589-18-910_CD Drawings-Revised_Electrical_BPA (002).docx
DOCX document 2 MB Posted
- Solicitation number
- 36C25520Q0746
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3
4 5 6 7
8 9 10 three inches = one foot 6"
10/5/2018 1:08:48 PM
)A RENOVATE 9 EAST FOR A
B
)SPECIALTY CLINIC
one and one half inches = one foot
)KANSAS CITY VA MEDICAL CENTER
589-18-910 IPT MEMBERS
NAME
Title Siganature Date Ahmad
Batrash Chief of
Staff Abdul
Ahad
Haleem Service chief Angel
Petznick Nurse Manager 9 West Ryan
Locasio Planner Gregory
Massey Facilities Management
Chief Brett
Twaddle Energy
Engineer Jeff
Hernbloom Supervisor
Projects Robert
Cheatham O&M
Supervisor Jamie
Miller Construction Crew
Supervisor Bryan
Bieri Fiscal Larry
Clayton
EMS
Constance
Webb Logistics Christy
Mears Pharmacy Gene
Parker
VA
Police Ed
Johnson
O&IT
Andrea
Grimwood Tele COM David
Sterrett Contracting Officer Dennis
Powers
COR
Christine
Zang/Shelia
Shipley Infection
Control Deborah
West Patient
Safety Matthew
Stewart Safety Rickey
Vest 910 Union Terry
Curry Women's Program
Rep Kelly
Flanders Interior
Design 6"
)VA #589-18-910
)CONSTRUCTION DOCUMENTS B
9/27/2018 one inch = one foot
)VICINITY MAP
LOCATION MAP
MAIN TOWER - 9TH FLOOR EAST 4801 LINWOOD BLVD.
KANSAS CITY, MO
DEDUCT ALTERNATES
ALTERNATE 1 - Omit (6) patient lifts and supports in rooms M9-309, M9-341, M9-343, M9-345, M9-349, and M9-351 and associated elec.
6"
)VERIFY STAGING LOCATION WITH PROJECT ENGINEER.
C
ALTERNATE 2 -
ALTERNATE 3 -
ALTERNATE 4 -
Omit (4) stair tower new doors, frames and card readers; Door #'s S2, S16, S22, and S23. Existing Hollow Metal door and hardware to remain Omit (4) patient lifts & supports in rooms M9-312, M9-314, M9-316, and M9-318 and associated elec. Omit Terrazzo floor and base from Lobby. Omit sawcuting of topping to recess the Terrazzo. Include new LVT-1 and RB-1 base. C three quarters inch = one foot 6" 0
)PROJECT VICINITY
NORTH
PROJECT LOCATION FLOOR 9 EAST
)D
SYMBOLS USED AS ABBREVIATIONS:
& AND
| C | CHANNEL/CELSIUS |
| CAB | CABINET |
| CB | CERAMIC BASE |
| (E) | EXISTING |
| E | EAST |
| EA | EACH |
COMMON ABBREVIATIONS
| HB | HOSE BIB | |
| HC | HANDICAP / HOLLOW CORE HD | HEAVY DUTY |
| (N) | NEW |
| N | NORTH |
| NA | NOT APPLICABLE |
| S | SOUTH |
| SB | SPLASH BLOCK |
| SC | SOLID CORE |
| UG | UNDERGROUND |
| UH | UNIT HEATER UNFIN UNFINISHED |
BATT INSULATION
SYMBOLS LEGEND
GENERAL
GI001 COVER SHEET
SHEET LIST
D
| L | ANGLE |
| LL | DOUBLE ANGLE |
| @ | AT |
one half inch = one foot
| )d | PENNEY |
| # | POUND OR NUMBER |
| Ø | ROUND OR DIAMETER |
ABBREVIATIONS:
| A/E | ARCHITECT/ENGINEER AB | ANCHOR BOLT/ROD |
| ABV | ABOVE | |
| AC | ASPHALTIC CONCRETE/AIR CONDITIONER |
ACC ACCESSIBLE
ACM ALUMINUM COMPOSITE MATERIAL ACOUS ACOUSTICAL
| CC | CONTRACTOR FURNISHED/CONTRACTOR INSTALLED |
| CD | CONSTRUCTION DOCUMENTS CEM CEMENT |
| CF | CUBIC FEET OR FOOT |
| CG | CORNER GUARD |
CIPC CAST-IN-PLACE CONCRETE
| CJ | CONTROL/CONSTRUCTION JOINT CL | CENTER LINE |
| CLG | CEILING CLKG CAULKING | |
| CLR | CLEAR, CLEARANCE | |
| CMU CONCRETE MASONRY UNIT CO | CHANGE ORDER/CLEAN OUT COL | COLUMN |
COMB COMBINATION
COMP COMPOSITE/COMPOSITION CONC CONCRETE
CONN CONNECT (ION)
| EF | EACH FACE | |
| EJ | EXPANSION JOINT | |
| EL | ELEVATION ELEC ELECTRICAL ELEV ELEVATOR ENL | ENLARGED EMER EMERGENCY ENGR ENGINEER |
EOP EDGE OF PAVEMENT
EPDM ETHYLENE PROPYLENE DIENE MONOMER
| EPS | EXPANDED POLYSTYRENE BOARD EPT | EPOXY PAINT |
| EQ | EQUAL EQUIP EQUIPMENT ES | EACH SIDE |
| EST | ESTIMATE | |
| ETC | ETCETERA | |
| ETR | EXISTING TO REMAIN |
HDBD HARDBOARD HDR HEADER HDWD HARDWOOD HDWR HARDWARE
| HM | HOLLOW METAL HORIZ HORIZONTAL |
| HPDL HIGH PRESSURE DEOCATIVE LAMINATE HR | HOUR |
| HT | HEIGHT |
HVAC HEATING, VENTILATION, AIR- CONDITIONING
| IBC | INTERNATIONAL BUILDING CODE ICC | INTERNATIONAL CODE COUNCIL ID | INSIDE DIAMETER/DIMENSION IFC | INTERNATIONAL FIRE CODE |
| IN | INCH(ES) |
INCL INCLUDE (D), INCLUDING INFO INFORMATION
| NIC | NOT IN CONTRACT |
| NO | NUMBER |
NOM NOMINAL
| NTS | NOT TO SCALE |
| ----------------------------------------------------- OC | ON CENTER |
| OD | OUTSIDE DIAMETER |
| OH | OVERHEAD |
OPP OPPOSITE
OPG OPENING
ORIG ORIGINAL
| ORD OVERFLOW ROOF DRAIN OZ | OUNCE | |
| ----------------------------------------------------- PAR | PARALLEL | |
| PCF | POUNDS PER CUBIC FOOT PED | PEDESTAL |
PERF PERFORATED PERP PERPENDICULAR
SCHED SCHEDULE
| SCR SHOWER CURTAIN ROD SCT | SECTION | |
| SD | SOAP DISPENSER | |
| SF | SQUARE FOOT | |
| SHT | SHEET SHTHG SHEATHING SIM | SIMILAR |
SLDG SLIDING
SLNT SEALANT
| SND SANITARY NAPKIN DISPENSER SNX | SANITARY NAPKIN DISPOSAL SOG SLAB ON GRADE |
| SPEC SPECIFICATION (S) SQ | SQUARE |
| SSM SOLID SURFACE MATERIAL SST | STAINLESS STEEL |
| ST | STREET |
| STC | SOUND TRANSMISSION CLASS |
UNO UNLESS NOTED OTHERWISE UON UNLESS OTHERWISE NOTED UTIL UTILITY
| ----------------------------------------------------- V | SHEAR | |
| VAR | VARIES | |
| VB | VAPOR BARRIER | |
| VC | VA FURNISHED / CONTRACTOR INSTALLED VCT | VINYL COMPOSITION TILE |
VERT VERTICAL VEST VESTIBULE
| VIF | VERIFY IN FIELD |
| VR | VAPOR RETARDER |
| VV | VA FURNISHED / VA INSTALLED VWC VINYL WALL COVERING |
| ----------------------------------------------------- W | WEST/WIDTH |
| W/ | WITH |
| W/O | WITHOUT |
GYPSUM BOARD
EARTH
CONCRETE
RIGID INSULATION
EXISTING CONSTRUCTION TO BE REMOVED
NEW CONSTRUCTION
X X-XX
X X-XX
DETAIL INDICATOR
WALL SECTION INDICATOR
| GI002 | ACCESSIBILITY DIAGRAMS |
| GI101 | LIFE SAFETY PLAN & SUMMARY |
| GI102 | PHASING PLANS |
HAZARDOUS
HA101 ASBESTOS ABATEMENT PLAN - 9TH LEVEL EAST HA102 ASBESTOS ABATEMENT PLAN - 8TH LEVEL EAST
ARCHITECTURAL
| AD101 | DEMOLITION FLOOR PLAN - 9TH LEVEL EAST AD102 | DEMOLITION CEILING PLAN - 9TH LEVEL EAST AD103 | DEMOLITION CEILING PLAN - 8TH LEVEL EAST AE101 | FLOOR PLAN - 9TH LEVEL EAST |
| AE102 | REFLECTED CEILING PLAN - 9TH LEVEL EAST |
| ACT | ACOUSTICAL CEILING TILE |
| ADA | AMERICANS WITH DISABILITIES ACT ADD ADDENDUM |
ADH ADHESIVE
| ADJ | ADJUSTABLE, ADJACENT, ADJOINING AFF | ABOVE FINISH FLOOR |
| AFG | ABOVE FINISH GRADE | |
| AHJ | AUTHORITY HAVING JURISDICTION ALT | ALTERNATE |
ALUM ALUMINUM
three eighths inch = one foot 0
| )E | ANSI AMERICAN NATIONAL STANDARDS INSTITUTE |
| APC | ACOUSTICAL PANEL CEILING APPROX APPROXIMATE |
ARCH ARCHITECT (URAL)
| ASI | ARCHITECTURAL SUPPLEMENTAL INFORMATION | |
| ----------------------------------------------------- BD | BOARD | |
| BEV | BEVELED | |
| BFF | BELOW FINISH FLOOR BL | BRICK LEDGE |
| BLDG BUILDING BLKG BLOCK (ING) BM | BEAM | |
| BOT | BOTTOM | |
| BO | BOTTOM OF |
BOC BOTTOM OF CONCRETE BOF BOTTOM OF FOOTING BRG BEARING
CONST CONSTRUCTION
CONT CONTINUOUS, CONTINUE CONTR CONTRACT (OR)
COORD COORDINATE
| CORR CORRUGATED/CORRIDOR CPT | CARPET | |
| CPPT CARPET TILE CSMT CASEMENT CT | CERAMIC TILE | |
| CTB | CARPET TILE BASE CTR | CENTER |
| ----------------------------------------------------- D | DEPTH | |
| DBL | DOUBLE |
DEMO DEMOLITION, DEMOLISH DEPT DEPARTMENT
| DET | DETAIL |
| DF | DRINKING FOUNTAIN |
| DIA | DIAMETER |
DIAG DIAGONAL
| DIM | DIMENSION |
| DIV | DIVIDE, DIVISION |
DISP DISPENSER
| DN | DOWN |
| DR | DOOR |
| DS | DOWNSPOUT |
| DW | DISHWASHER DWG DRAWING (S) DWR DRAWER DWTR DUMBWAITER |
| EW | EACH WAY | |
| EX | EXISTING EXIST EXISTING | |
| EXC | EXCAVATE/EXCAVATION EXH | EXHAUST |
| EXP | EXPANSION/EXPOSED EXT | EXTERIOR |
EWC ELECTRIC WATER COOLER
| ----------------------------------------------------- FA | FIRE ALARM | |
| FAB | FABRICATE/FABRICATION FD | FLOOR DRAIN |
| FDC | FIRE DEPARTMENT CONNECTION FDTN FOUNDATION | |
| FE | FIRE EXTINGUISHER | |
| FEC | FIRE EXTINGUISHER CABINET FF | FINISHED FLOOR |
| FFE | FINISH FLOOR ELEVATION FIN | FINISH (ED) |
| FLOUR FLUORESCENT FLR | FLOOR (ING) | |
| FO | FACE OF | |
| FOC | FACE OF CONCRETE FOM FACE OF MASONRY FOS | FACE OF STUD |
| FOF | FACE OF FINISH | |
| FR | FIRE RESISTANT/FRAME | |
| FRP | FIBERGLASS REINFORCED PANEL FS | FLOOR SINK |
| FT | FOOT, FEET/FIRE TREATED |
INSP INSPECTION INSTR INSTRUCTION(S)
| INSUL INSULATE (D), INSULATION INT | INTERIOR | |
| ----------------------------------------------------- JAN | JANITOR | |
| JST | JOIST | |
| JT | JOINT | |
| ----------------------------------------------------- KCJ | KEYED CONSTRUCTION JOINT KO | KNOCK OUT |
| ----------------------------------------------------- L | LENGTH / ANGLE | |
| LAB | LABORATORY | |
| LAM | LAMINATE (ED) | |
| LAV | LAVATORY | |
| LB | POUND | |
| LF | LINEAR FEET | |
| LH | LEFT HAND | |
| LKR | LOCKER | |
| LOC | LOCATION LONG LONGITUDINAL LT | LIGHT |
| LVR | LOUVER | |
| LVT | LUXURY VINYL TILE |
----------------------------------------------------- MAS MASONRY
MATL MATERIAL MAX MAXIMUM
MC MEDICINE CABINET
PL PLATE
PLAM PLASTIC LAMINATE PLYWD PLYWOOD
| PNL | PANEL | ||||
| PR | PAIR/PROPOSAL REQUEST PRCST PRECAST CONCRETE PREFAB PREFABRICATE | ||||
| PSI | POUNDS PER SQUARE INCH PSF | POUNDS PER SQUARE FOOT PT | PAINT / PRESSURE TREATED PTD | PAPER TOWEL DISPENSER PTN | PARTITION |
| PTR | PAPER TOWEL RECEPTACLE PVC | POLYVINYL CHLORIDE | |||
| ----------------------------------------------------- QT | QUARRY TILE | ||||
| ----------------------------------------------------- R | RADIUS/RISER | ||||
| RB | RUBBER BASE |
RBR RUBBER
RCP REFLECTED CEILING PLAN RD ROOF DRAIN
REBAR REINFORCING BAR REC RECESSED
REF REFERENCE/REFRIGERATOR REINF REINFORCE (D), (ING), (MENT) REQ REQUIRE
REQD REQUIRED
RES RESILIENT FLOORING RET RETURN
| STD | STANDARD | ||
| STL | STEEL STOR STORAGE | ||
| STRUCT STRUCTURAL SUSP SUSPENDED SV | SHEET VINYL | ||
| SW | SHEARWALL SYM SYMMETRICAL | ||
| ----------------------------------------------------- T | TREAD | ||
| T&B | TOP AND BOTTOM T&G | TONGUE AND GROOVE TB | TOWEL BAR |
| TBD | TO BE DETERMINED TEMP TEMPORARY/TEMPERED TER | TERRAZZO | |
| TFE | TOP FOOTING ELEVATION THD | THREAD (ED) (S) | |
| THK | THICKNESS THRU THROUGH TKBD TACKBOARD TL | TILE | |
| TO | TOP OF | ||
| TOB | TOP OF BEAM | ||
| TOC | TOP OF CONCRETE/CURB TOD | TOP OF DECK | |
| TOF | TOP OF FOOTING (FOUNDATION) TOM TOP OF MASONRY | ||
| TOP | TOP OF PIER | ||
| TOJ | TOP OF JOIST |
| WA | WEDGE ANCHOR | |
| WB | WOOD BASE | |
| WC | WATER CLOSET WD | WOOD/WOODWORK WDW WINDOW |
| WF (W) WIDE FLANGE WG | WALL GUARD | |
| WH | WATER HEATER | |
| WI | WROUGHT IRON | |
| WL | WIND LOAD | |
| WP | WATERPROOF (ING) WR | WATER RESISTANT WSCT WAINSCOT |
| WT | WEIGHT/WINDOW TREATMENT WWF WELDED WIRE FABRIC |
ROOM XXX
WOOD ROUGH (CONTINUOUS)
WOOD ROUGH (SPACED)
PLYWOOD
BLOCK WALL/VENEER
DIMENSION LINE
BREAK LINE
ROOM TAG DOOR TAG
X
X-XX
X X-XX
DRAWING TITLE
ELEVATION INDICATOR, EXTERIOR
ELEVATION INDICATOR, INTERIOR,
ELEVATION INDICATOR
CENTER LINE
NORTH ARROW
| AE501 | PARTITION AND WINDOW DETAILS | |
| AE502 | DOOR DETAILS AND SCHEDULE AE503 | MISC DETAILS |
| AI101 | FINISH AND WALL PROTECTION PLAN - 9TH LEVEL EAST AI102 | EQUIPMENT PLAN - 9TH LEVEL EAST |
| AI201 | ENLARGED PLANS | |
| AI401 | INTERIOR ELEVATIONS | |
| AI402 | INTERIOR ELEVATIONS |
E
| )AI501 | MILLWORK DETAILS |
| AI601 | TAKE OFF FINISH SCHEDULES |
FIRE PROTECTION
FG101 FIRE SUPPRESSION GENERAL NOTES AND DETAILS FD101 FIRE SUPPRESSION DEMOLITION PLAN - 9TH LEVEL EAST FX101 FIRE SUPPRESSION PLAN - 9TH LEVEL EAST
MECHANICAL
| MG101 | MECHANICAL SYMBOLS LEGEND AND GENERAL NOTES MD101 | MECHANICAL DEMOLITION PLAN - 9TH LEVEL EAST MH101 | HVAC PLAN - 9TH LEVEL EAST |
| MP101 | MECHANICAL PIPING PLAN - 9TH LEVEL EAST M-501 | MECHANICAL DETAILS | |
| M-502 | MECHANICAL DETAILS |
BRK BRICK BSMT BASEMENT BTWN BETWEEN
)BUR BUILT-UP ROOFING
one quarter inch = one foot )F
| FTG FOOTING FURG FURRING FUT | FUTURE |
| FV | FIELD VERIFY |
| GA | GAGE, GAUGE | |
| GB | GRAB BAR | |
| GC | GENERAL CONTRACTOR GALV GALVANIZED | |
| GC | GENERAL CONTRACTOR GI | GALVANIZED IRON |
| GL | GLASS |
GLU LAMGLUE LAMINATED (BEAM) GWB GYPSUM WALL BOARD
MECH MECHANICAL MEMB MEMBRANE MEZZ MEZZANINE
| MFR MANUFACTURE (R) MIN | MINIMUM | |
| MISC MISCELLANEOUS MO | MASONRY OPENING MR | MIRROR |
| MTL | METAL |
| REV | REVISION (S), REVISED | ||
| RFI | REQUEST FOR INFORMATION RFP | REQUEST FOR PROPOSAL RH | RIGHT HAND |
| RL | RIDGE LINE | ||
| RM | ROOM | ||
| RO | ROUGH OPENING ROW RIGHT OF WAY RVS | REVERSE (SIDE) |
RWL RAIN WATER LEADER
| TOS | TOP OF SLAB/STEEL TOW TOP OF WALL | |
| TPD | TOILET PAPER DISPENSER TPO | THERMOPLASTIC POLYOLEFIN TPTN TOILET PARTITION |
| TRANS TRANSVERSE TS | TUBE STEEL | |
| TYP | TYPICAL |
W#
A10
WINDOW TAG
INTERIOR PARTITION TYPES
FURNITURE, FIXTURE, & EQUIPMENT INDICATOR
KEYNOTE TAG
REVISION TAG
XX XX=XX
A
DRAWING BLOCK TITLE, TYPICAL
1 COLUMN GRID
| M-503 | MECHANICAL DETAILS | |
| M-601 | MECHANICAL CONTORLS | |
| M-701 | MECHANICAL SCHEDULES | |
| M-702 | MECHANICAL SCHEDULES | |
| PD100 | PLUMBING UNDERFLOOR DEMO PLAN - 9TH LEVEL EAST PD101 | PLUMBING DEMOLITION PLAN - 9TH LEVEL EAST |
| PL100 | UNDERFLOOR PLUMBING PLAN - 9TH LEVEL EAST PL101 | PLUMBING PLAN - 9TH LEVEL EAST |
| P-301 | PLUMBING FIXTURES | |
| P-401 | PLUMBING LARGE-SCALE PLANS | |
| P-501 | PLUMBING DETAILS | |
| P-601 | PLUMBING DIAGRAMS | F |
)GYP GYPSUM
CORNER GUARD
CG
CJ
)CONTROL JOINT
FEC FIRE EXTINGUISHER CABINET
FE FIRE EXTINGUISHER
CR CARD READER
ELECTRICAL
| EG101 | ELECTRICAL SYMBOLS LEGEND AND GENERAL NOTES ED101 | ELECTRICAL DEMOLITION PLAN - 9TH LEVEL EAST EL101 | LIGHTING PLAN - 9TH LEVEL EAST |
| EP101 | POWER PLAN - 9TH LEVEL EAST | ||
| EY101 | SPECIAL SYSTEMS PLAN - 9TH LEVEL EAST E-501 | ELECTRICAL DETAILS |
Project Number
VA #589-18-910
Building Key Plan:
M/E/P/F CONSULTANT
ARCHITECT / ENGINEER
)E-601 ELECTRICAL DIAGRAMS AND DETAILS
117 PIERCE ST, SUITE 110 SIOUX CITY, IOWA 712.252.4014
P.O.C.: Jennifer Unrein 816.249.1500
142 N. MOSLEY
ST.
WICHITA,
KANSAS
316.262.2500
A/E Seal:
one eighth inch = one foot
C:\_SGA
Revit
Local\589-18-910.1.A18_Jason
Nelson.rvt Revision# Description Date:
)VA FORM 08 - 6231 1 2 3
9E 9W
4 5 6
12700 W. DODGE ROAD OMAHA, NEBRASKA 68154
402.330.5900
)U.S. Department of Veterans Affairs
Building Number Project Title
RENOVATE 9 EAST FOR SPECIALTY CLINIC
Phase
CONSTRUCTION DOCUMENTS
Drawing Title
COVER SHEET
FARRIS
ENGINEERING
OMAHA
LINCOLN
COLORADO
SPRINGS
SIDNEY
farris-usa.com )Approved: Medical Center Director
FULLY SPRINKLERED
Location
KANSAS CITY, MISSOURI
Drawing Number
GI001
Office of Construction and Facilities Management
| )Issue Date | Checked | Drawn |
| 9/27/2018 | DM | JN |
9 10
1 2 3
1.6 1.6A
1.7
1.8
1.8A 1.9
6 7 8
9 10
6"
9/26/2018 4:16:22 PM
)STAIRWELL NO. 22
S22
CONSTRUCTION
KEYNOTES
1 CONNECT TO SPARE 20 AMP, SINGLE POLE CIRCUIT BREAKER OR A 20 AMP, SINGLE POLE CIRCUIT BREAKER MADE SPARE BY DEMOLITION WORK IN EXISTING PANEL INDICATED. USE PANEL SECTION 1 OR 2 AS NECESSARY TO BALANCE THE CONNECTED LOAD AS APPLICABLE.
2 CONNECT TO SALVAGED EXISTING SWITCHED LIGHTING CIRCUIT.
3 LIGHTING CONTROL STATION FOR LUMINAIRE CONTROL IN SCHEME 'CR1A'.
LIMITS P
LIGHTING CONTROL STATION FOR LUMINAIRE CONTROL IN SCHEME 'CO2A'.
b
E
| )A | EXAM ROOM-B | |
| M9-318 | A1 | X |
EXAM ROOM-B
M9-317 b )A1
COORDINATE INSTALLATION OF BACKBOX(ES) IN PRE-MANUFACTURED WALL SYSTEM FOR A
LIGHTING CONTROL STATION WITH WALL SYSTEM MANUFACTURER. CIRCUIT/CABLE INSTALLATION WILL BE SIMILAR TO THAT INDICATED ON THE SPECIAL SYSTEM DRAWING SHEET EY101.
A,1
DS,1
B,2
A1
)B,2
CONNECT EXISTING, UNSWITCHED, EMERGENCY LIGHTING CIRCUIT PRESERVED AT THIS APPROXIMATE LOCATION DURING DEMOLITION WORK. PROVIDE NEW CIRCUITING TO MATCH EXISTING TO EXTEND AND CONNECT NEW LUMINAIRES. CIRCUIT ORIGINATES FROM AN EMERGENCY PANEL AT THE 6TH FLOOR. FIELD VERIFY EXACT PANEL IDENTIFICATION AND LOCATION, AND CIRCUIT USED AT THE 9TH FLOOR.
B E
)EXAM ROOM-B
M9-316 A1
DS,1
one and one half inches = one foot
)A,1
)S b E )B,2
EXAM ROOM-B
E )A1 M9-315
DS,1
A,1 O E
CONSTRUCTION
LIMITS
)EXAM ROOM-B
REPLACE ROCKER TYPE SWITCH WITH SINGLE POLE TOGGLE SWITCH IN EXISTING BACKBOX GANGED WITH DUPLEX RECEPTACLE. CONNECT NEW LUMINAIRE.
1.4 1.4
1.5
)A,1
EXAM ROOM-B A1
M9-314
)CORRIDOR
C9-31
M9-313
1.10
1.11
1.12
1.13
6"
LIMITS
)A1
EXAM ROOM-B A1
)M9-312
EXAM ROOM-B
b
)A1 M9-311
SERVICE ELEV. NO.
E17
SOILED HOLDING
)M9-310
SERVICE ELEV. NO.
E16
ELEVATOR NO. 1
E1
ELEVATOR NO. 2
E2
ELEVATOR NO. 3
E3
ELEVATOR NO. 4
E4
1.
J1 B
1.J
H1
EXISTING PANEL 'LP1-9'
B
MECH. ROOM
E
)A B,2
E
)DS,1
EXAM ROOM-A
M9-309 H
SERVICE ELEV.
1.H2
E
)EQUIP STORAGE
M9-335
H1 H1
M9-333 B H1
S
)1 LP1-9
H LOBBY
M9-301
L,1
STAIRWELL NO. 23
S )S23
E E
B1
S
E
EC9A
J
S
ELEC. CLOSET
M9-331
D
O2 STORAGE
B 2
L,1
D,1
)D,1
ELEVATOR LOBBY
E9-M
D1,1
D,1 D1,1 E X
1.H one inch = one foot )X E S
E E
A1 S
1 X2 A
A M9-307 A1
S
A D,1
X
)S,1
G,2 G,2
RECEPTION
M9-300
S,1
E )X
6"
)A1 CORRIDOR E
C9-35
| X | A | CORRIDOR |
| C9-34 |
| A | LP1-9 |
| 6 |
TOILET, PATIENT
E 1
LP1-9
D,1
D1,1
D,1
B,2
S,2
B,2
D,1
D1,1 E
S B a
S D1
M9-330
CORRIDOR
C9-30
LP1-9
| 4 | 3 | |
| G,2 | d a |
1.G
A1
C STERILE
M9-334
E
)E B1 F
DS A1
1 G,2
S
E
)A1 EC9A
CHECK OUT STATION M9-306
A1,2 A,2
)A,1 DS,1
DA,3 DA,3
WAITING 9E
)M9-3DS,3
DA,3
D,3
D1 E
D1,1
S TOILET
M9-303
D,4
DA,4
E C
)WAITING 9W
M9-280
A B B
)MEDS ROOM
K M9-340
G,2
A,1
DA,3
DA1,3
D1
F TOILET
M9-304
F DA,4
DS,4
DA1,4
three quarters inch = one foot
)OPEN WORKSTATIONS (6)
S
ELEC. CLST J
E E )M9-342
EXAM ROOM-A
1 LP1-9 M9-341
1.F
M9-332
ELEC. CLST
M9-344
DS,1
b )A A,2
C1,1
)EXISTING PANEL 'EC9A'
)STAIRWELL NO. 1 H1
S1
EC9A
EXAM ROOM-A
)M9-343
6"
)X2
)A,2
DS,1 A,2
M9-345
1.E
PROCEDURE
M9-346
)DS,1
)A,1
)A1,1
CORRIDOR
C9-32
DS,1 A,2
)S
)A
HSK
one half inch = one foot E
)S S
)D1 E )F A
M9-347
EXAM ROOM-A
b )M9-349
1.D
D1
TOILET, PAT
M9-346A
)TOILET, STAFF
F M9-348
DS,1 A,2
CLEAN STORAGE
M9-350
)LP1-9 A1
b E )M9-351
DS,1
)B B three eighths inch = one foot 0
)E
C
)DS C
a
)C1
OPEN
A,2
)X S
)DS
S A E
)OPEN
1.C
RK
)WO C STATION (7)
M9-352
)C9-33
WORKSTAT ON (9)
M9-353
)A A
1.B
)SHARED OFFICE (3)
a
)M9-354
A DS
STAFF LOUNGE
E )M9-355
)F
A1
A A
E
1.A2
F
)CONSTRUCTION LIMITS
) LIGHTING PLAN - 9TH LEVEL EAST
1/8" = 1'-0"
B NURSING B A
)SUPERVISOR
M9-356 X
STAIRWELL NO. 16
S16
A A1
1.A
C:\Revit
Projects\182024
Central-R18_SCT.rvt
)ARCHITECT / ENGINEER
| FARRIS ENGINEERING | |
| OMAHA | LINCOLN | COLORADO SPRINGS | SIDNEY | |
| farris-usa.com |
Building Key Plan:
A/E Seal:
Office of Construction and Facilities
Drawing Title
)LIGHTING PLAN - 9TH LEVEL EAST
Phase
CONSTRUCTION DOCUMENTS
Project Title
RENOVATE 9 EAST FOR SPECIALTY CLINIC
Project Number VA #589-18-910 one eighth inch = one foot
)Revision#
Description
Date:
P.O.C.: Jennifer Unrein 816.249.1500
142 N. MOSLEY ST. WICHITA, KANSAS
316.262.2500
COPYRIGHT FE#:182024
This document and the information contained may not be reproduced or excerpted from without the express written permission of Farris Engineering, Inc.
Unauthorized copying, disclosure or construction use are prohibited by the copyright law.
9E 9W
Management
U.S. Department of Veterans Affairs
Approved: Medical Center Director
Location
KANSAS CITY, MISSOURI
| Issue Date | Checked | Drawn |
| 9/27/2018 | MDW | DMM |
Drawing Number
EL101
)VA FORM 08 - 6231 1 2 3 4 5
6 7 8
9 10
1 2 3
1.6 1.6A
1.7
1.8
1.8A 1.9
6 7 8
9 10
6"
9/26/2018 4:16:35 PM
)STAIRWELL NO. 22
S22
CR
KEYNOTES
1 PROVIDE WIRELESS ACCESS POINT TO MATCH EXISTING CURRENTLY INSTALLED DEVICES AND COMPATIBLE WITH EXISTING DATA SYSTEM. PROVIDE 20'-0" LENGTH OF DATA CABLE SERVICE LOOP ABOVE CEILING.
2 PROVIDE A WIRELESS, SECURITY/DURESS PUSHBUTTON ALARM NOTIFICATION SYSTEM EQUAL TO LYNX SYSTEMS LYNX-WLT-IDPNC-3 AS MANUFACTURED BY MICRO TECHNOLOGY SERVICES, INC.
)A
SD
N )+40" 13
EXAM ROOM-B(TYP)
ES
)2 S
EXAM ROOM-B
LIMITS P
INSTALL DEVICES TO THE UNDERSIDE OF THE COMPUTER SUPPORT COUNTER WITH PUSHBUTTON
ACCESSIBLE AT THE EDGE OF THE COUNTER. A
3 FOR DEVICES INSTALLED IN RECEPTION AND CHECK OUT STATION WALL SYSTEM FURNITURE (DASHED), ROUTE TELECOMMUNICATIONS CABLING IN CONDUIT FURNISHED AS PART OF THE
M9-318
)+46"
B
W,1
S 2
(TYP)
SD
N )2
M9-317 +46" +40" E
PRE-MANUFACTURED WALL SYSTEM. CONDUIT IS STUBBED FROM DEVICE BACKBOXES, FURNISHED IN WALL SYSTEM, TO ABOVE THE ACCESSIBLE CEILING. CONTRACTOR SHALL PROVIDE ALL COMMUNICATION CABLING, DEVICES AND FACEPLATES. FIELD VERIFY EXACT DEVICE BACKBOX LOCATION(S) IN WALL SYSTEM.
4 INSTALL IN VERTICAL SECTION OF SUPPLY AIR DUCTWORK FOR AHU FAN SHUTDOWN.
5 PROVIDE CONNECTION FOR PUBLIC ADDRESS/PAGING SPEAKERS TO THE NURSE CALL SYSTEM.
+40"
M9-316
WAP
N )1
M9-315
PROVIDE NEW 20 AMP, SINGLE POLE CIRCUIT BREAKER COMPATIBLE WITH EXISTING PANEL (SQUARE D, NQ) AND INSTALL IN AVAILABLE SPACE. NEW CIRCUIT BREAKER AIC RATING SHALL MATCH EXISTING.
one and one half inches = one foot 6"
)1.4
1.4A
1.5
)+40"
M9-314
+40"
S 2
S 2
(TYP)
B
)CORRIDOR
N )C9-31
(TYP)
N
2 S
+40" E
M9-313
)O
1.10
1.11
1.12
1.13
PROVIDE 30” WIDE X 72” HIGH X 34” THICK PLYWOOD BACKBOARD PAINTED WITH TWO COATS GRAY FIRE RESISTANT PAINT. SECURELY MOUNT TO WALL FOR CARD ACCESS SECURITY CONTROL PANEL(S).
8 PROVIDE ACCESS CONTROL PANEL(S) EQUAL TO AND COMPATIBLE WITH EXISTING ACCESS CONTROL SYSTEM PANEL(S) CURRENTLY OPERATIONAL IN EXISTING FACILITY. INSTALL PANEL(S) ONE OVER THE OTHER AND SLIGHTLY OFFSET AT THIS LOCATION IF QUANTITY REQUIRED IS GREATER THAN ONE. POWER CIRCUIT SHALL BE SHARED BETWEEN PANELS IF QUANTITY IS GREATER THAN ONE.
9 CONNECT CIRCUIT BREAKER INSTALLED BY KEYNOTE 6 IN EXISTING PANEL ‘DT9’.
10 CONNECT TO EXISTING BUILDING ACCESS CONTROL SYSTEM. PROVIDE NECESSARY DATA CABLE FROM ACCESS SYSTEM CONTROL PANEL(S) TO EXISTING DATA RACK IN OI&T CLOSET M9-302 (THIS ROOM).
11 CONNECT DOOR ACCESS CONTROL PANEL IN OI&T CLOSET, M9-302.
12 CONNECT 110 BLOCK AT TELECOMMUNICATIONS EQUIPMENT IN OI&T CLOSET, M9-302, USING
) M9-312
W,1 2
)SD
W,1 M9-311
SD
)+46"
EXISTING PANEL 'DT9'
1.
J1
CATEGORY 6 CABLE. B
13 SEE SHEET EP101 FOR POWER AND FIRE ALARM CONNECTION REQUIREMENTS TO SMOKE AND/OR FIRE SMOKE DAMPERS.
)WAP
SERVICE ELSEVR.VNICOE. ELEV. NO.ELEVATOR NO. 1
ELEVATOR NO. 2
ELEVATOR NO. 3
ELEVATOR NO. 4
1.J
SOILED HOLDING
M9-310
E16
17 E1 E17
E2 E3 E4
STAIRWELL NO. 23
S23
EQUIP STORAGE
F )M9-335
4 MECH. ROOM
DM
SD
)M9-333
W,1 +42"
13 (TYP)
N
)(TYP)
W,1
M9-309 +46" +40" E 1
O2 STORAGE
M9-307
SERVICE ELEV. LOBBY
M9-301
)9
ELEVATOR LOBBY
E9-M
1.H2
ELEC. CLOSEST
7 3
) SD
FSD
M9-331
S (TYP)
EV WAP S
1.H one inch = one foot F
)11 (TYP)
)CORRIDOR
(TYP)
NURSE CALL ANNUNCIATOR WITH CODE BLUE STATION
11 (TYP)
SD SD
S )5
6"
)C9-35 SD S
SD
WAP S
C9-34
C9-30
SD
S F
)WAP
SD
E )1
FOR
RECEPTION SD
M9-300
)F
)TOILET, PATIENT
PRINTER,
1.G
C STERILE
+46" W,1
1,2 1,2
)OPEN WORKSTATIONS (6) M9-332
M9-330
+40"
1,2
CHECK OUT STATION
)+72"
FIELD VERIFY MOUNTING HEIGHT
E
WAITING 9E
3 (TYP)
+72"
E
)WAITING 9W C
)M9-334
)1
MEDS ROOM
1,2
)M9-340
)+46"
S
ES
)SD
C R )2 1,2
M9-306
)1
S SD
M9-305
TOILET
M9-304
)+40"
TOILET
M9-303
SD
M9-280 three quarters inch = one foot
)M9-342
1.F
2 W,1 EXAM ROOM-A
M9-341
N )+40" E 1
(TYP)
)STAIRWELL NO. 1 M9-344 S1
(TYP) 2 S
F
6"
ES
)CR WAP
EXAM ROOM-A
M9-343
)+40" E 1
(TYP)
B
)F SD
2 W,1
M9-345
1.E
SUPPLEMENTAL ELECTRICAL SYMBOLS LEGEND
)PROCEDURE
M9-346
C9-32
E 1
SYMBOL
DESCRIPTION
(AS APPLICABLE)
COMMUNICATIONS
SYMBOL
DESCRIPTION
one half inch = one foot )+50" 2 2 E
S 2
(TYP)
HSK
M9-347
1.D
| W | TELEPHONE OUTLET - WALL MOUNTED # | TELEPHONE OUTLET BOX |
| # | DATA OUTLET BOX |
NUMBER BY SYMBOL INDICATES
QUANTITY OF JACKS. ZERO S
TELEPHONE CABINET
INTERCOM/PAGING SPEAKER - CEILING MOUNTED INTERCOM/PAGING SPEAKER - WALL MOUNTED
2 # PHONE OUTLET BOX - CEILING MOUNTED INDICATES EMPTY OUTLET BOX , S
INTERCOM/PAGING SPEAKER HORN - WALL MOUNTED
TOILET, PAT
OILET, STAFF
WAP
S +46"
# DATA OUTLET BOX - CEILING MOUNTED
BLANK PLATE AND CONDUIT.
S SOUND SYSTEM SPEAKER - CEILING MOUNTED
M9-346A
E )+40"
M9-348
W,1 EXAM ROOM-A
M9-349
N )+40" E 1
WAP #
WIRELESS ACCESS POINT - CEILING MOUNTED
COMBINATION TELEPHONE/DATA OUTLET BOX - (NUMBERS INDICATE QUANTITY OF TELEPHONE AND DATA JACKS RESPECTIVELY)
DATA OUTLET BOX - BLANK PLATE, 1" CONDUIT
S SOUND SYSTEM SPEAKER - WALL MOUNTED
A T.V. ANTENNA OUTLET GROUND BAR
NOTE: SYMBOLS SHOWN "STACKED" ON THE FLOOR PLANS
CLEAN STORAGE 2 S
INDICATE THAT THE DEVICES ARE TO BE LOCATED IN THE SAME
M9-350
SD +46"
)S W,1 EXAM ROOM-A
)M9-351
FIRE ALARM
OUTLET BOX AND FACEPLATE. (I.E. 1 )
+40" E 1
1.C
HD R/T
HEAT DETECTOR - COMBINATION
FIRE ALARM VISUAL SIGNAL - CEILING MOUNTED
)E 1,2
OPEN
1,2 FSD
FSD 1,2
HD F HD EV SD
HEAT DETECTOR - FIXED TEMPERATURE F
HEAT DETECTOR - FIXED TEMPERATURE (CONNECTED TO ELEVATOR RECALL) SMOKE DETECTOR
FIRE ALARM SPEAKER - CEILING MOUNTED
FIRE ALARM COMBINATION SPEAKER/VISUAL - CEILING MOUNTED E
FLOW SWITCH
three eighths inch = one foot 0 1,2
)WORKSTATION (7)
1,2 1,2 )M9-352
SD DM SMOKE DETECTOR - DUCT MOUNTED
TAMPER SWITCH
1,2
)S SD EV SMOKE DETECTOR (CONNECTED TO ELEVATOR RECALL)
DUCT DETECTOR REMOTE ALARM INDICATOR
1,2 1,2
)SD
1,2
)O EN WORKSTA ION (9)
F FIRE ALARM MANUAL STATION
R
FAN SHUT-DOWN RELAY MAGNETIC DOOR HOLDER
)1,2
C9-33
M9-353
1.B
S SECURITY/DURESS ALARM BUTTON PUSHBUTTON STATION, 'P' INDICATES PILOT
SECURITY
KP
MOTION DETECTOR KEYPAD
SHARED OFFICE (3)
M9-354
)1,2
NURSING
F SUPERVISOR
)M9-356
WAP SD
+46" W,1
STAFSF LOUNGE
M9-355
1.A2
1.A
DOOR MONITOR SWITCH
DOOR SWITCH
DOOR BELL CHIME/BUZZER DOOR CONTACT
| E | NURSE CALL DOME LIGHT EMERGENCY CALLS ONLY | |
| N | NURSE CALL DOME LIGHT EMERGENCY/NORMAL CALLS E | EMERGENCY CALL SWITCH |
| B | CODE BLUE STATION | |
| N | SINGLE BED NURSE CALL STATION (1 CORD SET) |
CR PS
NURSE CALL
N2
NC ND NS
ELECTRIC STRIKE
CARD READER POWER SUPPLY SECURITY CAMERA
DOUBLE BED NURSE CALL STATION (2 CORD SETS)
NURSE CALL ANNUNCIATOR & POWER SUPPLY F
NURSE CALL DUTY STATION NURSE CALL STAFF STATION
)SPECIAL SYSTEMS PLAN - 9TH LEVEL
CONSTRUCTION LIMITS
ES
CR
STAIRWELL NO. 16
) EAST
1/8" = 1'-0"
S16
C:\Revit
Projects\182024
Central-R18_SCT.rvt
)ARCHITECT / ENGINEER
| FARRIS ENGINEERING | |
| OMAHA | LINCOLN | COLORADO SPRINGS | SIDNEY | |
| farris-usa.com |
Building Key Plan:
Office of Construction and Facilities
Drawing Title
SPECIAL SYSTEMS PLAN - 9TH LEVEL EAST
Phase
)CONSTRUCTION DOCUMENTS
Project Title
RENOVATE 9 EAST FOR SPECIALTY CLINIC
Project Number VA #589-18-910 one eighth inch = one foot
)Revision#
Description
P.O.C.: Jennifer Unrein 816.249.1500
142 N. MOSLEY ST. WICHITA, KANSAS
316.262.2500
COPYRIGHT FE#:182024
This document and the information contained may not be reproduced or excerpted from without the express written permission of Farris Engineering, Inc.
9E 9W
Management
U.S. Department of Veterans Affairs
Approved: Medical Center Director
Location
KANSAS CITY, MISSOURI
| Issue Date | Checked | Drawn |
| 9/27/2018 | MDW | DMM |
Drawing Number
EY101
)VA FORM 08 - 6231 1 2 3 4 5
6 7 8
9 10
9/26/2018 4:16:12 PM
)1 2 3 4 5
6"
LIGHTING CONTROLS ROOM SCHEDULE
Room Number Room Name Lighting
Control
Scheme C9-30
CORRIDOR
CR1A
C9-31
CORRIDOR
CR1A
C9-32
CORRIDOR
CR1A
C9-33
CORRIDOR
CR1A
C9-34
CORRIDOR
CR1A
C9-35
CORRIDOR
CR1A
E9-M
ELEVATOR LOBBY
EV4A
M9-280
WAITING 9W
EV4A
M9-300
RECEPTION
EV4A
M9-303
TOILET
111A M9-304
TOILET
111A M9-305
WAITING 9E
EV4A
M9-306
CHECK OUT STATION
CO2A
M9-307
O2 STORAGE
211A M9-309
EXAM ROOM-A
ER2A
M9-310
SOILED HOLDING
211A M9-311
EXAM ROOM-B
ER2A
M9-312
EXAM ROOM-B
ER2A
M9-313
EXAM ROOM-B
ER2A
M9-314
EXAM ROOM-B
ER2A
M9-315
EXAM ROOM-B
ER2A
M9-316
EXAM ROOM-B
ER2A
M9-317
EXAM ROOM-B
ER2A
M9-318
EXAM ROOM-B
ER2A
M9-330
TOILET, PATIENT
111A M9-331
ELEC. CLOSET
011A M9-332
OPEN WORKSTATIONS (6)
NS1A
M9-333
MECH. ROOM
011A M9-334
STERILE
211A M9-335
EQUIP STORAGE
211A M9-340
MEDS ROOM
211A M9-341
EXAM ROOM-A
ER2A
M9-342
ELEC. CLST
011A M9-343
EXAM ROOM-A
ER2A
M9-344
ELEC. CLST
011A M9-345
EXAM ROOM-A
ER2A
M9-346
PROCEDURE
ER2A
M9-346A
TOILET, PAT
111A M9-347
HSK
211A M9-348
TOILET, STAFF
111A M9-349
EXAM ROOM-A
ER2A
M9-350
CLEAN STORAGE
NS1A
M9-351
EXAM ROOM-A
ER2A
M9-352
OPEN WORKSTATION (7)
NS1A
M9-353
OPEN WORKSTATION (9)
NS1A
M9-354
SHARED OFFICE (3)
NS1A
M9-355
STAFF LOUNGE
NS1A
M9-356
NURSING SUPERVISOR
NS1A
)LIGHTING CONTROL SYSTEM BASIS OF DESIGN:
6 7 8
9 10
NLIGHT (REFER TO ‘LIGHTING CONTROL REQUIREMENTS’ BELOW)
A LIGHTING CONTROL SCHEME NARRATIVE
CR1A– CORRIDOR (ONE ZONE)
· ZONE(S): ROOM LIGHTING
· LIGHTING CONTROL STATION(S): a (LOCATED IN ‘CHECK OUT STATION M9-306’)
· CONTROLLER(S): OCCUPANCY SENSOR
B )OPERATION: ALL LUMINAIRES SHALL BE CONTROLLED BY OCCUPANCY SENSOR FOR AUTOMATIC ‘ON’ OPERATION TO 80% OF LUMEN OUTPUT. MANUAL DIMMING INCREASE TO 100% AT CONTROL STATION WITH DIMMING DOWN TO 25% OF LUMEN OUTPUT.
· NOTES: NONE
one and one half inches = one foot
)ER2A– EXAM ROOM, PROCEDURE ROOM (TWO ZONES)
· ZONE(S): ROOM LIGHTING, CHARTING
· LIGHTING CONTROL STATION(S): b
· CONTROLLER(S): COMBINATION VACANCY/DAYLIGHT SENSOR
)OPERATION: ALL LUMINAIRES SHALL BE CONTROLLED BY VACANCY SENSOR PORTION OF COMBINATION SENSOR. LUMINAIRES IN ZONE ONE SHALL BE CONTROLLED BY DAYLIGHT SENSOR WITH OVERRIDE BY DIMMER SWITCH. LUMINAIRE IN ZONE TWO SHALL BE CONTROLLED BY DIMMER SWITCH.
· NOTES: NONE
6"
)EV4A– ELEVATOR LOBBY, RECEPTION, WAITING (FOUR ZONES)
· ZONE(S): ROOM LIGHTING
· LIGHTING CONTROL STATION(S): c (LOCATED IN ‘RECEPTION M9-300’)
· CONTROLLER(S): OCCUPANCY SENSOR, VACANCY SENSOR, COMBINATION VACANCY/DAYLIGHT SENSOR )OPERATION: ALL LUMINAIRES IN ZONE ONE SHALL BE CONTROLLED BY OCCUPANCY SENSOR FOR AUTOMATIC ‘ON’ OPERATION TO 80% OF LUMEN OUTPUT. ALL LUMINAIRES IN ZONE TWO SHALL MANUAL ‘ON’ AND CONTROLLED BY VACANCY SENSOR. ALL LUMINAIRES IN ZONES THREE AND FOUR SHALL BE CONTROLLED BY DAYLIGHT SENSOR WITH OVERRIDE BY DIMMER SWITCH. MANUAL DIMMING INCREASE TO 100% AT CONTROL STATION WITH DIMMING DOWN TO 25% IN ZONES ONE, THREE AND FOUR.
· NOTES: ZONE ONE WALL SCONCES ('L') SHALL NOT BE DIMMED WITH ZONE ONE DIMMER SWITCH BUT COME ON 100% FULL OUTPUT. ZONE TWO DOWNLIGHTS ('G') SHALL NOT BE DIMMED WITH ZONE TWO DIMMER SWITCH.
CO2A– CHECK OUT STATION (TWO ZONES)
· ZONE(S): ROOM LIGHTING
· LIGHTING CONTROL STATION(S): d (LOCATED IN ‘CHECK OUT STATION M9-306’)
· CONTROLLER(S): COMBINATION VACANCY/DAYLIGHT SENSOR
one inch = one foot )OPERATION: ALL LUMINAIRES SHALL BE CONTROLLED BY VACANCY SENSOR PORTION OF COMBINATION SENSOR. LUMINAIRES IN ZONE ONE SHALL BE CONTROLLED BY DAYLIGHT SENSOR WITH OVERRIDE BY DIMMER SWITCH. LUMINAIRE IN ZONE TWO SHALL BE CONTROLLED BY MANUAL DIMMER SWITCH.
· NOTES: ZONE TWO DOWNLIGHTS ('G') SHALL NOT BE DIMMED WITH ZONE TWO DIMMER SWITCH.
6"
)NS1A– NURSING SUPERVISOR, OPEN WORKSTATION, STAFF LOUNGE (ONE ZONE EACH)
· ZONE(S): ROOM LIGHTING
· LIGHTING CONTROL STATION(S): a
· CONTROLLER(S): COMBINATION VACANCY/DAYLIGHT SENSOR
· OPERATION: ALL LUMINAIRES SHALL BE MANUAL ‘ON’ TO 80% OF LUMEN OUTPUT AND CONTROLLED BY VACANCY SENSOR PORTION OF COMBINATION SENSOR.
C LUMINAIRES SHALL BE CONTROLLED BY DAYLIGHT SENSOR WITH OVERRIDE BY DIMMER SWITCH.
· NOTES: NOTE THAT OPEN WORKSTATIONS M9-352 & M9-354 REQUIRE CONTROL STATIONS AT TWO LOCATIONS FOR CONTROL LUMINAIRES IN SINGLE SPACE.
LUMINAIRE SCHEDULE
MARK
DESCRIPTION
MANUFACTURER/SERIES
CATALOG NO.
LIGHT SOURCE
FINISH
MOUNTING
INPUT
WATTS
VOLTS
ACCEPTABLE
MANUFACTURERS
REMARKS
QTY
TYPE
A
2'X4' VOLUMETRIC LED ARCHITECTRUAL TROFFER - 5600 LUMEN
COLUMBIA
LSER24-35HLG-C-EDU
5615 LUMEN | 3500K | LED
WHITE
RECESSED
53 VA
REMARK 1
A1
2'X4' VOLUMETRIC LED ARCHITECTRUAL TROFFER - 5600 LUMEN - EMERGENCY
COLUMBIA
LSER24-35HLG-C-EDU
5615 LUMEN | 3500K | LED
WHITE
RECESSED
53 VA
REMARK 1
B
2'X4' VOLUMETRIC LED ARCHITECTRUAL TROFFER - 4790 LUMEN
COLUMBIA
LSER24-35MLG-C-EDU
4795 LUMEN | 3500K | LED
WHITE
RECESSED
44 VA
REMARK 1
B1
2'X4' VOLUMETRIC LED ARCHITECTRUAL TROFFER - 4790 LUMEN - EMERGENCY
COLUMBIA
LSER24-35MLG-C-EDU
4795 LUMEN | 3500K | LED
WHITE
RECESSED
44 VA
REMARK 1
C
2'X4' VOLUMETRIC LED ARCHITECTRUAL TROFFER - 6990 LUMEN
COLUMBIA
LSER24-35VLG-C-EDU
6992 LUMEN | 3500K | LED
WHITE
RECESSED
62 VA
REMARK 1
C1
2'X4' VOLUMETRIC LED ARCHITECTRUAL TROFFER - 6990 LUMEN - EMERGENCY
COLUMBIA
LSER24-35VLG-C-EDU
6992 LUMEN | 3500K | LED
WHITE
RECESSED
62 VA
REMARK 1
D
2'X2' VOLUMETRIC LED ARCHITECTURAL TROFFER - 1900 LUMEN
COLUMBIA
LSER22-35MWG-C-EDU
1900 LUMEN | 3500K | LED
WHITE
RECESSED
19 VA
REMARK 1
D1
2'X2' VOLUMETRIC LED ARCHITECTURAL TROFFER - 1900 LUMEN - EMERGENCY
COLUMBIA
LSER22-35MWG-C-EDU
1900 LUMEN | 3500K | LED
WHITE
RECESSED
19 VA
REMARK 1
DA
2'X2' VOLUMETRIC LED ARCHITECTURAL TROFFER - 4290 LUMEN
COLUMBIA
LSER22-35VLG-C-EDU
4293 LUMEN | 3500K | LED
WHITE
RECESSED
44 VA
REMARK 1
DA1
2'X2' VOLUMETRIC LED ARCHITECTURAL TROFFER - 4290 LUMEN - EMERGENCY
COLUMBIA
LSER22-35VLG-C-EDU
4293 LUMEN | 3500K | LED
WHITE
RECESSED
44 VA
REMARK 1
F
36" LONG WALL MOUNT LED ARCHITECTURAL TASK
HE WILLIAMS
WMA-3-L23/835-AF-DIM-UNV
2300 LUMEN | 3500K | LED
WHITE
SURFACE / WALL
30 VA
REMARK 1
G
4" ROUND LED DOWNLIGHT
PRESCOLITE
LF4SLDM1-4LFSL15L35K8
1390 LUMEN | 3500K | LED
CLEAR ALZAK
RECESSED
13 VA
REMARK 2
H
NOMINAL 1'X4' LED WRAP - 4940 LUMEN
COLUMBIA
LWC4-35ML-EDU-PAF
4941 LUMEN | 3500K | LED
WHITE
PENDANT
45 VA
REMARK 1
H1
NOMINAL 1'X4' LED WRAP - 4940 LUMEN - EMERGENCY
COLUMBIA
LWC4-35ML-EDU-PAF
4941 LUMEN | 3500K | LED
WHITE
PENDANT
45 VA
REMARK 1
5, 7 J
24" LONG SURFACE WALL MOUNT LED
LITHONIA
WL2 18L
1890 LUMEN | 3500K | LED
WHITE
SURFACE / WALL
18 VA
REMARK 1
K
NOMINAL 24" LONG UNDERCABINET LED WITH INTEGRAL SENSOR
HEALTHCARE LIGHTING
HUC523 120 LED35 OS
1220 LUMEN | 3500K | LED
WHITE
UNDERCABINET
13 VA
KENALL, FAIL-SAFE
L
NOMINAL 14" LONG, VERTICAL, WALL MOUNTED, ADA, LED SCONCE
SPI LIGHTING
AIW8279 L14W PT02/COBR 120 3500K
928 LUMEN | 3500K | LED
WHITE
SURFACE / WALL
15 VA
VISA, OCL
X
LED DIE-CAST ALUMINUM EXIT SIGN - SINGLE FACE
DUAL-LITE
SESRBN
LED FURNISHED IN UNIT
ALUMINUM
REMARK 4
3 VA
REMARK 3
X2
LED DIE-CAST ALUMINUM EXIT SIGN - DOUBLE FACE
DUAL-LITE
SEDRBN
LED FURNISHED IN UNIT
ALUMINUM
REMARK 4
6 VA
REMARK 3
)LUMINAIRE SCHEDULE REQUIREMENTS
A. SUBMIT SHOP DRAWINGS FOR EACH LUMINAIRE, BALLAST, AND LAMP TYPE USED ON PROJECT.
B. ACCEPTABLE MANUFACTURERS LISTED ARE CAPABLE OF PROVIDING EQUIVALENT LUMINAIRES. SUBMIT PRODUCT AND ACCESSORIES EQUIVALENT OR SUPERIOR TO THE SPECIFIED B LUMINAIRE IN PHOTOMETRIC PERFORMANCE, CONSTRUCTION QUALITY, INCLUDED ACCESSORIES, AND AESTHETICS. ADDITIONAL MANUFACTURERS NOT LISTED MAY ALSO BE SUBMITTED FOR APPROVAL PRIOR TO BID. APPROVAL WILL BE BASED ON AN ASSESSMENT OF THE PRODUCT'S QUALITY, PHOTOMETRIC PERFORMANCE, INCLUDED ACCESSORIES, AND AESTHETICS.
C. ALL LUMINAIRES SHALL HAVE A U.L. LABEL. ALL LUMINAIRES USED IN EXTERIOR APPLICATIONS SHALL HAVE A U.L. WET LABEL.
D. VERIFY MOUNTING COMPATIBILITY OF LUMINAIRES WITH CEILING SYSTEMS/MATERIALS PRIOR TO ORDERING LUMINAIRES. NOTIFY ENGINEER OF ANY CONFLICTS WITH THE PROPOSED INSTALLATION.
E. FOR ALL SUSPENDED LUMINAIRES PROVIDE MOUNTING TYPE INDICATED IN LUMINAIRE SCHEDULE. REFER TO PLANS FOR SUSPENSION LENGTH(S) REQUIRED.
F. RECESSED DOWNLIGHTS SHALL HAVE ALZAK FINISH SELF-TRIMMING REFLECTORS. DOWNLIGHTS SHALL HAVE HARDWARE MOUNTING FOR REFLECTOR, SPRING CLIPS ARE NOT ACCEPTABLE.
G. PHILIPS, OSRAM SYLVANIA, G.E., CREE, NICHIA, XICATO, AND SAMSUNG ARE ACCEPTABLE LED MANUFACTURERS.
H. PROVIDE LED LUMINAIRES WITH MINIMUM 5-YEAR WARRANTY AND INTEGRAL SURGE PROTECTION. LED MODULES, DRIVERS, AND POWER SUPPLIES SHALL BE FIELD-REPLACEABLE. LUMINAIRE SCHEDULE REMARKS
1. COLUMBIA, DAY-BRITE, H.E. WILLIAMS, LITHONIA AND METALUX ARE ACCEPTABLE MANUFACTURERS FOR LUMINAIRE TYPE INDICATED WHERE NOT LISTED AS BASE MANUFACTURER.
2. GOTHAM, H.E. WILLIAMS, LIGHTOLIER, PATHWAY COVENTRY, PORTFOLIO AND PRESCOLITE ARE ACCEPTABLE MANUFACTURERS FOR LUMINAIRE TYPE INDICATED WHERE NOT LISTED AS BASE MANUFACTURER.
3. CHLORIDE, DUAL-LITE, EMERGI-LITE, HUBBELL, LITHONIA AND SURE-LITES ARE ACCEPTABLE MANUFACTURERS FOR LUMINAIRE TYPE INDICATED WHERE NOT LISTED AS BASE MANFACTURER.
4. REFER TO DRAWINGS FOR MOUNTING REQUIREMENTS SUCH AS WALL MOUNT, END MOUNT, CEILING MOUNT AND PROVIDE LUMINAIRES ACCORDINGLY. PROVIDE DIRECTIONAL CHEVRON ARROWS AS INDICATED ON PLANS.
5. PROVIDE LUMINAIRE WITH EMERGENCY DEVICE ALLOWING THE LUMINAIRE TO BE FED BY EMERGENCY POWER AND BE CONTROLLED WITH NORMAL POWER LUMINAIRES IN THE SAME ZONE. IF NORMAL POWER IS LOST, DEVICE SHALL REVERT THE LUMINAIRE TO 100% LIGHT OUPUT. IF NORMAL POWERED LUMINAIRES ARE NOT PRESENT IN ROOM, PROVIDE LUMINAIRE WITH EMERGENCY DEVICE ALLOWING THE LUMINAIRE TO BE FED BY EMERGENCY POWER AND BE CONTROLLED WITH LOCAL SWITCH; NORMAL SENSE WIRES SHALL BE CONNECTED TO NORMAL LIGHTING CIRCUIT IMMEDIATELY OUTSIDE OF ROOM. IF NORMAL POWER IS LOST, DEVICE SHALL REVERT THE LUMINAIRE TO 100% LIGHT OUTPUT.
6. WALL MOUNT LUMINAIRE WITH HORIZONTAL CENTERLINE +78" ABOVE FINISHED FLOOR AND VERTICAL CENTERLINE CENTERED ON MIRROR.
7. PENDANT MOUNT (CHAIN - LUMINAIRE MANFACTURER SUPPLIED) AS HIGH AS POSSIBLE BELOW MECHANICAL DUCTWORK AND PIPING, AS APPLICABLE, OR MAXIMUM 9'-0" TO TOP ABOVE FINISHED FLOOR.
8. MOUNT OVER DOOR WITH LONGITUDINAL CENTERLINE OF LUMINAIRE INSTALLED HORIZONTALLY APPROXIMATELY 6" ABOVE DOOR FRAME.
9. MOUNT LUMINAIRE AT HEIGHT ABOVE FINISHED FLOOR TO MATCH SIMILAR INSTALLATIONS IN ELEVATOR LOBBIES AT THE 5TH, 7TH AND 10TH FLOORS. VERIFY HEIGHT WITH COR PRIOR TO C
LUMINAIRE ROUGH-IN.
)CONVENTIONAL LIGHTING CONTROL SYSTEMS
011A – SINGLE POLE SWITCH (LINE VOLTAGE SWITCHING)
111A – OCCUPANCY SENSOR WALL SWITCH (LINE VOLTAGE SWITCHING)
three quarters inch = one foot 6" 0
)211A – VACANCY SENSOR WALL SWITCH (LINE VOLTAGE SWITCHING)
LIGHTING CONTROL REQUIREMENTS
1. PROVIDE SYSTEM FOR LIGHTING CONTROLS AS SHOWN ON PLANS, SCHEDULES, AND NOTES. SUBMIT SHOP DRAWING OF COMPLETE SYSTEM. COOPER GREEN GATE, HUBBELL BUILDING AUTOMATION, WATTSTOPPER, NLIGHT, LC&D, LUTRON, LEVITON, AND INTELLIGENT LIGHTING CONTROLS (ILC) SHALL BE CONSIDERED ACCEPTABLE MANUFACTURERS SUBJECT TO COMPLIANCE WITH REQUIREMENTS.
2. PROVIDE PROGRAMMING AS REQUIRED FOR LIGHTING CONTROL (ON/OFF, DIMMING, DAYLIGHT HARVESTING, OCCUPANCY/VACANCY SENSOR, AND TIME SCHEDULE CONTROL) AS INDICATED. PROVIDE INTERFACE BETWEEN LIGHTING CONTROL SYSTEM AND NETWORK TO ALLOW PROGRAMMING AND CALIBRATION OF SYSTEM THROUGH SOFTWARE.
3. PROVIDE INTERFACE/PROGRAMMING FOR DAYLIGHT SENSOR(S) AS REQUIRED TO AUTOMATICALLY CONTINUALLY DIM CORRESPONDING ZONES WHEN ADEQUATE DAYLIGHT IS AVAILABLE AND RETURN TO CURRENT SPACE LIGHTING STATUS WHEN ADEQUATE DAYLIGHT IS NOT AVAILABLE. FIELD COORDINATE SETTINGS PER MANUFACTURER RECOMMENDATIONS AND FOR OPERATION AS DIRECTED BY COR.
4. REFER TO SPECIFICATIONS FOR OCCUPANCY/VACANCY SENSOR REQUIREMENTS AND LOCATIONS. CONNECT ALL SENSORS IN CORRESPONDING AREA TOGETHER TO FEED INPUT OF OCCUPANCY/VACANCY TO CONTROL DEVICE. REFER TO DRAWINGS FOR QUANTITY OF SENSORS.
D ( )5. PROVIDE BRUSHED METAL CENTER PLATE AND GRAY BUTTON COLOR AND PERMANENT WHITE FILLED LABELING AS INDICATED FOR ALL CONTROL STATIONS. PROVIDE PROGRAMMING AS REQUIRED FOR CONTROL OF ZONES AS INDICATED.
6. PROVIDE CAT. 5 PATCH CABLE WITH RJ45 CONNECTORS TO CONNECT ALL CONTROL DEVICES AND CONTROL STATIONS TOGETHER. COORDINATE REQUIREMENTS WITH EQUIPMENT SUPPLIER.
7. ( one half inch = one foot )PROVIDE EXTERIOR GLOBAL PHOTOCELL, INTERFACE/PROGRAMMING, AND WIRING CONNECTIONS AS REQUIRED TO AUTOMATICALLY CONTROL INDICATED ZONES BASED ON DAYLIGHT CONDITIONS. FIELD COORDINATE SETTINGS PER MANUFACTURER RECOMMENDATIONS AND FOR OPERATION AS DIRECTED BY OWNER. INSTALL SENSOR ON ROOF FACING NORTH. PROVIDE WEATHERPROOF BOX AND ROOF PENETRATION AS REQUIRED.
8. INITIAL START-UP, COMMISSIONING, AND PROGRAMMING MUST BE COMPLETED BY A QUALIFIED FACTORY REPRESENTATIVE. PROVIDE 2 HOURS OF TRAINING FOR THE COR. COORDINATE TIME WITH ARCHITECT, LIGHTING DESIGNER, AND COR. COORDINATE FINAL CONTROL SEQUENCING WITH COR AND LIGHTING DESIGNER.
9. ALL LOW VOLTAGE CAT 5 CABLING TERMINATIONS SHALL BE FACTORY MOLDED FOR RUNS LESS THAN 30'. WHERE CABLES ARE GREATER THAN 30', A LOW VOLTAGE LICENSED TECHNICIAN AND/OR QUALIFIED CONTRACTOR SHALL PERFORM THE TERMINATIONS. POOR TERMINATIONS WILL RESULT IN A NON-OPERATING SYSTEM. INSTALLER SHALL USE ANY SPECIFIC TERMINATION TOOLS PROVIDED BY THE FACTORY - SEE INSTALLATION REQUIREMENTS. CABLE SHALL BE COLORED DIFFERENTLY THAN TELEPHONE, DATA, AND OTHER SYSTEMS CABLING. PROVIDE CABLE COLOR WITHIN SUBMITTAL. PREFERRED OWNER COLOR: PURPLE.
10. LIGHTING CONTROL WIRING AND CABLES ARE NOT SHOWN ON PLAN LAYOUTS. CONTRACTOR SHALL PROVIDE ALL CONTROL WIRING AND CABLING AS REQUIRED TO PROVIDE LIGHTING CONTROLS AS INDICATED.
11. COORDINATE DAYLIGHTING ZONE MAXIMUM SETPOINTS WHERE REQUIRED WITH THE COR.
12. COORDINATE OCCUPANCY/VACANCY SENSOR TIME DELAYS WHERE REQUIRED WITH THE COR.
13. ALL CONTROL RELAYS AND INTERFACE DEVICES SHALL BE INSTALLED INSIDE IN INSULATED, ACCESSIBLE AREAS UNLESS RATED FOR OUTDOOR USE. LIGHTING CONTROL DEVICES SHALL NOT BE INSTALLED EXPOSED IN OPEN CEILING AREAS. LOCATE ABOVE ACCESSIBLE ACOUSTICAL GRID CEILINGS IN ADJACENT ROOMS.
E ( )14. ALL DIMMER SWITCHES SHALL BE COMPATIBLE WITH LUMINAIRES CONTROLLED BY THE SWITCHES. COORDINATE DIMMER SWITCH COMPATIBILITY WITH LUMINAIRES.
three eighths inch = one foot 0 )15. PROVIDE EMERGENCY LIGHTING CONTROL IN ALL AREAS WHERE EMERGENCY LIGHTING IS SHOWN ON THE DRAWINGS. SOME AREAS THAT HAVE EMERGENCY LIGHTING AND NORMAL POWER LIGHTING ARE SHOWN TO BE CONTROLLED BY TOGGLE SWITCHES. THOSE AREAS MAY NEED SINGLE BUTTON PUSH-BUTTON SWITCHES INSTEAD TO ALLOW THE NORMAL POWER AND THE EMERGENCY POWER LUMINAIRES TO BE CONTROLLED TOGETHER. PROVIDE PUSH BUTTON SWITCHES IF NECESSARY.
B1 D1 D2
CONTROL STATION 'a'
D1 D2 B2 D3 D4
CONTROL STATION 'b'
CONTROL ELEMENTS:
· B1: ON/OFF ZONE ONE LIGHTING; ON TO 80%, FULL OUTPUT
· D1: DIMMER TO PROVIDE MANUAL RAISE FOR ZONE ONE LIGHTING
· D2: DIMMER TO PROVIDE MANUAL LOWER FOR ZONE ONE LIGHTING
APPLICATION: CORRIDOR, OFFICES, WORKSTATIONS, LOUNGE
· B1: ON/OFF ZONE ONE LIGHTING; ON TO 100%, FULL OUTPUT
· D1: DIMMER TO PROVIDE MANUAL RAISE FOR ZONE ONE LIGHTING
· D2: DIMMER TO PROVIDE MANUAL LOWER FOR ZONE ONE LIGHTING
· B2: ON/OFF ZONE TWO LIGHTING; ON TO 100%, FULL OUTPUT
· D3: DIMMER TO PROVIDE MANUAL RAISE FOR ZONE TWO LIGHTING
· D4: DIMMER TO PROVIDE MANUAL LOWER FOR ZONE TWO LIGHTING
APPLICATION: EXAM, PROCEDURE
CONTROL STATION 'c'
D1 D2 B2 D3 D4
CONTROL STATION 'd'
B3 D5 D6 B4 D7 D8 B1 D1 D2 B2 D3 D4
)B1: ON/OFF ZONE ONE LIGHTING; ON TO 80%, FULL OUTPUT
· D1: DIMMER TO PROVIDE MANUAL RAISE FOR ZONE ONE LIGHTING
· D2: DIMMER TO PROVIDE MANUAL LOWER FOR ZONE ONE LIGHTING
· B2: ON/OFF ZONE TWO LIGHTING; ON TO 100%, FULL OUTPUT
· D3: DIMMER TO PROVIDE MANUAL RAISE FOR ZONE TWO LIGHTING
· D4: DIMMER TO PROVIDE MANUAL LOWER FOR ZONE TWO LIGHTING
· B3: ON/OFF ZONE THREE LIGHTING; ON TO 100%, FULL OUTPUT
c
)D5: DIMMER TO PROVIDE MANUAL RAISE FOR ZONE THREE LIGHTING
· D6: DIMMER TO PROVIDE MANUAL LOWER FOR
ZONE THREE LIGHTING D
· B4: ON/OFF ZONE FOUR LIGHTING; ON TO
100%, FULL OUTPUT
· D7: DIMMER TO PROVIDE MANUAL RAISE FOR ZONE FOUR LIGHTING
· D8: DIMMER TO PROVIDE MANUAL LOWER FOR ZONE FOUR LIGHTING
APPLICATION: ELEVATOR LOBBY, RECEPTION, WAITING
· B1: ON/OFF ZONE ONE LIGHTING; ON TO 100%, FULL OUTPUT
· D1: DIMMER TO PROVIDE MANUAL RAISE FOR ZONE ONE LIGHTING
· D2: DIMMER TO PROVIDE MANUAL LOWER FOR ZONE ONE LIGHTING
· B2: ON/OFF ZONE TWO LIGHTING; ON TO 100%, FULL OUTPUT
· D3: DIMMER TO PROVIDE MANUAL RAISE FOR ZONE TWO LIGHTING
· D4: DIMMER TO PROVIDE MANUAL LOWER FOR ZONE TWO LIGHTING
APPLICATION: CHECK OUT STATION E
d
) LIGHTING CONTROL STATIONS
6" = 1'-0"
F (
COPYRIGHT
FE#:182024
This document and the information contained may not be reproduced or excerpted from without the express written permission of Farris Engineering, Inc.
FARRIS
ENGINEERING
OMAHA | LINCOLN | COLORADO SPRINGS |
SIDNEY
farris-usa.com Building Key Plan:
9W
NORTH
9E one quarter inch = one foot C:\Revit
Projects\182024
Central-R18_SCT.rvt Revision# Description
)F
ARCHITECT / ENGINEER
Office of Construction and Facilities Management Drawing Title
ELECTRICAL DETAILS
Phase
CONSTRUCTION DOCUMENTS
Project Title
RENOVATE 9 EAST FOR SPECIALTY CLINIC
Project Number
VA #589-18-910
Drawn
DMM
Checked
MDW
Issue Date 9/27/2018 Drawing Number E-501
FULLY SPRINKLERED
142 N. MOSLEY ST. WICHITA,
KANSAS
316.262.2500
117 PIERCE ST, SUITE 110 SIOUX CITY, IOWA 712.252.4014
P.O.C.: Jennifer Unrein 816.249.1500 one eighth inch = one foot
)VA FORM 08 - 6231 1 2 3
4 5 6
U.S. Department of Veterans Affairs Location
KANSAS CITY, MISSOURI
Approved: Medical Center Director Building Number )7
8 9 10 image5.png image6.png image7.png image8.png image9.png image10.png image11.png image12.png image13.png image14.png image15.png image16.png image17.png image18.png image19.png image20.png image21.png image22.png image23.png image24.png image25.png image26.png image27.png image28.png image29.png image30.png image31.png image32.png image33.png image34.png image35.png image36.png image37.png image38.png image39.png image40.png image41.png image42.png image43.png image44.png image45.png image46.png image47.png image48.png image49.png image50.png image51.png image52.png image1.png image53.png image54.png image55.png image56.png image57.png image58.png image59.png image60.png image61.png image62.png image2.png image63.png image64.png image65.png image66.png image67.png image68.png image69.png image70.png image3.png image71.png image72.png image73.png image74.png image4.png
File details come from the government source that posted it. Updated .