552-18-103 Renovate B116 Bid Dwgs_ 2022.12.13.pdf
PDF 20 MB Posted
- Solicitation number
- 36C25023B0013
About this file
This document provides details for a federal contract solicitation to renovate infrastructure for a history center building. The solicitation number is 36C25023B0013 and seeks to renovate Building 116 at a Veterans Health Administration facility within Veterans Integrated Service Network 10. Responses are due by December 13th, 2022. The awarding agency is the Department of Veterans Affairs Veterans Health Administration. The solicitation involves renovating infrastructure systems within the building but does not provide specifics on the scope of work required or pricing terms.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25023B0013 A00002.docx | DOCX document | |
| 36C25023B0013 A00001.docx | DOCX document | |
| 552-18-103 Renovate B116 Bid Specs_ 2022.12.13.pdf | ||
| Wage Determination 4.24.23.pdf | ||
| 36C25023B0013_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WISCONSIN
IOWA
K A
N S
A S
A V
E
McMAHON AVE.
KENTUCKY
C O
L O
R A
D O
A V
E
BROWN
IN
D
IA
N
A A
V E
A V E
MONUMENT
McMAHON
AVE.
AVE.
IL
L
IN
O
IS
A
V E
AVE.
NEW
O H
IO
YORK
KENTUCKY
S O
U T
H
AVE.
P E
N N
S Y
L V
A N
I A
AVE.
A V
E
O H
IO
WEST VIRGINIA
AVE.
A V E
AVE.
A V E
G E
T T
Y S
B U
R G
A V
E
WEST THIRD ST.
CEMETERY
MICHIGAN AVE
C O
N N
E C
T
IC
U T
A V
E
M A
IN
E
A V
E
DAKOTA AVE.
V E
R M
O N
T A
V E
O R
E G
O N
A V
E
NEW
M
EXIC
O P
LACE
S E R V
IC
E R
D
A V
E
N HAMPSHIRE
AVE.DELAWARE
DELAWARE
A V
E
N J
E R
S E
Y
B R O
W N
AVE.
CIRCLE
S E R V I C E
R D
R D
E
I C E
R V
S
R H
O D
E
IS
L A
N D
A V
E
MISSOURI AVEMICHIGAN AVE
E
D R
R
C I V
S E
M
IN
N E
S O
T A
A V
E
KENTUCKY AVE.
M A
R Y
L A
N D
A V
E
AVE.
WISCONSIN AVE.
TENN
ESSEE
P E
N N
S Y
L V
A N
IA
M
IN
N E
S O
T A
A V
E
HAWAII
PLACE
TEXAS AVE.
AVE.
MASSACHUSETTS BLVD.
E
A
B
C
D
118 400
131 26
34139
Liscum Dr.
Secondary
Supply
CEMETERY
CEMETERY
CEMETERY
LAKE
LAKE
CITY OF DAYTON
FIRE HOUSE NO. 17
RETENTION
POND
U.S. ROUTE 35
U.S . R
O U
TE 3
DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER
4100 WEST THIRD STREET
DAYTON, OHIO 45428
BUILDING SITE
EXTERIOR ELEVATION
INTERIOR ELEVATION
SEE 700 SERIES SHEETS
SECTION/DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TAG
COLUMN GRID
NOTE
WINDOW OPENING
DOOR OPENING
ROOM NAME
ROOM NUMBER
WALL TYPE
SEE SHEET A001
CEILING HEIGHT
FINISH DESIGNATION
X
10'-8"
X
X
XX.X-X
X
X
1/A101
X
XXXX
X
SIM
CONTRACTOR'S NAME
THE LIFE YOU SAVE MAY BE YOUR OWN
WITHOUT A LOST TIME ACCIDENT
0 0 0 DAYSHAS WORKED
THIS PROJECT
ON SAFETYin
ZERO
Department of Veterans Affairs
V
A R
IE
S
M
IN
4'-0"
Wood strips.
Blue
Blue outline with white interior.
Bracing. See Construction Sign Detail.
Red.
White.
Blue.
*FINAL LOCATION TO BE COORDINATED BY COR.
/8
DESIGNED AND SUPERVISED BY:
DEPARTMENT OF VETERANS
AFFAIRS WASHINGTON D.C.
Veterans Affairs Department of
8'-0"
M
IN
A
V E
R A
G E
V A
R
IE
S
M A
X
6"
NOTE:
Any seam in metal to be flat seam. Seams to be horizontal and occur between lines of lettering.
All lettering to be painted black with exception of project title, which is to be blue.
Final location to be coordinated with COR.
CL
Center to be white.
Surrounding to be blue.
Background to be painted white.
Border member painted black.
2" x 4" frame and braces in same plane.
Metal face white enamel
2" x 4" frame and braces in back.
Metal face. Stretch metal face tight, turn over frame and secure with flat head deformed nails.
Logos of Design Team to be provided by Architect
4" x 4" posts painted white.
ELEVATION SECTION
Renovate Infastructure B116
DESIGN TEAM
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Department of Veterans Affairs Medical Center
ARCHITECTURE PLANNING INTERIOR DESIGN
3131 NEWMARK DRIVE, SUITE 200
MIAMISBURG, OHIO 45342
937.461.3290 P
JOHN POE ARCHITECTS
HEAPY ENGINEERING
MECHANICAL ELECTRICAL PLUMBING ENGINEER
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
THP LIMITED INC.
STRUCTURAL ENGINEER
100 E. EIGHTH STREET
CINCINNATI, OH 45202
513.241.3222 P
513.241.2981 F
Dwg. of
LJB INC.
CIVIL ENGINEER
2500 NEWMARK DRIVE
MIAMISBURG, OH 45432
937.259.5000 P
937.259.5100 F
TERRACON
CONSULTANTS, INC.
ENVIRONMENTAL
611 LUNKEN PARK DRIVE
CINCINNATI, OH 45226
513.321.5816 P
513.321.4540 F
Renovate Infrastructure B116
12/09/2022
COVER SHEET
G001
CVTH
17007.00
552-18-103
Dayton, Ohio
Renovate Infrastructure B116
4100 West Third Street Dayton, Ohio 45428 PROJECT #: 552-18-103
N
CAMPUS PLAN
N
VICINITY MAP
DRAWING INDEX
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE, INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERAN AFFAIRS, TECHNICAL INFORMATION LIBRARY WEBSITE.
2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS) AND DEPARTMENT OF VETERANS AFFAIRS BARRIER FREE DESIGN GUIDE PG-18-13 WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS AFFAIRS TECHNICAL INFORMATION LIBRARY WEBSITE.
3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT EXISTING CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED WITH THE CONTRACTING
OFFICER'S REPRESENTATIVE.
4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH ADJACENT EXISTING SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT ARE DAMAGED DURING THE
COURSE OF DEMOLITION OR NEW WORK.
5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF NEW WORK, CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO REMAIN OR PROVIDE NEW
CONSTRUCTION TO MATCH EXISTING ADJACENT SURFACES TO REMAIN.
6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR TO ORDERING, FABRICATING OR INSTALLING NEW MATERIALS.
7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO BE INSTALLED AS PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE SPECIAL PROVISIONS TO
INSTALL EQUIPMENT THAT IS TOO LARGE TO FIT THROUGH FINISHED OPENINGS.
8. CONTRACTOR SHALL PROVIDE WOOD BLOCKING AT TOILET ACCESSORIES, HAND RAILS, BUMPER RAILS, SHELVING, CASEWORK, MOUNTING BRACKETS AND OTHER WALL MOUNTED ITEMS, AS INDICATED IN THE CONTRACT DOCUMENTS AND AS RECOMMENDED BY PRODUCT MANUFACTURERS. ALL WOOD BLOCKING SHALL BE FIRE RETARDANT TREATED.
9. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS SPECIFICALLY NOTED OTHERWISE. IF NO FINISH IS INDICATED AT A PARTICULAR SURFACE, CONTRACTOR SHALL
PROVIDE FINISH(S) AS INDICATED AT SIMILAR CONDITIONS.
10. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL SYSTEMS WHICH COMPLY WITH STATED CODES AND REGULATIONS. WHERE THE OMISSION OF A PART OR ELEMENT OF A SYSTEM WOULD RESULT IN THE NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM, CONTRACTOR SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.
11. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED WALLS SHALL BE SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF THE WALL.
GRAPHIC SYMBOLS
GENERAL CONSTRUCTION NOTES
S202 DETAILS
S202 DETAILS
S211 TRUSS REPAIR DETAILS
S211 TRUSS REPAIR DETAILS
S301 BRACING ELEVATIONS AND DETAILS
S301 BRACING ELEVATIONS AND DETAILS
FX001 LEGEND, INDEX, & FIRE SUPPRESSION DESIGN
NOTES
FX101 BASEMENT FIRE SUPPRESSION NEW WORK PLAN
FX102 NEW WORK PLANS
P001 LEGENDS, INDEX, & GENERAL NOTES
P002 SCHEDULE, DETAILS, & DIAGRAM
PD101 BASEMENT REMOVAL PLAN
PP101 BASEMENT NEW WORK PLAN
PP102 NEW WORK PLANS
PP103 ATTIC NEW WORK PLAN
PP104 ROOF NEW WORK PLAN
M001 LEGENDS & GENERAL NOTES
MD101 REMOVAL PLANS
MP101 FLOOR PLANS - PIPING
MS101 SITE PLAN
M501 DETAILS
M601 SCHEDULES, DIAGRAMS AND CONTROLS
E001 LEGENDS & GENERAL NOTES
ED101 REMOVAL PLANS
ES101 SITE PLAN
EL101 FLOOR PLANS - LIGHTING
EL102 ROOF PLAN - LIGHTNING PROTECTION
EP101 FLOOR PLANS - POWER & SYSTEMS
E501 MEDIUM VOLTAGE SINGLE-LINE DIAGRAM
E502 SINGLE-LINE DIAGRAM & SCHEDULE
E601 LIGHTING DESCRIPTIONS
G001 COVER SHEET
G100 CODE PLANS
G101 EXISTING CONDITIONS PHOTOGRAPHS
G102 EXISTING CONDITIONS PHOTOGRAPHS
G103 EXISTING CONDITIONS PHOTOGRAPHS
G104 EXISTING CONDITIONS PHOTOGRAPHS
G105 EXISTING CONDITIONS PHOTOGRAPHS
C100 EXISTING CONDITIONS
C200 DEMOLITION PLAN
C300 SITE/ UTILITY PLAN
C600 CONSTRUCTION DETAILS
AD101 DEMOLITION PLANS
A101 NEW WORK PLANS
A102 ROOF PLAN
A201 EXTERIOR ELEVATIONS
A301 BUILDING SECTIONS
A501 WALL SECTION, ENLARGED ELEVATION
A502 DETAILS
A503 DETAILS
A504 DETAILS
A505 STAIR DETAILS
A601 DOOR SCHEDULE AND WINDOW DETAILS
S001 GENERAL STRUCTURAL NOTES
S001 GENERAL STRUCTURAL NOTES
S002 TYPICAL DETAILS
S002 TYPICAL DETAILS
S101 PHASING PLANS
S101 PHASING PLANS
S102 STRUCTURAL RENOVATION PLANS
S102 STRUCTURAL RENOVATION PLANS
S201 DETAILS
S201 DETAILS
N.T.S.Scale:
SAFETY SIGN
N.T.S.Scale:
CONSTRUCTION SIGN
Revision s
Date
DN
ELECTRICAL
DATA
SECUITY
Fire Alarm Panel
STAIR
ELEV EQUIP
ELEVATOR
STAIR
WATER
ROOM
76'-0"
50'- 0"
UP
UP
UP
MECHANICAL
MECHANICAL
FUTURE
ASSEMBLY
'B'
FUTURE
ASSEMBLY
'A'
FUTURE
BUSINESS
EXIT
EXIT
STAIR
STAIR
LOBBY
82'-0
74'-6" 72'-6"
68'-6"
Room
FUTURE
BUSINESS
ELEC CL
201 ELEVATOR
STAIR
STAIR
FUTURE
BUSINESS
51'-6"
65'-0"
2-HR Fire Barrier
Means of Egress
Existing Wall to Remain
New Wall
Fire Extinguisher
Egress Travel Path Actual Travel Dist.
STAIR
DN DN
MECHANICAL PLATFORM
MAINTENANCE CATWALK MAINTENANCE CATWALK
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. of
Renovate Infrastructure B116
12/09/2022
CODE PLANS
G100
SOTH
17007.00
552-18-103
Dayton, Ohio
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
Scale: 1/8" = 1'-0"
BASEMENT - CODE PLAN
Scale: 1/8" = 1'-0"
FIRST FLOOR - CODE PLAN
Scale: 1/8" = 1'-0"
SECOND FLOOR - CODE PLAN
Dayton Building 116 Renovation Code Bullets
2021 NFPA 101 Life Safety Code Review
• 6.1.2 - Assembly (Future) - See Chapter 12.
• 6.1.11 - Business (Future) - See Chapter 38.
• 6.1.14 - Multiple Occupancies
• Mixed occupancies
• 6.1.14.3.2 The building shall comply with the most restrictive requirements of the occupancies involved, unless separate safeguards are approved.
• 6.1.14.1.3- Where incidental to another occupancy, areas used as follows shall be permitted to be considered part of the predominant occupancy and shall be subject to the provisions of the Code that apply to the predominant occupancy
• 6.2.2. - Hazard classification: Ordinary
Chapter 7 – Means of Egress
• 7.1.3.1 – Exit Access Corridors , Corridors used as exit access and serving an area having an occupant load exceeding 30 shall be separated from other parts of the building by not less than one hour ire resistance rating.
• 7.1.3.2.1 – Exit Separation, Where this code requires an exit to be separated from other parts of the building, the separating construction shall meet the requirements of 8.2 and the following:
(1) The separation shall have a minimum 1-hour fire resistance rating where the exit connects three or fewer stories.
• 7.1.4.1 – Interior Wall & Ceiling Finish in Exit Encl: Class A or B per 10.2.
• 7.1.4.2 – Interior Floor Finish in Exit Encl: Class II per 10.2.
• 7.2.2.31.2- Each stair, platform, and landing, not including handrails, and existing stairs, in buildings required in the Code to be Type I or Type II construction shall be non-combustible material throughout.
• 7.2.12.1.1 – An Areas of Refuge used as part of the required accessible means of egress in accordance with 7.5.4 consisting of a story in a building that is protected throughout by an automatic sprinkler shall meet the following criteria:
• Each elevator landing shall be provided with a two-way communication system between the elevator landing and the fire command center.
• Directions for use, instructions for summoning assistance and written identification of the location shall be posted adjacent to the communication system.
• The two way communication shall include both audible and visible signals.
• 7.2.13.3 – Every floor served by the elevator shall have an elevator lobby. Barriers forming the elevator lobby shall have a minimum 1-hour fire resistive rating and shall be arranged as a smoke barrier per 8.5
• 7.3.1 – Occupant Load:
Future Interior Build-out - Not included in this project Phase
Floor 1:
Assembly-A: 1,198 s.f. @ 15 sf/occ. = 80 occup. (Exhibit Space) Business: 680 s.f. @ 100 sf/occ = 7 occup.
Assembly-B: 1,348 s.f. @ 15 sf/occ. = 90 occup. (Lecture Space)
Floor 2:
Business: 3,416 s.f. @ 100 sf/occ. = 35 occup.
N.T.S.Scale:
Code Legend
Scale: 1/8" = 1'-0"
ATTIC - CODE PLAN
• 7.3.2.2 – Max. projection within means of egress on ea. side: 4-1/2” (38” hgt. max.).
• 7.4.1.1 – Min. number of means of egress from any story shall not be less than 2, except under one of the following conditions:
1. A single means of egress shall be permitted where permitted in Chapters 11 thru 43. See 39.2.4.6
• 7.4.1.6.1 – Each Elevator landing and lobby shall have access to at least one exit.
• 7.5.1.2.2 – Corridors not req’d. to be fire-rated shall be permitted to discharge into open floor plan areas.
• 7.5.1.3.3 – Remoteness of exits – Bldgs. protected by AFSS per 9.7, Min. separation distance between 2 exits = 1/3 max. overall diag.
dimension of the area or bldg. served.
• 7.5.4.1. – Areas accessible to people with severe mobility impairment , other than in existing buildings shall not have less than two accessible means of egress. , unless otherwise provided in 7.5.4.1.2 through 7.5.4.1.4.
• 7.5.4.1.1 – Access within the allowable travel distance shall be provided to not less than one accessible area of refuge or one accessible exit providing an accessible route to an exit discharge.
• 7.5.4.2.2 – The requirement of 7.5.4.2 shall not apply to a building protected throughout by an approved supervised automatic sprinkler system in accordance with section 9.7.
• 7.5.4.9 – An area of refuge used as part of a required accessible means of egress shall be in accordance with 7.2.12
• A.7.6 – Maximum travel distance with an approved supervised automatic sprinkler system is 250 ft
• 7.7.2– Exit discharge through interior building spaces is allowed.
• 7.12.1(1) – Mechanical equip. rms., common path of travel = 100’ max.
Chapter 8 – Features of Fire Protection
• 8.2.1. – Construction Type: III(200), Sprinkled (noncombustible)
Allowable number of stories: ≥4 Actual number of stories: 3
• Openings thru fire barriers for air-handling ductwork shall be protected per 9.2.1.
• 8.3.4.2 – Min Fire Protection for Openings in Fire-rated Assemblies:
Component Walls Fire Drs Fire Window Elevator hoistways: 2 hr 1-1/2 hr NP Vert. shafts (stairs, exits):2 hr 1-1/2 hr NP
1 hr 1 hr NP Fire Barriers: 2 hr 1-1/2 hr NP
1 hr 3/4 hr NP Horiz. Exits: 2 hr 1-1/2 hr NP Smoke Barriers: 1 hr 1/3 hr 3/4 hr
• 8.3.5.1 – Firestop Systems – Penetrations that pass thru a barrier shall be protected by a firestop system or device.
• 8.3.5.7 – Openings thru fire barriers for air-handling ductwork shall be protected per 9.2.1.
• 8.4.3.5 – Smoke Partition doors shall be self or auto-closing per 7.2.1.8. Exception: see 19.3.6.3.11).
• 8.5.3 – A Fire Barrier shall be permitted to be used as Smoke Barrier per Section 8.5.
• 8.6.1 Floor Smoke Barriers – Every floor that separates stories in a bldg. shall be constructed as a smoke barrier per 8.5 and shall be permitted opg’s. per 8.6.6 thru 8.6.8.
• 8.6.4.1 – Shafts shall be enclosed at lowest or highest level of the shaft per 8.6.5.
• 8.6.5 – Shafts- Req’d Fire Rating:
Connecting 4 or more stories: 2-hr Fire Barrier.
Other new shaft enclosures: 1-hr Fire Barrier.
8.7.1.3 – Special Hazard Protection – Doors: min. ¾ hr fire rated, self or auto-closing per 7.2.1.8
Chapter 9 – Building Service and Fire Protection Equipment
• 9.4.1 – An elevator, other than an elevator in accordance with 7.2.13, shall not be considered a component in a required means of egress but shall be permitted as a component in an accessible means of egress.
• 9.6.1.3 – Fire Alarm System req’d for life safety shall be per NFPA70.
• 9.6.3.1 – Occupant notification shall be provided per 9.6.3 and 39.3.4.3.
• 9.6.4.1 – Emergency Forces notification req’d per 9.6.4 and 39.3.4.
• 9.6.5.1 – Fire safety functions shall be installed per NFPA 72 as req’d per 9.6.5 and 39.3.4.
• 9.6.7.1 – Alarm annunciation is required per 9.6.7 and 39.3.4.3.
• 9.7.1.1 – Supervised automatic sprinkler system as req’d by 9.7.1 and 39.3.4shall comply with NFPA 13.
Chapter 10 – Interior Finish, Contents, and Furnishings
• 10.2.3 – Interior Wall or Ceiling Finish – Class A, B, or C shall be classified based on ASTM E 84.
• 10.2.3.4 – Wall and Ceiling – Classifications characteristics:
1. Class A: Flame spread: 0-25; Smoke dev.: 0-450.
2. Class B: Flame spread: 26-75; Smoke dev.: 0-450.
3. Class C: Flame spread: 76-200; Smoke dev.: 0-45
• 10.2.7.3 – Interior Floor Finish –shall be classified based on NFPA 253 or ASTM E 648.
• 10.2.3.4 – Interior Floor – Classifications characteristics:
1. Class I: Rad flux: min .45 W/cm².
2. Class II: Rad flux: min .22 W/cm², and max. .45 W/cm².
• 10.2.8.1 – Wall and Ceiling finishes, where sprinkled:
Class C permitted in any location where Class B is req’d.
Class B permitted in any location where Class A is req’d.
• 10.2.8.2 – Floor finishes, where sprinkled:
1. Class II permitted in any location where Class I is req’d.
2. No critical rad. flux permitted in any location where Class II is req’d.
CODE NOTES
62'-0" 85'-0"
Revision
2.56
2.34
2.362.36
2.75
2.00
2.34
2.362.36
2.75
2.34
2.64
2.56
2.34
2.12
2.58 2.002.00
2.34
2.56
2.00
2.39
2.36
2.28
2.36
2.34
2.452.64
2.392.39
2.342.34
2.392.39
2.36
2.392.39
2.36
2.342.34
2.36
2.39
2.342.34
2.362.36
2.39
2.362.362.36
2.34
B1
B14
B2
B4B5
B6
B7
B8B9
B10
B11
B12
B3
B16
B13
B15
2.36
2.34
2.36
2.75
2.34
2.56
2.75
2.34
2.75
2.56
2.34
2.00
2.002.00
2.56
2.34
2.75
2.36
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. of
Renovate Infrastructure B116
12/09/2022
EXISTING CONDITIONS
PHOTOGRAPHS
G101
ACTH
17007.00
552-18-103
Dayton, Ohio
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
N.T.S.Scale:1
IMAGE B-1
N.T.S.Scale:2
IMAGE B-2
N.T.S.Scale:3
IMAGE B-3
N.T.S.Scale:4
IMAGE B-4
N.T.S.Scale:5
IMAGE B-5
N.T.S.Scale:6
IMAGE B-6
N.T.S.Scale:7
IMAGE B-7
N.T.S.Scale:8
IMAGE B-8
N.T.S.Scale:9
IMAGE B-9
N.T.S.Scale:10
IMAGE B-10
N.T.S.Scale:11
IMAGE B-11
N.T.S.Scale:12
IMAGE B-12
KEY NOTES
2.00 Remove all inactive electrical, telephone and data equipment and back panels. Verify status with VA.
2.12 Remove existing door and frame.
2.28 Remove existing wood stair, structure and handrails and wall below.
2.34 Remove existing wood flooring, sleeper system, supporting structure, and any systems supported from floor structure. See Detail 5 on Sheet AD101 for existing floor construction and Structural Sheet S101 for Phasing Plans.
2.36 Remove existing masonry wall and foundation. Remove walls down to top of slab. Existing slab, soil and rock below contains asbestos. Abatement contractor to remove from top of slab down to foundation / footing.
2.39 Remove shoring as floor removal permits; See Structural
drawings.
2.45 Existing steel column to be removed. Salvage decorative
column and deliver to owner.
2.56 Existing windows at basement to be removed and opening
filled with CMU. See Detail 3 on Sheet A504.
2.58 Remove existing concrete steps and foundation. Patch
concrete slab as required. Existing slab and soil below contains asbestos. Abatement contractor to remove concrete from top of slab down to foundation.
2.64 Remove all inactive utility infrastructure penetrating exterior wall and close opening with masonry prior to waterproofing basement walls.
2.75 Remove existing concrete slab as required for new column and wall foundations. Patch and repair slab as required. See Structural. Existing slab and soil below contains asbestos.
Abatement contractor to remove from top of slab down to depth of new footings.
1. All new materials that replace existing shall match existing profiles and dimensions, unless noted otherwise.
2. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.
3. See structural drawings for demoliton and new work phasing.
4. See specifications for types and locations of hazardous materials and requirements for their removal.
5. Salage and stack all existing whole bricks from demolition phase and store on site to be reused for exterior facade repairs.
GENERAL NOTES
N.T.S.Scale:13
IMAGE B13
N.T.S.Scale:14
IMAGE B14
N.T.S.Scale:15
IMAGE B15
N.T.S.Scale:16
IMAGE B16
Revision
2.81
2.282.28
2.37
2.21
2.36
2.45
2.34
2.212.21
2.34
2.212.21
2.81
5.02
2.45
2.21
2.100
2.36
2.81
2.34
2.212.21
2.802.802.80
2.21
2.61
2.81
2.36
2.80
2.212.21
2.34
2.21
2.802.80
2.37
2.34
2.922.92
2.81
2.21
2.32
2.34
2.32
2.21
2.382.38
2.212.21
2.81
2.212.21
2.34
2.21
2.81
2.552.55
2.34
2.55
2.81
2.212.21
2.34
2.802.80
2.21
2.80
2.55
5.025.02
7.767.767.777.77
1-1
1-2
1-3
1-4
1-51-6
1-10
1-12
1-13
1-14
1-11
1-8
1-9
1-7
2.552.55
2.34
2.81
2.952.95
2.212.212.21
2.34
2.81
2.81
2.212.21
2.81
2.212.212.21
2.802.802.80
2.34
2.21
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. of
Renovate Infrastructure B116
12/09/2022
EXISTING CONDITIONS
PHOTOGRAPHS
G102
ACTH
17007.00
552-18-103
Dayton, Ohio
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
N.T.S.Scale:1
IMAGE 1-1
KEY NOTES
2.21 Existing wood sash and sill to be removed at all windows.
Existing wood frame and interior trim to remain. Remove all paint from wood trim and sand smooth in preparation for new sash. Paint. Protect during construction. See Details 3 and 4 on Sheet A503.
2.28 Remove existing wood stair, structure and handrails and wall below.
2.32 Remove existing wood frame wall.
2.34 Remove existing wood flooring, sleeper system, supporting structure, and any systems supported from floor structure. See Detail 5 on Sheet AD101 for existing floor construction and Structural Sheet S101 for Phasing Plans.
2.36 Remove existing masonry wall and foundation. Remove walls down to top of slab. Existing slab, soil and rock below contains asbestos. Abatement contractor to remove from top of slab down to foundation / footing.
2.37 Remove and salvage safe door and frame. Deliver to owner.
2.38 Remove existing partition.
2.45 Existing steel column to be removed. Salvage decorative
column and deliver to owner.
2.55 Remove existing wood stud wall and windows. Some walls
have ACM Transite panels. See Asbestos Abatement specifications for removal requirements.
2.61 Remove existing security mesh over existing window. Patch and repair wood frame and adjacent masonry as required.
(Typical of 2)
2.80 Existing interior trim to remain. Protect during construction.
2.81 Remove First Floor existing metal panel ceiling and cornice finish, plaster and lath and wood ceiling supports.
2.92 Remove existing safe concrete walls, floor & ceiling.
2.95 Remove 'red' wall plaster with ACM. See Asbestos Abatement specifications for removal requirements.
2.100 Carefully remove and salvage existing wood door, frame and trim and turn over to owner.
5.02 Aluminum finial - Color P-3, were previously fabricated & shall be provided by owner. Contractor to paint and install in this project. See Detail 7 and 8 on Sheet A503. Typical of 18.
7.76 Roof drains, pans, and strainers provided for previous, unrealized project are available for cotractors use on this project.
7.77 Steel angel cornice supports provided for previous, unrealized project are available for contractors use on this project at cornice manufacturers direction.
1. All new materials that replace existing shall match existing profiles and dimensions, unless noted otherwise.
2. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.
3. See structural drawings for demoliton and new work phasing.
4. See specifications for types and locations of hazardous materials and requirements for their removal.
5. Salage and stack all existing whole bricks from demolition phase and store on site to be reused for exterior facade repairs.
GENERAL NOTES
N.T.S.Scale:2
IMAGE 1-2
N.T.S.Scale:3
IMAGE 1-3
N.T.S.Scale:4
IMAGE 1-4
N.T.S.Scale:5
IMAGE 1-5
N.T.S.Scale:6
IMAGE 1-6
N.T.S.Scale:7
IMAGE 1-7
N.T.S.Scale:8
IMAGE 1-8
N.T.S.Scale:9
IMAGE 1-9
N.T.S.Scale:10
IMAGE 1-10
N.T.S.Scale:15
IMAGE 1-15
N.T.S.Scale:16
IMAGE 1-16
N.T.S.Scale:11
IMAGE 1-11
N.T.S.Scale:12
IMAGE 1-12
N.T.S.Scale:13
IMAGE 1-13
N.T.S.Scale:14
IMAGE 1-14
Revision
2.83
2.34
2.212.21
2.802.80
2.21
2.80
2.32
2.83
2.32
2.34
2.83
2.34
2.802.80
2.212.21
2.80
2.21
2.83
2.32
2.34
2.83
2.34
2.21
2.80
2.83
2.34
2.34
2.32
2.28
2.83
2.32 2.28
2-1 2-2
2-3
2-4
2-5
2-6
2-7
2-8
2-9
2-10
2-11
2-12
2.97
2.432.43
2.34
2.83
2.83
2.272.27
2.34
2.80
2.21
2.34
2.32
2.83
2.80
2.21
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. of
Renovate Infrastructure B116
12/09/2022
EXISTING CONDITIONS
PHOTOGRAPHS
G103
ACTH
17007.00
552-18-103
Dayton, Ohio
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
N.T.S.Scale:1
IMAGE 2-1
N.T.S.Scale:2
IMAGES 2-2
N.T.S.Scale:3
IMAGES 2-3
N.T.S.Scale:4
IMAGE 2-4
N.T.S.Scale:5
IMAGE 2-5
N.T.S.Scale:6
IMAGE 2-6
N.T.S.Scale:11
IMAGE 2-11
KEY NOTES
2.21 Existing wood sash and sill to be removed at all windows.
Existing wood frame and interior trim to remain. Remove all paint from wood trim and sand smooth in preparation for new sash. Paint. Protect during construction. See Details 3 and 4 on Sheet A503.
2.27 Remove existing ladder.
2.28 Remove existing wood stair, structure and handrails and wall below.
2.32 Remove existing wood frame wall.
2.34 Remove existing wood flooring, sleeper system, supporting structure, and any systems supported from floor structure. See Detail 5 on Sheet AD101 for existing floor construction and Structural Sheet S101 for Phasing Plans.
2.43 Existing concrete floor and vault structure to remain.
2.80 Existing interior trim to remain. Protect during construction.
2.83 Remove existing second floor plaster ceiling finish and lath only. Existing floor joists will be removed strategically in phased sequential order to be replaced with new structural floor framing. See Structural Dwg S101.
2.97 Existing recessed ducts / chases in exterior masonry walls shall be encapsulated to prevent disturbance of possible asbestos containing duct wrap. All encapsulated panels shall be labeled appropriately and encapsulated per Asbestos Abatement specifications. See Detail 5 on Sheet A504.
1. All new materials that replace existing shall match existing profiles and dimensions, unless noted otherwise.
2. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.
3. See structural drawings for demoliton and new work phasing.
4. See specifications for types and locations of hazardous materials and requirements for their removal.
5. Salage and stack all existing whole bricks from demolition phase and store on site to be reused for exterior facade repairs.
GENERAL NOTES
N.T.S.Scale:12
RECESSED DUCT
N.T.S.Scale:7
IMAGE 2-7
N.T.S.Scale:8
IMAGE 2-8
N.T.S.Scale:9
IMAGE 2-9
N.T.S.Scale:10
IMAGE 2-10
Revision
2.63
2.49
2.98
2.98
2.482.48
2.63
2.48
2.63
2.482.482.48
2.632.63
2.49
2.83
2.482.482.48
2.83
2.632.632.63
2.98
2.49
2.83
7.24
7.37
7.35
2.49
2.63
2.632.632.63
2.63
2.83
A-1A-2
A-3
A-4
A-5
A-6
A-7
A-8 A-9
A-10
A-11
A-12
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. of
Renovate Infrastructure B116
12/09/2022
EXISTING CONDITIONS
PHOTOGRAPHS
G104
ACTH
17007.00
552-18-103
Dayton, Ohio
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
N.T.S.Scale:5
IMAGE A-5
N.T.S.Scale:6
IMAGE A-6
KEY NOTES
2.48 Remove existing horizontal masonry chimney and associated wood support.
2.49 Remove existing wood plank catwalk and associated wood
support framing.
2.63 Existing heavy timber roof trusses to remain. Protect during construction. See Structural Sheet S211 for repair details.
2.83 Remove existing second floor plaster ceiling finish and lath only. Existing floor joists will be removed strategically in phased sequential order to be replaced with new structural floor framing. See Structural Dwg S101.
2.98 Remove existing ornamental light housing and rings in Second Floor ceiling. Salvage and deliver to owner.
7.24 Existing 1x roof deck to remain. Re-nail deck as indicated in specifications.
7.35 Existing mansard roof/wall framing to remain.
7.37 Existing 1x mansard roof/wall deck to remain. Re-nail deck as indicated in specifications.
1. All new materials that replace existing shall match existing profiles and dimensions, unless noted otherwise.
2. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.
3. See structural drawings for demoliton and new work phasing.
4. See specifications for types and locations of hazardous materials and requirements for their removal.
5. Salage and stack all existing whole bricks from demolition phase and store on site to be reused for exterior facade repairs.
GENERAL NOTES
N.T.S.Scale:7
IMAGE A-7
N.T.S.Scale:8
IMAGE A-8
N.T.S.Scale:9
IMAGE A-9
N.T.S.Scale:10
IMAGE A-10
N.T.S.Scale:11
IMAGE A-11
N.T.S.Scale:12
IMAGE A-12
N.T.S.Scale:1
IMAGE A-1
N.T.S.Scale:2
IMAGE A-2
N.T.S.Scale:3
IMAGE A-3
N.T.S.Scale:4
IMAGE A-4
Revision
2.222.232.19
Typ.
2.56
Typ.
2.212.21
2.782.78Typ. Typ. 2.03
2.11
2.04
2.21
Typ.
2.61
2.79
2.21
2.78
2.46
2.22
Typ.
2.19
2.22
2.11
2.04
2.21
Typ.
2.56
2.41
2.21
2.78 Typ.
2.46
2.922.93
2.04
2.22
2.14
2.11
2.03
2.16
2.222.222.22
2.46
2.11
2.17
2.16
2.18
2.03
2.17
2.19
2.11
2.22
2.04
2.042.042.04
2.03
2.16
2.16
2.22
2.46
2.23
2.16
2.03
2.14
2.04
2.46
2.03
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. of
Renovate Infrastructure B116
12/09/2022
EXISTING CONDITIONS
PHOTOGRAPHS
G105
CVTH
17007.00
552-18-103
Dayton, Ohio
N.T.S.Scale:1
SOUTH ELEVATION
N.T.S.Scale:2
EAST ELEVATION - WEST SIMILAR
N.T.S.Scale:3
NORTH ELEVATION
KEY NOTES
N.T.S.Scale:4
LOWER MANSARD ROOF
N.T.S.Scale:5
SLATE PATTERN
N.T.S.Scale:6
UPPER ROOF
N.T.S.Scale:8
ROOFTOP VENTILATOR
N.T.S.Scale:9
GUTTER AND CORNICE FROM ABOVE
N.T.S.Scale:10
GUTTER AND CORNICE FROM BELOW
N.T.S.Scale:7
UPPER CORNICE
N.T.S.Scale:12
DORMER TYPE A
N.T.S.Scale:11
DORMER TYPE B
2.03 Existing metal upper fascia/cornice removed in previous
project. Remove existing temporary membrane coving gap between the mansard and flat roof. See Details on Sheet A503 for new upper fascia/cornice construction.
2.04 Existing metal gutter/lower cornice, fasteners and accessories removed during previous project. Remove all existing remaining wood framing. See Details on Sheet A502 for newgutter/lower cornice construction. Steel frames to support cornice have been fabricated and are stored on site.
Coordinate installation of existing frames with COR
2.11 Existing slate roof to be removed and replaced with new slate to match existing. See Details on Sheet A501 for new shingle layout.
2.14 Existing metal corner trim removed in previous project. See Elevation Detail on Sheet A501 for new corner trim flashing.
2.16 Existing attic dormer metal roofing to be removed and replaced with new. See Details 1 and 2 on Sheet A503.
2.17 Existing metal roof to be removed and replaced with new
membrane. See Key Note 7.01 on Sheets A102 and A201.
2.18 Existing roof drain to be removed and replaced with new. See Detail 2 on Sheet A501.
2.19 Existing metal roof ventilator to remain and be refinished. See Key Note 2.09 on Sheets A102 and A201.
2.21 Existing wood sash and sill to be removed at all windows.
Existing wood frame and interior trim to remain. Remove all paint from wood trim and sand smooth in preparation for new sash. Paint. Protect during construction. See Details 3 and 4 on Sheet A503.
2.22 Existing Dormer (Type A) and surround to remain and be
refinished. See Detail 2 on Sheet A503.
2.23 Existing Dormer (Type B) and surround to remain and be
refinished. See Detail 1 on Sheet A503.
2.41 Remove existing handrails, concrete stair, concrete landing, and concrete retaining wall. See civil for back fill information.
2.46 Existing dormer wood sash to be removed at all attic windows.
Existing exterior trim to remain. Remove all paint from wood trim and sand smooth in preparation for new sash and paint.
Protect during construction. See Details 1 and 2 on Sheet A503.
2.56 Existing windows at basement to be removed and opening
filled with CMU. See Detail 3 on Sheet A504.
2.61 Remove existing security mesh over existing window. Patch and repair wood frame and adjacent masonry as required.
(Typical of 2)
2.78 Remove existing plywood infill at wood windows.
2.79 Existing downspouts removed in previous project. Remove any remaining existing downspout wall brackets. See Key Note
7.09 on Sheet A201 for new downspouts.
2.92 Remove existing safe concrete walls, floor & ceiling.
2.93 Remove existing exterior wood door, transom and frame. See Schedule and Details on Sheet A601.
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
1. All new materials that replace existing shall match existing profiles and dimensions, unless noted otherwise.
2. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.
3. See structural drawings for demoliton and new work phasing.
4. See specifications for types and locations of hazardous materials and requirements for their removal.
5. Salage and stack all existing whole bricks from demolition phase and store on site to be reused for exterior facade repairs.
GENERAL NOTES
Revision
FF= 955.37
(937) 259-5000 tel (937) 259-5100 fax LJBinc.com
Miamisburg, OH 45342
LJB Inc. 2500 Newmark Drive
17007.00
552-18-103
INFRASTRUCTURE B116
RENOVATE
08.17.2022
Dayton, Ohio
Revisions Date
PSB JAH
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number
Dwg. of o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
Management and Facilities
Construction
Office of
XX
JPA Project No.
S T
A
TE OF O
H
I O
P R
O F
E
S S
IONAL
E N
G I
N E
E R
R
E
GISTERE
D
E51255
BATTAGLIA
S.
PETER
KENTUCKY AVE
N E
W
H A
M P S
H
IR
V
E N
U E
N
GRAPHIC SCALE
0 10 20
- STORM LINE
- ELECTRIC LINE
- COMMUNICATIONS LINE
- GAS LINE
- SANITARY LINE
- TREE
- SHRUB
- STORM STRUCTURE
- FIRE HYDRANT
- WATER VALVE
- SANITARY MANHOLE
- SIGN
- ELECTRIC BOX
- ELECTRIC MANHOLE
- TELEPHONE MANHOLE
- IRON PIN
- MONUMENTATION
- LIGHT POLE
- FENCE
- BOLLARD
- PULL BOX
- STRAIN POLE
LEGEND:
- POWER/ COMM. POLE
- STORM MANHOLE
- ELECTRIC TRANSFORMER
- FLAG POLE
- LIGHTING
- WATER LINE
THE LOCATIONS OF UNDERGROUND FACILITIES SHOWN ON THIS PLAN
ARE BASED ON FIELD SURVEYS AND LOCAL UTILITY COMPANY RECORDS.
IT SHALL BE THE CONTRACTOR'S FULL RESPONSIBILITY TO CONTACT
THE VARIOUS UTILITY COMPANIES TO LOCATE THEIR FACILITIES
PRIOR TO STARTING CONSTRUCTION. NO ADDITIONAL COMPENSATION
SHALL BE PAID TO THE CONTRACTOR FOR DAMAGE AND REPAIR TO
DIG PERMIT ON SITE DURING WORK OPERATIONS.
CONTRACTOR SHALL BE RESPONSIBLE FOR HAVING A COPY OF THE APPROVED
FROM THE MEDICAL CENTER PER STANDARD OPERATING PROCEDURE 32 DIG PERMITS.
BEFORE DIGGING CONTRACTOR SHALL OBTAIN AN APPROVED DIG PERMIT
CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING MARKINGS.
BEFORE DIGGING CONTRACTOR SHALL HIRE A UTILITY LOCATE SERVICE.
THESE FACILITIES CAUSED BY HIS WORK FORCE.
NOTE:
ALL CURB RADII ARE GIVEN TO FACE-OF-CURB.
ARE GIVEN FROM FACE-OF-CURB TO FACE-OF-CURB.
ALL LINEAR DIMENSIONS, AND SPOT GRADES
CONSTRUCTION LAYOUT NOTES
EXISTING CONDITIONS
SHEET NOTES
INV 6" (N)= 949.63
INV 6" (S)= 949.68
TOP= 953.78
SAN MH
INV 6" (W)= 951.31
INV 4" (E)= 950.74
INV 6" (E)= 949.51
INV 4" (S)= 949.66
TOP= 953.56
STM MH
INV= FULL OF DIRT
TOP= 953.11
CB
INV 6" (W)= 950.34
INV 4" (SW)= 951.34
TOP= 952.69
CB
INV 8" (N)= 945.68
INV 8" (NW)= 945.68
INV 6" (S)= 947.63
INV 12" (E)= 945.53
TOP= 952.98
STM MH
INV. 12" RCP (W)=943.6
INV. 12" RCP (SE)=943.75
TOP=947.55
CI
INV. 18" RCP (S)=942.55
INV. 12" RCP (NW)=942.55
TOP=947.55
CI
TOP=947.83
STMH
C100
- STEAM LINE
LOCATION SERVICE
LOCATED BY UTILITY
UNKNOW UTILITY AS
- CLEANOUT
EXISTING PLANS
STRUCTURE FROM
UNKNOW UNIDENTIFIED
FF= 955.37
EXISTING BUILDING
S t e a m
T u n n e l
S T
E A
M
S T
E A
M
S T
E A
M
STEAM
Miamisburg, OH 45342
LJB Inc. 2500 Newmark Drive
17007.00
552-18-103
INFRASTRUCTURE B116
RENOVATE
08.17.2022
Dayton, Ohio
Revisions Date
PSB JAH
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number
Dwg. of o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
Management and Facilities
Construction
Office of
XX
JPA Project No.
S T
A
TE OF O
H
I O
P R
O F
E
S S
IONAL
E N
G I
N E
E R
R
E
GISTERE
D
E51255
BATTAGLIA
M P S
H
E N
U E
N
GRAPHIC SCALE
0 10 20
- STORM LINE
- ELECTRIC LINE
- COMMUNICATIONS LINE
- GAS LINE
- SANITARY LINE
- TREE
- SHRUB
- STORM STRUCTURE
- FIRE HYDRANT
- WATER VALVE
- SANITARY MANHOLE
- SIGN
- ELECTRIC BOX
- ELECTRIC MANHOLE
- TELEPHONE MANHOLE
- IRON PIN
- MONUMENTATION
- LIGHT POLE
- FENCE
- BOLLARD
- PULL BOX
- STRAIN POLE
LEGEND:
- POWER/ COMM. POLE
- STORM MANHOLE
- ELECTRIC TRANSFORMER
- FLAG POLE
- LIGHTING
- WATER LINE
THE LOCATIONS OF UNDERGROUND FACILITIES SHOWN ON THIS PLAN
ARE BASED ON FIELD SURVEYS AND LOCAL UTILITY COMPANY RECORDS.
IT SHALL BE THE CONTRACTOR'S FULL RESPONSIBILITY TO CONTACT
THE VARIOUS UTILITY COMPANIES TO LOCATE THEIR FACILITIES
PRIOR TO STARTING CONSTRUCTION. NO ADDITIONAL COMPENSATION
SHALL BE PAID TO THE CONTRACTOR FOR DAMAGE AND REPAIR TO
DIG PERMIT ON SITE DURING WORK OPERATIONS.
CONTRACTOR SHALL BE RESPONSIBLE FOR HAVING A COPY OF THE APPROVED
FROM THE MEDICAL CENTER PER STANDARD OPERATING PROCEDURE 32 DIG PERMITS.
BEFORE DIGGING CONTRACTOR SHALL OBTAIN AN APPROVED DIG PERMIT
CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING MARKINGS.
BEFORE DIGGING CONTRACTOR SHALL HIRE A UTILITY LOCATE SERVICE.
THESE FACILITIES CAUSED BY HIS WORK FORCE.
CONSTRUCTION LAYOUT NOTES
SHEET NOTES
1 SIDEWALK TO BE REMOVED.
2 TREE TO BE REMOVED.
DEMOLITION PLAN
AND RELOCATED.
TRANSFORMER TO BE REMOVED
REQUIRED AS PER OSHA REGUALTIONS.
AND FOUNDATION DRAINS. SHORING
EXCAVATION FOR WATER PROOFING
CONTRACTOR TO PROVIDE SAFE
5 BASEMENT ACCESS TO BE REMOVED.
C200
- STEAM LINE
- CLEANOUT
AS REQUIRED
SUPPORT DURING CONSTRUCTION
STORM STRUCTURE TO REMAIN
8 8
STORM LINE TO BE REMOVED
STORM STRUCTURE TO BE REMOVED
9 9
AND REPLACED
STORM STRUCTURE TO BE REMOVED
CONSTRUCTION OF WATER MAIN.
PAVEMENT TO BE REPLACED POST
FOR WATER MAIN INSTALLATION.
WALK TO BE REMOVED6
11 WATER LINE TO BE REMOVED.
MATERIALS.
PROVIDING TEMPORARY FENCING AROUND ANY
WITH COR. CONTRACTOR IS REPSONSIBLE FOR
CONTRACTOR TO COORDINATE EXACT LOCATION
MATERIALS SHALL BE ADJACENT TO BUILDING 116.
LOCATION OF LAY DOWN AREA FOR CONSTRUCTOIN
TOP=947.83
STMH
TOP=947.55
CI
INV. 12" RCP (W)=943.6
INV. 12" RCP (SE)=943.75
TOP=947.55
CI
FF= 955.37
EXISTING BUILDING
S t e a m u n n e l
S T
E A
M
S T
E A
M
S T
E A
M
STEAM
Miamisburg, OH 45342
LJB Inc. 2500 Newmark Drive
17007.00
552-18-103
INFRASTRUCTURE B116
RENOVATE
08.17.2022
Dayton, Ohio
Revisions Date
PSB JAH
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number
Dwg. of o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
Management and Facilities
Construction
Office of
XX
JPA Project No.
S T
A
TE OF O
H
I O
P R
O F
E
S S
IONAL
E N
G I
N E
E R
R
E
GISTERE
D
E51255
BATTAGLIA
M P S
H
E N
U E
N
GRAPHIC SCALE
0 10 20
- STORM LINE
- ELECTRIC LINE
- COMMUNICATIONS LINE
- GAS LINE
- SANITARY LINE
- TREE
- SHRUB
- STORM STRUCTURE
- FIRE HYDRANT
- WATER VALVE
- SANITARY MANHOLE
- SIGN
- ELECTRIC BOX
- ELECTRIC MANHOLE
- TELEPHONE MANHOLE
- IRON PIN
- MONUMENTATION
- LIGHT POLE
- FENCE
- BOLLARD
- PULL BOX
- STRAIN POLE
LEGEND:
- POWER/ COMM. POLE
- STORM MANHOLE
- ELECTRIC TRANSFORMER
- FLAG POLE
- LIGHTING
- WATER LINE
THE LOCATIONS OF UNDERGROUND FACILITIES SHOWN ON THIS PLAN
ARE BASED ON FIELD SURVEYS AND LOCAL UTILITY COMPANY RECORDS.
IT SHALL BE THE CONTRACTOR'S FULL RESPONSIBILITY TO CONTACT
THE VARIOUS UTILITY COMPANIES TO LOCATE THEIR FACILITIES
PRIOR TO STARTING CONSTRUCTION. NO ADDITIONAL COMPENSATION
SHALL BE PAID TO THE CONTRACTOR FOR DAMAGE AND REPAIR TO
DIG PERMIT ON SITE DURING WORK OPERATIONS.
CONTRACTOR SHALL BE RESPONSIBLE FOR HAVING A COPY OF THE APPROVED
FROM THE MEDICAL CENTER PER STANDARD OPERATING PROCEDURE 32 DIG PERMITS.
BEFORE DIGGING CONTRACTOR SHALL OBTAIN AN APPROVED DIG PERMIT
CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING MARKINGS.
BEFORE DIGGING CONTRACTOR SHALL HIRE A UTILITY LOCATE SERVICE.
THESE FACILITIES CAUSED BY HIS WORK FORCE.
CONSTRUCTION LAYOUT NOTES
PIV
DS DS DS DS
DS
DSDSDSDS
DS
SHEET NOTES
INV 6" (W)= 951.31
INV 4" (E)= 950.74
INV 6" (E)= 949.51
INV 4" (S)= 949.66
TOP= 953.56
Ex. STM MH
INV= FULL OF DIRT
TOP= 953.11
Ex. CB
INV 6" (W)= 950.34
INV 4" (SW)= 951.34
TOP= 952.69
Ex. CB
INV 8" (N)= 945.68
INV 8" (NW)= 945.68
INV 6" (S)= 947.63
INV 12" (E)= 945.53
TOP= 952.98
Ex. STM MH
INV. 12" RCP (W)=943.6
INV. 12" RCP (SE)=943.75
TOP=947.55
Ex. CI
TOP=947.55
Ex. CI
TOP=947.83
Ex. STMH
1313 13 13
14 NEW SIDEWALK
C300
SITE/ UTILITY PLAN
LATERAL
USE INV FOR NEW 6"
INV 6" (S)= 949.68
INV 6" (N)= 949.63
TOP= 953.78
Ex. SAN MH
LATERAL @ 1.0%
NEW 35' ~ 6" SANITARY
SAN INV @ BLDG 950.05
WITH MEP PLANS
WATER MAIN COORDINATE
NEW 6" COMBINATION
TO MEP PLANS
TRANSFORMER REFER
RELOCATED ELECTRIC
DRAINS. REFER TO MEP PLAN.
SUMP PUMP FOR FOUNDATION
LEADER INV 952.00
NEW DOWNSPOUT W/ 6"
20 STM CO INV 951.80
21 79' ~ 6" STM @ 2.0%
23 31' ~ 8" STM @ 2.0%
24 STM CO INV 949.38
26 11' ~ 8" STM @ 1.0%
INV = 950.11 8" S
GRATE 952.70
NEW CB TYPE 2-2B
27 16' ~ 8" STM @ 2.0%
28 STM CO INV 949.06
29 46' ~ 8" STM @ 2.0%
COORDINATE WITH MEP PLANS
3" SUMP PUMP DISCHARE LINE
INV 958.00
DISCHARE TO STM MH
CONNECT 3" SUMP PUMP
33 STM CO INV 951.80
34 42' ~ 6" STM @ 1.0%
35 STM CO INV 950.96
36 120' ~ 8" STM @ 2.0%
37 STM CO INV 948.56
38 19' ~ 8" STM @ 2.0%
INV 948.18
CONNECT TO EXIST STM MH
INV 948.14
CONNECT TO EXIST STM MH
36 37
OF CONSTRUCTION
LOCATION PRIOR TO THE START
VERIFY TELECOMMUNICATIONS
40 40
OF CONSTRUCTION
LOCATION PRIOR TO THE START
VERIFY POSSSIBLE ELECTRIC MAIN
43 REPLACE CURB AS REQUIRED
PAVEMENT REPLACEMENT
REFERENCE ONLY
& PIERS TYP. FOR
FUTURE PORCH ADDITION
PIV VALVE
CONSTRUCTION
PRIOR TO THE START OF
VERIFY GAS MAIN LOCATION
DRAIN
NEW 4" FOUNDATION
8" WATER MAIN (AS PER PLAN NOT FIELD VERIFIED)
INV = 950.00 8" N & E
INV = 950.12 6" W & S
GRATE 952.70
NEW CB TYPE 2-2B
LOCATION WITH MEP PLANS
31' ~ 6" STM @ 1.0% COORDINATE
SLEEVE AND VALVE
10" X 6" TAPPING
REMOVE PORTION AS REQUIRED.
RECORDS INDICATE A 14" ABANDONED WATER MAIN (APPROX. LOCATION)
WALK
CONNNECT TO EXISTING
DS
DS
EXISTING BUILDING
Miamisburg, OH 45342
LJB Inc. 2500 Newmark Drive
17007.00
552-18-103
INFRASTRUCTURE B116
RENOVATE
08.17.2022
Dayton, Ohio
Revisions Date
PSB JAH
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number
Dwg. of o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
Management and Facilities
Construction
Office of
XX
JPA Project No.
S T
A
TE OF O
H
I O
P R
O F
E
S S
IONAL
E N
G I
N E
E R
R
E
GISTERE
D
E51255
BATTAGLIA
VARIES
FIRST FLOOR
NOT TO SCALE
M
IN
5-(DOWNSPOUT CONNECTION DETAIL)
WALL
FOUNDATION
EXISTING
BUILDING
AWAY FROM
GRADE, SLOPE
EXISTING EXTERIOR WALL
EXISTING DOWNSPOUT
CONCRETE SLAB
EXISTING FIRST FLOOR
TO BE RECEIVED)
AND SIZE OF DOWNSPOUTS
(SIZE TO ACCEPT NUMBER
ABOVE GRADE BOOT.
USE CAST IRON PIPE FOR
M
IN
" 4
LEADER
DOWN SPOUT
TRANSITION TO PVC
VARIES
FIRST FLOOR
NOT TO SCALE
1-(TYPICAL GRADING AT BUILDING WALL DETAIL)
SLOPE
FOUNDATION
GRADE, SLOPE AWAY FROM
EXISTING EXTERIOR WALL
CONCRETE SLAB
EXISTING FIRST FLOOR
AT BUILDING FACE
FILL DEPRESSIONS
CONSTRUCTION DETAILS
C600
GATE VALVE
WATER MAIN
CONC. SLAB
OPEN
NOT TO SCALE
POST INDICATOR VALVE
6"
POST INDICATOR VALVE BOX
ADJUSTABLE CAST IRON
(W/6" OVERLAP)
#3 BAR ALL AROUND
COLLAR
ROUND CONCRETE
TYP
LAWN
NOT TO SCALE
CLEANOUT AND FRAMES AND LIDS
1'-0" 1'-0"
3'-0"
8" MIN.
FINISHED GRADE
STANDARD FRAME AND LID
GRAVEL BACKFILL
6" PVC PIPE
CONCRETE
PVC STOPPER
DEGREE OF BEND
BRANCH
BENDS
TEES
PIPE
OF
SIZE
RUN
L L L LD D D D
L L L LD D D D
3",4"&6"
3",4"&6"
8"
8"
12"
12"
16"
16"
8"
8" 8"
8"
8"
6" 6" 6" 6"10"
12" 12"
12"
12"12"
9"
9"
14"
14" 8"
14"
14"
16"
16" 16" 16"
16"
16"18" 18"
18"
18" 18"
7"
24"
28" 26"30"
22"
22"
24"
24"
20" 36"
36"
30"
33"
9" 50"
60" 15"
70"
3'-3" LONG
3'-0" WIDE
3'-6" LONG
3'-0" WIDE
5'-3" LONG
3'-0" WIDE
NOT TO SCALE
CONCRETE BLOCKING FOR WATER MAINS
OF THE ENGINEER.
LIEU OF CONCRETE BLOCKING AT THE DIRECTION
TIED OR RESTRAINED JOINTS MAY BE USED IN
NOTE:
ALL BLOCKING.
CLASS "A" CONCRETE TO BE USED FOR
9" 9"
9"
L
L/2 L
L
D
M A
X
11 1/4° 22 1/2° 11 1/4̰ & 22 1/2°
TEES SECTION
TYPICAL
90° BENDS BENDS < 90°
CONCRETE BLOCKING FOR VERTICAL BENDS
CONCRETE BLOCKING FOR HORIZONTAL BENDS
UNDISTURBED EARTH
11̰ 22а 45° 90°
2-2B CATCH BASIN
NOT TO SCALE (UNPAVED AREAS ONLY)
8"2'-0"8" 8"2'-0"8"
D E
P
R
IA
B L
E
R4871 LIGHT DUTY
NEENAH CASTING No.
2-2-B GRATE
NOT TO SCALE
6" MAX.
V A
R
IA
B L
E
6" O.D. 6"
TOPSOIL
PAVEMENT AREASSOIL AREAS
COMPACTED GRANULAR BACKFILL
GRANULAR BACKFILL
HAND-PLACED AND COMPACTED
PROCTOR)
BACKFILL (6" LAYERS) (90% MODIFIED
COMPLETE COMPACTED GRANULAR
AND SEAL WITH AC-20
SAWCUT EXISTING ASPHALT
IN 2 LIFTS
AS EXISTING PAVEMENT (4" MIN.) PLACED
ITEM 404: ASPHALT CONCRETE SAME THICKNESS
SEED OR SOD
APPROVED BY THE ENGINEER
(90% (90% MODIFIED PROCTOR) OR AS
12" ODOT 304 COMPACTED IN 6" LAYERS
AREA SHALL BE CLEANED OF ALL DIRT, MUD AND DEBRIS.
4. DURING CONSTRUCTION AND UPON COMPLETION OF THE JOB, THE
APPROVED EQUAL.
3. ALL JOINTS SHALL BE SEALED WITH AN AC-20 SEAL OR
LAYERS TO INSURE AGAINST SETTLEMENT.
2. ALL BACKFILL MATERIAL SHALL BE COMPACTED IN UNIFORM
TO THE CLOSING.
AND SUBMITTED TO THE CONTRACTING OFFICIER TWO (2) WEEKS PRIOR
OFFICIER. REQUESTS FOR CLOSING SHALL BE MADE IN WRITING
1. CLOSING OF A CITY ROAD REQUIRES THE APPROVAL OF THE CONTRACTING
GENERAL NOTES:
TRENCH RESTORATION
UP
2.81
2.342.342.34
2.32
2.55
2.37
2.32
2.28
2.342.34
2.34
2.81
2.34
2.81
2.36
2.81
2.34
2.81
2.34
2.21
2.432.432.432.43
2.28
2.55
2.36
2.81
2.59
2.36
2.21
TYP.
2.212.212.212.21
2.212.21
TYP. TYP.
TYP.
2.35
2.35
2.35 2.212.21
TYP.
2.212.21
TYP.
2.55
TYP.
2.602.602.602.60
2.612.61
2.21
TYP.
TYP.
2.45 2.45
9" 9"
2' - 4"
1' - 2"
2.80
TYP.
2.80
TYP.
2.402.40
2.44
2.38
2.84
2.59
2.35
TYP.
2.952.952.95 2.97
2.97
2.97
2.97
2.97
TYP.
2.97
2.922.922.922.92
2.97
2.97
2.97 2.972.97
2.97
2.97
2.972.97
2.97
2.972.97 2.97 2.38
2.102
2.102
2.102
2.27
2.32
2.32
2.32
2.28
2.34
2.832.83
2.34
TYP.
2.432.432.432.43
2.51
2.21
2.21
TYP.
2.62
2.35
TYP.2.21
2.212.21
TYP.
TYP.
2.212.21
TYP.
2.21
TYP.
2.21
TYP.
2.292.292.292.29
2.80
2.80
TYP.
TYP.
2.90
TYP.
2.35
2.35
TYP.
2.97
2.97
2.972.97
2.97 2.97 2.97
2.972.97
2.972.97
A504
TYP.
2.88
2.392.39
2.392.39
2.39
2.39
2.28
2.41
2.392.39
2.422.42
2.56
2.56
TYP.
2.572.57
2.562.56
TYP.
2.58
TYP.
2.562.56
2.39
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
2.572.57
TYP.
2.392.392.39
2.392.392.39
2.392.392.39
2.362.36
2.362.36
2.36
2.36
2.392.39
2.39
2.362.36
2.68
2.75
2.362.36
2.41
2.86
2.39
2.91
2.75
2.96
2.42
TYP.
2.91
2.91
TYP.
TYP.
2.42
2.36
2.12
2.96
2.96
2.00
2.39
2.00
2.422.42
2.14
TYP.
2.11
2.48
2.49
2.46
TYP.
TYP.
2.46
TYP.
2.462.46
TYP.
2.632.63
2.632.63
2.632.63
TYP.
TYP.
TYP.
2.85
2.46
TYP.
2.11
TYP.
2.11 2.46
TYP.
TYP.
2.85
2.98 2.98
2.04
TYP.
2.04
TYP.
2.04
TYP.
2.062.99
2.98 2.98
2.14
TYP.2.14
TYP.
2.49
2.70
2.73
2.72
2.74
2.71
LEGEND
Wall to be Demolished
Existing Wall to Remain
New Wall
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o…