAL DETAILS
OCEANA
REVIEWED BY SUBMITTED B;n _-ff -;,.{ft;;, '--'I� "-----1--
- - _ __ Bryan Pennamon
PROJECT ENGINEER MGR; ENGINEERING - CENTER A
APVD
AREA
VA
DES,GNED
CAK
ISSUED BY
DATE
OS/01/20l?
JCN
ENGINEERING SERVICES DRAWING NO
1400368
DRAWN
CHECKED
4 3 2
RCL NAVAJOS QVR-1400368-EOOS
,EV
H
G
F
E
D
C
B z z
| qvr-1400368-g001 |
| qvr-1400368-g002 |
| qvr-1400368-g003 |
| qvr-1400368-g004 |
| qvr-1400368-g005 |
| qvr-1400368-d001 |
| qvr-1400368-a001 |
| qvr-1400368-a002 |
| qvr-1400368-m001 |
| qvr-1400368-m002 |
| qvr-1400368-m003 |
| qvr-1400368-m004 |
| qvr-1400368-e001 |
| qvr-1400368-e002 |
| qvr-1400368-e003 |
| qvr-1400368-e004 |
| qvr-1400368-e005 |