The provided document contains the technical specifications for a 6-Volt battery system required to power microwave systems under a federal contract opportunity. The key details are:
The battery system must consist of three 2-Volt lead acid/glass mat battery cells configured into a single 6-Volt assembly, with a minimum capacity of 860 amp hours for 8 hours at 1.75 Volts. The 6-Volt modules must have front facing terminals and be configurable up to a 48-Volt system. All higher-voltage configurations must meet or exceed Uniform Building Code 97 Seismic Zone 4 specifications and include a mounting base, interconnecting cables, and other necessary hardware. 48-Volt configurations must be less than 30-inches in width and 70-inches in height, including the mounting base.
The related federal contract opportunity is a solicitation (Solicitation Number 7604) from the Department of Agriculture Forest Service for (48) Six Volt Battery Modules configured into Six (6) 48-Volt systems, with associated hardware, to power microwave systems. Interested vendors are directed to review the RFQ, BOM, and technical specifications for full order details.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| ART Contract Language Template.pdf | ||
| Configuration Drawiing.JPG | JPG image | |
| BOM_12760424Q0130.xlsx | XLSX spreadsheet | |
| RFQ_12760424Q0130_1.pdf | ||
| USDA Security Language.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USFS Land Mobile Radio
Minimum Technical Specifications
6-Volt Battery System
· Three 2-Volt cells modularized into a single 6-Volt assembly. Lead acid/glass mat battery cells, capable of a minimum capacity of 860 amp hours for 8 hours at 1.75 Volts
· 6-Volt modules shall have front facing terminals
· 6-Volt modules must be configurable up to a 48 Volt system
· All higher-voltage configurations of 6-V modules must be affixed so as to meet or exceeding Uniform Building Code 97 Seismic Zone 4 specifications
· All higher voltage configurations of 6-V modules must include a mounting base, interconnecting cables and any other hardware necessary for specified system functionality
· 48-Volt configurations must be less than 30-inches in width and less than 70-inches in height, including mounting base and excluding any optional accessories