528A7-CSI-712 Renovate A320 for Canon Ultimax - Bid Drawings.pdf
PDF 7 MB Posted
- Solicitation number
- 36C24221Q0677
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Y 26 1-1-21.pdf | ||
| 36C24221Q0677_1.docx | DOCX document | |
| 528A7-CSI-712 Renovate A320 - Bid Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE VA
MEDICAL
CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
3/24/2021
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-CSI-712RENOVATE A320 FOR
CANON ULTIMAX
G-001
KWSR
COVER
DRAWINGS INDEX
SHEET NO. DRAWING TITLE
GENERAL
1. GI-001 COVER SHEET
2. GC-101 INFECTION CONTROL (ICRA) PLAN
STRUCTURAL
3. S-100 STRUCTURAL PLANS
ARCHITECTURAL
4. A-001 ARCHITECTURAL ABBREVIATIONS, SYMBOLS & DETAILS
5. AE-101 LIFE SAFETY FLOOR PLAN
6. AD-101 ARCHITECTURAL DEMOLITION PLAN
7. A-101 ARCHITECTURAL PLAN
8. A-702 FINISH FLOOR PLAN & DETAILS
PLUMBING
9. P-001 PLUMBING ABBREVIATIONS, SYMBOLS AND NOTES
10. P-101 PLUMBING FLOOR PLAN
MECHANICAL
11. MG-001 MECHANICAL ABBREVIATION, SYMBOLS & NOTES
12. M-101 MECHANICAL PLAN
13. MI-701 CONTROLS DIAGRAM, SEQUENCE OF OPERATIONS & CONTROLS
POINTS
ELECTRICAL
14. EG-001 ELECTRICAL ABBREVIATION, SYMBOLS & NOTES
15. ED-101 ELECTRICAL DEMOLITION
16. EL-101 ELECTRICAL LIGHTING PLAN
17. EG-501 ELECTRICAL DETAILS
CANON ULTIMAX FOR REFERENCE
18. C1 COVERSHEET
19. A1 EQUIPMENT LAYOUT
20. A2 EQUIPMENT ELEVATIONS
21. A3 EQUIPMENT ELEVATIONS
22. S1 STRUCTURAL LAYOUTS
23. S2 STRUCTURAL DETAILS
24. E1 ELECTRICAL LAYOUT
25. E2 CONDUIT SCHEMATIC
26. E3 ELECTRICAL DETAILS
27. E4 CABLE LENGTH DIAGRAMS
KEY PLAN
SCALE: NONE
N
A320
THIRD FLOOR
AutoCAD SHX Text DEPARTMENT OF VETERANS AFFAIRS PROJECT NO. 528A7-CSI-712 VA MEDICAL CENTER BUILDING NO. 1 800 IRVING AVENUE SYRACUSE, NEW YORK, 13210
AutoCAD SHX Text
SYRACUSE VAMC RENOVATE A320 FOR CANON ULTIMAX
A320
RADIOLOGY
SF
A324
CONTROL
SF
A309A311
A308
A306
A307
A303
A301
A301
B300
SERVICE ELEVATOR
A327
A3
A3
A318
A318A
A335
A336
A337
A3
A3 15A317
A226
EXAM
SF
A224
EXAM
120SF
A222
EXAM
SF
A227A
ELECT
SF
A220
EXAM
SF
A228
EXAM
SF
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE VA
MEDICAL
CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
3/24/2021
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-CSI-712RENOVATE A320 FOR
CANON ULTIMAX
GC-101
KWSR
INFECTION CONTROL FLOOR PLAN
GENERAL NOTES:
1. CONTRACTOR MUST FOLLOW ALL INFECTION CONTROL PROCEDURES AND TEMPORARY
CONSTRUCTION DEFINED IN PROJECT SPECIFICATIONS.
2. CONTRACTOR SHALL MAINTAIN EGRESS FOR ALL OCCUPANTS AT ALL TIMES
THROUGHOUT CONSTRUCTION. THIS SHALL INCLUDE EGRESS FROM STAIR 3S2.
3. CONTRACTOR IS TO COORDINATE ALL WORK AND SCHEDULES WITH VAMC COR. SEE
SHEET AD-101 FOR ADDITIONAL INFORMATION.
4. NEGATIVE PRESSURE MUST BE MAINTAINED 24/7 IN EACH ACTIVE WORK AREA. SEE
SHEET AD-101 FOR ADDITIONAL INFORMATION.
5. NO CONTRACTOR STORAGE IS ACCEPTABLE IN CORRIDORS. ALL MATERIALS MUST BE
CONTAINED IN THE ACTIVE WORK AREA, OR ASSIGNED AREAS ACCEPTABLE TO THE
VAMC COR.
6. REFER TO SPECIFICATION SECTION 01 74 19 FOR CONSTRUCTION WASTE MANAGEMENT.
7. PROJECT AREA IS TO BE SEALED WITH A 2 HOUR FIRE-RATED TEMPORARY PARTITION
SUCH THAT NEGATIVE AIR PRESSURE IS MAINTAINED BETWEEN CORRIDOR(S) AND
ROOM BY EXHAUSTING AIR OUT OF WORK AREA.
8. TEMPORARY 2 HOUR FIRE-RATED BARRIERS ARE TO BE SEALED USING UL LISTED
MATERIALS TO INHIBIT TRANSFER OF DUST AND SMOKE. THEY SHALL ALSO BE
CONSTRUCTED TO MINIMIZE NOISE FROM CONSTRUCTION ACTIVITIES. ONCE IN PLACE,
THESE BARRIERS ARE TO BE INSPECTED AND ACCEPTED BY VAMC COR PRIOR TO
STARTING ANY CONSTRUCTION WORK.
9. PROVIDE DUST WALK-OFF MATS AT EACH ENTRANCE / EXIT TO PROJECT WORK AREA.
WALK-OFF MATS SHALL BE CHANGED WHEN THEY BECOME VISIBLY SOILED, OR AS
REQUIRED BY PROJECT SPECIFICATIONS.
10. PROVIDE TEMPORARY CONSTRUCTION SIGNAGE AT INTERIOR AND EXTERIOR OF
PROJECT WORK AREA. COORDINATE WITH VAMC COR ON REQUIREMENTS AND
LOCATIONS.
11. ANY WORK TO BE PERFORMED OUTSIDE OF THE CONSTRUCTION BARRIER SHALL BE
COORDINATED WITH THE VAMC COR.
12. ALL CONTRACTOR EQUIPMENT / CARTS, ETC. MUST BE WIPED DOWN PRIOR TO ENTRY
OR EXIT. ONCE IN, CARTS SHOULD BE WIPED DOWN PRIOR TO RELOCATION TO NEW
WORK AREA. THIS SHALL INCLUDE ALL EQUIPMENT / CART WHEELS.
13. PATCH ALL FINISHES DAMAGED BY TEMPORARY PARTITION INSTALLATION AND
REMOVAL TO MATCH EXISTING FINISHES.
14. THE CONTRACTOR SHALL NOT TRANSFER ANY CART THROUGH THE HOSPITAL THAT
DOES NOT HAVE A CLEAN COVER.
15. THE CONTRACTOR SHALL CLEAN THE SERVICE ELEVATORS IF CONSTRUCTION
MATERIAL IS TRACKED ON TO IT.
16. NEGATIVE AIR PRESSURE TO BE USED DURING PHASES OF CONSTRUCTION.
DRAWING LEGEND:
TEMPORARY ICRA 2 HOUR FIRE-RATED BARRIER WITH 36" 11
2 HOUR DOOR
CONSTRUCTION WORK BOUNDARY
WALK-OFF MAT
N
INFECTION CONTROL FLOOR PLAN
SCALE: 1/4" = 1'-0"1
2ND FLOOR INFECTION CONTROL PLAN
SCALE: 1/8" = 1'-0"2
N ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE VA
MEDICAL
CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
3/24/2021
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-CSI-712RENOVATE A320 FOR
CANON ULTIMAX
A-001
KWSR
ABBREVIATIONS, SYMBOLS, AND
NOTES
ARCHITECTURAL ABBREVIATIONS
@ AT
∠ ANGLE
℄ CENTERLINE
[ CHANNEL
┴ PERPENDICULAR
⅊ PLATE
∅ ROUND/DIAMETER
AB ANCHOR BOLT
AFF ABOVE FINISH FLOOR
A/C AIR CONDITIONING
ACC ACCESSIBLE
ACS PNL ACCESS PANEL
ADDM ADDENDUM
ADJ ADJACENT, ADJUSTABLE
AHR ANCHOR(AGE)
ALT ALTERNATE
ALUM ALUMINUM
ANNPNL ANNUNCIATOR PANEL
ANOD ANODIZED
ACT ACOUSTICAL CEILING TILE
APPROX APPROXIMATE
ARCH ARCHITECT(URAL)
ASB ASBESTOS
ASPH ASPHALT
B/O BOTTOM OF
BEV BEVELED
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BLKT BLANKET
BM BEAM, BENCHMARK
BRG BEARING
BRK BRICK
BSMT BASEMENT
BUR BUILT-UP ROOF
BW BOTH WAYS
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CLL CONTRACT LIMIT LINE
CMP CORRUGATED METAL PIPE
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CT CERAMIC TILE
CAB CABINET
CH BD CHALKBOARD
CEM CEMENT
CLO CLOSET
CLG CEILING
CLR CLEAR
CMPST COMPOSITE
COL COLUMN
COMB COMBINATION
CONC CONCRETE
CONSTR CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
CORR CORRIDOR
CPRS FL COMPRESSIBLE FILLER
CPT CARPET
CR CARDREADER
CRS COLD ROLLED STEEL
D DEPTH
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DR DOOR
DEFL DEFLECTION
DIA DIAMETER
DIAG DIAGONAL
DIMEN DIMENSION
DL DEAD LOAD
DTL DETAIL
DWG DRAWING
EA EACH
EJ EXPANSION JOINT
EP ELECTRIC PANEL
EIFS EXTERIOR INSULATION
& FINISH SYSTEM
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMHO ELECTROMAGNETIC HOLD OPEN
ENTR ENTRANCE
EQ EQUAL
EQUIP EQUIPMENT
ESTIM ESTIMATE
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXP EXPOSED, EXPANSION
EXT EXTERIOR
FCU FAN COIL UNIT
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FH FIRE HYDRANT
FLG FLOORING
FO FINISHED OPENING
FP FIREPROOFING
F/O FACE OF
FAAP FIRE ALARM ANNUNCIATOR PANEL
FDN FOUNDATION
FIN FINISH(ED)
FIXT FIXTURE
FLASH FLASHING
FLR FLOOR
FM FACTORY MUTUAL
FR FRAME
FRMG FRAMING
FRP FIBERGLASS REINFORCED
PLASTIC/PANEL
FRTW FIRE RETARDANT TREATED WOOD
FT FOOT/FEET
FTG FOOTING
FURG FURRING
FURN FURNISHED/FURNITURE
FWC FABRIC WALL COVERING
GB GRAB BAR
GC GENERAL CONTRACTOR
GCT GLAZED CERAMIC TILE
GA GAUGE GALV GALVANIZED
GL GLASS, GLAZING
GWB GYPSUM WALLBOARD
GYP GYPSUM
HT HEIGHT
HC HOLLOW CORE
HM HOLLOW METAL
HCP HANDICAPPED
HDBD HARDBOARD
HDWD HARDWOOD
HDW HARDWARE
HORIZ HORIZONTAL
HR HOUR
HVAC HEATING/VENTILATING/AIR COND.
ID INSIDE DIAMETER
INCL INCLUDE(D) (-ING)
INSUL INSULATE(D) (-ION) (-ING)
INT INTERIOR
INV INVERT
JAN JANITOR
JT JOINT LAM LAMINATE(D)
LAV LAVATORY
LF LINEAR FEET
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
Loc LocATE(D) (-ION)
LT-GA LIGHT GAUGE
LTG LIGHTING
LVR LOUVER
MO MASONRY OPENING
MR MOISTURE RESISTANT
MACH MACHINE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MET METAL(LIC)
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MKR BD MARKER BOARD
MLDG MOULDING
MMB MEMBRANE
MTL METAL
MULL MULLION
NA NOT APPLICABLE
NAT NATURAL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NPS NOMINAL PIPE SIZE
NTS NOT TO SCALE
OA OVERALL
oc ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
OPH OPPOSITE HAND
OSU OHIO STATE UNIV. (TEST)
P&M PATCH & MATCH
PBD PARTICLE BOARD
PCT PORCELAIN CERAMIC TILE
PERIM PERIMETER
PL PLASTIC
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PNL PANEL
P PAINT
PNTD PAINTED
PR PAIR
PREFAB PREFABRICATE(D)
PT PRESSURE TREATED
PTD PAPER TOWER DISPENSER
PTN PARTITION
PVC POLYVINYL CHLORIDE
PVG PAVING
QT QUARRY TILE
QTY QUANTITY
R RADIUS/RISER
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCE
REQ'D REQUIRED
RESIL RESILIENT
RESIL C RESILIENT CHANNEL
RET RETURN
REV REVISION
RM ROOM
RO ROUGH OPENING
RUB RUBBER
SC SOLID CORE
SST STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
SCHED SCHEDULE
SECT SECTION
SHT SHEET
SHTHG SHEATHING
SIM SIMILAR
SLNT SEALANT
SND SANITARY NAPKIN DISPENSER
SNDU SANITARY NAPKIN DISPOSAL UNIT
SPEC SPECIFICATION
SPKLR SPRINKLER
SQ SQUARE
SSM SOLID SURFACE MATERIAL
STL STEEL
STD STANDARD
STRUCT STRUCTURAL
SUSP SUSPENDED
SYMM SYMMETRICAL
DC DOOR CONTROL
EFTR EXIST FINISH TO REMAIN
RF RAISED RUBBER FLOORING
RTF RESILIENT TILE FLOORING
RST RESILIENT STAIR TREADS
VSF VINYL SHEET FLOORING (HEAT
WELDED SEAMS)
PFW POLYPROPYLENE FABRIC WALL
COVERING
PCP PORTLAND CEMENT PLASTER
ICB INTEGRAL COVE BASE
BE BAKED ON ENAMEL
SD SOAP DISPENSER
TPD TOILET PAPER DISPENSER
MTD MOUNTED
FC FILE CABINET
DISTR DISTRIBUTION
AMP ACOUSTICAL METAL PANEL
RCT RADIANT CEILING TILE
CTG COATING
REF REFRIGERATOR
MW MICROWAVE
LGMF LIGHT GA METAL FRAMING
ZVB ZONE VALVE BOX
ZA ZONE ALARM
CC CONTRACTOR SUPPLIED &
INSTALLED
VV VA SUPPLIED & INSTALLED
VC VA SUPPLIED & CONTRACTOR
INSTALLED
MC METAL CEILING
VAMC SYRACUSE VA MEDICAL CENTER
COR CONTRACTING OFFICER'S
REPRESENTATIVE
TREAD T T&G TONGUE & GROOVE
T/CONC TOP OF CONCRETE
T/D TOP OF DECK
T/O TOP OF
T/S TOP OF STEEL
T/W TOP OF WALL
TK BD TACKBOARD
TEL TELEPHONE
TMPD TEMPERED
TEMP TEMPERATURE
TERM TERMINAL
TER TERRAZZO
THK THICK(NESS)
THRES THRESHOLD
TRANS TRANSOM, TRANSPARENT
TYP TYPICAL
UC UNDERCUT
UNO UNLESS NOTED OTHERWISE
UC UNIV. OF CALIF. (TEST)
UL UNDERWRITER'S LAB. (TEST)
UR URINAL
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VNR VENEER
VP VENEER PLASTER
VR VAPOR RETARDER
VWC VINYL WALLCOVERING
W WIDE
WC WATER CLOSET
WGL WIRE GLASS
WP WATERPROOF
WPT WORKPOINT
WR WATERREPELLENT/RESISTANT
WS WEATHER STRIP
WWF WELDED WIRE FABRIC
W/ WITH
W/O WITHOUT
WDW WINDOW
WD WOOD
XFMR TRANSFORMER
JOB SPECIFIC ABBREVIATIONS
CONTRACT LIMIT LINE
DEMOLITION LINE
ELEVATION INDICATOR
CENTER LINE INDICATOR
EXISTING TO REMAIN LINE
FEATURES ABOVE LINE INDICATOR
HIDDEN FEATURES LINE
NEW LINE
PROPERTY LINE
SMOKE BARRIER LINE
BREAK, ROUND (USER DEFINES SIZE)
BREAK, STRAIGHT (SEE SECTION
INDICATORS,
BUILDING, WITH BREAK STANDARDS)
DETAIL INDICATOR
DETAIL INDICATOR
DETAIL INDICATOR FOR SMALL CONDITIONS
DIMENSION LINE
DOOR OPENING
TYPICAL DRAWING BLOCK OR DETAIL TITLE
ELEVATION INDICATOR, EXTERIOR
ELEVATION INDICATOR; INTERIOR, MULTIPLE
VIEW
ELEVATION INDICATOR, INTERIOR, SINGLE
VIEW
ARCHITECTURAL SYMBOLS
CENTER LINE
FURNITURE, FIXTURE, & EQUIPMENT
INDICATOR
GRAPHIC SCALE; 18"=1'-0"
A-201 A4
S
ROOM NAME AND NUMBER
A
CG
COLUMN GRID
KEYNOTE
WALL OR PARTITION TYPE
FIRE EXTINGUISHER CABINET
CORNER GUARD
NORTH ARROW
EXISTING CONSTRUCTION TO
REMAIN
EXISTING CONSTRUCTION TO
BE REMOVED
NEW CONSTRUCTION
CONCRETE
RIGID
INSULATION
BATT
INSULATION
V V ITEM - VA SUPPLIED & INSTALLED
VC ITEM - VA SUPPLIED & CONTRACTOR
INSTALLED
CC ITEM - CONTRACTOR SUPPLIED &
INSTALLED
DETAIL NUMBER
SHEET WHERE REF.
SHEET WHERE DRAWN
BUILDING SECTION INDICATOR
DETAIL INDICATOR
MATERIALS LEGEND
D2 A-512
D2 A-512
A4 A-201
A4 A-201
AA
10'-0"
A
C B
D
FEC
A-202 A2
A3.1 A4.3
16'8'4'0
D2 A-512
121212
EXISTING DOOR TO REMAIN, IN EXISTING
PARTITION.
EXISTING DOOR TO BE REMOVED: SEE
REMOVAL PLAN.
NEW DOOR IN NEW OR EXISTING PARTITION:
SEE DOOR SCHEDULE.
XXX
CORRIDOR
SF
SMOKE WALLS
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
EXIT TRAVEL PATH
N
CLG
CLG
CLG
CLG
CLG
VARIES
CLG
STRUCTURE/SLAB.
ABOVE, AS REQUIRED.
STUDS AT STRUCTURE
FOR DETAILS. BRACE
VARY; SEE DRAWINGS
BULKHEAD CONDITIONS
STOP ALL MATERIAL
AT CEILING.
STOP GWB ABOVE
CEILING ONE SIDE;
EXTEND ALL OTHER
MATERIALS TO
UNDERSIDE OF
HEIGHTS.
DRAWINGS FOR
LOW WALL, SEE
AS REQUIRED.
STRUCTURE ABOVE,
BRACE STUDS AT
ABOVE CEILING &
EXTEND GWB MATERIAL
STRUCTURE/SLAB.
TO UNDERSIDE OF
EXTEND ALL MATERIAL
HEIGHT TYPES :
4"
4"
E
C
A
F
D
B
4-1/4"
3 5/8" METAL STUDS - 20 GA AT
16"oc
1 LAYER 5/8" GWB - TYPE 'X' BOTH
SIDES.
1 HR FIRE-RATED
UL TEST: U-465
STC = 47
W/ 2" BATT INSULATIONW/ 2 1/2" BATT INSULATION
1 5/8" METAL STUD FURRING - 20
GA AT 16"oc
1 LAYER 5/8" GWB 6
3 5/8" METAL STUDS - 20 GA AT
16"oc
2 LAYERS 5/8" GWB - TYPE 'X'
BOTH SIDES.
1 LAYER 5/8" GWB LAMINATE TO
EXISTING PLASTER
7/8" FURRING
1 LAYER 5/8" GWB
8"
W/ 31
2" BATT INSULATION
2 HR FIRE-RATED
UL TEST: U-618
1 LAYER 5/8" GWB - TYPE 'X'
2 1/4" METAL STUDS - 20 GA AT
16"oc
1 5/8" METAL STUD FURRING - 20
GA AT 16"oc
8"
1 HR FIRE-RATED
UL TEST: U-465
STC = 47
8"
3 5/8" METAL STUDS - 20 GA AT
16"oc
1 LAYER 5/8" GWB - TYPE 'X' ONE
SIDES.
4"
SF
A324
CONTROL
SF
A309A311
A308
A306
A307
A303
A301
A301
B300
SERVICE ELEVATOR
A3
A3
A318
A318A
A335
A336
A337
A3
A3 15A317
A226
EXAM
SF
A224
EXAM
120SF
A222
EXAM
SF
A227A
ELECT
SF
A220
EXAM
SF
A228
EXAM
SF
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE VA
MEDICAL
CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
3/24/2021
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-CSI-712RENOVATE A320 FOR
CANON ULTIMAX
AE-101
KWSR
LIFE SAFETY FLOOR PLAN
N
1ST FLOOR LIFE SAFETY PLAN
SCALE: 1/4" = 1'-0"1
CODE SYNOPSIS
PROJECT OVERVIEW:
RENOVATE A320 FOR CANON ULTIMAX
SYRACUSE VA MEDICAL CENTER
APPLICABLE CODES:
· NFPA 13-2016 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
· NFPA 14-2016 STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOUSE
SYSTEMS
· NFPA 24-2013 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE
MAINS AND THEIR APPURTENANCES
· NFPA 72-2016 NATIONAL FIRE ALARM CODE
· NFPA 90A-2018 STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND
VENTILATING SYSTEMS
· NFPA 99-2018 STANDARD FOR HEALTH CARE FACILITIES
· NFPA 101-2018 LIFE SAFETY CODE
· NFPA 220-2012 STANDARD ON TYPES OF BUILDING CONSTRUCTION
· NFPA 291-2013 RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND
MARKING OF HYDRANTS
· NFPA 1963-2009 STANDARD FOR FIRE HOSE CONNECTIONS
· VA DESIGN GUIDE AND TECHNICAL GUIDE
· VA FIRE PROTECTION DESIGN MANUAL - DECEMBER 2015
· UNIFORM FEDERAL ACCESSIBILITY STANDARDS WITH VA BARRIER FREE DESIGN
GUIDE (PG 18-13)
BUILDING USE CLASSIFICATION:
HEALTH CARE
EXISTING HEALTH CARE OCCUPANCY (NFPA 101 - CHAPTER 19)
BUILDING CONSTRUCTION:
BUILDING STRUCTURE: STEEL COLUMNS/BEAMS, ENCASED IN CONCRETE,
CONCRETE SLABS
NUMBER OF STORIES: ELEVEN (B, G, 1-9) PLUS PENTHOUSE
CONSTRUCTION TYPE: TYPE II (222) NFPA-101
SPRINKLER: FULLY SPRINKLERED IN ACCORDANCE WITH "NFPA13 -
INSTALLATION OF SPRINKLER SYSTEMS"
FIRE EXTINGUISHERS: PROVIDE IN ACCORDANCE WITH
"NFPA-10-PORTABLE FIRE EXTINGUISHERS" WITH TRAVEL DISTANCE - OF 75 FT.
MAX. ALLOWABLE NUMBER OF STORIES (ABOVE GRADE):
EXISTING
MAX ALLOWABLE AREAS:
LIFE SAFETY CODE: UNLIMITED
BUILDING COMPONENTS NFPA 220 2012
NFPA 101 2018
RATED CONSTRUCTION FIRE RATING (IN HOURS)
EXTERIOR WALLS -
LOAD BEARING 2
NON-LOADBEARING 0
INTERIOR BEARING WALLS 2
RATED CONSTRUCTION FIRE RATING (IN HOURS)
EXIT, EXIT HALLWAY STAIRWAY ENCLOSURE 2
(4 OR MORE STORIES)
MECHANICAL SHAFTS, ELEVATOR HOIST WAYS 2
(4 OR MORE)
EXIT ACCESS CORRIDORS 0 (SMOKE TIGHT)
HORIZONTAL EXITS NA
MIN. # OF EXITS/FLOOR (<500 OCCUP. LOAD) 2
(>501-1,000) 3
SMOKE BARRIERS 1
COLUMNS 2
COLUMNS (ROOF ONLY) 1
BEAMS 1
BEAMS (ROOF ONLY) 1
FLOOR CONSTRUCTION (INCLUDING BEAMS) 2
ROOF CONSTRUCTION -
SOILED LINEN ROOMS 1 HR
STORAGE ROOMS MORE THAN 100 SF 1 HR
TRAVEL DISTANCE (FT)
· FROM ANY POINT TO EXIT (WITH AUTO FIRE SUPP. SYS) 200 FT
(19.2.6.2.1 & 19.26.2.2)
· MAXIMUM DEAD END LENGTH REQUIRED 30 FT (19.2.5.2)
(SPRINKLERED BUILDING)
· FROM ANY POINT WITHIN SLEEPING ROOM TO 50 FT (19.2.6.2.3)
EXIT ACCESS CORRIDOR
· FROM ANY POINT IN NON-PATIENT SLEEPING 100 FT/1 ROOM 100 FT.
(WITH AUTO FIRE SUPP SYS)
· SUITE TO EXIT ACCESS CORRIDOR/NUMBER 50 FT/2 ROOMS (12-2.5.8) OF
INTERVENING ROOMS TO EXIT CORRIDOR
REQUIRED EGRESS WIDTH:
DOORWAYS 34" MIN.
STAIR DOORS 36" WIDE
STAIRS 44"
CORRIDOR WIDTH 44"
OPENING PROTECTIVES IN RATED CONSTRUCTION
DOORS IN OTHER 1 HR. RATED CONSTRUCTION 3/4 HR., LABEL "C"
DOORS IN 2 HR. RATED CONSTR. (SELF CLOSING) 1-1/2 HR., LABEL "B"
DOORS IN SMOKE BARRIER PARTITIONS (SELF CLOSING) 3/4 HR
SMOKE COMPARTMENT
· MINIMUM OF 2 PER FLOOR 19.3.7.1
· MAXIMUM OF 22,500 SF 19.3.7.1 (4)
· IF LESS THEN 150 FT IN LENGTH OR WIDTH, TRAVEL DISTANCE TO IS NOT
LIMITED.
DRAWING LEGEND
SMOKE WALL
1 HR. FIRE RATED WALL
2 HR. FIRE RATED WALL
EXIT TRAVEL PATH
TEMPORARY 2 HR. RATED
PARTITION
PROJECT WORK BOUNDRY
108 FT TO EXIT STAIRWELL
12 FT
2ND FLOOR LIFE SAFETY PLAN
SCALE: 1/8" = 1'-0"2
N
22 FT TO EXIT ROOM
15 FT TO EXIT ROOM
34 FT TO STAIRWELL
SF
A324
CONTROL
SF
A318
A318A
A320
RADIOLOGY
SF
A324
CONTROL
SF
A318
A318A
A226
EXAM
SF
A224
EXAM
120SF
A222
EXAM
SF
A227A
ELECT
SF
A228
EXAM
SF
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE VA
MEDICAL
CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
3/24/2021
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-CSI-712RENOVATE A320 FOR
CANON ULTIMAX
AD-101
KWSR
ARCHITECTURAL DEMOLITION
PLANS
N
ARCHITECTURAL DEMOLITION FLOOR PLAN
SCALE: 1/4" = 1'-0"1
GENERAL REMOVAL NOTES:
1. THE DEMOLITION AND ALTERATION NOTES ON THIS PLAN SHALL NOT BE
DEEMED TO BE ALL-INCLUSIVE. PRIOR TO THE START OF DEMOLITION
INSPECT AND ASSESS EACH AREA AND TO FULFILL THE DESIGN INTENT
OF THE WORK INDICATED BY THE PROJECT DOCUMENTS.
2. VERIFY ALL CONDITIONS AND DIMENSIONS WITHIN THE PROJECT LIMITS
AND NOTIFY THE COR IMMEDIATELY OF ANY DEVIATION FROM PROJECT
DOCUMENTS NECESSITATED BY FIELD CONDITIONS OR ITEMS NOT
COVERED.
3. DASHED LINES ON DEMOLITION PLANS REPRESENT WALLS, DOORS,
SOFFITS, CEILINGS, CASEWORK, ETC. TO BE REMOVED.
4. FOR ALL SURFACES SCHEDULED TO REMAIN, PATCH, MATCH SURFACES
DISTURBED BY DEMOLITION OR REMOVAL OF EQUIPMENT OR UTILITIES.
PROVIDE PATCHING TO MATCH ADJACENT WORK IN FINISH, STRUCTURAL
QUALITIES, COURSING OF MASONRY AND OTHER CHARACTERISTICS.
PATCH SURFACES TO COMPLY WITH FIRE RATINGS, SMOKE-TIGHT
RATINGS, ACOUSTICAL CRITERIA AND OTHER PERFORMANCE CRITERIA
INDICATED. PREPARE SURFACES AS NECESSARY TO PROVIDE A PROPER
SUBSTRATE FOR SPECIFIED FINISH. REFINISH ENTIRE SURFACE CORNER
TO CORNER AS NECESSARY TO PROVIDE AN EVEN FINISH TO MATCH
ADJACENT FINISHES. ALL WORK SHALL REFLECT HIGHEST LEVEL OF
INDUSTRY STANDARDS FOR EACH TRADE.
5. ALL DEMOLITION SHALL BE PERFORMED IN A SAFE AND ACCEPTABLE
MANNER TO ALL AUTHORITIES HAVING JURISDICTION AND THE
SYRACUSE VAMC. A FIRE WATCH SHALL BE PROVIDED AS REQUIRED BY
SYRACUSE VAMC AND APPLICABLE CODES.
6. PROVIDE TEMPORARY PARTITIONS/DUST PROTECTION (RATED AND/OR
NON-RATED) AS REQUIRED BY ICRA. REVIEW LOCATIONS OF TEMPORARY
PARTITIONS/DUST PROTECTION WITH COR PRIOR TO START OF WORK.
7. HAZARDOUS MATERIAL NOTE: STOP WORK AND INFORM COR
IMMEDIATELY OF ANY HAZARDOUS MATERIAL ENCOUNTERED OR
THOUGHT TO BE HAZARDOUS. COR SHALL INSTRUCT CONTRACTOR ON
HOW TO PROCEED. HAZARDOUS MATERIAL NOT ANTICIPATED.
8. ALL WORK SHALL BE DONE IN PROTECTED SPACE. NO DUST, DIRT OR
LIQUID SHALL TRAVEL FROM CONSTRUCTION AREA TO ADJACENT AREAS.
TEMPORARY ICRA PARTITIONS SHALL BE ERECTED PRIOR TO
COMMENCING WORK.
9. PRIOR TO ANY DEMOLITION, COORDINATE BRACING AND MAINTAIN THE
STRUCTURAL INTEGRITY OF THE REMAINING ELEMENTS OF THE BUILDING
AND ITS SYSTEMS AS REQUIRED.
10. COMPLY WITH GOVERNING REGULATIONS PERTAINING TO
ENVIRONMENTAL PROTECTION FOR POLLUTION CONTROL.
THOROUGHLY CLEAN ADJACENT AREAS OF DUST, DIRT AND DEBRIS
CAUSED BY DEMOLITION WORK. BEFORE NEW WORK BEGINS, RETURN
ADJACENT AREAS TO CONDITION FOUND PRIOR TO START OF
DEMOLITION WORK.
11. REVIEW ALL ITEMS TO BE DEMOLISHED WITH COR TO IDENTIFY ANY ITEMS
TO BE SALVAGED PRIOR TO START OF DEMOLITION.
12. PREPARE FLOOR SLABS SO FINISH FLOORS ARE FLUSH WITH EACH
OTHER AND PREPARED TO ACCEPT NEW FINISH. SEE CANON DRAWINGS
FOR FLOOR LEVELNESS AND FLATNESS REQUIREMENTS OF EQUIPMENT.
13. MAINTAIN ACCESS TO EXITS AND EXIT STAIRS AT ALL TIMES. FIRE ALARM
AND SMOKE DETECTION SYSTEM SHALL REMAIN OPERATIONAL AT ALL
TIMES. PROTECT SMOKE DETECTORS AS REQUIRED AND IN
CONFORMANCE WITH CODES AND LOCAL AUTHORITIES HAVING
JURISDICTION.
14. PRIOR TO DEMOLITION, PERFORM A THOROUGH ABOVE-CEILING
INSPECTION FOR EXISTING SERVICES THAT ARE TO REMAIN AND NOTIFY
COR IMMEDIATELY OF ANY CONFLICTS WITH INSTALLATION OF NEW
WORK.
15. MAINTAIN 60" MINIMUM CLEARANCE AT ALL CORRIDORS AT ANY GIVEN
TIME.
16. DIVISION 13 - SPECIAL CONSTRUCTION
17. PROVIDE ROLLED LEAD FOR PATCHING AS REQUIRED. ALL OUTLET
BOXES, JUNCTION BOXES, ETC. IN LEADED WALLS SHALL BE LINED WITH
1/16" LEAD.
18. DURING CONSTRUCTION WORK AND PRIOR TO CLOSING WALLS AND
PENETRATIONS, LEAD PROTECTION WILL BE INSPECTED BY VA RADIATION
SPECIALIST.
N
3RD FLOOR CEILING DEMOLITION PLAN
SCALE: 1/4" = 1'-0"2
R1
R2 R5
R4
R4 R7 R7
R1
R6
R6
R6
R6
R6 R3
R3
R3
R3
R3R3
R3
R3
R3
R3
R1
R1
R8
R9
R6
2ND FLOOR CEILING DEMOLITION PLAN
SCALE: 1/4" = 1'-0"2
N
R10
R1
R2
R3
R4
R5
KEYED REMOVAL NOTES
REMOVE WELDED SEAM SHEET FLOORING, VCT AND MASTIC FROM
FLOOR SUBSTRATE. PATCH/ REPAIR ANY DAMAGE ASSOCIATED WITH
REMOVALS AND PREPARE EXISTING SUBSTRATE TO RECEIVE NEW
FINISH WORK.
REMOVE ACOUSTICAL CEILING TILE, ASSOCIATED GRID AND SUPPORT
HANGERS. PATCH AND REPAIR ANY DAMAGE ASSOCIATED WITH
REMOVAL. PREPARE WALLS TO RECEIVE NEW FINISH WORK AT EXISTING
WALLS TO REMAIN.
REMOVE WALL BASES AND ANY ADHESIVES AND RESIDUES.
REMOVE ALL LAMINATE COUNTERS AND BASE CABINETS. PATCH AND
REPAIR ALL WALLS AND FLOORS TO RECEIVE NEW MATERIALS. VERIFY
EXISTING MILLWORK DIMENSIONS PRIOR TO REMOVALS.
REPLACE CEILING TILES. GRID TO REMAIN.
REMOVE WALL PROTECTION. PATCH AND REPAIR ANY DAMAGE
ASSOCIATED WITH REMOVAL. PREPARE WALLS TO RECEIVE NEW FINISH
WORK.
SALVAGE LIGHT FIXTURE FOR REUSE AND RE INSTALL.
REMOVE SINK AND PATCH WALL TO RECEIVE NEW FINISH WORK.
SEE STRUCTURAL DRAWINGS FOR ADDITIONAL REMOVALS.
REMOVE CABINET AND PATCH WALL TO RECEIVE NEW FINISH WORK.
MODIFY AND RELOCATE EXISTING LAY IN CEILING SYSTEM UTILITIES AND
ALL ABOVE CEILING UTILITIES AS NEEDED TO COORDINATE STRUCTURAL
STEEL INSTALLATION.
R6
R7
R8
R9
R10
R11
R11 R11
R11
SF
A324
CONTROL
SF
A318
A318A
14'-6"
6' -7
3-∠6X6X3/8
W
F4
W
F3
W
F3
W
F3
W
F5
16WF58 16WF58
16WF50 16WF50
16WF45
A320
RADIOLOGY
SF
A324
CONTROL
SF
ACT
8'-11 12"
8'- 2"
ACT
A318
A318A
9'-11 2"
7' -0
8W24
A226
EXAM
SF
A224
EXAM
120SF
A222
EXAM
SF
A227A
ELECT
SF
A228
EXAM
SF
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE VA
MEDICAL
CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
3/24/2021
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-CSI-712RENOVATE A320 FOR
CANON ULTIMAX
A-101
KWSR
ARCHITECTURAL PLANS
EXISTING PLASTER &
LATH WALL
N
3RD ARCHITECTURAL FLOOR PLAN
SCALE: 1/4" = 1'-0"1
GENERAL PLAN NOTES:
1. FOLLOW ALL INFECTION CONTROL PROCEDURES AND TEMPORARY
CONSTRUCTION DEFINED IN PROJECT SPECIFICATION & VA APPROVED ICRA.
2. NEGATIVE PRESSURE MUST BE MAINTAINED 24/7 IN EACH ACTIVE WORK
AREA.
3. NO STORAGE IS ACCEPTABLE IN CORRIDORS. ALL MATERIALS MUST BE
CONTAINED IN THE ACTIVE WORK AREA.
4. PROVIDE WALK OFF MATS BY EACH DOOR OUTSIDE EACH ROOM IDENTIFIED
AS A CONSTRUCTION AREA FOR THE DURATION OF THE PROJECT. SEE DWG.
GC-101
5. ALL EQUIPMENT / CARTS ETC. MUST BE WIPED DOWN PRIOR TO ENTRY.
ONCE IN, CARTS SHOULD BE WIPED DOWN PRIOR TO BE TAKEN OUTSIDE OF
THE CONSTRUCTION AREA.
6. PROVIDE THOROUGH CLEANING FOLLOWING EACH WORK DAY. ALL DEBRIS
MUST BE REMOVED BY END OF DAY.
7. VERIFY ALL EXISTING CONDITIONS AND ESTABLISHING THE COMPATIBILITY
OF ALL NEW WORK WITH THE EXISTING CONDITIONS.
8. ALL WORK IS BEING DONE ADJACENT TO, & BELOW, OCCUPIED SPACE. TAKE
EVERY PRECAUTION TO ELIMINATE THE TRAVEL OF LIQUID, DUST AND DIRT
FROM THE CONSTRUCTION AREA TO THOSE SPACES.
9. TAKE EVERY PRECAUTION TO MINIMIZE DISRUPTION WITH ADJACENT
OCCUPIED SPACE. SCHEDULE AND SEQUENCING OF WORK TO BE
COORDINATED WITH COR PRIOR TO BEGINNING WORK.
10. PATCH ALL SURFACES TO REMAIN AFFECTED BY DEMOLITION OR REMOVAL
OF EXISTING EQUIPMENT & CONSTRUCTION. NEW SURFACES TO BE FILLED,
SANDED SMOOTH & FINISHED TO MATCH ADJACENT SURFACE.
11. MAINTAIN EXISTING UTILITIES INDICATED TO REMAIN, KEEP IN SERVICE, AND
PROTECT AGAINST DAMAGE DURING ALL RENOVATION WORK. COORDINATE
CONSTRUCTION AROUND EXISTING EQUIPMENT, CONDUIT CABLING, ETC.
WITH COR AS REQUIRED TO MAINTAIN CONTINUOUS OPERATION.
12. COORDINATE EXACT LOCATION OF ALL NEW EQUIPMENT TO BE INSTALLED IN
CEILING WITH EXISTING MECHANICAL AND ELECTRICAL WORK TO REMAIN IN
PLACE. SEE CANON EQUIPMENT DRAWINGS FOR EQUIPMENT REQUIREMENT.
13. COMPLY WITH GOVERNING REGULATIONS PERTAINING TO ENVIRONMENTAL
PROTECTION FOR POLLUTION CONTROL & HAZARDOUS MATERIALS.
14. ALL PENETRATIONS IN RATED ASSEMBLIES SHALL BE SEALED WITH UL/FM
APPROVED MATERIAL ASSEMBLIES AND PROCEDURES.
15. ALL DIMENSIONS ARE FROM FINISH FACE OF WALL TO FINISH FACE OF WALL.
16. LOCATE ALL NEW DOORS 5" FROM INSIDE CORNER UNLESS NOTED
OTHERWISE.
17. CONTRACTOR TO PROVIDE NON COMBUSTIBLE BLOCKING AS REQUIRED
BEHIND ALL WALLS FOR PROPER INSTALLATION OF BUMPER GUARDS, WALL
MOUNTED EQUIPMENT, WALL CABINETRY, ETC.
18. DRAWINGS SHALL NOT BE SCALED AS A BASIS FOR ESTABLISHING
DIMENSIONS OR OTHER INFORMATION.
19. ALL NEW CORRIDOR WALLS MUST HAVE THE SAME FIRE/SMOKE RATING AS
THE WALL THEY ARE MEETING. REFER TO THE LIFE SAFETY DRAWINGS FOR
DESIGNATION.
20. ALL BLOCK WALLS SHALL HAVE LAMINATE GWB ON THEM AND BE FLUSH AND
SQUARED.
21. NO TILE SHALL BE LESS THAN 50% OF THE WIDTH OF THE TILE ALONG THE
WALL.
22. IN AREAS OF NEW PARTITION WORK WITHIN EXISTING BUILDING: MODIFY
EXISTING GRID AND CEILING TILES AT INTERSECTIONS WITH NEW
PARTITIONS. CUT EXISTING GRID AND CEILING TILES AS NECESSARY TO
ACCOMMODATE NEW WORK. PROVIDE NEW CEILING EDGE TRIM AND
RELATED COMPONENTS AS NEEDED TO MATCH AND COMPLETE EXISTING
SYSTEM.
23. IN AREAS OF NEW CEILING WORK WITHIN EXISTING BUILDING: CONTINUE
EXISTING GRID AND CEILING TILES AS SHOWN. USE EXISTING GRID AND
TILES FROM AREAS TO BE REMOVED OR PROVIDE NEW TO MATCH EXISTING.
ALIGN NEW GRID WITH EXISTING.
24. PROVIDE CAULK BETWEEN WALL AND CEILING GRID.
25. IF NECESSARY, RELOCATED SPRINKLER HEADS TO BE LOCATED IN THE
CENTER OF THE GRIDS.
26. CEILING GRID SHALL BE INSTALLED PER ASTM C636 /C636M, "STANDARD
PRACTICE FOR INSTALLATION OF METAL CEILING SUSPENSION SYSTEMS
FOR ACOUSTICAL TILE AND LAY-IN PANELS".
27. DIVISION 13 - SPECIAL CONSTRUCTION PROVIDE ROLLED LEAD FOR
PATCHING AS REQUIRED. ALL OUTLET BOXES, JUNCTION BOXES, ETC. IN
LEADED WALLS SHALL BE LINED WITH 1/16" LEAD.
N
3RD FLOOR REFLECTED CEILING PLAN
SCALE: 1/4" = 1'-0"2
KEYED NOTES:
PATCH WALL AND LEAD LINING FOLLOWING WALL
BUCKEY REMOVAL. LEAD LINING SHALL BE 116" THICK
AND CONTINUOUS.
USE 2' X 4' CEILING TILES CUT DOWN TO SIZE TO INFILL
CEILING AT UNISTRUT FOR TRACK. SEE STRUCTURAL
DRAWINGS FOR SUPPORT INSTALLATION.
INSTALL NEW SOLID SURFACE COUNTERS AND BASE
CABINETS. CONTRACTOR TO VERIFY EXISTING
DIMENSIONS PRIOR TO MILL WORK. CONTRACTOR TO
MATCH EXISTING DIMENSIONS.
CONTRACTOR TO MATCH EXISTING CEILING HEIGHT.
REFER TO CANON DRAWING FOR ADDITIONAL
DIMENSION & DETAILS.
MODIFY AND RELOCATE EXISTING LAY IN CEILING
SYSTEM UTILITIES AND ALL ABOVE CEILING UTILITIES
AS NEEDED TO COORDINATE STRUCTURAL STEEL
INSTALLATION.
EQEQ
2'x4' SUSPENDED ACOUSTIC CEILING
SUSPENDED ACOUSTIC CEILING
(W/FALSE JOINT)
2'x2' SUSPENDED ACOUSTIC CEILING
GWB CEILING
GWB SOFFIT AT CEILING
HEIGHT TRANSITION
VERTICAL DIFFUSERS AT SOFFITS
SUPPLY DIFFUSER GRILLE
RETURN DIFFUSER GRILLE
CEILING PENDANT SPRINKLER HEAD
FIRE ALARM SMOKE DETECTOR
EXIT SIGN
CAN (RECESSED & SEMI-RECESSED)
LIGHT FIXTURES
LED LIGHT FIXTURE (2x2)
SUSPENDED FLUORESCENT OR LED
LIGHT FIXTURE
SUSPENDED LIGHT FIXTURE
BELOW CEILING
LAYOUT INSTRUCTIONS:
EQ = EQUAL SPACES
= START @ THIS WALL W/STANDARD GRID
= ALIGN NEXT ROOMS GRID W/THIS GRID
SOFFIT-MOUNTED CAN LIGHT
FIXTURES AT SKYLIGHT WALLS OR
WALL-MOUNTED LIGHTS DIRECTLY
BELOW CEILING
OCCUPANCY / MOTION SENSOR
CEILING LEGEND
PA P.A. SPEAKER
M
LED LIGHT FIXTURE (2x2)
NIGHT LIGHT-LIFE SAFETY CIRCUITLS16
54 LED LIGHT FIXTURE (2x4)
L#
A-702 A
B
2ND FLOOR REFLECTED CEILING PLAN
SCALE: 1/4" = 1'-0"2
N
6 6 6
A324
CONTROL
SF
A320
RADIOLOGY
SF
A320
RADIOLOGY
SF
A324
CONTROL
SF
A318A
3' 3' 3' on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE
VA MEDICAL
CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
3/24/2021
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-CSI-712RENOVATE A320 FOR
CANON ULTIMAX
A-702
KWSR
FINISH FLOOR PLAN & DETAILS
N
MATERIAL LEGEND
SCALE: NONE3
FINISH SCHEDULE
SCALE: NONE2
FINISH FLOOR PLAN
SCALE: 1/4" = 1'-0"1
COUNTER TOP DETAILS
SCALE: 1" = 1'-0"4A COUNTER TOP DETAILS
SCALE: 1" = 1'-0"4B
A-702 A
B
FINISH NOTES:
ALL WALLS IN A320 TO BE PAINTED WITH PT-1.
ALL WALLS IN A324 TO BE PAINTED WITH PT-1.
WALL PROTECTION TO REMAIN & PAINT EXCEPT AS NOTED ON 1/A-702.
CONTRACTOR TO REPLICATE DIMENSION OF EXISTING CABINETS.
REPLACE SECTION OF WALL PROTECTION AND PAINT TO MATCH.
PLUMBING ABBREVIATIONS
A/E ARCHITECT / ENGINEER
AD AREA DRAIN/ACCESS DOOR
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AG AIR GAP
AP ACCESS PANEL
AS AUTOMATIC SPRINKLER
ASD ADJUSTABLE SPEED DRIVES
ASD AUTOMATIC SPRINKLER DRAIN
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION, AIR
CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS
ASR AUTOMATIC SPRINKLER RISER
AV ACID VENT
AW ACID WASTE
BFP REDUCED PRESSURE BACKFLOW PREVENTER
BHP BREAK HORSEPOWER
BSP BLACK STEEL PIPE
BT BATHTUB
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CELSIUS
CA COMPRESSED AIR
CGA COMPRESSED GAS ASSOCIATION
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CO CLEANOUT
COR CONTRACTING OFFICER'S REPRESENTATIVE
CS CLINICAL SINK
CV CONTROL VALVE
DCW DOMESTIC COLD WATER
DFU DRAINAGE FIXTURE UNITS
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DI DEIONIZED WATER
DN DOWN
DOE DEPARTMENT OF ENERGY
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
EL ELEVATION
EMCS ENERGY MONOSERRAT AND CENTRAL SYSTEM
EPA ENVIROMENTAL PROTECTION AGENCY
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
EWS EYE WASH STATION
EWS/SH EYE WASH/DRENCH SHOWER
EX EXISTING
F FAHRENHEIT
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FM FLOW METER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FS FLOOR SINK
FS FLOW SWITCH
FU FIXTURE UNITS
GAL GALLON
GCO GRADE CLEANOUTS
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GRS GAS REGULATOR STATION
GT GREASE TRAP
GVTR GAS VENT THROUGH ROOF
GWH GAS FIRED WATER HEATER
H&CW HOT AND COLD WATER
HB HOSE BIBB
HD HUB DRAIN
HEX HEAT EXCHANGER
HP HORSEPOWER
HS HAND SINK
HST HOT WATER STORAGE TANK (DOMESTIC)
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HYD HYDRANT
ID INSIDE DIAMETER
IE INVERT ELEVATION
ICW INDUSTRIAL COLD WATER
IHW INDUSTRIAL HOT WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
KW KILOWATT
KWH KILOWATT-HOUR
L/S LITER PER SECOND
LA LABORATORY AIR
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LCW LABORATORY COLD WATER
LHW LABORATORY HOT WATER
LNG LIQUID NATURAL GAS
LOX LIQUID OXYGEN
LV LABORATORY VACUUM
LW LOW WATER
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH 1000 BTUH
MED MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MH MANHOLE
MOU MEMORANDUM OF UNDERSTANDING
MSB MOP SERVICE BASIN
MV MEDICAL VACUUM
N2 NITROGEN
N20 NITROUS OXIDE
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM. NOMINAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
O2 OXYGEN
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OR OPERATING ROOM
OVFL OVERFLOW
PA PASCAL
PD PRESSURE DROP OR DIFFERENCE
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAGE
PP PLUMBING PUMP
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ATMOSPHERE
PSIG POUNDS PER SQUARE INCH GAGE
PTRV PRESSURE TEMPERATURE RELIEF VALVE
PW POTABLE WATER
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RP RECIRCULATION PUMP
RO REVERSE OSMOSIS WATER
RWL RAIN WATER LEADER
SAN SANITARY SEWER
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION
SCFM STANDARD CUBIC FOOT/MINUTE
SCW SOFTENED COLD WATER
SDMH STORM DRAIN MANHOLE
SMH SANITARY MANHOLE
SP SUMP PUMP
SPR SPRINKLER LINE
SQFT/SF SQUARE FEET
SS STAINLESS STEEL
ST STORAGE TANK
SW STORM WATER
TCV TEMPERATURE CONTROL VALVE
TD TEMPERATURE DIFFERENCE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSTAT THERMOSTAT
TWR TEMPERED WATER RETURN
TWS TEMPERED WATER SUPPLY
TYP TYPICAL
V VENT
VAC VACUUM
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
VP VACUUM PUMP
VS VENT STACK
VSD VARIABLE SPEED DRIVE
VTR VENT THROUGH ROOF
W WASTE
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAGE
WH WALL HYDRANT
WH WATER HEATER
WHA WATER HAMMER ARRESTER
WL WATER LINE
WM WATER METER
WPD WATER PRESSURE DROP
WS WASTE STACK
WSFU WATER SUPPLY FIXTURE UNITS
YCO YARD CLEANOUT
YH YARD HYDRANT
TYPICAL UNIT NO.
GENERAL DRAWING SYMBOLS
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
SECTION LETTER
DRAWING NUMBER WHERE SHOWN
NATURAL GAS, BELOW GRADE
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
EQUIPMENT ABBREVIATION (PUMP)
PUMP NO.3 IN BUILDING NO.26
DIRECTION OF PIPE PITCH (DOWN)
DOMESTIC COLD WATER, COLD WATER
DOMESTIC HOT WATER, HOT WATER
DOMESTIC HOT WATER RETURN
MEDICAL AIR
MEDICAL VACUUM
LABORATORY AIR
LABORATORY VACUUM
ORAL EVACUATION
INDUSTRIAL AIR
DRAIN
UNION
VENT (SANITARY)
SOIL, WASTE, OR SANITARY SEWER
SANITARY SEWER, BELOW GRADE
STORM WATER
STORM WATER, BELOW GRADE
SOFT WATER
FILTERED COLD WATER
DRINKING WATER SUPPLY
DRINKING WATER RETURN
TEMPERED WATER SUPPLY
TEMPERED WATER RETURN
NITROUS OXIDE
OXYGEN
NITROGEN
NATURAL GAS
FUEL OIL SUPPLY
GLOBE VALVE
FUEL OIL DISCHARGE
FUEL OIL VENT
FUEL OIL RETURN
BUTTERFLY VALVE
GENERAL PLUMBING SYMBOLS
DIRECTION OF FLOW
ANCHOR
REDUCER OR INCREASER
ECCENTRIC REDUCER
TOP CONNECTION, 45° OR 90°
THREE-WAY MODULATING CONTROL VALVE
BOTTOM CONNECTION, 45° OR 90°
SIDE CONNECTION
CAPPED OUTLET
RISE OR DROP IN PIPE
PIPE DOWN
PIPE UP
POINT OF CONNECTION BETWEEN
NEW AND EXISTING WORK
LIMIT OF DEMOLITION
AV
INVERTED BUCKET TRAP SET
INCLUDING PIPING ACCESSORIES
FLOAT & THERMOSTATIC TRAP SET
INCLUDING PIPING ACCESSORIES
STRAINER
THERMOMETER
PRESSURE GAGE
FLOW ELEMENT
CLEAN OUT; FLOOR AND WALL
HOSE BIB
PLUMBING VALVE SYMBOLS
PLUMBING PIPING SYMBOLS
GATE VALVE
GATE VALVE WITH 3/4 " HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BALL VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY TWO POSITION CONTROL VALVE
PRESSURE REGULATING VALVE
AUTOMATIC FLOW CONTROL VALVE
PRESSURE RELIEF VALVE
MANUAL AIR VENT
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
P-105
A P-105
FE
CO CO
1 2
KEY NOTE SYMBOL
MULTIPLE KEY NOTES
APPLYING TO THE SAME ITEM
HB
FLEXIBLE CONNECTION
PLUG VALVE
PRESSURE REDUCING VALVE
DRAWING BLOCK OR DETAIL TITLE, TYPICAL
D D
SW SW
MA MA
MV MV
SAN SAN
FOV
DRAWING TITLE
SCALE: 1/8" = 1'-0"1
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE
VA MEDICAL
CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
3/24/2021
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
52847-RENOVATE A320 FOR
CANON ULTIMAX
PG-001
KWSR
PLUMBING ABBREVIATIONS, SYMBOLS
AND NOTES
SF
A324
CONTROL
SF
RISER #19
DOM. COLD &
HOT
WASTE
#37A
WASTE/VENT
#36A
A320
RADIOLOGY
SF
A324
CONTROL
SF
RISER #19
DOM. COLD &
HOT
WASTE
#37A
WASTE/VENT
#36A
A226
EXAM
SF
A224
EXAM
120SF
A222
EXAM
SF
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE
VA MEDICAL
CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
3/24/2021
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
52847-RENOVATE A320 FOR
CANON ULTIMAX
P-101
KWSR
PLUMBING FLOOR PLANS
N
A320 PLUMBING DEMOLITION PLAN
SCALE: 1/4" = 1'-0"1
DRAWING KEYED NOTES:
EXISTING:
· REMOVE FIXTURE AND SINK.
NEW:
· INSTALL SINK AND FIXTURE AS SHOWN ON PLAN (SEE
SPECIFICATIONS).
· INSTALL NECESSARY DOMESTIC HOT AND COLD PIPING FOR NEW
FIXTURES, CONNECT TO RELOCATED RISER #19. COORDINATE WITH
GENERAL CONTRACTOR AND VAMC COR.
DRAWING GENERAL NOTES:
1. SCHEDULE ALL SHUTDOWNS REQUIRED WITH VAMC COR. SHUTDOWNS
SHALL NOT INTERFERE WITH FACILITY OPERATIONS. PROVIDE TEMPORARY
SYSTEMS DURING SHUTDOWNS AS REQUIRED.
2. MAINTAIN THE INTEGRITY OF ALL EXISTING EQUIPMENT AND SYSTEMS
LOCATED OUTSIDE THE WORK AREA AND INTERRUPTED BY ANY REMOVAL
OR NEW INSTALLATION WORK. PROVIDE ALL ADDITIONAL PIPING, FITTINGS,
ACCESSORIES, ETC. REQUIRED TO EXTEND AND RECONNECT ANY
REMAINING EQUIPMENT AND SYSTEMS.
3. VERIFY ALL INVERTS AND PIPING ROUTES PRIOR TO INSTALLATION.
PROVIDE ALL NECESSARY OFFSETS AND FITTINGS REQUIRED TO MAKE
SYSTEM OPERATIONAL.
4. PROVIDE ALL SLEEVES, CORE DRILLING, WATER AND SMOKE FIRE SEALING
OF PIPING PENETRATIONS THROUGH WALLS AND FLOORS AS REQUIRED.
COORDINATE WITH VAMC COR.
5. COORDINATE THE INSTALLATION OF ALL PLUMBING PIPING SLEEVE
LOCATIONS INSTALLED THROUGH OR WITHIN CONCRETE FLOORS OR
BLOCK WALLS WITH VAMC COR.
6. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED.
OFFSETS IN PIPING AROUND OBSTRUCTIONS SHALL BE PROVIDED AS
REQUIRED.
7. ACCESS DOORS FOR VALVES AND EQUIPMENT LOCATED IN CONCEALED
LOCATIONS WILL BE PROVIDED BY THE GENERAL TRADES. THE PLUMBING
TRADE SHALL BE RESPONSIBLE FOR THE SIZE AND LOCATION. COORDINATE
ALL WORK.
8. THE PLUMBING CONTRACTOR IS REQUIRED TO REMOVE ALL EXISTING DEAD
LEG PIPING WITHIN THE CONSTRUCTION LIMITS OF THIS PROJECT. THE
PLUMBING CONTRACTOR SHALL DEMOLISH ALL PIPING BACK TO THE
EXISTING MAINS.
9. MODIFY AND RELOCATE EXISTING LAY IN CEILING SYSTEM UTILITIES AND
ALL ABOVE CEILING UTILITIES AS NEEDED TO COORDINATE STRUCTURAL
STEEL INSTALLATION.
N
A320 PLUMBING PLAN
SCALE: 1/4" = 1'-0"2
N
2ND FLOOR PLUMBING PLAN
SCALE: 1/4" = 1'-0"3
ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE
VA MEDICAL
CENTER
ENGINEERING
DEPARTMENT
ISSUED DATE
800 IRVING AVE. SYRACUSE, NY 13210
3/24/2021
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
52847-CSI-712RENOVATE A320 FOR
CANON ULTIMAX
MG-001
KWAM
MECHANICAL ABBREVIATIONS,
SYMBOLS & NOTES
GENERAL PIPING SYMBOLS
A/E ARCHITECT / ENGINEER
AAD AUTOMATIC AIR DAMPER
AAV AUTOMATIC AIR VENT
AD ACCESS DOOR
AF AFTER FILTER
AFF ABOVE FINISHED FLOOR
AHU AIR-HANDLING UNIT
A.I. ANALOG INPUT
AMP AMPERAGE
A.O. ANALOG OUTPUT
AP ACCESS PANEL
APD AIR PRESSURE DROP
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AV AUTOMATIC VENT
AW AIR WASHER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BOD BOTTOM OF DUCT ELEVATION
BOD BASIS OF DESIGN
BOP BOTTOM OF PIPE ELEVATION
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CEILING DIFFUSER
CD-1 CONSTRUCTION DOCUMENTS
(SUBMISSION1)
CD-2 CONSTRUCTION DOCUMENTS
(SUBMISSION2)
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CO CLEAN OUT
CP CONDENSATE PUMP
CR CEILING REGISTER
CRAC COMPUTER ROOM AIR CONDITIONING
UNIT
CU CONDENSING UNIT
CW COLD WATER (POTABLE)
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN (TO
COOLING TOWER)
CWS CONDENSER WATER SUPPLY
(FROM COOLING TOWER)
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
DB DECIBELS
Db DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG, ° DEGREE(S)
DF DIFFUSER
D.I. DIGITAL INPUT
DIA, Ø DIAMETER
D.O. DIGITAL OUTPUT
DOM DOMESTIC
DP DEW POINT TEMPERATURE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DSS DUCTLESS SPLIT-SYSTEM (EVAPORATOR)
DX DIRECT EXPANSION
EA EXHAUST AIR
EA. EACH
EAT ENTERING AIR TEMPERATURE
E.C. ELECTRICAL CONTRACTOR
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EH EXHAUST HOOD
EJ EXPANSION JOINT
ENT ENTERING
ER EXHAUST REGISTER
(ER) EXISTING TO REMAIN
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
(E) EXISTING
EXH EXHAUST
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/S DPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
FM FLOW METER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FR FLOOR REGISTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
G.C. GENERAL CONTRACTOR
GF/CI GOVERNMENT FURNISHED,
CONTRACTOR INSTALLED
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GRR GLYCOL-WATER RUN AROUND RETURN
GRS GLYCOL-WATER RUN AROUND SUPPLY
GS GALVANIZED STEEL
H HUMIDIFIER
H&CW HOT & COLD WATER
HCP HEATING WATER CIRCULATING PUMP
HC HEATING COIL
HD HEAD
HD HOOD
HOA HAND/OFF/AUTOMATIC
HP HORSEPOWER
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
HZ HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IRH INFRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
J (INTENTIONALLY LEFT BLANK)
kPa KILOPASCAL kW KILOWATT
L/s LITERS PER SECOND
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LH LATENT HEAT
LPR LOW PRESSURE RETURN (STEAM CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN (CLEAN)
LPS LOW PRESSURE STEAM
LPSC LOW PRESSURE STEAM (CLEAN)
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MA MIXED AIR
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MD MOTORIZED DAMPER
MIN MINIMUM
MM, mm MILLIMETER
MOD MOTOR OPERATED DAMPER
MOV MOTOR OPERATED VALVE
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MV MANUAL VENT
MZ MULTI-ZONE
(N) NEW
NA NOT APPLICABLE
NC NORMALLY CLOSED
NO NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OAD OUTSIDE AIR DAMPER
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
P PUMP
PA PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PG PRESSURE GAUGE
PHC PREHEAT COIL
PPM PARTS PER MILLION
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAUGE
PSV PRESSURE SAFETY VALVE
(R) RELOCATE/RELOCATED
R/E RETURN OR EXHAUST
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
RCP RADIANT CEILING PANEL
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RTU ROOF TOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATOR DEVICE
SAT SUPPLY AIR TEMPERATURE
SCFM STANDARD CUBIC FEET PER MINUTE
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SENS SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS, SST STAINLESS STEEL
ST STEAM TRAP
SVS STEAM VENT SILENCER
T&PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TYP TYPICAL
UC UNDER CUT
UL UNDERWRITERS LABORATORY
V VALVE
VAV VARIABLE AIR VOLUME
VB VACUUM BREAKER
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
W WATTS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCACU WATER-COOLED COMP RM A/C
WEF WALL EXHAUST FAN
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOW METER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAUGE
WHA WATER HAMMER ARRESTOR
1 2
GENERAL NOTES AND CONDITIONS
1. THESE DRAWINGS WERE PREPARED FROM INFORMATION TAKEN FROM THE AVAILABLE
BUILDING DRAWINGS, ARCHITECTURAL BACKGROUNDS PROVIDED AND FIELD SURVEY
INFORMATION COMPILED BY THE VA ENGINEERING DESIGN TEAM FOR THE PURPOSE OF
ENGINEERING DESIGN. EXISTING CONDITIONS ARE SHOWN AS ACCURATELY AS
POSSIBLE. THERE IS THE POSSIBILITY THAT CONDITIONS SHOWN ARE NOT EXACTLY AS
EXISTING. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, LOCATIONS,
SIZES AND CONDITIONS AT THE SITE AND REPORT ANY DISCREPANCIES TO THE
ENGINEER PRIOR TO BEGINNING INSTALLATION OR FABRICATION WORK.
1.1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO REVIEW THE PLANS AND
SPECIFICATIONS, AS WELL AS ALL RELATED PROJECT PLANS AND SPECIFICATIONS
FROM OTHER DISCIPLINES, TO BECOME FAMILIAR WITH THE FULL PROJECT SCOPE
AND COORDINATED RESPONSIBILITIES.
1.2. SHOULD IT APPEAR THAT THE WORK INTENDED TO BE DESCRIBED OR RELATED
WORK ARE NOT SUFFICIENTLY DETAILED OR EXPLAINED ON THE DRAWINGS, OR IN
THE SPECIFICATIONS, CONSULT THE COR FOR NECESSARY CLARIFICATIONS, AND
CONFORM TO THOSE CLARIFICATIONS INSOFAR AS THEY ARE CONSISTENT WITH
THE ORIGINAL DRAWINGS AND SPECIFICATIONS. IN NO CASE SHALL WORK
PROCEED IN UNCERTAINTY.
1.3. EQUIPMENT ARRANGEMENTS ARE DESIGNED TO SHOW PREFERRED
CONFIGURATIONS TO SUIT KNOWN CONDITIONS. ACTUAL INSTALLATION BY
CONTRACTOR MAY BE ALTERED AS REQUIRED TO SUIT FIELD CONDITIONS
ENCOUNTERED DURING CONSTRUCTION WITHOUT COMPROMISING THE INTENT OF
THE ORIGINAL DESIGN. COORDINATE ANY MODIFICATIONS WITH THE COR PRIOR
TO STARTING WORK IN AREAS AFFECTED.
1.4. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS
AT SITE PRIOR TO STARTING WORK.
1.5. DO NOT SCALE DRAWINGS.
2. THE CONTRACTOR WILL BE RESPONSIBLE FOR ENSURING THAT ALL RULES AND
REGULATIONS, INCLUDING THOSE WHICH MAY BE ISSUED BY THE OWNER, ARE BEING
OBSERVED, PARTICULARLY WORKPLACE SAFETY AND THE CONDUCT OF ALL THOSE
EMPLOYED DIRECTLY AND INDIRECTLY ON THE PREMISES, AND THE OWNER'S
EMPLOYEES WHO MAY BE IMPACTED OR AFFECTED BY CONSTRUCTION ACTIVITIES. THE
CONTRACTOR WILL INSTALL SIGNAGE, BARRIERS, AND OTHER MEANS TO PROVIDE
WARNING AND PERSONNEL SAFETY. PLACEMENT OF THESE ITEMS WILL BE
COORDINATED WITH THE OWNER AND HIS ONGOING OPERATIONS AND WILL PROMPTLY
BE REVISED WHEN WORK IN A PARTICULAR AREA HAS BEEN COMPLETED.
2.1. DURING PERFORMANCE OF WORK, THE CONTRACTOR SHALL BE RESPONSIBLE
FOR PROVISION AND MAINTENANCE OF WARNING SIGNS, LIGHT SIGNAL DEVICES,
GUARD LIGHTS, BARRICADES, GUARD RAILS, FENCES AND OTHER DEVICES,
APPROPRIATELY LOCATED ON AND AROUND THE JOB SITE WHICH GIVE PROPER
AND UNDERSTANDABLE WARNING TO PERSONS WITH REGARD TO HAZARDOUS
CONDITIONS, EQUIPMENT AND OPERATIONS BEING PERFORMED IN CONJUNCTION
WITH THE WORK.
3. THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH OTHER TRADES FOR
ITEMS IN THEIR SCOPE OF WORK WHICH COULD REQUIRE ADDITIONAL
MECHANICAL/PLUMBING WORK, AND ITEMS THAT ARE NOT INDICATED ON THE
DRAWINGS.
4. THIS INSTALLATION WILL CONFORM TO ALL CODES AND THE REQUIREMENTS OF
FEDERAL, STATE, AND LOCAL REGULATORY AGENCIES HAVING JURISDICTION. IN
PARTICULAR, THE WORK WILL BE IN ACCORDANCE WITH THE CURRENT ADOPTED
EDITION OF THE NEW YORK STATE UNIFORM FIRE PROTECTION AND BUILDING CODE
AND ALL OF ITS APPLICABLE SUBCODES AND AMENDMENTS.
5. ALL WORK WILL BE LAWFULLY EXECUTED IN A NEAT AND WORKMANLIKE MANNER AND
WILL BE COMPLETED IN ACCORDANCE WITH THE GOVERNING CODES (ABOVE),
INDUSTRY STANDARDS, AND IN CONFORMANCE WITH THE MANUFACTURERS
RECOMM…