467189 Aberdeen Armory FACP Bid Drawings.pdf

PDF 2 MB Posted

Attached to
Replace and Install Fire Alarm System - Aberdeen Armory
Solicitation number
26IFB19927
Issued by
Brown County, South Dakota

About this file

This is a set of bid drawings for a fire alarm system replacement project issued by the South Dakota Department of the Military, Army National Guard, Construction & Facility Management Office, for the Aberdeen Armed Forces Readiness Center (CFMO# 467189). The project involves removing and replacing an existing broken and outdated fire alarm control panel (FACP), notification appliance circuits (NAC), addressable relays, smoke detectors, heat sensors, horn strobes, and other fire detection and notification devices throughout the facility. The contractor shall install a new FA/MNS combination system using Honeywell Fire-Lite ES-200X as the FACP basis and ECC-50/100(E) as the emergency command center, with all devices, wiring, conduit, and accessories necessary for a fully functioning fire detection and notification system. The project includes installation of manual pull stations, duct smoke detection, HVAC shut-down capability per NFPA 90A, and mass notification system (MNS) devices including scrolling LED message centers at points of egress and speaker/strobe combinations compatible with the new system. The drawings are dated July 2026 at 100% submittal phase and cover four armory sections (Southwest, Southeast, Northwest, and Northeast) plus site overview and single-line diagram sheets.

The project requires compliance with UFC 3-600-01, 4-021-01, 4-101-01, Army National Guard Design Guide 415, NFPA 70, NFPA 72, NFPA 90A, NFPA 101, and the 2024 IBC. The contractor must verify actual device locations, quantities, and types in the field and coordinate with the owner prior to installation to resolve any conflicts, with no additional compensation provided for conflicts discovered during rough-in. All fire alarm cables shall be installed in metal raceways independent of other cabling, with all equipment securely fastened and properly labeled. The contractor is responsible for completing touch-up painting, replacing damaged acoustic ceiling tiles, and obtaining a Certificate of Final Electrical Inspection. All new equipment shall be Honeywell Technologies Fire-Lite system unless approved otherwise by the owner, and no work shall be performed in the Army Reserve section of the facility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET No:

SO

U

TH

D

AK

O

TA

A

RM

Y

N

AT

IO

N

AL

G

U

AR

D

CO

N

ST

RU

CT

IO

N

F

AC

IL

IT

Y M

AN

AG

EM

EN

T O

FF

IC

E

W

ES

T M

AI

N

S

TR

EE

T, R

AP

ID

C

IT

Y, S D

5)

-6

FA

X

(6

) 7

-6

DATE:

SUBMITTAL:

CO

VE

R

SH

EE

T

R

EP

LA

C

E

FI

R E

SY

ST

EM

S

A B

ER

D

EE

N

A R

M

ED

F O

R C

ES

R

EA

D

IN

ES

S C

EN

TE

R C

FM

O

DEPARTM

ENT

OF

TH

E M

IL ITARY

S T A

T E

O F

S

U

T H

D

A K

O

TA

100%

8/2026

G-001

SCALE: NTS REVISIONS

ZONE LTR DATE APPROVED

SHEET INDEX

SOUTH DAKOTA

DEPARTMENT OF THE MILITARY

REPLACE FIRE SYSTEMS

CFMO# 467189

ABERDEEN ARMED FORCES READINESS CENTER

JULY 2026

STATE REFERENCE MAP

UNAUTHORIZED CHANGES

THE ENGINEER PREPARING THESE PLANS WILL NOT BE RESPONSIBLE FOR, OR

LIABLE FOR, UNAUTHORIZED CHANGES TO OR USES OF THESE PLANS. ALL

CHANGES TO THE PLANS MUST BE IN WRITING AND MUST BE APPROVED BY THE

PREPARER OF THESE PLANS. THE ENGINEER SIGNING THESE PLANS IS

RESPONSIBLE FOR ASSURING THE ACCURACY AND ACCEPTABILITY OF THE

DESIGN HERON.

NOTICE TO CONTRACTOR

THE CONSTRUCTION CONTRACTOR AGREES THAT IN ACCORDANCE WITH

GENERALLY ACCEPTED CONSTRUCTION PRACTICES, HE/SHE WILL BE

REQUESTED TO ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE

CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THE PROJECT,

INCLUDING THE SAFETY OF ALL PERSONS AND PROPERTY. THIS

REQUIREMENT SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO

NORMAL WORKING HOURS. THE CONSTRUCTION CONTRACTOR FURTHER

AGREES TO DEFEND, INDEMNIFY AND HOLD THE DESIGN PROFESSIONAL

HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION

WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING LIABILITY

ARISING FROM THE SOLE NEGLIGENCE OF THE DESIGN ENGINEER.

CITY MAP

DE

PA

RTM

ENT OF THE MIL ITARY

S T A T E O F S O U T H DA KOT A

G-001 COVER SHEET

G-101 GENERAL NOTES

F-101 SITE OVERVIEW

F-102 SOUTHWEST ARMORY

F-103 SOUTHEAST ARMORY

F-104 NORTHWEST ARMORY

F-105 NORTHEAST ARMORY

F-601 FACP SL DIAGRAM

TE

OF

SOUTH DAKOTAATS

R G

TA

E L

AES9881

U

REDN

DOG

EL

UR

ELP

OET PEH

AutoCAD SHX Text N

SHEET No:

SO

U

TH

D

AK

O

TA

A

RM

Y

N

AT

IO

N

AL

G

U

AR

D

CO

N

ST

RU

CT

IO

N

F

AC

IL

IT

Y M

AN

AG

EM

EN

T O

FF

IC

E

W

ES

T M

AI

N

S

TR

EE

T, R

AP

ID

C

IT

Y, S D

5)

-6

FA

X

(6

) 7

-6

DATE:

SUBMITTAL:

CO

DE

IN

FO

RM

AT

IO

N

A N

D G

EN

ER

AL

N

O

TE

S

R

EP

LA

C

E

FI

R E

SY

ST

EM

S

A B

ER

D

EE

N

A R

M

ED

F O

R C

ES

R

EA

D

IN

ES

S C

EN

TE

R C

FM

O

DEPARTM

ENT

O F

TH

E M

IL ITARY

S T A

T E

U

K

O

TA

100%

8/2026

G-101

DESCRIPTION OF WORK:

CONTRACTOR SHALL INSTALL AND FURNISH NEW FACP,

DEVICES, AND WIRING NECESSARY FOR A FULLY FUNCTIONING

FIRE DETECTION AND NOTIFICATION SYSTEM THAT MEETS ALL

CODES, REGULATIONS, AND STANDARDS. SYSTEM SHALL BE A

FA/MNS COMBINATION SYSTEM USING HONEYWELL FIRE-LITE

ES-200X AND ECC-50/100(E) AS A BASIS OF FACP AND ECC

RESPECTIVELY.

THIS PROJECT CONSISTS OF REMOVING THE EXISTING BROKEN

AND OUTDATED FACP, NAC, ADDRESSABLE RELAYS, SMOKE

DETECTORS, HEAT SENSORS, HORN STROBES, STROBES, AND

OTHER OUTDATED DEVICES AND REPLACING WITH NEW DEVICES

AS NEEDED. ADDITIONALLY, AN ECC WITH ACCESS TO TEXTUAL

SIGNAGE AND SPEAKER/STROBE SYSTEM WILL BE CONSTRUCTED.

PRIOR TO INSTALLATION, CONTRACTOR SHALL VERIFY DEVICE FIT,

COMPATIBILITY, AND COUNT.

GENERAL NOTES:

1. PROVIDE A NEW AUTOMATIC FIRE DETECTION AND NOTIFICATION

SYSTEM THROUGHOUT THE ENTIRE FACILITY COMPLYING WITH

UFC 3-600-01, 4-021-01, 4-101-01, AND ARMY NATIONAL GUARD

CRITERIA/GUIDELINES DG 415. SYSTEM INCLUDES MANUAL PULL

STATIONS, DUCT SMOKE DETECTION, HVAC SHUT-DOWN PER

NFPA 90A, NOTIFICATION DEVICES.

2. ALL ELECTRICAL WORK SHALL BE INSTALLED IN STRICT

ACCORDANCE WITH THE APPLICABLE EDITIONS OF NFPA 70,

NFPA 72, IBC, AND ANY OTHER LOCAL, STATE, OR FEDERAL

CODES, ORDINANCES, OR AUTHORITATIVE INTERPRETATIONS

THAT MAY APPLY. A CERTIFICATE OF FINAL ELECTRICAL

INSPECTION SHALL BE OBTAINED BY THE CONTRACTOR AT THE

COMPLETION OF THE WORK AND PRESENTED TO THE

CONTRACTING OFFICER.

3. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE AND

SATISFACTORILY OPERATING SYSTEMS AS INDICATED ON THE

CONTRACT DOCUMENTS AND AS EVIDENTLY INTENDED. IT IS

NOTED THAT THE DRAWINGS ARE DIAGRAMMATIC IN NATURE

AND INDICATE GENERAL ARRANGEMENTS OF SYSTEMS AND

WORK. CONTRACTOR SHALL FURNISH AND INSTALL CONDUIT

AND WIRING AS REQUIRED ACCOMPLISHING THE FUNCTIONS

INDICATED. ADDITIONALLY, FIRE ALARM SYSTEM DEVICES HAVE

BEEN SHOWN AND THE CONTRACTOR SHALL FURNISH AND

INSTALL THE REQUIRED QUANTITIES AND TYPES OF CABLES,

CONDUCTORS, RACEWAYS, REMOTE POWER SUPPLIES AND

CONNECTIONS, SHIELDING REQUIREMENTS, ETC., AS REQUIRED

BY THE SYSTEM MANUFACTURER, THE SPECIFICATIONS, AND

ANY APPLICABLE CODES. ALL WIRING SHOWN ON RISER

DIAGRAMS SHALL ALSO BE FURNISHED AND INSTALLED

REGARDLESS OF WHETHER THESE ITEMS ARE SHOWN ON THE

FLOOR PLANS.

4. THE SMOKE DETECTOR PLACEMENT DETAILED ON DRAWINGS IS

BASED UPON SMOOTH CEILING DESIGN. THE ACTUAL

PLACEMENT OF SMOKE DETECTORS WILL BE DEPENDENT UPON

THE LOCATION AND ARRANGEMENT OF STRUCTURAL

COMPONENTS. THE CONTRACTOR’S DESIGN SHALL TAKE INTO

CONSIDERATION ALL STRUCTURAL MEMBERS AND SMOKE

DETECTORS SHALL BE PLACED ACCORDINGLY.

5. THE CONTRACTOR SHALL RESOLVE ALL INSTALLATION

CONFLICTS THROUGH THE CONTRACTING OFFICER PRIOR TO

ROUGH-IN. FAILURE TO PROVIDE SUCH COORDINATION PRIOR

TO WORK BEING INSTALLED SHALL NOT BE CAUSE FOR

ADDITIONAL COMPENSATION TO THE CONTRACTOR, AND MAY

RESULT IN REJECTION OF THE WORK.

6. ADDITIONAL DEVICES MAY BE REQUIRED. DO NOT USE THESE

DRAWINGS FOR DEVICE COUNTS.

7. ALL EQUIPMENT SHALL BE NEW, SHALL BE SUITABLE FOR THE

APPLICATION INTENDED, AND SHALL BEAR LABELS OR MARKINGS

INDICATING THIRD PARTY TESTING LABORATORY LISTINGS

ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.

8. VERIFY LOCATIONS OF WIRING DEVICES IN FINISHED SPACES,

MILLWORK, AND CASEWORK PRIOR TO ROUGH-IN.

9. ALL FIRE ALARM CABLES SHALL BE INSTALLED IN METAL

RACEWAYS, INDEPENDENT OF OTHER CABLING.

10. ALL RACEWAY AND WIRING SHALL BE CONCEALED IN FINISHED

SPACES, AND MAY BE INSTALLED EXPOSED IN UNFINISHED

SPACES SUCH AS MECHANICAL AND ELECTRICAL ROOMS. ALL

RACEWAY AND WIRING, WHETHER CONCEALED OR EXPOSED,

SHALL BE RUN EITHER PERPENDICULAR OR PARALLEL TO THE

BUILDING'S STRUCTURAL COMPONENTS. CONDUITS THAT ARE

EXPOSED IN FINISHED AREAS SHALL BE BURIED WITHIN THE

WALL, OR SOFFIT TO BE PROVIDED TO CONCEAL IT.

11.PROVIDE PULL AND JUNCTION BOXES AS REQUIRED TO MEET

CODE AND INSTALLATION REQUIREMENTS. PULL AND JUNCTION

BOXES SHALL BE CONCEALED IN FINISHED SPACES AND

LOCATIONS SHALL BE COORDINATED WITH THE WORK OF ALL

OTHER TRADES SO AS TO AVOID CONFLICTS.

12. ALL CONDUCTORS SHALL BE IDENTIFIED AT EACH JUNCTION BOX,

OUTLET BOX, CABINET, PULL BOX, ETC., WITH VINYL

SELF-ADHESIVE TAGS INDICATING PANEL AND CIRCUIT NUMBER,

CONTROL WIRE IDENTIFICATION NUMBER, OR OTHER

APPROPRIATE INFORMATION. ALL PULL AND JUNCTION BOXES

SHALL BE LABELED AS TO FUNCTION. SEE THE UFC FOR

CONDUCTOR TYPES AND SIZES ALLOWED. FIRE ALARM/MNS

CONDUCTORS SHALL BE POWER-LIMITED CIRCUITS AS DEFINED

BY NFPA 70 UNLESS OTHERWISE INDICATED.

13. ALL EQUIPMENT SHALL BE SECURELY FASTENED BY MEANS OF

ANCHORS, RODS, HANGERS, SUPPORTS, GUIDES, SWAY BRACES,

ETC., TO MAINTAIN ALIGNMENT AND PREVENT EQUIPMENT

MOVEMENT. ALL EQUIPMENT LOCATED IN SEISMIC ZONES SHALL

BE SECURED WITH MEANS APPROVED FOR THE SEISMIC

CLASSIFICATION ENCOUNTERED.

14. ALL PENETRATIONS OF FIRE OR SMOKE RATED CONSTRUCTION

SHALL BE SEALED WITH FIRESTOPPING MATERIALS APPROVED

AND LISTED FOR THE RATING OF THE CONSTRUCTION TO BE

PENETRATED. PROVIDE DOCUMENTATION ON ALL SUCH

PENETRATION SEALING SYSTEMS FOR VERIFICATION OF PROPER

INSTALLATION. DOCUMENT ON AS-BUILT DRAWINGS THE

LOCATION OF ALL FIRE AND SMOKE RATED BARRIER

PENETRATIONS. PLACE IDENTIFYING PLACARD OR LABEL AT

EACH PENETRATION LOCATION DETAILING DATE, CONTRACTOR,

AND CONTRACT NUMBER AND SEQUENTIAL SERIAL NUMBER (I.E.

B145-XXX). A DETAILED INVENTORY OF EACH PENETRATION

SHALL BE MAINTAINED. THE INVENTORY SHALL INCLUDE

BUILDING NO, LOCATION DATA (ROOM NUMBER, ETC.), TYPE OF

BARRIER, AND METHOD OF SEALANT (I.E. FIRE CAULK, MORTAR,

PILLOW, ETC.).

15.WHERE EMPTY RACEWAYS ARE INSTALLED, THEY SHALL BE

LABELED AT BOTH ENDS AND FITTED WITH NYLON PULLSTRINGS

FOR FUTURE USE.

CODE INFORMATION

APPLICABLE CODES AND REGULATIONS:

2024 IBC

NFPA 101

NFPA 70

NFPA 72

NFPA 90A

UNIFIED FACILITY CRITERIA 3-600-01

UNIFIED FACILITY CRITERIA 4-021-01

UNIFIED FACILITY CRITERIA 4-101-01

NG DESIGN GUIDE 415

16. ELECTRICAL WORK SHALL BE PERFORMED ON DE-ENERGIZED SYSTEMS ONLY

TO PREVENT PERSONNEL INJURY AND POTENTIAL SYSTEM FAILURE. WHERE WORK

ON EXISTING SYSTEMS WILL REQUIRE INTERRUPTION OF ELECTRICAL SERVICE,

THEN TEMPORARY PROVISIONS ACCEPTABLE TO THE OWNER FOR TEMPORARY

POWER SHALL BE UTILIZED UNTIL THE WORK IS COMPLETE.

17. FIRE ALARM SYSTEM SHALL COMPLY WITH ALL RELATED NFPA AND BUILDING

CODES, AND LOCAL FIRE DEPARTMENT REGULATIONS.

18. WALL MOUNTED FIRE ALARM PULL STATIONS ARE TO BE LOCATED 44" A.F.F.

TO THE OPERATING MECHANISM OF THE STATION AND WITHIN 5' OF THE NEAREST

ADJACENT EXIT DOOR FROM THE FLOOR OR BUILDING.

BUILDING IS SPRINKLERED AND HAS A PIV THAT IS TO BE MONITORED BY THE FIRE

ALARM SYSTEM.

19. WALL MOUNTED FIRE ALARM/MNS NOTIFICATION APPLIANCES, EITHER VISUAL,

OR COMBINATION AUDIO/VISUAL, SHALL BE LOCATED SUCH THAT THE ENTIRE LENS

OF THE VISUAL PORTION IS BETWEEN 82" AND 96" A.F.F. AUDIO ONLY APPLIANCES

SHALL BE LOCATED, NOT LESS THAN, 90" A.F.F. TO TOP OF APPLIANCE, OR 6" BELOW

CEILING.

20. CONTRACTOR SHALL COMPLETE ANY NECESSARY TOUCH-UP PAINTING

REQUIRED AS THE RESULT OF CONSTRUCTION ACTIVITIES.

21. CONTRACTOR SHALL REPLACE ANY ACCOUSTICAL CEILING TILES (ACT) THAT

ARE DAMAGED AS THE RESULT OF CONSTRUCTION OR WHERE NEW DEVICES DO

NOT FIT PROPERLY IN THE PREVIOUSLY CUT OR DRILLED ACT.

22. MASS NOTIFICATION SIGNS SHALL BE SCROLLING SIGNS WITH CAPABILITY OF

CUSTOM MESSAGES AND CONNECTION TO MULTIPLE BUILDINGS.

LOCAL OPERATORS CONSOLE

ADDRESSABLE INPUT MODULE

ADDRESSABLE OUTPUT MODULE

ADDRESSABLE HEAT DETECTOR

END OF LINE SUPERVISION DEVICE

FLOW DETECTOR/SWITCH

NON-ADDRESSABLE OUTPUT RELAY

PRESSURE DETECTOR/SWITCH

SURGE SUPPRESSOR

VALVE SUPERVISORY SWITCH

LOW TEMPERATURE SUPERVISORY SWITCH, 40°F LOW LIMIT

MANUAL STATION, FIRE ALARM

ADDRESSABLE SMOKE DETECTOR, PHOTOELECTRIC

ADDRESSABLE DUCT MOUNTED SMOKE DETECTOR

NAC EXTENDER BOOSTER POWER SUPPLY

DOOR HOLDER

TAMPER SWITCH

STROBE ONLY, WALL MOUNT

ADDRESSABLE DUAL INPUT MODULE

SPEAKER/STROBE COMBO, WALL MOUNT, CLEAR LENS

STROBE ONLY, CEILING MOUNT

SPEAKER ONLY, CEILING MOUNT

2 DUAL

40°F 40 DEGREES FAHRENHEIT

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AS ASPIRATING SMOKE TYPE

C CEILING MOUNT

CA CLEAN AGENT

CO CARBON MONOXIDE

CO2 NITROGEN DIOXIDE

EX EXISTING

FO FOAM

FT FIXED TEMPERATURE

G GONG

GSO GAS SHUTOFF

H HIGH AUDIBLE SETTING

HEF HIGH EXPANSION FOAM

HPS HIGH POWERED SPEAKER

IR INFRA-RED

L LOW AUDIBLE SETTING

LVHV LOW VELOCITY / HIGH VOLUME FAN

M MASS NOTIFICATION DEVICE

MEZZ UNDER MEZZANINE MOUNT

MNS MASS NOTIFICATION SYSTEM

MRC MARINE RESERVE CENTER

NH4 METHANE

NO2 NITROGEN DIOXIDE

OWS OIL-WATER SEPARATOR

P PENDANT

PRE PREACTION

RF RADIO FREQUENCY

RI REMOTE INDICATOR

ROOF ROOF CEILING MOUNT

RTS REMOTE TEST STATION

RTU ROOF TOP UNIT

SB SOUNDER BASE

SF SUB-FLOOR MOUNTED

SOV SOLENOID OUTPUT VALVE

TOS TOP OF SHAFT

TYP TYPICAL

U or UF UNDER-FLOOR MOUNTED

UV ULTRA VIOLET

V VIBRATING

VFD VARIABLE FREQUENCY DRIVE

VMF VEHICLE MAINTENANCE FACILITY

W WALL

nW WATTAGE SETTING (n=SPEAKER TAP)

WP WEATHERPROOF

WG WIRE GUARD

XCVR TRANSCEIVER

XP EXPLOSION PROOF

SPEAKER ONLY, WALL MOUNT

SPEAKER/STROBE COMBO, CEILING MOUNT, CLEAR LENS

SPEAKER ONLY, EXTERIOR WEATHERPROOF

KNOX BOX

POST INDICATOR VALVE

FIRE ALARM ANNUNCIATOR PANEL

NOTE: NOT ALL SYMBOLS MAY BE USED

ET MNS TEXTURAL SIGN

MASS NOTIFICATION SYSTEM CONTROL UNIT

FIRE ALARM TERMINAL CABINET

NOTE: NOT ALL ABBREVIATIONS MAY BE USED

HD

C

C

K

FIRE ALARM/MASS NOTIFICATION SYSTEM AMPLIFIER

WPHPS

FIRE ALARM SYMBOLS LEGEND

- PANELS CABINETS AND CONTROLLERS -

- DEVICE SUBSCRIPTS & PROJECT ABBREVIATIONS -

- MANUAL STATIONS -

- DETECTION -

- ADDRESSABLE MODULES -

- NOTIFICATION APPLIANCES -

- PERIPHERAL DEVICES -

HORN/STROBE COMBO WALL, CLEAR LENS

AOM

REMOTE TEST/STATUS STATION

FIRE ALARM / MASS NOTIFICATION SYSTEM CONTROL UNIT

AIM

WF

R

PS

SS

VS

TSS40°F

P

DH

FMCP

2AIM

P

LOC

NAC

FAA

MNS

FATC

P

EOL

PIV

AMP

S

S

ASSEMBLY HALL

MECH.

ROOM

ADMIN

ADMIN OFFICE

ADMIN OFFICE

CLASSROOM

OFFICEOFFICE

MEN

VEST.

SUPPLY

AHU #1

AHU #2

AIR

HANDLER

OFFICE

CLASSROOM

KITCHEN

FOOD

STG.

MECH.

ROOM

VAULT

STG.

AHU #3

LOCKER ROOM

AIR

HANDLER

AIM

NAC

JAN.

SUPPLY

HALL

DISTRIBUTION

ROOM

ADMIN OFFICE

P

P P P P

PPP

P P P

PPP

P

P

P

P

P

P

P

P

P

P P

DH

HD

HD

HD

HD

HD

HD

HD

P

P

P

HD

HD

HD

HD

HD

HD HD

HD

P

P

P

P

P

P

R

R

R

R

R

R

R

F

F

F

ET

WP

FAA

ET

P

P

ENTRY

02 03

TOILET

ADMIN OFFICE

ADMIN OFFICE

WOMEN

STG.

VAULT

FA

CP

MNS

7 12

NO WORK TO BE DONE IN ARMY RESERVE

SHEET No:

SO

U

TH

D

AK

O

TA

A

RM

Y

N

AT

IO

N

AL

G

U

AR

D

CO

N

ST

RU

CT

IO

N

F

AC

IL

IT

Y M

AN

AG

EM

EN

T O

FF

IC

E

W

ES

T M

AI

N

S

TR

EE

T, R

AP

ID

C

IT

Y, S D

5)

-6

FA

X

(6

) 7

-6

DATE:

SUBMITTAL:

SI

TE

O

VE

RV

IE

W

R

EP

LA

C

E

FI

R E

SY

ST

EM

S

A B

ER

D

EE

N

A R

M

ED

F O

R C

ES

R

EA

D

IN

ES

S C

EN

TE

R C

FM

O

DEPARTM

ENT

O F

TH

E M

IL ITARY

S T A T

E

U

K O

TA

100%

8/2026

F-101

KEY NOTES:

CONTRACTOR TO REMOVE/REPLACE

CEILING-MOUNTED SMOKE

DETECTORS. TYP

CONTRACTOR TO REMOVE EXISTING

HORN/STROBE OR STROBE AND REPLACE

WITH NEW SPEAKER/STROBE COMPATIBLE

WITH ECC-50/100 MNS. MODEL

TO BE DISCUSSED WITH OWNER PRIOR

TO INSTALLATION. TYP.

CONTRACTOR TO REMOVE/REPLACE

MANUAL PULL BOXES. TYP

CONTRACTOR TO REMOVE/REPLACE

ADDRESSABLE RELAYS. TYP

CONTRACTOR TO REMOVE/REPLACE

SIGA-HRS HEAT DETECTORS. TYP

CONTRACTOR TO REMOVE/REPLACE

REMOTE FIRE ALARM ANNUNCIATOR

PANEL. TYP

CONTRACTOR TO REMOVE/REPLACE

SIGA-HFS HEAT DETECTORS. TYP

CONTRACTOR TO REMOVE/REPLACE

EXISTING FACP FOR NEW FLUSH-MOUNTED

FIRE-LITE ES-200X WITH LCD ANNUNCIATOR.

CONTRACTOR TO INSTALL NEW MNS LED

MESSAGE CENTERS AT POINTS OF EGRESS.

MODEL TO BE DISCUSSED WITH

OWNER PRIOR TO INSTALLATION. TYP

CONTRACTOR TO REMOVE WEATHER-PROOF

HORN/STROBE AND REPLACE WITH

WEATHERPROOF SPEAKER STROBE. TYP

CONTRACTOR TO REMOVE/REPLACE

ADDRESSABLE INPUT MODULE FOR

KITCHEN EQUIPMENT. TYP

CONTRACTOR TO INSTALL FIRE-LITE

ECC-50/100(E) EMERGENCY COMMAND

CENTER AND CONNECT TO

SPEAKER/STROBE CIRCUITS

CONTRACTOR TO REMOVE NAC

BOOSTER PANELS AND REPLACE AS

NEEDED FOR A FUNCTIONING SYSTEM

CONTRACTOR TO REMOVE/REPLACE

STROBE. TYP14

GENERAL NOTES:

1. EXISTING DEVICES ARE SHOWN TO BEST OF ABILITIES. CONTRACTOR SHALL VERIFY

ACTUAL NUMBER OF EXISTING DEVICES.

2. EXISTING DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. CONTRACTOR TO

VERIFY ACTUAL FIELD LOCATIONS.

3. ALL EXISTING PANELS, CONTROLLERS, STATIONS, DETECTORS, ADDRESSABLE

MODULES, NOTIFICATION APPLIANCES, AND PERIPHERAL DEVICES NOT COMPATIBLE

WITH NEW FACP SHALL BE REMOVED AND REPLACED BY THE CONTRACTOR.

4. CONTRACTOR SHALL COMPLETE ALL NECESSARY REPAIRS AND TOUCH UP PAINTING

RESULTING FROM REMOVED EQUIPMENT.

5. CONTRACTOR SHALL PROVIDE NEW FACP AND MNS COMPATIBLE DEVICES AND

HARDWARE FOR A FULLY FUNCTIONAL SYSTEM.

6. CONTRACTOR SHALL VERIFY DEVICE LOCATIONS, QUANTITIES, AND TYPE MEET ALL

CURRENT CODES AND REGULATIONS.

7. CONTRACTOR SHALL VERIFY FIT WITH OWNER PRIOR TO INSTALLATION OF NEW

PANELS, DEVICES, ETC.

8. CONTRACTOR SHALL PAINT ALL NEW CONDUIT TO MATCH ROOM SURROUNDINGS.

9. CONTRACTOR SHALL REUSE EXISTING FIRE SYSTEM CONDUIT AND WIRING WHERE

POSSIBLE UNLESS CODE DICTATES OTHERWISE.

10. ALL EQUIPMENT SHOULD BE OF HONEYWELL TECHNOLOGIES FIRE-LITE SYSTEM

UNLESS APPROVED BY OWNER PRIOR TO INSTALLATION.

SITE OVERVIEW

SCALE: NTS

CLASSROOM

OFFICEOFFICE

MEN

VEST.

AHU #1

AHU #2

OFFICE

KITCHEN

FOOD

STG.

AIM

NAC

JAN.

HALL

DISTRIBUTION

ROOM

ADMIN OFFICE

P

P

P

P

P

P

P

P

P

P

P

P P

HD

HD

HD

HD

HD

P

P

P

HD

HD HD

P

P

P

R

R

R

6F

F

ET

WP

FAA

P

ENTRY

02 03

TOILET

ADMIN OFFICE

ADMIN OFFICE

WOMEN

FA

CP

MNS

7 12

SHEET No:

SO

U

TH

D

AK

O

TA

A

RM

Y

N

AT

IO

N

AL

G

U

AR

D

CO

N

ST

RU

CT

IO

N

F

AC

IL

IT

Y M

AN

AG

EM

EN

T O

FF

IC

E

W

ES

T M

AI

N

S

TR

EE

T, R

AP

ID

C

IT

Y, S D

5)

-6

FA

X

(6

) 7

-6

DATE:

SUBMITTAL:

SO

U

TH

W

ES

T

AR

M

O

RY

R

EP

LA

C

E

FI

R E

SY

ST

EM

S

A B

ER

D

EE

N

A R

M

ED

F O

R C

ES

R

EA

D

IN

ES

S C

EN

TE

R C

FM

O

DEPARTM

ENT

OF

TH

E M

IL ITARY

S T A

T E

U

K

O

TA

100%

8/2026

F-102

KEY NOTES:

CONTRACTOR TO REMOVE/REPLACE

CEILING-MOUNTED SMOKE

DETECTORS. TYP

CONTRACTOR TO REMOVE EXISTING

HORN/STROBE OR STROBE AND REPLACE

WITH NEW SPEAKER/STROBE COMPATIBLE

WITH ECC-50/100 MNS. MODEL

TO BE DISCUSSED WITH OWNER PRIOR

TO INSTALLATION. TYP.

CONTRACTOR TO REMOVE/REPLACE

MANUAL PULL BOXES. TYP

CONTRACTOR TO REMOVE/REPLACE

ADDRESSABLE RELAYS. TYP

CONTRACTOR TO REMOVE/REPLACE

SIGA-HRS HEAT DETECTORS. TYP

CONTRACTOR TO REMOVE/REPLACE

REMOTE FIRE ALARM ANNUNCIATOR

PANEL. TYP

CONTRACTOR TO REMOVE/REPLACE

SIGA-HFS HEAT DETECTORS. TYP

CONTRACTOR TO REMOVE/REPLACE

EXISTING FACP FOR NEW FLUSH-MOUNTED

FIRE-LITE ES-200X WITH LCD ANNUNCIATOR.

CONTRACTOR TO INSTALL NEW MNS LED

MESSAGE CENTERS AT POINTS OF EGRESS.

MODEL TO BE DISCUSSED WITH

OWNER PRIOR TO INSTALLATION. TYP

CONTRACTOR TO REMOVE WEATHER-PROOF

HORN/STROBE AND REPLACE WITH

WEATHERPROOF SPEAKER STROBE. TYP

CONTRACTOR TO REMOVE/REPLACE

ADDRESSABLE INPUT MODULE FOR

KITCHEN EQUIPMENT. TYP

CONTRACTOR TO INSTALL FIRE-LITE

ECC-50/100(E) EMERGENCY COMMAND

CENTER AND CONNECT TO

SPEAKER/STROBE CIRCUITS

CONTRACTOR TO REMOVE NAC

BOOSTER PANELS AND REPLACE AS

NEEDED FOR A FUNCTIONING SYSTEM

CONTRACTOR TO REMOVE/REPLACE

STROBE. TYP14

GENERAL NOTES:

1. EXISTING DEVICES ARE SHOWN TO BEST OF ABILITIES. CONTRACTOR SHALL VERIFY

ACTUAL NUMBER OF EXISTING DEVICES.

2. EXISTING DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. CONTRACTOR TO

VERIFY ACTUAL FIELD LOCATIONS.

3. ALL EXISTING PANELS, CONTROLLERS, STATIONS, DETECTORS, ADDRESSABLE

MODULES, NOTIFICATION APPLIANCES, AND PERIPHERAL DEVICES NOT COMPATIBLE

WITH NEW FACP SHALL BE REMOVED AND REPLACED BY THE CONTRACTOR.

4. CONTRACTOR SHALL COMPLETE ALL NECESSARY REPAIRS AND TOUCH UP PAINTING

RESULTING FROM REMOVED EQUIPMENT.

5. CONTRACTOR SHALL PROVIDE NEW FACP AND MNS COMPATIBLE DEVICES AND

HARDWARE FOR A FULLY FUNCTIONAL SYSTEM.

6. CONTRACTOR SHALL VERIFY DEVICE LOCATIONS, QUANTITIES, AND TYPE MEET ALL

CURRENT CODES AND REGULATIONS.

7. CONTRACTOR SHALL VERIFY FIT WITH OWNER PRIOR TO INSTALLATION OF NEW

PANELS, DEVICES, ETC.

8. CONTRACTOR SHALL PAINT ALL NEW CONDUIT TO MATCH ROOM SURROUNDINGS.

9. CONTRACTOR SHALL REUSE EXISTING FIRE SYSTEM CONDUIT AND WIRING WHERE

POSSIBLE UNLESS CODE DICTATES OTHERWISE.

10. ALL EQUIPMENT SHOULD BE OF HONEYWELL TECHNOLOGIES FIRE-LITE SYSTEM

UNLESS APPROVED BY OWNER PRIOR TO INSTALLATION.

SOUTHWEST ARMORY

SCALE: NTS

MEN

CLASSROOM

KITCHEN

FOOD

STG.

MECH.

ROOM

VAULT

LOCKER ROOM

AIR

HANDLER

AIM

JAN.

SUPPLY

HALL

DISTRIBUTION

ROOM

ADMIN OFFICE

PPP

P P P

PPP

P

P

P

P

P

P

P

DH

HD

HD

HD

HD

P

P

HD

HD HD

HD

P

P

P

R

R

R

F

F

F

ET

P

P

ENTRY

TOILET

ADMIN OFFICE

ADMIN OFFICE

WOMEN

FA

CP

SHEET No:

SO

U

TH

D

AK

O

TA

A

RM

Y

N

AT

IO

N

AL

G

U

AR

D

CO

N

ST

RU

CT

IO

N

F

AC

IL

IT

Y M

AN

AG

EM

EN

T O

FF

IC

E

W

ES

T M

AI

N

S

TR

EE

T, R

AP

ID

C

IT

Y, S D

5)

-6

FA

X

(6

) 7

-6

DATE:

SUBMITTAL:

SO

U

TH

EA

ST

A

RM

O

RY

R

EP

LA

C

E

FI

R E

SY

ST

EM

S

A B

ER

D

EE

N

A R

M

ED

F O

R C

ES

R

EA

D

IN

ES

S C

EN

TE

R C

FM

O

DEPARTM

ENT

O F

TH

E M

IL ITARY

S T A

T E

U

K

O

TA

100%

8/2026

F-103

SOUTHEAST ARMORY

SCALE: NTS

KEY NOTES:

CONTRACTOR TO REMOVE/REPLACE

CEILING-MOUNTED SMOKE

DETECTORS. TYP

CONTRACTOR TO REMOVE EXISTING

HORN/STROBE OR STROBE AND REPLACE

WITH NEW SPEAKER/STROBE COMPATIBLE

WITH ECC-50/100 MNS. MODEL

TO BE DISCUSSED WITH OWNER PRIOR

TO INSTALLATION. TYP.

CONTRACTOR TO REMOVE/REPLACE

MANUAL PULL BOXES. TYP

CONTRACTOR TO REMOVE/REPLACE

ADDRESSABLE RELAYS. TYP

CONTRACTOR TO REMOVE/REPLACE

SIGA-HRS HEAT DETECTORS. TYP

CONTRACTOR TO REMOVE/REPLACE

REMOTE FIRE ALARM ANNUNCIATOR

PANEL. TYP

CONTRACTOR TO REMOVE/REPLACE

SIGA-HFS HEAT DETECTORS. TYP

CONTRACTOR TO REMOVE/REPLACE

EXISTING FACP FOR NEW FLUSH-MOUNTED

FIRE-LITE ES-200X WITH LCD ANNUNCIATOR.

CONTRACTOR TO INSTALL NEW MNS LED

MESSAGE CENTERS AT POINTS OF EGRESS.

MODEL TO BE DISCUSSED WITH

OWNER PRIOR TO INSTALLATION. TYP

CONTRACTOR TO REMOVE WEATHER-PROOF

HORN/STROBE AND REPLACE WITH

WEATHERPROOF SPEAKER STROBE. TYP

CONTRACTOR TO REMOVE/REPLACE

ADDRESSABLE INPUT MODULE FOR

KITCHEN EQUIPMENT. TYP

CONTRACTOR TO INSTALL FIRE-LITE

ECC-50/100(E) EMERGENCY COMMAND

CENTER AND CONNECT TO

SPEAKER/STROBE CIRCUITS

CONTRACTOR TO REMOVE NAC

BOOSTER PANELS AND REPLACE AS

NEEDED FOR A FUNCTIONING SYSTEM

CONTRACTOR TO REMOVE/REPLACE

STROBE. TYP14

GENERAL NOTES:

1. EXISTING DEVICES ARE SHOWN TO BEST OF ABILITIES. CONTRACTOR SHALL VERIFY

ACTUAL NUMBER OF EXISTING DEVICES.

2. EXISTING DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. CONTRACTOR TO

VERIFY ACTUAL FIELD LOCATIONS.

3. ALL EXISTING PANELS, CONTROLLERS, STATIONS, DETECTORS, ADDRESSABLE

MODULES, NOTIFICATION APPLIANCES, AND PERIPHERAL DEVICES NOT COMPATIBLE

WITH NEW FACP SHALL BE REMOVED AND REPLACED BY THE CONTRACTOR.

4. CONTRACTOR SHALL COMPLETE ALL NECESSARY REPAIRS AND TOUCH UP PAINTING

RESULTING FROM REMOVED EQUIPMENT.

5. CONTRACTOR SHALL PROVIDE NEW FACP AND MNS COMPATIBLE DEVICES AND

HARDWARE FOR A FULLY FUNCTIONAL SYSTEM.

6. CONTRACTOR SHALL VERIFY DEVICE LOCATIONS, QUANTITIES, AND TYPE MEET ALL

CURRENT CODES AND REGULATIONS.

7. CONTRACTOR SHALL VERIFY FIT WITH OWNER PRIOR TO INSTALLATION OF NEW

PANELS, DEVICES, ETC.

8. CONTRACTOR SHALL PAINT ALL NEW CONDUIT TO MATCH ROOM SURROUNDINGS.

9. CONTRACTOR SHALL REUSE EXISTING FIRE SYSTEM CONDUIT AND WIRING WHERE

POSSIBLE UNLESS CODE DICTATES OTHERWISE.

10. ALL EQUIPMENT SHOULD BE OF HONEYWELL TECHNOLOGIES FIRE-LITE SYSTEM

UNLESS APPROVED BY OWNER PRIOR TO INSTALLATION.

MEN

SUPPLY

AIR

HANDLER

VAULT

STG.

NAC

JAN.

SUPPLY

P P

PPP

P P P

DH

HD

HD

HD

HD

HD

HD

HD

HD

HD

HD

P

R

R

TOILET

WOMEN

STG.

VAULT

SHEET No:

SO

U

TH

D

AK

O

TA

A

RM

Y

N

AT

IO

N

AL

G

U

AR

D

CO

N

ST

RU

CT

IO

N

F

AC

IL

IT

Y M

AN

AG

EM

EN

T O

FF

IC

E

W

ES

T M

AI

N

S

TR

EE

T, R

AP

ID

C

IT

Y, S D

5)

-6

FA

X

(6

) 7

-6

DATE:

SUBMITTAL:

N O

RT

HW

ES

T

AR

M

O

RY

R

EP

LA

C

E

FI

R E

SY

ST

EM

S

A B

ER

D

EE

N

A R

M

ED

F O

R C

ES

R

EA

D

IN

ES

S C

EN

TE

R C

FM

O

DEPARTM

ENT

O F

TH

E M

IL ITARY

S T A

T E

U

K

O

TA

100%

8/2026

F-104

NORTHWEST ARMORY

KEY NOTES:

CONTRACTOR TO REMOVE/REPLACE

CEILING-MOUNTED SMOKE

DETECTORS. TYP

CONTRACTOR TO REMOVE EXISTING

HORN/STROBE OR STROBE AND REPLACE

WITH NEW SPEAKER/STROBE COMPATIBLE

WITH ECC-50/100 MNS. MODEL

TO BE DISCUSSED WITH OWNER PRIOR

TO INSTALLATION. TYP.

CONTRACTOR TO REMOVE/REPLACE

MANUAL PULL BOXES. TYP

CONTRACTOR TO REMOVE/REPLACE

ADDRESSABLE RELAYS. TYP

CONTRACTOR TO REMOVE/REPLACE

SIGA-HRS HEAT DETECTORS. TYP

CONTRACTOR TO REMOVE/REPLACE

REMOTE FIRE ALARM ANNUNCIATOR

PANEL. TYP

CONTRACTOR TO REMOVE/REPLACE

SIGA-HFS HEAT DETECTORS. TYP

CONTRACTOR TO REMOVE/REPLACE

EXISTING FACP FOR NEW FLUSH-MOUNTED

FIRE-LITE ES-200X WITH LCD ANNUNCIATOR.

CONTRACTOR TO INSTALL NEW MNS LED

MESSAGE CENTERS AT POINTS OF EGRESS.

MODEL TO BE DISCUSSED WITH

OWNER PRIOR TO INSTALLATION. TYP

CONTRACTOR TO REMOVE WEATHER-PROOF

HORN/STROBE AND REPLACE WITH

WEATHERPROOF SPEAKER STROBE. TYP

CONTRACTOR TO REMOVE/REPLACE

ADDRESSABLE INPUT MODULE FOR

KITCHEN EQUIPMENT. TYP

CONTRACTOR TO INSTALL FIRE-LITE

ECC-50/100(E) EMERGENCY COMMAND

CENTER AND CONNECT TO

SPEAKER/STROBE CIRCUITS

CONTRACTOR TO REMOVE NAC

BOOSTER PANELS AND REPLACE AS

NEEDED FOR A FUNCTIONING SYSTEM

CONTRACTOR TO REMOVE/REPLACE

STROBE. TYP14

GENERAL NOTES:

1. EXISTING DEVICES ARE SHOWN TO BEST OF ABILITIES. CONTRACTOR SHALL VERIFY

ACTUAL NUMBER OF EXISTING DEVICES.

2. EXISTING DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. CONTRACTOR TO

VERIFY ACTUAL FIELD LOCATIONS.

3. ALL EXISTING PANELS, CONTROLLERS, STATIONS, DETECTORS, ADDRESSABLE

MODULES, NOTIFICATION APPLIANCES, AND PERIPHERAL DEVICES NOT COMPATIBLE

WITH NEW FACP SHALL BE REMOVED AND REPLACED BY THE CONTRACTOR.

4. CONTRACTOR SHALL COMPLETE ALL NECESSARY REPAIRS AND TOUCH UP PAINTING

RESULTING FROM REMOVED EQUIPMENT.

5. CONTRACTOR SHALL PROVIDE NEW FACP AND MNS COMPATIBLE DEVICES AND

HARDWARE FOR A FULLY FUNCTIONAL SYSTEM.

6. CONTRACTOR SHALL VERIFY DEVICE LOCATIONS, QUANTITIES, AND TYPE MEET ALL

CURRENT CODES AND REGULATIONS.

7. CONTRACTOR SHALL VERIFY FIT WITH OWNER PRIOR TO INSTALLATION OF NEW

PANELS, DEVICES, ETC.

8. CONTRACTOR SHALL PAINT ALL NEW CONDUIT TO MATCH ROOM SURROUNDINGS.

9. CONTRACTOR SHALL REUSE EXISTING FIRE SYSTEM CONDUIT AND WIRING WHERE

POSSIBLE UNLESS CODE DICTATES OTHERWISE.

10. ALL EQUIPMENT SHOULD BE OF HONEYWELL TECHNOLOGIES FIRE-LITE SYSTEM

UNLESS APPROVED BY OWNER PRIOR TO INSTALLATION.

SCALE: NTS

AIR

HANDLER

AHU #3

LOCKER ROOM

P P P

P

DH

P

R

R

R

P

SHEET No:

SO

U

TH

D

AK

O

TA

A

RM

Y

N

AT

IO

N

AL

G

U

AR

D

CO

N

ST

RU

CT

IO

N

F

AC

IL

IT

Y M

AN

AG

EM

EN

T O

FF

IC

E

W

ES

T M

AI

N

S

TR

EE

T, R

AP

ID

C

IT

Y, S D

5)

-6

FA

X

(6

) 7

-6

DATE:

SUBMITTAL:

N O

RT

HE

AS

T

AR

M

O

RY

R

EP

LA

C

E

FI

R E

SY

ST

EM

S

A B

ER

D

EE

N

A R

M

ED

F O

R C

ES

R

EA

D

IN

ES

S C

EN

TE

R C

FM

O

DEPARTM

ENT

O F

TH

E M

IL ITARY

S T A

T E

U

K

O

TA

100%

8/2026

F-105

SCALE: NTS

KEY NOTES:

CONTRACTOR TO REMOVE/REPLACE

CEILING-MOUNTED SMOKE

DETECTORS. TYP

CONTRACTOR TO REMOVE EXISTING

HORN/STROBE OR STROBE AND REPLACE

WITH NEW SPEAKER/STROBE COMPATIBLE

WITH ECC-50/100 MNS. MODEL

TO BE DISCUSSED WITH OWNER PRIOR

TO INSTALLATION. TYP.

CONTRACTOR TO REMOVE/REPLACE

MANUAL PULL BOXES. TYP

CONTRACTOR TO REMOVE/REPLACE

ADDRESSABLE RELAYS. TYP

CONTRACTOR TO REMOVE/REPLACE

SIGA-HRS HEAT DETECTORS. TYP

CONTRACTOR TO REMOVE/REPLACE

REMOTE FIRE ALARM ANNUNCIATOR

PANEL. TYP

CONTRACTOR TO REMOVE/REPLACE

SIGA-HFS HEAT DETECTORS. TYP

CONTRACTOR TO REMOVE/REPLACE

EXISTING FACP FOR NEW FLUSH-MOUNTED

FIRE-LITE ES-200X WITH LCD ANNUNCIATOR.

CONTRACTOR TO INSTALL NEW MNS LED

MESSAGE CENTERS AT POINTS OF EGRESS.

MODEL TO BE DISCUSSED WITH

OWNER PRIOR TO INSTALLATION. TYP

CONTRACTOR TO REMOVE WEATHER-PROOF

HORN/STROBE AND REPLACE WITH

WEATHERPROOF SPEAKER STROBE. TYP

CONTRACTOR TO INSTALL FIRE-LITE

ECC-50/100(E) EMERGENCY COMMAND

CENTER AND CONNECT TO

SPEAKER/STROBE CIRCUITS

CONTRACTOR TO REMOVE NAC

BOOSTER PANELS AND REPLACE AS

NEEDED FOR A FUNCTIONING SYSTEM

CONTRACTOR TO REMOVE/REPLACE

STROBE. TYP14

CONTRACTOR TO REMOVE/REPLACE

ADDRESSABLE INPUT MODULE FOR

KITCHEN EQUIPMENT. TYP

GENERAL NOTES:

1. EXISTING DEVICES ARE SHOWN TO BEST OF ABILITIES. CONTRACTOR SHALL VERIFY

ACTUAL NUMBER OF EXISTING DEVICES.

2. EXISTING DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. CONTRACTOR TO

VERIFY ACTUAL FIELD LOCATIONS.

3. ALL EXISTING PANELS, CONTROLLERS, STATIONS, DETECTORS, ADDRESSABLE

MODULES, NOTIFICATION APPLIANCES, AND PERIPHERAL DEVICES NOT COMPATIBLE

WITH NEW FACP SHALL BE REMOVED AND REPLACED BY THE CONTRACTOR.

4. CONTRACTOR SHALL COMPLETE ALL NECESSARY REPAIRS AND TOUCH UP PAINTING

RESULTING FROM REMOVED EQUIPMENT.

5. CONTRACTOR SHALL PROVIDE NEW FACP AND MNS COMPATIBLE DEVICES AND

HARDWARE FOR A FULLY FUNCTIONAL SYSTEM.

6. CONTRACTOR SHALL VERIFY DEVICE LOCATIONS, QUANTITIES, AND TYPE MEET ALL

CURRENT CODES AND REGULATIONS.

7. CONTRACTOR SHALL VERIFY FIT WITH OWNER PRIOR TO INSTALLATION OF NEW

PANELS, DEVICES, ETC.

8. CONTRACTOR SHALL PAINT ALL NEW CONDUIT TO MATCH ROOM SURROUNDINGS.

9. CONTRACTOR SHALL REUSE EXISTING FIRE SYSTEM CONDUIT AND WIRING WHERE

POSSIBLE UNLESS CODE DICTATES OTHERWISE.

10. ALL EQUIPMENT SHOULD BE OF HONEYWELL TECHNOLOGIES FIRE-LITE SYSTEM

UNLESS APPROVED BY OWNER PRIOR TO INSTALLATION.

NORTHEAST ARMORY

FMCP

FIRE-LITE

ES-200X

WITH

ECC-50/100

COMBO

FA/MNS

DH

RRR

WP

ET

P P P

HD AIMHD

F

DACT

BATTERY

BACKUP

MASS NOTIFICATION

TEXTUAL SIGNAGE

STROBES (WHITE/CLEAR)

AND SPEAKERS

AHU DOOR HOLDER FIRE/SMOKE DAMPERS

FIRE & MASS NOTIFICATION SYSTEM SLD

SHEET No:

SO

U

TH

D

AK

O

TA

A

RM

Y

N

AT

IO

N

AL

G

U

AR

D

CO

N

ST

RU

CT

IO

N

F

AC

IL

IT

Y M

AN

AG

EM

EN

T O

FF

IC

E

W

ES

T M

AI

N

S

TR

EE

T, R

AP

ID

C

IT

Y, S D

5)

-6

FA

X

(6

) 7

-6

DATE:

SUBMITTAL:

FA

CP

S

IN

G

LE

L

IN

E

DI

AG

RA

M

R

EP

LA

C

E

FI

R E

SY

ST

EM

S

A B

ER

D

EE

N

A R

M

ED

F O

R C

ES

R

EA

D

IN

ES

S C

EN

TE

R C

FM

O

DEPARTM

ENT

O F

TH

E M

IL ITARY

S T A

T E

U

K

O

TA

100%

8/2026

F-601

SCALE: NTS

Sheets and Views
Aberdeen Armory FACP 100%-G-001
Aberdeen Armory FACP 100%-G-101
Aberdeen Armory FACP 100%-F-101
Aberdeen Armory FACP 100%-F-102
Aberdeen Armory FACP 100%-F-103
Aberdeen Armory FACP 100%-F-104
Aberdeen Armory FACP 100%-F-105
Aberdeen Armory FACP 100%-F-601

File details come from the government source that posted it. Updated .