This is a Standard Form 30 (Amendment of Solicitation/Modification of Contract) issued by the GSA PBS Office of Acquisition Management on June 29, 2026, for solicitation 47PD5326R0039. The amendment incorporates site visit questions and answers along with a site visit sign-in sheet for the USMS Egress Modifications project at the William Guy Federal Building in Bismarck, North Dakota. The proposal due date remains unchanged at 10:00 AM CST on July 17, 2026, and all other terms and conditions remain unmodified.

The site visit documentation dated June 25, 2026, addresses five key technical questions regarding egress modifications. Question 1 clarifies that alarmed crash bars on three doors should utilize independent battery-operated local audible alarms rather than hardwired integration with the building's security system, with all devices standardized. Question 2 confirms that signage reading "Emergency Exit Only" with audible alarm warnings must be provided on the egress side of each alarmed door per Section 5, Note 4. Questions 3 and 4 address junction box placement for exterior access badge readers at the courthouse front entrance, directing compliance with PBS Core Building Standards, ADA guidelines, and USMS Publication 64 regulations. Question 5 specifies that double gang back boxes with mud rings must be flush-mounted per USMS Publication 64, with the USMS NPSC responsible for providing and installing security hardware and the general contractor responsible for installation unless special back boxes are required by the NPSC.

View the file

Other files for this federal contract opportunity

Other files attached to ND0037ZZ USMS Egress Modifications Bismarck 3409747, newest first.
File Type Posted
RFP 47PD5326R0039 Unsuccessful Letter.pdf PDF
Solicitation Amendment 47PD5326R0039_0001.pdf PDF
GSA527 Contractors Qualifications and Financial Information.pdf PDF
Vendor Fitness Determination Training Manual.pdf PDF
RFP 47PD5326R0039 Form 1442.pdf PDF
RFP 47PD5326R0039 EQPMBA-26-0299 USMS Egress Modifications Bismarck 3409747.pdf PDF
FO SB Agreement 20260617.pdf PDF
FO SB Soliciation 20260617.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE

2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)

7. ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15C. DATE SIGNED

15A. NAME AND TITLE OF SIGNER (Type or print)

16C. DATE SIGNED

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PAGE OF PAGES

6. ISSUED BY CODE

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

Previous edition unusable

PQCC

Chanel Bennett, Contracting Officer

The purpose of this modification is to:

-Incorporate site visit questions and answers -Site visit sign-in sheet The proposal due date remains unchanged and due NLT 10:00AM CST July 17, 2026.

All other terms and conditions remain unchanged.

PQCC

PBS Office of Acquisition Management/Acquisition Project Delivery Contracting Division West/Contracting Branch C 1800 F Street NW Washington , DC 20405 USA

PBS Office of Acquisition Management/Acquisition Project Delivery Contracting Division West/Contracting Branch C 1800 F Street NW Washington , DC 20405 USA

EQPMBA-26-0299

47PD5326R0039

1 3

6/29/2026

6/17/2026

6/29/2026

1: Alarmed crash bars: the three doors identified for alarmed crash bars already have monitored open/close sensors on them that the CSO's observe from their central control room. Do you want the alarmed crash bars hooked up to the building's security system directly? No Or do you want the new crash bars to only have a battery powered local audible alarm when someone uses the crash bar to open the door? Yes, the independent battery-operated device is sufficient. One option is very expensive while the other is very economical. Can you specify an example of the desired alarmed crash bar and if you want battery or hardwired alarm? All we will ask is that all devices are the same.

2: Do you want signage included in the bid indicating the presence of alarmed exits placed in advance of the exits? Yes, Section 5, Note 4) The contractor shall provide signage on the egress side of each door stating Emergency Exit Only and warn of audible alarm.

3: Do you have a specific rough opening size for the junction box required for the exterior access badge reader by the front door of the courthouse? No

4: The logical placement for the card reader is crowded by a handicap door opener and electrical outlet (see attached picture). Can the new junction box get moved to the door side of the column? And are there any specific parameters for the installation height of the junction box? Please follow the PBS Core Building Standards in reference to the ABAAS guidelines and the USMS Publication 64 regulations.

5: Is there a specific call out for surface mounted junction box verses a flush mount junction box? And if a flush mount is required, is a "goof plate" permissible to cover over-cuts for the rectangular opening? USMS PUBLICATION 64 states: The GSA General Contractor is responsible for installing double gang back boxes for all OSS security equipment, unless otherwise noted by OSS. Double gang back boxes with a mud ring are the standard installation practice for court space. Back boxes must be flush mounted and when necessary, comply with the American with Disabilities Act (ADA) height specifications. The USMS NPSC is responsible for providing and installing the security hardware. If special back boxes are necessary, the NPSC shall supply them to the general contractor for installation.

_Solicitation Amendment 47PD5326R0039_0001