This Statement of Need (SoN) details a wire purchase requirement for Offutt Air Force Base. The project calls for procuring 1,500 linear feet of #4/0 15KV 133% EPR tape shielded 220mil wire, with specific cuts at 500 ft, along with 9 indoor termination kits including stranded shield adapter kits and two-hole crimp terminals. The wire is Type MV-105 cable designed for aerial, direct burial, and underground duct installations, capable of operating at conductor temperatures up to 105°C under normal conditions, 140°C for emergency overload, and 250°C for short circuit conditions.

The technical specifications require an annealed uncoated copper compact stranded conductor, extruded semiconducting EPR strand and insulation screens, and a 5 mil bare copper tape shield with 12.5% nominal overlap. The wire must meet multiple industry standards including ICEA, NEMA, AEIC, CSA, and UL requirements. Delivery is specified to Offutt AFB at 106 Peacekeeper Dr., Building 301, with the contractor required to provide a manufacturer's warranty on the equipment. No alterations to the specifications are permitted without prior approval from the government Project Manager and Procuring Contract Officer.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Need

Project Title: B500 Feeder 2B Wire Purchase

1. Objectives:

Provide and deliver a new #4/0 15KV 133% EPR tape shielded 220mil wire; 1,500 LF with cuts at 500 ft and 9 each indoor termination kits with stranded shield adapter, incuding two hole crimp terminals.

2. General Requirements:

Project includes, but is not limited to, the following work elements. The contractor shall furnish materials and incidentals. No alterations, additions, or deletions shall be made unless by prior approval of the government Project Manager and the government Procuring Contract Officer (PCO). The Contractor shall use SON requirements. Must be able to deliver Type MV-105 Cable is for use in aerial, direct burial, and underground duct installations as permitted by the NEC®. These cables are capable of operating continuously at a conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions, and are rated at 15,000 V, 133% insulation level (ungrounded system). This cable may be installed without the need for pulling lubricant.

3. Project Requirements

- The contractor shall procure and deliver a new wire with the minimum following characteristics or equal:

- Specifications

- Conductor:

- Annealed uncoated copper compact stranded per ASTM B-496.

- Strand Screen:

- Extruded semiconducting EPR strand screen. Meets or exceeds Electrical and physical requirements of

ICEA S-93-639/NEMA WC74, AEIC CS8, CSA C68.10 and UL 1072.

- Insulation:

- Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC

CS8,

- CSA C68.10 and UL 1072.

- Insulation Screen:

- Extruded semiconducting EPR insulation screen. Meets or exceeds electrical and physical requirements of

ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.10 and UL 1072.

- Shield:

- 5 mil bare copper tape helically applied with 12.5% nominal overlap.

The contractor shall deliver the #4/0 15KV 133% EPR tape shielded 220mil wire; 1,500 LF with cuts @ 500 ft, 9 each indoor termination kits including stranded shield adapter kits, and 9 each 4/0 two-hole crimp terminals to Offutt AFB, 106 Peacekeeper Dr. Building 301. The contractor shall provide manufacturer warranty on the equipment.