4262-02-26 - Lee County Government Center Generator_Replacement - Construction Drawings.pdf

PDF 2 MB Posted

Attached to
Lee County Government Center Generator Replacement
Solicitation number
204-4262-02-26
Issued by
Lee County, North Carolina

About this file

These construction documents detail the Optional Stand-By Generator Replacement project for the Lee County Government Center located at 106 Hillcrest Drive in Sanford, North Carolina. The project scope involves replacing the existing backup generator with a new 250kW optional stand-by generator featuring a natural gas connection and installing a new lighting inverter. The bid number is 4262-02-26, and the documents are 100% construction documents prepared by Dewberry Engineers Inc. from Raleigh, North Carolina. The project involves electrical and plumbing work, including demolition of existing electrical equipment, installation of a new generator, replacement of natural gas piping and regulators, and reconfiguration of electrical panels and circuits.

The project includes comprehensive electrical system modifications, such as installing a new remote annunciator, replacing the automatic transfer switch (ATS), providing new feeders for panel EM, and implementing a 12.5kVA lighting inverter for life safety loads. The natural gas infrastructure will be updated to support the new generator, with the existing gas demand of 300 CFH being increased to a total of 3,300 CFH. The utility provider will be responsible for replacing the natural gas meter to accommodate the increased demand. The construction documents provide detailed specifications for electrical and plumbing work, including site plans, riser diagrams, panel schedules, and technical notes for contractor guidance, with a focus on minimizing disruption to the government center's operations during the installation process.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COVER

SHEET

G-001

C

B

A

SHEET NO.

D

E

APPROVED BY

CHECKED BY

REVISIONS

TITLE

DRAWN BY

DATE

PROJECT NO.

2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929

Dewberry Engineers Inc.

KEY PLAN

SCALE

SEAL

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T C

EN

TE

R O

PT

IO

N

AL

S

TA

N D

-B Y

G

EN

ER

AT

O R

R

EP

LA

C

EM

EN

T

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T

H

IL

LC

R

ES

T D

R

SA

N

FO

R

D , N

C

LEE COUNTY

GOVERNMENT CENTER

LEE COUNTY GOVERNMENT

805 SOUTH FIFTH STREET

SANFORD, NORTH CAROLINA 27330

CONTACT:

RYAN FAULK

GENERAL SERVICES DIRECTOR

P: (919) 718-4622

RFAULK@LEECOUNTYNC.GOV

OWNER:

DEWBERRY ENGINEERS, INC.

2610 WYCLIFF ROAD, SUITE 410

RALEIGH, NORTH CAROLINA 27607

CONTACT:

BILL HAMILTON, PE

P: (984) 833-4832 whamilton@dewberry.com

ENGINEERING:

PROJECT LOCATION:

DRAWING INDEX:

G-001 COVER SHEET

E-001 ELECTRICAL LEGEND, NOTES AND DETAILS

E-100 ELECTRICAL DEMOLITION AND NEW WORK FLOOR PLANS

E-101 ELECTRICAL NEW WORK SITE PLAN

E-300 ELECTRICAL DEMOLITION AND NEW WORK RISER DIAGRAMS

E-400 ELECTRICAL DEMOLITION AND NEW WORK PANEL SCHEDULE

P-001 PLUMBING SYMBOLS & ABBREVIATIONS

P-101 PLUMBING NEW WORK SITE PLAN

100% CONSTRUCTION DOCUMENTS

OPTIONAL STAND-BY

PROJECT LOCATION

LEE COUNTY GOVERNMENT CENTER

106 HILLCREST DR.

SANFORD, NC 27330

SCALE:1 VICINITY MAP

NTS

PROJECT SCOPE NARRATIVE:

THE SCOPE OF THIS PROJECT IS TO REPLACE THE EXISTING BACKUP

GENERATOR AT THE LEE COUNTY GOVERNMENT CENTER WITH A NEW

250KW OPTIONAL STAND-BY GENERATOR WITH NATURAL GAS

CONNECTION, AND TO PROVIDE A NEW LIGHTING INVERTER.

GENERATOR REPLACEMENT

N O

R

TH

BID NUMBER 4262-02-26

Docusign Envelope ID: A781AA8B-867C-4EA5-A458-87D732FEFAF3

9/19/2025

LEGEND

EQUIPMENT CONNECTION

1. THESE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND DO NOT SHOW ALL DETAILS REQUIRED FOR THE COMPLETE SYSTEMS. THEY SHOULD HOWEVER BE FOLLOWED AS CLOSELY AS POSSIBLE IN THE GENERAL ARRANGEMENT AND LOCATION OF EQUIPMENT. ALL DIMENSIONS SHALL BE CHECKED AT THE BUILDING AND ALL STRUCTURAL AND FINISH CONDITIONS INVESTIGATED. THE CONTRACTOR SHALL ARRANGE HIS WORK TO MEET THESE CONDITIONS AND PROVIDE SUCH EQUIPMENT

AND ACCESSORIES AS MAY BE REQUIRED.

2. BEFORE INSTALLING EQUIPMENT, MAKE FIELD MEASUREMENTS TO INSURE THAT ALL ITEMS OF EQUIPMENT FURNISHED WILL FIT INTO THE SPACE AS SHOWN ON THE DRAWINGS. WHERE EQUIPMENT WILL NOT FIT AS SHOWN ON THE DRAWINGS, PROVIDE A DRAWING TO THE ENGINEER FOR APPROVAL WITH A PROPOSED REVISED

ARRANGEMENT BEFORE INSTALLING THE EQUIPMENT.

3. CONTRACTOR SHALL REFER TO THE SEQUENCE OF CONSTRUCTION TO DETERMINE THE EXTENT OF CONSTRUCTION REQUIRED FOR EACH PHASE OF THE PROJECT.

CONTRACTOR SHALL RESTORE ALL SYSTEMS AS OPERATIONAL AND IN SERVICE AT THE END OF EACH CONSTRUCTION PHASE.

4. PROPERLY SUPPORT ALL WORK AND EQUIPMENT INSTALLED UNDER THIS CONTRACT PLUMB AND PARALLEL WITH BUILDING LINES. STUDY ALL GENERAL, STRUCTURAL, PLUMBING, HVAC, AND ELECTRICAL DRAWINGS, SHOP DRAWINGS, AND CATALOG DATA TO DETERMINE HOW EQUIPMENT, ACCESSORIES, PIPING, FIXTURES, AND RELATED ITEMS ARE TO BE SUPPORTED, MOUNTED, OR SUSPENDED. PROVIDE ALL BOLTS, INSERTS, PIPE STANDS, BRACKETS, STRUCTURAL SUPPORTS, AND ACCESSORIES FOR PROPER SUPPORT OF EQUIPMENT FURNISHED UNDER THIS CONTRACT. COORDINATE THE ELECTRICAL WORK WITH ALL OTHER CONTRACTORS BEFORE BEGINNING WORK TO INSURE THAT THE ELECTRICAL WORK DOES NOT INTERFERE WITH OTHER WORK. LINES WHICH REQUIRE SLOPE SHALL TAKE PRECEDENCE OVER ELECTRICAL WORK. COORDINATE THIS WITH THE PLUMBING AND GENERAL CONTRACTORS.

5. ALL ELECTRICAL WORK SHALL COMPLY WITH APPLICABLE CODES AND THE GOVERNMENTAL AUTHORITIES HAVING JURISDICTION.

6. VERIFY LOCATION AND DIMENSIONS OF ALL EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

7. CONTRACTOR SHALL VISIT THE SITE TO DETERMINE PRE-EXISTING CONDITIONS PRIOR TO SUBMISSION OF BID.

8. CONTRACTOR SHALL PROVIDE CONDUCTORS AND RACEWAYS AS REQUIRED FOR CONNECTION TO NEW EQUIPMENT. REFER TO DRAWINGS FOR NEW EQUIPMENT

LOCATIONS.

9. CONTRACTOR SHALL PROVIDE BLANK STAINLESS STEEL COVER PLATES FOR ALL EXISTING OUTLET BOXES THAT ARE NOT REUSED.

10. ALL CIRCUITS SHALL BE 2#12 THWN WITH #12G THWN-3/4"C UNLESS OTHERWISE NOTED ON PLANS, PANEL SCHEDULES, OR SPECIFICATIONS. ALL UNDERGROUND

CONDUIT SHALL BE A MINIMUM OF 1".

11. NOTIFY THE ENGINEER IN WRITING IMMEDIATELY UPON DISCOVERY OF ANY DISCREPANCY OR POINTS OF CONFLICT IN THE DRAWINGS OR THE SPECIFICATIONS. THE ENGINEER WILL CLARIFY SUCH DISCREPANCY OR POINT OF CONFLICT IN WRITING PRIOR TO THE PROGRESS OF WORK BEYOND THE POINT CONCERNED.

12. CONTRACTOR SHALL INCREASE WIRE SIZE BY ONE SIZE FOR BRANCH CIRCUIT WIRING THAT EXCEEDS 100' IN LENGTH. CONTRACTOR SHALL INCREASE THE WIRE SIZE FOR BRANCH CIRCUIT WIRING ADDITIONALLY BY ONE SIZE FOR EVERY ADDITIONAL 100' IN LENGTH BEYOND 100'.

GENERAL PLAN NOTES

120/208V SURFACE MOUNTED PANELBOARD

PROPOSED ELECTRICAL CONDUIT ROUTE

ARROWHEADS INDICATE HOMERUN CIRCUITS UNLESS

OTHERWISE NOTED. MULTIPLE ARROW HEADS INDICATE

MULTIPLE CIRCUITS DISTRIBUTED EVENLY ACROSS

RECEPTACLES.

TURNED UP CIRCUIT LOCATION

DENOTES EXISTING EQUIPMENT TO BE DEMOLISHED

DENOTES EXISTING EQUIPMENT TO REMAIN

DISCONNECT SWITCH

ELECTRICAL

LEGEND, NOTES

AND DETAILS

E-001

ELECTRICAL EQUIPMENT, AS NOTED ON PLANS

C

B

A

SHEET NO.

D

E

APPROVED BY

CHECKED BY

REVISIONS

TITLE

DRAWN BY

Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929

Dewberry Engineers Inc.

KEY PLAN

SCALE

SEAL

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T C

EN

TE

R O

PT

IO

N

AL

S

TA

N D

-B Y

G

EN

ER

AT

O R

R

EP

LA

C

EM

EN

T

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T

H

IL

LC

R

ES

T D

R

SA

N

FO

R

D , N

C

DENOTES NEW EQUIPMENT

AA

NOTES :

1. MAXIMUM DIAMETER OF OPENING = 6".

2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 5-3/8".

3. MINIMUM 1/4" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT IS REQUIIRED ON EACH SIDE OF A

WALL ASSEMBLY.

4. F-RATING IS 3-HR. WHEN HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT IS USED, AND 2-HR. WHEN HILTI

CP 604 SELF-LEVELING FIRESTOP STOP SEALANT IS USED.

1. CONCRETE FLOOR OR WALL ASSEMBLY (2-HR. OR 3-HR. FIRE-RATING) :

A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MINIMUM 4-1/2" THICK).

B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.

2. MAXIMUM 6" DIAMETER STEEL PIPE SLEEVE (SCHEDULE 40 OR HEAVIER).

3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING :

A. MAXIMUM 4" DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER).

B. MAXIMUM 4" DIAMETER CAST IRON PIPE.

C. MAXIMUM 4" NOMINAL DIAMETER COPPER PIPE.

D. MAXIMUM 4" NOMINAL DIAMETER STEEL CONDUIT.

E. MAXIMUM 4" NOMINAL DIAMETER EMT.

4. MINIMUM 4" THICKNESS MINERAL WOOL (MINIMUM 4 PCF DENSITY) TIGHTLY PACKED.

5. MINIMUM 1/4" DEPTH CP 604 SELF-LEVELING FIRESTOP SEALANT OR HILTI FS-ONE INTUMESCENT

FIRESTOP SEALANT.

6. MINIMUM 1/4" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT AT POINT OF CONTACT. (NOT

REQUIRED WHEN HILTI CP 604 SELF-LEVELING FIRESTOP SEALANT IS USED, ITEM NO. 5).

UL/cUL SYSTEM NO. C-AJ-1421

F-RATING = 2-HR. AND 3-HR.

T-RATING = 0-HR.

1 2

B. WALLBOARD, GYPSUM*--TWO LAYERS OF 5/8 IN. THICK GYPSUM WALLBOARD, AS SPECIFIED IN

D. COPPER PIPE--NOM 4 IN. DIAM. (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

A. STEEL PIPE--NOM 10 IN. DIAM. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

C. COPPER TUBING--NOM 4 IN. DIAM. (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

INDIVIDUAL WALL AND PARTITION DESIGN. MAX. DIAM. OF OPENING TO BE 12 1/2 IN.

TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED.

HILTI CONSTRUCTION CHEMICALS, INC.--FS601 SEALANT

THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS IN THE U.L. FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS--WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM. 2 BY 4 IN. LUMBER SPACED 16 IN. O.C. STEEL STUDS TO BE MIN. 2 1/2 IN. WIDE

2. THROUGH PENETRANTS-- ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. AN ANNULAR SPACE OF MIN. 1/4 IN. TO MAX. 1 1/4 IN. IS REQUIRED WITHIN FIRESTOP SYSTEM.

PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING

B. CONDUIT--NOM 4 IN. DIAM. (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.

3. FILL, VOID OR CAVITY MATERIAL*--SEALANT--MIN 1 1/4 IN. THICKNESS OF FILL MATERIAL APPLIED WIHTIN THE

1. WALL ASSEMBLY--THE FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF

ANNULUS, FLUSH WITH BOTH SURFACES OF WALL.

*BEARING THE U.L. CLASSIFICATION MARKING

AND SPACED MAX. 24 IN. O.C.

A

1B

METAL PIPE THROUGH 2-HR. GYPSUM WALL

U.L. SYSTEM NO. WL1054

T RATING = 0-HR.

F RATING = 2-HR.

A

FRONT VIEW

1A

SECTION A-A

PENETRATION DETAIL

SCALE: N.T.S.

E-001

PENETRATION DETAIL

SCALE: N.T.S.

E-001

E E E

BLACK

PHASE-C BLUE

PHASE-B RED

PHASE-A BLACK

DODO

BLACK

BLUE

RED

BLUE

RED

DO

120/208 VOLTS

DO

BLACK

BLACK

BLUE

RED

BLUE

RED

GROUND BUS

NEUTRAL BUS

WHITE

120/208 VOLTS

GREEN

TOP OR BOTTOM FEED

(SEE RISER DIAGRAM)

WIRE COLOR CODING 120/208V

SCALE: N.T.S.

E-001

GENERAL NOTES:

ALL CUTOVERS, POTENTIAL POWER LOSS CASES, DIRVEWAY CLOSURES, OR SPACES THAT NEED TO BE USED DURING OPERATIONAL HOURS MUST BE COORDINATED WITH OWNER PRIOR TO THE EVENTS LISTED BELOW AND ALL OTHER EVENTS EFFECTING BUILDING OPERATION. UPON RECEIVING NTP CONTRACTOR SHALL COORDINATE ALL MAJOR SHUT DOWN DATES. CONTRACTOR SHALL PROVIDE A REMINDER 2 WEEKS AND AN ADDITIONAL REMINDER THE DAY BEFORE THE FOLLOWING EVENTS ARE TO OCCUR.

·1.1. COORDINATING ANY ROAD CLOSURES NEEDED TO PERFORM WORK NEAR GENERATOR LOCATION.

·1.2. UPDATE GAS METER.

·1.3. INSTALL GENERATOR PAD.

·1.4. TRENCHING OF CONDUITS FOR THE GENERATOR

·1.5. INSTALLATION OF NEW GENERATOR FEEDS

·1.6. INSTALLATION AND RELOCATION OF EQUIPMENT AND BRANCH CIRCUITS RELATED TO THE INVERTER

GENERATOR INSTALLATION:

1. IT IS IMPORTANT TO NOTE THAT CONTRACTOR SHALL HAVE STEPS 2 AND 3 COMPLETE BEFORE THE GENERATOR ARRIVES ON SITE. EC CAN COMPLETE ALL OTHER STEPS

BEFORE OR AFTER THE GENERATOR ARRIVES DEPENDING ON ARRIVAL OF OTHER EQUIPMENT AND SCHEDULING CONFLICTS. CONTRACTOR SHALL INSTALL GENERATOR

ON PAD UPON ARRIVAL, COORDINATE WITH OWNER ON ARRIVAL DATE.

2. EC SHALL TRENCH AND STUB UP ALL CONDUITS FROM GENERATOR TO ATS AND PANEL "EM" AS NOTED ON THE DRAWINGS.

3. CONTRACTOR SHALL POUR EQUIPMENT PAD FOR GENERATOR ACCORDING TO DETAILS.

4. EC SHALL COMPLETE GENERATOR INSTALLATION. MAKING ALL FINAL CONNECTIONS. EC SHALL COORDINATE SHUT DOWN OF DRIVEWAY TO INSTALL NEW GENERATOR.

5. EC SHALL COORDINATE SHUT DOWN TIME WITH OWNER TO SCHEDULE A DAY AND TIME WHEN THE BUILDING IS NOT OCCUPIED. EITHER BEFORE OR AFTER NORMAL

BUSINESS HOURS, ON WEEKENDS OR HOLIDAYS.

6. REMOVE EXISTING ATS AND PROVIDE A NEW FEEDER FOR PANEL EM USING THE ATS AS A JUNCTION BOX IS THE CONTRACTOR CHOOSES TO DO SO.

7. SECOND SHUT DOWN SHALL NOT BE LONGER THAN 60 MINUTES. IF SHUT DOWN IS REQUIRED TO BE LONGER THAN PROVIDE OWNER ENOUGH NOTICE TO SWITCH

CRITICAL LOADS TO NORMAL POWER AND OFF PREVIOUS GENERATOR POWER.

SEQUENCE OF CONSTRUCTION

UP

EXISTING

PANEL "EM"

EXISTING

JUNCTION BOX

ATS (D)

EXISTING PANEL

"MDP"

EXISTING SERVICE

ENTRANCE ECBEXISTING

ATS

EXISTING

SPD

UP

UP

EXISTING

PANEL "EM"

EXISTING

JUNCTION BOX

E

E

E

EXISTING PANEL

"MDP"

EXISTING SERVICE

ENTRANCE ECBEXISTING

ATS

EXISTING

J-BOX

NEW RA

EXISTING

SPD

EX. PANEL "3E"

NEW LIGHTING INVERTER

ELECTRICAL

DEMOLITION AND

NEW WORK

FLOOR PLANS

E-100

B

A

SHEET NO.

D

E

APPROVED BY

CHECKED BY

REVISIONS

TITLE

DRAWN BY

0' 4' 8'2' 1/4" = 1'-0"

2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929

Dewberry Engineers Inc.

KEY PLAN

SCALE

SEAL

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T C

EN

TE

R O

PT

IO

N

AL

S

TA

N D

-B Y

G

EN

ER

AT

O R

R

EP

LA

C

EM

EN

T

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T

H

IL

LC

R

ES

T D

R

SA

N

FO

R

D , N

C

MAIN ELECTRICAL ROOM DEMOLITION

SCALE: 1/4"= 1'-0"

E-100

MAIN ELECTRICAL ROOM NEW WORK

SCALE: 1/4"= 1'-0"

E-100

## KEYED NOTES NEW WORK:KEYED NOTES DEMO:

1. DEMOLISH EXISTING ATS RETAIN ENCLOSURE FOR NEW WORK. REFER TO RISER FOR ADDITIONAL INFORMATION.

2. DEMOLISH EXISTING FEEDERS BETWEEN EXISTING GENERATOR AND ATS, MDP AND ATS, ATS AND PANEL EM. REFER TO RISER DIAGRAM

FOR ADDITIONAL INFORMATION.

1. PROVIDE REMOTE ANNUNCIATER FOR GENERATOR. CONFIRM FINAL LOCATION OF RA WITH OWNER BEFORE

FINAL INSTALLATION.

2. RE-USE DEMOLISHED ATS ENCLOSURE AS A JUNCTION BOX FOR NEW FEEDER FOR PANEL "EM". REUSE

CONDUIT RETAINED FROM DEMOLITION FOR NEW FEEDER WIRE.

3. PROVIDE NEW BREAKERS IN PANEL "EM" AS SHOWN ON PANEL SCHEDULE ON SHEET E-400.

4. PROVIDE NEW LIGHTING INVERTER FOR EGRESS LIGHTS. REFER TO PANEL SCHEDULE ON SHEET E-400 FOR

BRANCH CIRCUITS THAT NEED TO BE MOVED TO INVERTER.

5. PROVIDE FEEDERS AND BRANCH CIRCUITS ASSOCIATED WITH GENERATOR. REFER TO SHEET E-101 FOR MORE INFORMATION. ROUTE NEW FEEDER AND BRANCH CIRCUITS ABOVE CEILING IN STORAGE SPACE ON LEVEL

BELOW ELECTRICAL ROOM. STUB INTO ELECTRICAL ROOM AS INDICATED ON PLANS.

6. DATA CLOSET ROOM LOCATED ON THIRD FLOOR NEXT TO MAIN ELEVATOR. REMOVE EXISTING FOLDING TABLE

FROM DATA CLOSET TO ALLOW FOR INSTALLATION SPACE OF NEW LIGHTING INVERTER.

DATA CLOSET RM 3241

E-100 SCALE: 1/4" = 1'-0"

EX. TAP BOX

UP

EXISTING PANEL "EM"

EXISTING

JUNCTION BOX

EXISTING

CONDUITS

EX. UNDERGROUND

TUNNEL

E

E

E

E

E

E

E

E

E

EX. UTILITY XFMR

NEW 250kW/300kVA

OPTIONAL STAND-BY

GASEOUS GENERATOR

EXISTING

PANEL "MDP"

EXISTING

SERVICE

ENTRANCE

ECBEXISTING

ATS

EXISTING

J-BOX

e e

EM-13

EM-2,4

NEW RA

EPO

EXISTING

SPD

M

AX - 182"

35" M

IN

35" M

IN

ELECTRICAL SITE PLAN - NEW WORK

SCALE: 1/8"= 1'-0"

E-101

ELECTRICAL

NEW WORK

SITE PLAN

E-101

KEYED NOTES NEW WORK:

1. REFER TO SHEET E-001 FOR ADDITIONAL GENERAL NOTES.

GENERAL NOTES:

1. PROVIDE NEW OPTIONAL STAND-BY GENERATOR. NEW STAND-BY GENERATOR IS REQUIRED TO FIT IN EXISTING SPACE AS SHOWN. REFER TO PLAN DIMENSIONS FOR SIZE REFERENCES. REFER TO RISER

DIAGRAM AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. PROVIDE EQUIPMENT PAD FOR GENERATOR PER DETAIL ON THIS SHEET.

3. TURN UP ON EXTERIOR OF BUILDING WITH CONDUITS ASSOCIATED WITH NEW GENERATOR. TURN INTO

BUILDING ABOVE CEILING OF GROUND FLOOR.

4. PROVIDE FEEDER TO ATS AND BRANCH CIRCUITS FOR GENERATOR BLOCK HEATER AND BATTERY

CHARGER.

5. PROVIDE NEW BRANCH CIRCUIT TO SERVE BATTERY CHARGER AND CONNECT TO EXISTING SPARE

BREAKER IN EXISTING PANEL "EM" . REFER TO RISER DIAGRAM FOR CIRCUIT SIZE.

6. PROVIDE NEW BRANCH CIRCUIT AND CONNECT TO NEW BREAKER IN EXISTING PANEL "EM". PROVIDE NEW TWO-POLE, 30A, BREAKER IN PANEL "EM" TO SERVE BLOCK HEATER. REFER TO PANEL SCHEDULE AND

RISER DIAGRAM FOR ADDITIONAL INFORMATION.

7. TURN UP CONDUITS UP FROM BELOW (BASEMENT) TO FIRST FLOOR IN SECONDARY ELECTRICAL ROOM.

CONTINUE ROUTING CONDUITS TO FINAL DESTINATION ON FIRST FLOOR AS SHOWN ON RISER AND FLOOR

PLANS.

8. PROVIDE CONCRETE BOLLARDS AROUND GENERATOR TO PREVENT ACCIDENTAL DAMAGE TO EQUIPMENT.

REFER TO BOLLARD DETAIL.

9. PROVIDE SURFACE MOUNT REMOTE ANNUNCIATOR FOR GENERATOR. COORDINATE WITH OWNER ON FINAL LOCATION. PROVIDE ADDITIONAL 200' OF 3/4"C AND CABLING TO REACH THE RECEPTIONIST DESK.

ALL CONDUIT WILL BE EXPOSED OR ABOVE ACT TILE. ALL EXPOSED CONDUIT SHALL BE PAINTED WHITE TO

MATCH EXISTING EXPOSED CONDUITS.

10. GENERATOR SHALL BE INSTALLED SUCH THAT EXHAUST IS PLACED AWAY FROM BUILDING AND ACCESS TO TERMITE PLUGS IS MAINTAINED. COORDINATE FINAL PLACEMENT OF GENERATOR WITH ACCESS

REQUIREMENTS.

C

B

A

SHEET NO.

D

E

APPROVED BY

CHECKED BY

REVISIONS

TITLE

DRAWN BY

0' 8' 16'4' 1/8" = 1'-0"

2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929

Dewberry Engineers Inc.

KEY PLAN

SCALE

SEAL

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T C

EN

TE

R O

PT

IO

N

AL

S

TA

N D

-B Y

G

EN

ER

AT

O R

R

EP

LA

C

EM

EN

T

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T

H

IL

LC

R

ES

T D

R

SA

N

FO

R

D , N

C

A

TYPICAL SECTION

(DIRECT BURIAL)

24"

MAGNETIC CABLE

MARKING TAPE

3"

3" LAYER OF

COMPACT

SAND (TYP.)

FINAL

BACKFILL

3"

1-1/2" CONDUIT

(TYP. UNLESS NOTED

OTHERWISE)2"

2" MINIMUM BETWEEN

CONDUITS ON ALL SIDES

(TYP. FOR ALL CONDUITS)

2"

SECTION A

(DIRECT BURIAL)

2-1/2"C FOR GEN

POWER2-1/2"C FOR GEN

POWER

2-1/2"C FOR GEN

POWER

1 " C FOR BATTERY

CHARGER

1 " C FOR CTRLS

AND RA

DIRECT BURY SECTIONS

SCALE: NTS

E-101

NEW GENERATOR

STUB-UP AREA. PROVIDE CONDUCTOR

LENGTHS INTO STUB-UP AREA AS

REQUIRED .

20' CONCRETE ENCASED BARE COPPER

ELECTRODE NOT SMALLER THAN 4 AWG

PER NEC 250.52(A)(3).

GROUND ROD WITH EXOTHERMIC WELDED

CONNECTIONS TO GROUNDING CONDUCTORS

TYPICAL

#3/0 BARE COPPER

CONDUCTOR IN CONDUIT

TO EQUIPMENT OPENING

GENERATOR ENCLOSURE

AS REQUIRED BY MANUFACTURER

CONCRETE PAD

AS

R

EQ

'D

B Y

M

AN

U F.

6"

6"

6"

6"

AS REQUIRED BY MANUFACTURER

#4 @ 8" O.C. EACH WAY

3"

3"

#4 @ 8" O.C. EACH WAY

12"Ø

30" 24"

2"

54"

PROVIDE CONC. OVERFILL

TO CREATE DOME CAP

6" SCHEDULE 40 BLACK

STEEL PIPE, FILL W/ 3000

PSA CONC., PAINT ENTIRE

ASSEMBLY YELLOW

CONC. 3000 PSI, W/ 3/4"

CHAMFER

3/4" STUD, WELD TO

PIPE, TYP. FOR THREE

EQUALLY SPACED

ROUND PIPE

GENERATOR BASE - GROUNDING AND STRUCTURAL DETAIL

SCALE: NTS

E-101

BOLLARD DETAIL

SCALE: NTS

E-101

NOTE:

BOLLARD SHALL BE POWDER COATED, SHERWIN WILLIAMS POWDURA COATING

OR APPROVED EQUAL, TO PROVIDE WEATHER RESISTANCE.

NON-SEPARATELY DERIVED GENERATOR

BONDING BUSHING

W/METAL RACEWAYS

NCBA

G

NEW OPTIONAL

STANDBY PNL

MDP

NEW SERVICE

ENTRANCE ECB

NEW OPTIONAL

STANDBY

ATS

GROUNDING

ELECTRODE

CONDUCTOR

5 WIRES

W

IR

ES

5 WIRES-INCLUDING

NEUTRAL AND EQUIPMENT

GROUND CONDUCTOR (EGC)

EGC

5 WIRES

G

A

C N

B A

C N

B

LEVEL 1

ENCLOSURE

BRANCH CIRCUIT

JUNCTION BOX

UNIT CIRCUIT

BREAKERS

CONCRETE BASE

SEE DETAILS

GENERATOR

CONTROL BOX

POWER TO "ATS"

TO EPO

LOAD BANK

CIRCUIT BREAKER

TO EXISTING PNL "EM"

CONTROLS TO NEW ATS

GENERATOR DETAIL

SCALE: NTS

E-101

NCBA

G

GENERATOR GROUNDING

SCALE: NTS

E-101

1 " C FOR BLOCK

HEATER

ELECTRICAL

DEMOLITION AND

NEW WORK

RISER DIAGRAMS

E-300

NEW ELECTRICAL EQUIPMENT

EXISTING ELECTRICAL PANEL, EQUIPMENT AND FEEDERS TO REMAIN

EXISTING ELECTRICAL EQUIPMENT TO BE REMOVED

C

B

A

SHEET NO.

D

E

APPROVED BY

CHECKED BY

REVISIONS

TITLE

DRAWN BY

Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929

Dewberry Engineers Inc.

KEY PLAN

SCALE

SEAL

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T C

EN

TE

R O

PT

IO

N

AL

S

TA

N D

-B Y

G

EN

ER

AT

O R

R

EP

LA

C

EM

EN

T

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T

H

IL

LC

R

ES

T D

R

SA

N

FO

R

D , N

C

DEMAND LOADDESCRIPTION

TOTAL LOAD= 279.6 KVA

LOAD SUMMARY EXISTING SERVICE

223.68 KW

LOAD ADDED: NEW GENERATOR - HEATER,

CHARGER

NEW SOURCE CAPACITY= 1000 AMPS

METERING LOAD DATA PROVIDED BY OWNER

FROM UTILITY COMPANY. METERED LOAD BY DUKE

ENERGY OVER THE LAST 24 MONTHS.

2.5 KW

768 @ 208/120V, 3PH

KEYED NOTES DEMO:

1. CONTRACTOR SHALL DEMOLISH EXISTING GENERATOR LOAD CENTER. REMOVE ALL WIRING BETWEEN LOAD CENTER AND SOURCE.

CONDUIT SHALL REMAIN, CAP OFF AND LABEL. TURN SOURCE BREAKER OFF AND LABEL AS SPARE. REPRINT EXISTING PANEL SCHEDULE

WITH UPDATED CIRCUIT NAMES.

2. CONTRACTOR SHALL DEMOLISH EXISTING FEEDERS. CONDUIT FROM GENERATOR TO ATS SHALL REMAIN, CAP OFF AND LABEL. CONDUIT

BETWEEN ATS, PLANELBOARD, AND SWITCHBOARD SHALL BE REUSED FOR NEW WORK.

3. DEMOLISH EXISTING WALL MOUNTED ATS. RETAIN EXISTING ENCLOSURE FOR NEW WORK. REMOVE ALL LABELING ON EXTERIOR OF ATS

THAT INDICATE TYPE OF EQUIPMENT.

4. DEMOLISH ALL CONNECTIONS TO EXISTING GENERATOR AND ABANDON IN PLACE. REFER TO PLUMBING PLANS FOR DEMOLITION TO GAS

LINES.

#KEYED NOTES NEW WORK:

1. PROVIDE NEW 250KW NATURAL GAS GENERATOR FOR OPTIONAL STAND-BY

LOADS. REFER TO FLOOR PLAN FOR LOCATION OF GENERATOR. REFER TO

SPECIFICATIONS FOR MORE INFORMATION ON GASEOUS GENERATOR.

2. PROVIDE NEW FEEDER FOR GENERATOR POWER SOURCE IN ATS.

3. PROVIDE NEW BRANCH CIRCUITS FOR GENERATOR HEATER AND BATTERY

CHARGER. REFER TO FLOOR PLAN FOR ADDITIONAL INFORMATION.

4. REUSE DEMOLISHED ATS ENCLOSURE RETAINED DURING DEMOLITION AS A

JUNCTION BOX FOR NEW FEEDER.

5. PROVIDE NEW FEEDER FOR PANEL EM. REUSE EXISTING CONDUIT RETAINED

DURING DEMOLITION.

6. PROVIDE NEW FEEDER FOR NEW LIGHTING INVERTER. REFER TO PANEL

SCHEDULE FOR INFORMATION ON LOADS BEING RELOCATED TO LIGHTING

INVERTER.

7. PROVIDE NEW 12.5KVA, 208/120V, THREE PHASE INVERTER FOR LIFE SAFETY

LOADS.REMOVE EXISTING BRANCH CIRCUITS SERVING EXIT SIGNS AND LIGHTING

CIRCUITS FROM PANEL 3E AND EXTEND THE BRANCH CIRCUITS (3#12-3/4"C) TO

LIGHTING INVERTER. CONNECT TO NEW CIRCUIT BREAKERS PROVIDED IN

INVERTER. REFER TO E-400 FOR ADDITIONAL INFORMATION ON RELOCATED

CIRCUITS.

8. LABEL NEW MDP, ENCLOSED CIRCUIT BREAKER, AND GENERATOR DISCONNECT:

"BUILDING SERVED BY 2 SOURCES OF POWER: "UTILITY SE-ECB (MAIN

ELECTRICAL ROOM), OPTIONAL STAND-BY GENERATOR (YARD)."

9. REMOVE EXISTING BRANCH CIRCUITS SERVING EXIT SIGNS AND LIGHTING

CIRCUITS FROM PANEL EM AND EXTEND THE BRANCH CIRCUITS (3#12-3/4"C) TO

NEW LIGHTING INVERTER ON THIRD FLOOR. CONNECT TO NEW CIRCUIT

BREAKERS PROVIDED IN INVERTER . REFER TO E-400 FOR ADDITIONAL

INFORMATION ON RELOCATED CIRCUITS.

10. PROVIDE A NEW 60A, 3P BREAKER IN EXISTING PANEL 3E. REFER TO PANEL

SCHEDULE FOR ADDITIONAL INFORMATION.PARTIAL DEMOLITION WORK RISER DIAGRAM

SCALE: N.T.S.

E-300

EX.

GEN

208Y/120V

106 HILLCREST DR.

LEVEL 1

LEVEL 2

MDP

208/120V

3PH, 4W

MCB

PNL

EM

208Y/120V 400A

MCB

EMERGENCY

ATS

"ATS-LS"

208/120V 400A

PNL

GEN CTRL

208Y/120V

60A

PARTIAL NEW WORK RISER DIAGRAM

SCALE: N.T.S.

E-300

EX.

GEN

208Y/120V

106 HILLCREST DR.

LEVEL 1

LEVEL 2

EXTERIOR YARD

MDP

208/120V

3PH, 4W

MCB

PNL

EM

208Y/120V 400A

MCB

EMERGENCY

NEW GEN

250KW

300KVA

208/120V

3PH

4-500KCMIL, 1#3G

IN 4"C

3 SETS OF 4-300KCMIL, 1#1/0G IN 2-1/2"C EA SET

2 SETS OF

2#10, #10G IN 1"C EA SET

2 SETS OF: 4-300KCMIL, 1#3G IN

4"C

4-500KCMIL, 1#3G IN 4"C

800A

LINETYPE LEGEND:

106 HILLCREST DR.

SE ECB

1000A 208/120V

3PH

NEMA 1

SE ECB

1200A 208/120V

3PH

NEMA 1

3/4"C FOR ATS CTRLS

RA

1"C FOR REMOTE

ANNUCIATOR & CTRLS

SPD

SPD

J

3/4"C FOR ATS CTRLS

ATS 208/120V

3PH, 3P

1200A

NEMA 1

ATS 208/120V

3PH, 3P

1000A

NEMA 1

LEVEL 3

12.5KVA

LIGHTING

LINV

208/120V

3PH

PNL

3E

208Y/120V 100A

MLO

EMERGENCY

3#6, #6N, #10G, IN 1"C 6

EX.

100A

LOAD ADDED: GENERATOR LOAD CENTER -2.5 KW

EXISTING LOAD AT 125%= 960 AMPS

J TO EXISTING

1ST AND 2ND FLOOR

EGRESS LIGHTING

CIRCUITS

#3/0CU

ELECTRICAL

DEMOLITION AND

NEW WORK

PANEL SCHEDULE

E-400

B

A

SHEET NO.

D

E

APPROVED BY

CHECKED BY

REVISIONS

TITLE

DRAWN BY

Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929

Dewberry Engineers Inc.

KEY PLAN

SCALE

SEAL

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T C

EN

TE

R O

PT

IO

N

AL

S

TA

N D

-B Y

G

EN

ER

AT

O R

R

EP

LA

C

EM

EN

T

LE

E

C O

U N

TY

G

O

VE

R N

M

EN

T

H

IL

LC

R

ES

T D

R

SA

N

FO

R

D , N

C

EXISTING PANEL EM SCHEDULE

SCALE: N.T.S.

E-400

LIGHTING INVERTER "LINV" SCHEDULE

SCALE: N.T.S.

E-400

EXISTING PANEL 3E SCHEDULE

SCALE: N.T.S.

E-400

PLUMBING

SYMBOLS &

ABBREVATIONS

P-001

B

A

SHEET NO.

D

E

APPROVED BY

CHECKED BY

REVISIONS

TITLE

DRAWN BY

0' 4' 8'2' 1/4" = 1'-0"

2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929

Dewberry Engineers Inc.

KEY PLAN

SCALE

SEAL

L E

E C

O U

N T

Y G

O V

E R

N M

E N

T C

E N

T E

R O

P T

IO

N

A L

S T

A N

D -B

Y G

E N

E R

A T

O R

R E

P

LA

C E

M E

N T

L E

E C

O U

N T

Y G

O V

E R

N M

E N

T

H

IL

L C

R E

S T

D R

S

A N

F O

R D

, N C

ABBREVIATIONS - PLUMBING

BLV GLOBE VALVE

BTV BUTTERFLY VALVE

BV BALL VALVE

CKV CHECK VALVE

DN DOWN

FBO FURNISHED BY OWNER

G NATURAL GAS

INV INVERT ELEVATION

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

PRV PRESSURE REDUCING VALVE

TYP TYPICAL

1. PROVIDE ALL MATERIALS AND LABOR NECESSARY FOR A COMPLETE PLUMBING

SYSTEM. WARRANTY ALL WORK AND MATERIAL FOR A PERIOD OF AT LEAST ONE

YEAR AFTER ACCEPTANCE BY OWNER.

2. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST

EDITIONS OF:

A. NORTH CAROLINA PLUMBING CODE

B. ANSI

C. UNDERWRITERS LABORATORIES (UL)

D. ALL STATE AND LOCAL CODES AND ORDINANCES

E. NORTH CAROLINA GAS CODE

3. DO NOT SCALE DRAWINGS. OBTAIN ROUGH-IN DIMENSIONS FROM

ARCHITECTURAL DRAWINGS OR FROM MANUFACTURERS PRINTED

INSTRUCTIONS AND RECOMMENDATIONS ONLY. CONTRACTOR SHALL

COORDINATE EXACT LOCATIONS OF ALL EQUIPMENT, CONNECTIONS AND LINES

WITH THE OWNER PRIOR TO INSTALLATION OF ANY PIPING.

4. COORDINATE PLUMBING SYSTEMS WITH ALL TRADES TO AVOID INTERFERENCE

AND CONFLICTS PRIOR TO INSTALLATION OF PIPING, FIXTURES, AND

EQUIPMENT.

5. COORDINATE WITH AND OBTAIN PERMITS AND INSPECTIONS FROM THE LOCAL

AUTHORITY HAVING JURISDICTION.

6. PROVIDE OWNER WITH CERTIFICATES OF FINAL INSPECTION FROM THE LOCAL

AUTHORITY HAVING JURISDICTION.

7. WHENEVER THE WORD "PROVIDE" IS USED, IT SHALL MEAN FURNISH AND

INSTALL COMPLETE AND READY FOR USE.

8. UNLESS OTHERWISE SHOWN OR NOTED, ALL PIPING SHALL BE ROUTED

CONCEALED IN WALLS, CHASES AND/OR ABOVE CEILINGS.

9. ALL SUSPENDED PIPING SHALL BE SUPPORTED FROM FLOOR AND/ OR ROOF

STRUCTURAL MEMBERS. IN NO CASE SHALL PIPING BE SUSPENDED FROM

FLOOR OR ROOF DECKING.

10. UNLESS OTHERWISE INDICATED PLUMBING CONTRACTOR IS RESPONSIBLE FOR

ALL CUTTING, CORE DRILLING, AND PATCHING REQUIRED TO INSTALL PLUMBING

WORK.

11. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE NOT INTENDED TO

SHOW EXACT LOCATIONS AND/OR SIZES OF EXISTING PLUMBING, MECHANICAL,

OR ELECTRICAL OR STRUCTURAL FEATURES, ETC. CONTRACTORS SHALL FIELD

VERIFY EXISTING CONDITIONS BEFORE THE START OF CONSTRUCTION.

CONTRACTORS SHALL COORDINATE WITH OTHER TRADES TO AVOID CONFLICTS

DURING CONSTRUCTION. CONTRACTORS SHALL CONSULT SPECIFICATIONS FOR

CONSTRUCTION MATERIALS AND STANDARDS.

12. WHERE AFFECTED BY THE NEW WORK CONTRACTOR SHALL RELOCATE ANY

EXISTING PIPING, COMPONENTS OR SYSTEMS THAT ARE REQUIRED TO REMAIN

IN ORDER TO KEEP EXISTING SYSTEM OPERATIVE.

GENERAL NOTES - PLUMBING PLUMBING PIPING SYMBOLS

SYMBOL DESCRIPTION

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

CONTROL VALVE

3-WAY CONTROL VALVE

GATE VALVE

GLOBE VALVE

PRESSURE REGULATING VALVE

PIPE TURN UP

PIPE TURN DOWN

PIPE BOTTOM TAKE OFF

PIPE TOP TAKE OFF

PIPE CAP OR PLUG

PIPE UNION

NATURAL GAS

G

TNA

CCC

CCC

EX. TAP BOX

EXISTING PANEL "EM"

EXISTING

JUNCTION BOX

EXISTING

CONDUITS

EX. UNDERGROUND

TUNNEL

NEW 4KVA INVERTER

EX. UTILITY XFMR

NEW 230kW OPTIONAL

STAND-BY GASEOUS

GENERATOR

NEW PANEL

"MDP"

NEW SERVICE

ENTRANCE

ECB

NEW ATS

J-BOX

NEW RA

EPO

NEW SPD

G

G

G

6 7

PLUMBING

NEW WORK

SITE PLAN

P-101

KEYED NOTES NEW WORK:

1. REFER TO P-001 FOR PLUMBING GENERAL NOTES.

GENERAL NOTES:

1. COORDINATE WITH THE UTILITY PROVIDER TO REPLACE THE EXISTING METER TO SUPPORT THE NEW

NATURAL GAS DEMAND AND SUPPLY PRESSURE. UTILITY PROVIDER TO REPLACE NATURAL GAS METER

AND UTILITY SUPPLY AS NECESSARY TO ACCOMMODATE. SUPPLY PRESSURE TO BUILDING SHALL BE 2.0

PSI.

2. UPSIZE EXISTING SUPPLY PIPING DOWNSTREAM TO MATCH SUPPLY SIZE INDICATED ON PLAN FOR

GENERATOR.

3. PROVIDE NEW CONNECTION AND ROUTE ON WALL SURFACE TO NEW GENERATOR LOCATION GOING

ABOVE AND AROUND THE DOOR FRAME.

4. CONTRACTOR TO REPLACE THE EXISTING PRESSURE REGULATING VALVE SERVING THE EXISTING BOILER

(300 CFH) INSIDE THE BUILDING FOR ONE THAT ACCEPTS THE NEW 2.0 PSI INLET AND REDUCES THE

PRESSURE DOWN TO THE NECESSARY RANGE OF EXISTING EQUIPMENT (ASSUMED TO BE 0.5 PSI).

5. EXISTING DIESEL FUEL TANK TO REMAIN.

6. CUT AND CAP BOTH ENDS OF UNDERGROUND DIESEL FUEL SUPPLY PIPING ABOVEGROUND. PRIOR TO

CAPPING BOTH ENDS AND ABANDONING UNDERGROUND PIPING IN PLACE, FULLY EVACUATE ALL DIESEL

FUEL FROM UNDERGROUND PIPING AND FILL PIPING WITH FLOWABLE FILL. CAP AND WATERPROOF FUEL

LINE CONNECTION AT TOP OF TANK.

7. DISCONNECT AND REMOVE ALL DIESEL FUEL SUPPLY PIPING, AND ASSOCIATED SUPPORTS, ROUTED UP

BUILDING EXTERIOR, ALONG ROOF, UP TO AND INCLUDING FINAL CONNECTION TO EXISTING GENERATOR

IN ROOM LOCATED ON ROOF. EVACUATE DIESEL FUEL FROM HOLDING TANK AT GENERATOR AND CAP AND

SEAL FUEL LINE CONNECTION. REFER TO ELECTRICAL SHEETS FOR ADDITIONAL INFORMATION.

C

B

A

SHEET NO.

D

E

APPROVED BY

CHECKED BY

REVISIONS

TITLE

DRAWN BY

0' 8' 16'4' 1/8" = 1'-0"

2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929

Dewberry Engineers Inc.

KEY PLAN

SCALE

SEAL

L E

E C

O U

N T

Y G

O V

E R

N M

E N

T C

E N

T E

R O

P T

IO

N

A L

S T

A N

D -B

Y G

E N

E R

A T

O R

R E

P

LA

C E

M E

N T

L E

E C

O U

N T

Y G

O V

E R

N M

E N

T

H

IL

L C

R E

S T

D R

S

A N

F O

R D

, N C

NATURAL GAS PIPE SIZING CRITERIA:

EXISTING NATURAL GAS DEMAND = 300.0 CFH.

NEW NATURAL GAS DEMAND = 3000.0 CFH.

TOTAL NATURAL GAS DEMAND = 3300.0.

LONGEST PIPE LENGTH ~ 50 FT.

PIPING SIZED IN ACCORDANCE WITH TABLE 402.4(5) OF THE

NC FUEL GAS CODE. EACH PIECE OF EQUIPMENT SHALL BE

PROVIDED WITH A PRESSURE REGULATOR.

NATURAL GAS REGULATOR AND METER DETAIL

SCALE: NTS

GRADE

PLUG/BLEED

VALVE (TYP)

SCHEDULE 40

GALVANIZED STEEL PIPE

SERVICE REGULATOR BY GAS

COMPANY, REFER TO SITE

PLAN FOR TOTAL DEMAND

CFH AND DEVELOPED LENGTH

SERVICE LINE RISER

WITH ANODE

TRANSITION FITTING

UNDERGROUND PIPING

EXISTING GAS

SERVICE TO BUILDING

UNION (TYP)

GAS METER

CONNECTION TO

EMERGENCY GENERATOR

NATURAL GAS VALVE ASSEMBLY DETAIL

SCALE: NTS

G

GAS PRESSURE REGULATOR WITH INTERNAL OVER PRESSURE

DEVICE

SPRING RANGE: 6 TO 14" W.C.

MAX. OUTLET PRESSURE: 13" W.C.

AUTOMATIC GAS SAFETY SHUTOFF VALVE

PER NFPA 37, 5,2,1(3), TYPICAL OF 2

TEE FITTING FOR CONNECTING

DOWNSTREAM PRESSURE-MEASURING

DEVICE

MIN. 10 PIPE DIAMETERS

TEE FITTING WITH THREADED OPENING

POSITIONED TO ALLOW FOR CONNECTION OF A

PRESSURE-MEASURING DEVICE & TO SERVE AS A

SEDIMENT TRAP

-6 TO 10 FOOT LENGTH-

EXCESS FLOW

VALVE ON GAS

SERVICE

STRAINER

1 1/4" NG

EX 3/4" NGSEE PLANS FOR CONTINUATION

2.0 PSI GAS MAIN FROM METER,

SEE PLAN FOR SIZE

TNA

CCC

CCC

2025.09.19 - Lee County Generator Replacement - Permit Set - Electrical
CS-1
E-001 Legend
E-100 ELECTRICAL FLOOR PLAN
E-101 ELECTRICAL SITE PLAN
E-300 ELECTRICAL RISER
E-400 PANEL SCHEDULES

2025.09.19 - Lee County Generator Replacement - Permit Set - Plumbing

2025-09-19T11:43:24-0700
Digitally verifiable PDF exported from www.docusign.com

File details come from the government source that posted it. Updated .