491.26585.KMM CFP Electrical.pdf
PDF 1 MB Posted
- Solicitation number
- RFP 171 270000000293 1
- Issued by
- Washtenaw County, Michigan
About this file
Summary
This is a set of electrical construction drawings for the TLC Center for Forensic Psychiatry - Create Kitchen project located in Saline, Michigan, prepared by the State of Michigan Department of Technology, Management and Budget, Facilities and Business Services Administration, Design and Construction Division. The documents include a First Floor Electrical Demolition Plan (Sheet ED1.01) and a First Floor Power Plan for Unit H (Sheet E3.01), both dated September 6, 2023, with project number 491/20167.SDW and contract number 171CODHHS7255. The drawings were prepared by Peter Basso Associates Inc., consulting engineers based in Troy, Michigan, and are part of Phase 500 of the project. The electrical work involves demolition of existing systems and installation of new electrical infrastructure to support the kitchen renovation, including power distribution, lighting circuits, fire alarm compatibility with existing Simplex Grinnel 4120 systems, lightning protection for the building addition, and coordination with mechanical and security systems. The scope includes removal of conduits and wiring, relocation of branch circuits and junction boxes, installation of new equipment connections, and proper disposal of all demolition materials in accordance with federal, state, and local regulations.
The contract documentation specifies general construction requirements including site examination prior to bid submission, coordination with other trades' drawings, maintenance of electrical service to equipment remaining in service, proper support and rerouting of existing systems, and comprehensive documentation updates such as circuit directories and tagged circuits. Specific construction notes address equipment relocation, TV installation coordination, floor and wall core drilling, ceiling routing of conduits, lightning protection system installation with UL listing requirements, and coordination of ground rod placement with existing utilities. The contract references transformer secondary conductors and motor circuit protection sizing per electrical standard schedules and requires verification of mechanical equipment electrical requirements through shop drawing submittals.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SAMPLE Billable Rate Contract (Rev 04-25).pdf | ||
| Prebid meeting location CFP.pdf | ||
| Billable Rate 26585.pdf | ||
| Project Statement 26585.pdf | ||
| Access and Touring_CFP_SS_008F.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T A
C C
P
T
T
T
T
T
T
ATS ATS ATS
A C
C P
ATS
IC
IC
F
IC
IC
J
FACP
SECURE CORR.
E126
ELECTRICAL
E125
GYMNASIUM
E124
STAIR
F139
ELEVATOR
F138
TRAP
F140
SERVICE LOBBY
F141
CORRIDOR
F137
EQUIP. STORAGE
H102
ELECTRICAL
H101
SOILED
LINEN/RECYCLE
HOLD.
H103
WAREHOUSE
H104
F F.4
F.8 G.1 H J K LG.3 J.8 K.7K.2K.3J.6
14.
14.1
12.9
12.712.6
12.5
11.9
11.6
11.3
14.2
(E)T-DL1HB
(E)DL1HB
(E)L1HD
(E)H1HC
(E)EQDH1HB
(E)T-EQDL1HB
(E)EQDL1HB
(E)EQL1HB
(E)LSDH1HB
(E)LSH1HB
(E)T-LSDL1HB
(E)LSDL1HB
(E)LSH1HB
(E)CRH1HB SECTION 2
(E)CRH1HB SECTION 1
(E)CRDL1HB
(E)T-CRDL1HB
(E)CRDH1HB
(E)CRH1HB
(E )C
V R
P -1
(E)EQATS-5
(E)CRATS-2
(E)LSATS-2
(E)EQATS-2
(E)EDH1HB
(E)T-H1HB2
(E)T-H1HB1
(E)SWGR #1
(E)LSL1EA
(E)CRL1EA
(E)EQL1EA
(E)EQH1EA
(E )T
-D L
E
A
(E)DL1EA
(E)L1EA
(E)LSH1EA
(E)CRH1EA
C R
C -1
E
F
D F
R O
M
E )E
Q H
E
A R
M E
S
IN
G L
E P
H A
S
R
A
N S
F O
R M
E R
C R
C -1
F F
E D
F R
O M
E
)E Q
H E
A R
M E
(E)
(E)
(E)SWBD-H1HB
THE FOLLOWING DIMENSION EQUALS
ONE INCH WHEN PRINTED TO SCALE.
1"
5145 Livernois, Suite 100
Troy, Michigan 48098-3276
Tel: 248-879-5666
Fax: 248-879-0007 www.PeterBassoAssociates.com
Peter Basso Associates Inc
CONSULTING ENGINEERS
PROJECT TITLE
SHEET TITLE
PROJECT NUMBER
PROJECT DATE
CHECKED BY
SHEET NUMBER
KEY PLAN
NOT TO SCALE
H
PBA Project No.: 2021-0402
J
A RCHITECTS
FILE NO.
FUNDING CODE CONTRACT NO.
STATE OF MICHIGAN
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION
ADAM LACH, RA, DIRECTOR
491/20167.SDW
171CODHHS7255 Y22003
989 752 8107 COPYRIGHT © 2023
WTAARCH.COM
Saginaw, Michigan 48607
100 S Jefferson Ave, Suite 601
2021094
SEPTEMBER 6, 2023
TLC
CENTER FOR FORENSIC
PSYCHIATRY - CREATE
KITCHEN
ED1.01
FIRST FLOOR ELECTRICAL
DEMOLITION PLAN
SALINE, MICHIGAN
491/20167.SDW - PHASE 500:
C R
E V
IT
L
O C
A L
F
IL
E S
\2
-0
-M E
P
F o re n s ic
P s y c h v
G
H e n tr ic h .r v t
/5
/2
:3
:1
P M
ELECTRICAL DEMOLITION GENERAL NOTES:
1 VISIT THE SITE PRIOR TO SUBMISSION OF BID TO EXAMINE THE EXISTING CONDITIONS AND THE EXTENT OF
DEMOLITION WORK.
2 EXAMINE THE DRAWINGS OF OTHER TRADES AND BE FAMILIAR WITH THE DEMOLITION REQUIRED BY OTHER TRADES. PERFORM ALL INCIDENTAL ELECTRICAL DEMOLITION AND/OR RELOCATION REQUIRED TO FACILITATE THE DEMOLITION WORK OF OTHER TRADES, WHETHER OR NOT SPECIFICALLY INDICATED.
3 REMOVE EQUIPMENT OR MATERIALS AS INDICATED ON PLAN WITH CROSS HATCHING. DEMOLITION SHALL
INCLUDE, BUT NOT BE LIMITED TO, THOSE COMPONENTS SHOWN.
4 COORDINATE WITH NEW WORK PLANS, ONE LINE DIAGRAMS AND RISER DIAGRAMS FOR EXTENT OF
DEMOLITION WORK
5 PROVIDE PROPER SUPPORT FOR EXISTING TO REMAIN CONDUITS AND BOXES WHERE EXISTING SUPPORT IS TO BE REMOVED. RE-ROUTE BRANCH CIRCUIT CONDUITS AND RELOCATE JUNCTION BOXES AS REQUIRED TO FACILITATE INSTALLATION OF NEW EQUIPMENT AND SYSTEMS IN CEILING SPACES.
6 REMOVE ALL CONDUIT AND WIRE BACK TO THE SOURCE OR NEAREST UPSTREAM DEVICE REMAINING IN
SERVICE.
7 MAINTAIN ELECTRICAL SERVICE TO ALL LIGHTING FIXTURES, DEVICES AND EQUIPMENT THAT ARE TO REMAIN. EXTEND CONDUIT AND WIRE AS REQUIRED WHERE DEMOLITION WORK AFFECTS ELECTRICAL
SERVICE TO DOWNSTREAM LOADS THAT ARE TO REMAIN.
8 DISPOSE OF ALL MATERIALS OFF SITE AND INCLUDE ALL COSTS FOR DISPOSAL IN BID. ALL MATERIALS SHALL BE DISPOSED OF IN ACCORDANCE WITH ALL FEDERAL, STATE, AND LOCAL REGULATIONS, INCLUDING TCLP TESTING, PROPER DISPOSAL AND/OR RECYCLING OF FLUORESCENT LAMPS.
9 PROVIDE BLANK COVER PLATES WHERE SWITCHES AND DEVICES ARE REMOVED BUT EXISTING WALLS
REMAIN INTACT.
10 RING OUT AND TAG ALL CIRCUITS AFFECTED BY THIS ALTERATION AT BOTH ENDS. MARK ALL UNUSED
CIRCUIT BREAKERS "SPARE".
11 PROVIDE UPDATED TYPED-IN DIRECTORIES FOR ALL PANELS AFFECTED BY THIS ALTERATION.
12 VERIFY ALL UNDERGROUND AND IN SLAB UTILITY LOCATIONS PRIOR TO SAW-CUTTING OR PENETRATING
ANY FLOOR SLAB.
13 COORDINATE ANY SHUT DOWN OF EXISTING SERVICES AND EQUIPMENT THAT ARE REMAINING IN USE WITH THE OWNER'S REPRESENTATIVE. WHERE EXISTING BUILDING SERVICE IS REQUIRED TO BE SHUT DOWN, INCLUDE ALL ASSOCIATED OVERTIME COSTS TO PERFORM THIS WORK DURING WEEKENDS AND EVENINGS INCLUDE ALL COSTS FOR PROVIDING TEMPORARY POWER WHERE SHUT DOWNS MUST OCCUR FOR PERIODS LONGER THAN THESE HOURS. COORDINATE ELECTRICAL SHUT DOWNS WITH THE OWNER
72 HOURS PRIOR TO SHUT DOWN.
# DEMOLITION KEY NOTES:
A SALVAGE FOR RELOCATION. EXISTING BRANCH CIRCUIT TO REMAIN.
B SALVAGE FOR RELOCATION. REMOVE CONTROL WIRING UP TO CEILING SPACE.
C SALVAGE FOR RELOCATION. EXISTING LIGHTING BRANCH CIRCUIT TO REMAIN.
SCALE: 1/8" = 1'-0"
ELECTRICAL DEMOLITION PLAN
A
A
A
B
C
C
NO. REVISION DATE
T
T
T
T
T
ATS ATS ATS
C
(6 .6 x
.2 x
(6
.6 x x
(6
.6 x x
(6 .6 x x
(609.6 x 1524)
24x60 (609.6 x 1524)
24x60 (609.6 x 1524)
24x60 (609.6 x 1524)
24x60
(609.6 x 1524)
24x60 (609.6 x 1219.2)
24x48
C
H
C
H
E1
E1
D
C H
D
C
H
DC
H
D
D
C C W I
C W O
(6 .6 x
.2 x
D (6
.6 x
.8 x
H
C
C
C
H
D D
D
C
H
C
H
D
C C
C
H
HC
G G
G
CWI
G D
G G
G
G
G
C
H
C
H
C
H
C
H
H C
DC
H
D C H
D
CWOCWI
UTILITY
CABINET.
UTILITY
CABINET.
x
(6
.6 x
.2
24x48 (609.6 x 1219.2)
24x48 (609.6 x 1219.2) x
(6
.6 x x
(6
.6 x x
(6
.6 x x
(6
.6 x x
(6
.6 x
.2 x
(6
.6 x x
(6
.6 x
.2 x
(6
.6 x x
(6
.6 x
.2 x
(6
.6 x x
(6
.6 x
.2 x
(6
.6 x
1'-3"
(6 .6 x
.8 x
(6 .6 x
.6 x
ATS
@2
@3
@4
@4.5
@6
@E@D@C
DRY STORAGE
H124
FREEZER
COOLER
COOLER
OFFICE
H125
CHEMICAL STOR.
H129
STAFF TOILET
H126
CORRIDOR
(SOUTH
CONNECTOR)
H132
SECURE CORR.
E126
GYMNASIUM
E124
SOILED
LINEN/RECYCLE
HOLD.
H103
ELECTRICAL
H101
EQUIP. STORAGE
H102
ELECTRICAL
E125
SUPV.
F118
SUPV.
F117
CART WASH
H128
FITNESS
E127
TOILET
F119
PROGRAM
OFFICES
F120
DINING
H131
KITCHEN
H123
CORRIDOR
H122
CORRIDOR
F137
ELEVATOR
F138
STAIR
F139
TRAP
F140
SERVICE LOBBY
F141
WAREHOUSE
H104
SERVERY
H130
BREAK ROOM
H127
STAIR
H121
E6.01
F F.4
F.8 G.1 H J K L M N PG.3 J.8 K.7K.2K.3J.6
14.
14.1
12.9
12.712.6
12.5
11.9
11.6
11.3
14.2
15.
(E)SWGR #1
(E)T-H1HB1
(E)T-H1HB2
(E)EDH1HB
(E)EQATS-2
(E)SWBD-H1HB
(E)LSATS-2
(E)CRATS-2
(E)T-DL1HB
(E)T-EQDL1HB
(E)CRH1HB
(E)CRDH1HB
(E)EQDL1HB
(E)T-CRDL1HB
(E)LSH1HB
(E)T-LSDL1HB
(E )C
V R
P -1
(E)CRDL1HB
(E)LSDL1HB (E)CRH1HB SECTION 1
(E)LSH1HB
(E)CRH1EA
(E)LSH1EA
(E)L1EA
(E)DL1EA
(E )T
-D L
E
A
(E)EQH1EA
(E)EQL1EA
(E)CRL1EA
(E)LSL1EA
@B.5 @C.5
@4.6
@5
@5.5
STORAGE
H119
CORR. (GYM
CONN.)
H133
RP-1-1
RP-1-1 RP-1-1
RP-1-1
RP-1-1
RP-1-1
RP-1-2
RP-1-2
RP-1-2
RP-1-2
RP-1-2
RP-1-2
RP-1-3RP-1-3
RP-1-3
RP-1-3
RP-1-3
RP-1-3
SECUR. VEST.
H116A
RP-1-4
RP-1-4
R P
-1 -4
R P
-1 -4
R P
-1 -4
RP-1-4
RP-1-5
R P
-1 -5
W P
,T R
W P
,T R
WP,TR
WP,TR
W P
,T R
WP
(E)DL1HB
(E)EQDH1HB
(E)EQL1HB
(E)LSDH1HB
(E)CRH1HB SECTION 2
(E)EQATS-5
(E)H1HC
(E)L1HD
+72"
RP-1-10
RP-1-11
R P
-1 -2
UP TO
GROUND BUS
BAR IN H201
UP TO
DP-1-H201
UP TO T-
DP-2-H201
5H
CUH
6H
CUH
RP-1-16
RP-1-17
3H
CUH
RP-1-18
4H
CUH
RP-1-19
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
UP TO
GROUND BUS
BAR IN H201
UP TO
LS-H201
CORRIDOR (WEST
CONNECTOR)
H120
11H
UH
RP-1-25
UP TO
EQD-H201
WP
WP
+96"
THE FOLLOWING DIMENSION EQUALS
ONE INCH WHEN PRINTED TO SCALE.
1"
5145 Livernois, Suite 100
Troy, Michigan 48098-3276
Tel: 248-879-5666
Fax: 248-879-0007 www.PeterBassoAssociates.com
Peter Basso Associates Inc
CONSULTING ENGINEERS
PROJECT TITLE
SHEET TITLE
PROJECT NUMBER
PROJECT DATE
CHECKED BY
SHEET NUMBER
KEY PLAN
NOT TO SCALE
H
PBA Project No.: 2021-0402
J
A RCHITECTS
FILE NO.
FUNDING CODE CONTRACT NO.
STATE OF MICHIGAN
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION
ADAM LACH, RA, DIRECTOR
491/20167.SDW
171CODHHS7255 Y22003
989 752 8107 COPYRIGHT © 2023
WTAARCH.COM
Saginaw, Michigan 48607
100 S Jefferson Ave, Suite 601
2021094
SEPTEMBER 6, 2023
TLC
CENTER FOR FORENSIC
PSYCHIATRY - CREATE
KITCHEN
E3.01
FIRST FLOOR POWER PLAN
- UNIT H
SALINE, MICHIGAN
491/20167.SDW - PHASE 500:
C R
E V
IT
L
O C
A L
F
IL
E S
\2
-0
-M E
P
F o re n s ic
P s y c h v
G
H e n tr ic h .r v t
/5
/2
:3
:0
P M
ELECTRICAL GENERAL NOTES:
1 THESE DRAWINGS REPRESENT THE GENERAL EXTENT AND ARRANGEMENT OF SYSTEMS.
COORDINATE EXACT EQUIPMENT LOCATIONS, ELEVATIONS, AND FINAL CONNECTION
REQUIREMENTS. PROVIDE EACH SYSTEM COMPLETE, INCLUDING ALL NECESSARY
COMPONENTS, FITTINGS AND OFFSETS.
2 INSTALL SYSTEMS SUCH THAT REQUIRED CLEARANCE AND SERVICE ACCESS SPACE IS
PROVIDED AROUND ALL MECHANICAL AND ELECTRICAL EQUIPMENT, AND AROUND ANY
COMPONENTS WHICH REQUIRE SERVICE ACCESS.
3 COORDINATE AND PROVIDE ACCESS DOORS WITHIN INACCESSIBLE CEILING, SHAFT, AND
CHASE AREAS FOR ALL COMPONENTS WHICH REQUIRE SERVICE ACCESS. REFER TO
ARCHITECTURAL DRAWINGS FOR CEILING TYPES.
4 PROVIDE SUPPLEMENTARY STEEL AS REQUIRED FOR THE PROPER SUPPORT OF ALL
SYSTEMS.
5 TRANSFORMER SECONDARY CONDUCTORS SHALL BE SIZED IN ACCORDANCE WITH
TRANSFORMER CIRCUIT SIZING SCHEDULE SHOWN ON "ELECTRICAL STANDARD
SCHEDULES DRAWING" UNLESS OTHERWISE NOTED.
6 MOTOR CIRCUIT PROTECTION SHALL BE SIZED IN ACCORDANCE WITH MOTOR CIRCUIT
SIZING SCHEDULES SHOWN ON "ELECTRICAL STANDARD SCHEDULES DRAWING" UNLESS
OTHERWISE NOTED.
7 COORDINATE THE MOUNTING HEIGHTS OF DEVICES WITH ARCHITECTURAL ELEVATIONS
AND THE TRADES INSTALLING THE WORK.
8 REFER TO MECHANICAL SCHEDULE SHEETS FOR ELECTRICAL REQUIREMENTS FOR
MECHANICAL EQUIPMENT. PROVIDE ALL CONNECTIONS, STARTERS, DISCONNECTS, ETC. AS
REQUIRED BY SCHEDULES AND WHERE NOTED ELSEWHERE. VERIFY REQUIREMENTS OF
ALL MECHANICAL EQUIPMENT WITH SHOP DRAWINGS SUBMITTALS. NOTIFY ENGINEER OF
ANY CONFLICTS BETWEEN EQUIPMENT SUBMITTALS AND ELECTRICAL DRAWINGS. WHERE
CIRCUIT SIZES ARE SHOWN ON THE ELECTRICAL DRAWINGS THAT DIFFER FROM WHAT IS
INDICATED ON THE MECHANICAL SCHEDULES, PROVIDE THE CIRCUIT OF HIGHER AMPACITY.
9 REFER TO TEMPERATURE CONTROLS SHEETS FOR REQUIRED FIRE ALARM CONTROL
MODULES, DUCT SMOKE DETECTORS, AND MOTOR CONTROLLERS. PROVIDE ALL
ACCESSORIES INDICATED.
10 REFER TO LIGHTING CONTROL SCHEDULE FOR ROOM CONTROL AND EMERGENCY
LIGHTING CIRCUIT CONTROL REQUIREMENTS. DESIGNATION FOR ROOM IS INDICATED AS A
LETTERED OVAL SYMBOL.
11 ALL FIRE ALARM DEVICES SHALL BE COMPATIBLE WITH EXISTING SIMPLEX GRINNEL 4120
FIRE ALARM SYSTEM. PROVIDE NECESSARY COMPONENTS, MODULES, ETC. AS REQUIRED
FOR A FULLY FUNCTIONAL SYSTEM. RE-TEST AND CERTIFY EXISTING FIRE ALARM SYSTEM
AT COMPLETION OF PROJECT.
12 PROVIDE TAMPER RESISTANT COVER PLATE KENALL WPP SERIES OR EQUAL WHERE
PATIENTS WILL HAVE ACCESS TO DEVICES.
13 REFER TO SECURITY/TELECOMMUNICATION DRAWINGS FOR FINAL DEVICE LOCATIONS AND
RACEWAY REQUIREMENTS. COORDINATE WITH SECURITY REQUIREMENTS WITH
INSTALLING TRADES.
14 COORDINATE ELECTRICAL REQUIREMENTS DEVICE LOCATIONS AND MOUNTING HEIGHTS
WITH KITCHEN EQUIPMENT DRAWINGS, SHOP DRAWINGS AND KITCHEN EQUIPMENT
INSTALLER.
SCALE: 1/8" = 1'-0"
FIRST FLOOR POWER PLAN - UNIT H
# CONSTRUCTION KEY NOTES:
1 INSTALL SALVAGED EQUIPMENT ON NEW ROOF. EXTEND EXISTING BRANCH CIRCUITS AS
REQUIRED.
2 COORDINATE FINAL LOCATION OF TV WITH ARCHITECTURAL DRAWINGS AND TRADES PRIOR
TO ROUGH IN.
3 UP TO SECOND FLOOR ELECTRICAL ROOM E203. CORE EXISTING FLOOR.
4 CORE EXISTING WALL.
5 ROUTE IN CEILING SPACE OF GYM. ROUTE ALONG SIDE NEW MECHANICAL PIPING.
COORIDINATE FINAL ROUTING WITH MECHANICAL TRADES.
6 COORDINATE GROUND ROD PLACEMENT WITH EXISTING UTILITIES PRIOR TO DRIVING THEM
IN.
7 20'-0" #4/0 BARE COPPER CONDUCTOR FOR CONCRETE-ENCASED ELECTRODE IN
FOUNDATION ENCASED BY AT LEASET 2" OF CONCRETE.
8 PROVIDE LIGHTNING PROTECTION FOR WHOLE BUILDING ADDITION. LIGHTNING
PROTECTION SYSTEM SHALL BE UL LISTED MASTER LABEL. REFER TO SPECIFICATIONS FOR
SYSTEM REQUIREMENTS.
9 TIE INTO THE EXISTING LIGHTNING PROTECTION ON EXISTING BUILDING AS REQUIRED.
10 LINE VOLTAGE CLOCK STANDARD ELECTRIC TIME FARADAY 2364 OR OTHER CLOCK
COMPATABLE WITH EXISTING SYSTEM. EXTEND WIRING FROM EXISTING CLOCK HEAD END
SYSTEM AS REQUIRED.
NO. REVISION DATE
COPYRIGHT © 2023
Saginaw, Michigan 48607 989 752 8107
100 S Jefferson Ave, Suite 601
WTAARCH.COM
A RCHITE SCT
CHECKED BY
PROJECT DATE
SHEET NUMBERPROJECT NUMBER
SHEET TITLE
DATENO.
PROJECT TITLE
REVISION
491/20167.SDW - PHASE 500:
CENTER FOR FORENSIC
PSYCHIATRY - CREATE
SALINE, MICHIGAN
2021094
AUGUST 23, 2023
CONSULTING ENGINEERS
Peter Basso Associates Inc
5145 Livernois, Suite 100
Fax: 248-879-0007 Troy, Michigan 48098-3276
Tel: 248-879-5666 www.PeterBassoAssociates.com
PBA Project No.: 2021-0402
FILE NO.
FUNDING CODE CONTRACT NO.
STATE OF MICHIGAN
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION
ADAM LACH, RA, DIRECTOR
491/20167.SDW
171CODHHS7255 Y22003
08/02/23OWNER REVIEW1
KITCHEN
ONE LINE DIAGRAM - NEW
WORK
E5.01
TLC