4262-02-26 - Lee County Government Center Generator_Replacement - Construction Drawings.pdf
PDF 2 MB Posted
- Solicitation number
- 204-4262-02-26
- Issued by
- Lee County, North Carolina
About this file
These construction documents detail the Optional Stand-By Generator Replacement project for the Lee County Government Center located at 106 Hillcrest Drive in Sanford, North Carolina. The project scope involves replacing the existing backup generator with a new 250kW optional stand-by generator featuring a natural gas connection and installing a new lighting inverter. The bid number is 4262-02-26, and the documents are 100% construction documents prepared by Dewberry Engineers Inc. from Raleigh, North Carolina. The project involves electrical and plumbing work, including demolition of existing electrical equipment, installation of a new generator, replacement of natural gas piping and regulators, and reconfiguration of electrical panels and circuits.
The project includes comprehensive electrical system modifications, such as installing a new remote annunciator, replacing the automatic transfer switch (ATS), providing new feeders for panel EM, and implementing a 12.5kVA lighting inverter for life safety loads. The natural gas infrastructure will be updated to support the new generator, with the existing gas demand of 300 CFH being increased to a total of 3,300 CFH. The utility provider will be responsible for replacing the natural gas meter to accommodate the increased demand. The construction documents provide detailed specifications for electrical and plumbing work, including site plans, riser diagrams, panel schedules, and technical notes for contractor guidance, with a focus on minimizing disruption to the government center's operations during the installation process.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 4262-02-26 - Lee County Government Center Generator_Replacement - Project Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COVER
SHEET
G-001
C
B
A
SHEET NO.
D
E
APPROVED BY
CHECKED BY
REVISIONS
TITLE
DRAWN BY
DATE
PROJECT NO.
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KEY PLAN
SCALE
SEAL
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T C
EN
TE
R O
PT
IO
N
AL
S
TA
N D
-B Y
G
EN
ER
AT
O R
R
EP
LA
C
EM
EN
T
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T
H
IL
LC
R
ES
T D
R
SA
N
FO
R
D , N
C
LEE COUNTY
GOVERNMENT CENTER
LEE COUNTY GOVERNMENT
805 SOUTH FIFTH STREET
SANFORD, NORTH CAROLINA 27330
CONTACT:
RYAN FAULK
GENERAL SERVICES DIRECTOR
P: (919) 718-4622
RFAULK@LEECOUNTYNC.GOV
OWNER:
DEWBERRY ENGINEERS, INC.
2610 WYCLIFF ROAD, SUITE 410
RALEIGH, NORTH CAROLINA 27607
CONTACT:
BILL HAMILTON, PE
P: (984) 833-4832 whamilton@dewberry.com
ENGINEERING:
PROJECT LOCATION:
DRAWING INDEX:
G-001 COVER SHEET
E-001 ELECTRICAL LEGEND, NOTES AND DETAILS
E-100 ELECTRICAL DEMOLITION AND NEW WORK FLOOR PLANS
E-101 ELECTRICAL NEW WORK SITE PLAN
E-300 ELECTRICAL DEMOLITION AND NEW WORK RISER DIAGRAMS
E-400 ELECTRICAL DEMOLITION AND NEW WORK PANEL SCHEDULE
P-001 PLUMBING SYMBOLS & ABBREVIATIONS
P-101 PLUMBING NEW WORK SITE PLAN
100% CONSTRUCTION DOCUMENTS
OPTIONAL STAND-BY
PROJECT LOCATION
LEE COUNTY GOVERNMENT CENTER
106 HILLCREST DR.
SANFORD, NC 27330
SCALE:1 VICINITY MAP
NTS
PROJECT SCOPE NARRATIVE:
THE SCOPE OF THIS PROJECT IS TO REPLACE THE EXISTING BACKUP
GENERATOR AT THE LEE COUNTY GOVERNMENT CENTER WITH A NEW
250KW OPTIONAL STAND-BY GENERATOR WITH NATURAL GAS
CONNECTION, AND TO PROVIDE A NEW LIGHTING INVERTER.
GENERATOR REPLACEMENT
N O
R
TH
BID NUMBER 4262-02-26
Docusign Envelope ID: A781AA8B-867C-4EA5-A458-87D732FEFAF3
9/19/2025
LEGEND
EQUIPMENT CONNECTION
1. THESE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND DO NOT SHOW ALL DETAILS REQUIRED FOR THE COMPLETE SYSTEMS. THEY SHOULD HOWEVER BE FOLLOWED AS CLOSELY AS POSSIBLE IN THE GENERAL ARRANGEMENT AND LOCATION OF EQUIPMENT. ALL DIMENSIONS SHALL BE CHECKED AT THE BUILDING AND ALL STRUCTURAL AND FINISH CONDITIONS INVESTIGATED. THE CONTRACTOR SHALL ARRANGE HIS WORK TO MEET THESE CONDITIONS AND PROVIDE SUCH EQUIPMENT
AND ACCESSORIES AS MAY BE REQUIRED.
2. BEFORE INSTALLING EQUIPMENT, MAKE FIELD MEASUREMENTS TO INSURE THAT ALL ITEMS OF EQUIPMENT FURNISHED WILL FIT INTO THE SPACE AS SHOWN ON THE DRAWINGS. WHERE EQUIPMENT WILL NOT FIT AS SHOWN ON THE DRAWINGS, PROVIDE A DRAWING TO THE ENGINEER FOR APPROVAL WITH A PROPOSED REVISED
ARRANGEMENT BEFORE INSTALLING THE EQUIPMENT.
3. CONTRACTOR SHALL REFER TO THE SEQUENCE OF CONSTRUCTION TO DETERMINE THE EXTENT OF CONSTRUCTION REQUIRED FOR EACH PHASE OF THE PROJECT.
CONTRACTOR SHALL RESTORE ALL SYSTEMS AS OPERATIONAL AND IN SERVICE AT THE END OF EACH CONSTRUCTION PHASE.
4. PROPERLY SUPPORT ALL WORK AND EQUIPMENT INSTALLED UNDER THIS CONTRACT PLUMB AND PARALLEL WITH BUILDING LINES. STUDY ALL GENERAL, STRUCTURAL, PLUMBING, HVAC, AND ELECTRICAL DRAWINGS, SHOP DRAWINGS, AND CATALOG DATA TO DETERMINE HOW EQUIPMENT, ACCESSORIES, PIPING, FIXTURES, AND RELATED ITEMS ARE TO BE SUPPORTED, MOUNTED, OR SUSPENDED. PROVIDE ALL BOLTS, INSERTS, PIPE STANDS, BRACKETS, STRUCTURAL SUPPORTS, AND ACCESSORIES FOR PROPER SUPPORT OF EQUIPMENT FURNISHED UNDER THIS CONTRACT. COORDINATE THE ELECTRICAL WORK WITH ALL OTHER CONTRACTORS BEFORE BEGINNING WORK TO INSURE THAT THE ELECTRICAL WORK DOES NOT INTERFERE WITH OTHER WORK. LINES WHICH REQUIRE SLOPE SHALL TAKE PRECEDENCE OVER ELECTRICAL WORK. COORDINATE THIS WITH THE PLUMBING AND GENERAL CONTRACTORS.
5. ALL ELECTRICAL WORK SHALL COMPLY WITH APPLICABLE CODES AND THE GOVERNMENTAL AUTHORITIES HAVING JURISDICTION.
6. VERIFY LOCATION AND DIMENSIONS OF ALL EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
7. CONTRACTOR SHALL VISIT THE SITE TO DETERMINE PRE-EXISTING CONDITIONS PRIOR TO SUBMISSION OF BID.
8. CONTRACTOR SHALL PROVIDE CONDUCTORS AND RACEWAYS AS REQUIRED FOR CONNECTION TO NEW EQUIPMENT. REFER TO DRAWINGS FOR NEW EQUIPMENT
LOCATIONS.
9. CONTRACTOR SHALL PROVIDE BLANK STAINLESS STEEL COVER PLATES FOR ALL EXISTING OUTLET BOXES THAT ARE NOT REUSED.
10. ALL CIRCUITS SHALL BE 2#12 THWN WITH #12G THWN-3/4"C UNLESS OTHERWISE NOTED ON PLANS, PANEL SCHEDULES, OR SPECIFICATIONS. ALL UNDERGROUND
CONDUIT SHALL BE A MINIMUM OF 1".
11. NOTIFY THE ENGINEER IN WRITING IMMEDIATELY UPON DISCOVERY OF ANY DISCREPANCY OR POINTS OF CONFLICT IN THE DRAWINGS OR THE SPECIFICATIONS. THE ENGINEER WILL CLARIFY SUCH DISCREPANCY OR POINT OF CONFLICT IN WRITING PRIOR TO THE PROGRESS OF WORK BEYOND THE POINT CONCERNED.
12. CONTRACTOR SHALL INCREASE WIRE SIZE BY ONE SIZE FOR BRANCH CIRCUIT WIRING THAT EXCEEDS 100' IN LENGTH. CONTRACTOR SHALL INCREASE THE WIRE SIZE FOR BRANCH CIRCUIT WIRING ADDITIONALLY BY ONE SIZE FOR EVERY ADDITIONAL 100' IN LENGTH BEYOND 100'.
GENERAL PLAN NOTES
120/208V SURFACE MOUNTED PANELBOARD
PROPOSED ELECTRICAL CONDUIT ROUTE
ARROWHEADS INDICATE HOMERUN CIRCUITS UNLESS
OTHERWISE NOTED. MULTIPLE ARROW HEADS INDICATE
MULTIPLE CIRCUITS DISTRIBUTED EVENLY ACROSS
RECEPTACLES.
TURNED UP CIRCUIT LOCATION
DENOTES EXISTING EQUIPMENT TO BE DEMOLISHED
DENOTES EXISTING EQUIPMENT TO REMAIN
DISCONNECT SWITCH
ELECTRICAL
LEGEND, NOTES
AND DETAILS
E-001
ELECTRICAL EQUIPMENT, AS NOTED ON PLANS
C
B
A
SHEET NO.
D
E
APPROVED BY
CHECKED BY
REVISIONS
TITLE
DRAWN BY
Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KEY PLAN
SCALE
SEAL
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T C
EN
TE
R O
PT
IO
N
AL
S
TA
N D
-B Y
G
EN
ER
AT
O R
R
EP
LA
C
EM
EN
T
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T
H
IL
LC
R
ES
T D
R
SA
N
FO
R
D , N
C
DENOTES NEW EQUIPMENT
AA
NOTES :
1. MAXIMUM DIAMETER OF OPENING = 6".
2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 5-3/8".
3. MINIMUM 1/4" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT IS REQUIIRED ON EACH SIDE OF A
WALL ASSEMBLY.
4. F-RATING IS 3-HR. WHEN HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT IS USED, AND 2-HR. WHEN HILTI
CP 604 SELF-LEVELING FIRESTOP STOP SEALANT IS USED.
1. CONCRETE FLOOR OR WALL ASSEMBLY (2-HR. OR 3-HR. FIRE-RATING) :
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MINIMUM 4-1/2" THICK).
B. ANY UL/cUL CLASSIFIED CONCRETE BLOCK WALL.
2. MAXIMUM 6" DIAMETER STEEL PIPE SLEEVE (SCHEDULE 40 OR HEAVIER).
3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING :
A. MAXIMUM 4" DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER).
B. MAXIMUM 4" DIAMETER CAST IRON PIPE.
C. MAXIMUM 4" NOMINAL DIAMETER COPPER PIPE.
D. MAXIMUM 4" NOMINAL DIAMETER STEEL CONDUIT.
E. MAXIMUM 4" NOMINAL DIAMETER EMT.
4. MINIMUM 4" THICKNESS MINERAL WOOL (MINIMUM 4 PCF DENSITY) TIGHTLY PACKED.
5. MINIMUM 1/4" DEPTH CP 604 SELF-LEVELING FIRESTOP SEALANT OR HILTI FS-ONE INTUMESCENT
FIRESTOP SEALANT.
6. MINIMUM 1/4" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT AT POINT OF CONTACT. (NOT
REQUIRED WHEN HILTI CP 604 SELF-LEVELING FIRESTOP SEALANT IS USED, ITEM NO. 5).
UL/cUL SYSTEM NO. C-AJ-1421
F-RATING = 2-HR. AND 3-HR.
T-RATING = 0-HR.
1 2
B. WALLBOARD, GYPSUM*--TWO LAYERS OF 5/8 IN. THICK GYPSUM WALLBOARD, AS SPECIFIED IN
D. COPPER PIPE--NOM 4 IN. DIAM. (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
A. STEEL PIPE--NOM 10 IN. DIAM. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
C. COPPER TUBING--NOM 4 IN. DIAM. (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
INDIVIDUAL WALL AND PARTITION DESIGN. MAX. DIAM. OF OPENING TO BE 12 1/2 IN.
TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED.
HILTI CONSTRUCTION CHEMICALS, INC.--FS601 SEALANT
THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS IN THE U.L. FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS--WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM. 2 BY 4 IN. LUMBER SPACED 16 IN. O.C. STEEL STUDS TO BE MIN. 2 1/2 IN. WIDE
2. THROUGH PENETRANTS-- ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. AN ANNULAR SPACE OF MIN. 1/4 IN. TO MAX. 1 1/4 IN. IS REQUIRED WITHIN FIRESTOP SYSTEM.
PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING
B. CONDUIT--NOM 4 IN. DIAM. (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.
3. FILL, VOID OR CAVITY MATERIAL*--SEALANT--MIN 1 1/4 IN. THICKNESS OF FILL MATERIAL APPLIED WIHTIN THE
1. WALL ASSEMBLY--THE FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF
ANNULUS, FLUSH WITH BOTH SURFACES OF WALL.
*BEARING THE U.L. CLASSIFICATION MARKING
AND SPACED MAX. 24 IN. O.C.
A
1B
METAL PIPE THROUGH 2-HR. GYPSUM WALL
U.L. SYSTEM NO. WL1054
T RATING = 0-HR.
F RATING = 2-HR.
A
FRONT VIEW
1A
SECTION A-A
PENETRATION DETAIL
SCALE: N.T.S.
E-001
PENETRATION DETAIL
SCALE: N.T.S.
E-001
E E E
BLACK
PHASE-C BLUE
PHASE-B RED
PHASE-A BLACK
DODO
BLACK
BLUE
RED
BLUE
RED
DO
120/208 VOLTS
DO
BLACK
BLACK
BLUE
RED
BLUE
RED
GROUND BUS
NEUTRAL BUS
WHITE
120/208 VOLTS
GREEN
TOP OR BOTTOM FEED
(SEE RISER DIAGRAM)
WIRE COLOR CODING 120/208V
SCALE: N.T.S.
E-001
GENERAL NOTES:
ALL CUTOVERS, POTENTIAL POWER LOSS CASES, DIRVEWAY CLOSURES, OR SPACES THAT NEED TO BE USED DURING OPERATIONAL HOURS MUST BE COORDINATED WITH OWNER PRIOR TO THE EVENTS LISTED BELOW AND ALL OTHER EVENTS EFFECTING BUILDING OPERATION. UPON RECEIVING NTP CONTRACTOR SHALL COORDINATE ALL MAJOR SHUT DOWN DATES. CONTRACTOR SHALL PROVIDE A REMINDER 2 WEEKS AND AN ADDITIONAL REMINDER THE DAY BEFORE THE FOLLOWING EVENTS ARE TO OCCUR.
·1.1. COORDINATING ANY ROAD CLOSURES NEEDED TO PERFORM WORK NEAR GENERATOR LOCATION.
·1.2. UPDATE GAS METER.
·1.3. INSTALL GENERATOR PAD.
·1.4. TRENCHING OF CONDUITS FOR THE GENERATOR
·1.5. INSTALLATION OF NEW GENERATOR FEEDS
·1.6. INSTALLATION AND RELOCATION OF EQUIPMENT AND BRANCH CIRCUITS RELATED TO THE INVERTER
GENERATOR INSTALLATION:
1. IT IS IMPORTANT TO NOTE THAT CONTRACTOR SHALL HAVE STEPS 2 AND 3 COMPLETE BEFORE THE GENERATOR ARRIVES ON SITE. EC CAN COMPLETE ALL OTHER STEPS
BEFORE OR AFTER THE GENERATOR ARRIVES DEPENDING ON ARRIVAL OF OTHER EQUIPMENT AND SCHEDULING CONFLICTS. CONTRACTOR SHALL INSTALL GENERATOR
ON PAD UPON ARRIVAL, COORDINATE WITH OWNER ON ARRIVAL DATE.
2. EC SHALL TRENCH AND STUB UP ALL CONDUITS FROM GENERATOR TO ATS AND PANEL "EM" AS NOTED ON THE DRAWINGS.
3. CONTRACTOR SHALL POUR EQUIPMENT PAD FOR GENERATOR ACCORDING TO DETAILS.
4. EC SHALL COMPLETE GENERATOR INSTALLATION. MAKING ALL FINAL CONNECTIONS. EC SHALL COORDINATE SHUT DOWN OF DRIVEWAY TO INSTALL NEW GENERATOR.
5. EC SHALL COORDINATE SHUT DOWN TIME WITH OWNER TO SCHEDULE A DAY AND TIME WHEN THE BUILDING IS NOT OCCUPIED. EITHER BEFORE OR AFTER NORMAL
BUSINESS HOURS, ON WEEKENDS OR HOLIDAYS.
6. REMOVE EXISTING ATS AND PROVIDE A NEW FEEDER FOR PANEL EM USING THE ATS AS A JUNCTION BOX IS THE CONTRACTOR CHOOSES TO DO SO.
7. SECOND SHUT DOWN SHALL NOT BE LONGER THAN 60 MINUTES. IF SHUT DOWN IS REQUIRED TO BE LONGER THAN PROVIDE OWNER ENOUGH NOTICE TO SWITCH
CRITICAL LOADS TO NORMAL POWER AND OFF PREVIOUS GENERATOR POWER.
SEQUENCE OF CONSTRUCTION
UP
EXISTING
PANEL "EM"
EXISTING
JUNCTION BOX
ATS (D)
EXISTING PANEL
"MDP"
EXISTING SERVICE
ENTRANCE ECBEXISTING
ATS
EXISTING
SPD
UP
UP
EXISTING
PANEL "EM"
EXISTING
JUNCTION BOX
E
E
E
EXISTING PANEL
"MDP"
EXISTING SERVICE
ENTRANCE ECBEXISTING
ATS
EXISTING
J-BOX
NEW RA
EXISTING
SPD
EX. PANEL "3E"
NEW LIGHTING INVERTER
ELECTRICAL
DEMOLITION AND
NEW WORK
FLOOR PLANS
E-100
B
A
SHEET NO.
D
E
APPROVED BY
CHECKED BY
REVISIONS
TITLE
DRAWN BY
0' 4' 8'2' 1/4" = 1'-0"
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KEY PLAN
SCALE
SEAL
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T C
EN
TE
R O
PT
IO
N
AL
S
TA
N D
-B Y
G
EN
ER
AT
O R
R
EP
LA
C
EM
EN
T
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T
H
IL
LC
R
ES
T D
R
SA
N
FO
R
D , N
C
MAIN ELECTRICAL ROOM DEMOLITION
SCALE: 1/4"= 1'-0"
E-100
MAIN ELECTRICAL ROOM NEW WORK
SCALE: 1/4"= 1'-0"
E-100
## KEYED NOTES NEW WORK:KEYED NOTES DEMO:
1. DEMOLISH EXISTING ATS RETAIN ENCLOSURE FOR NEW WORK. REFER TO RISER FOR ADDITIONAL INFORMATION.
2. DEMOLISH EXISTING FEEDERS BETWEEN EXISTING GENERATOR AND ATS, MDP AND ATS, ATS AND PANEL EM. REFER TO RISER DIAGRAM
FOR ADDITIONAL INFORMATION.
1. PROVIDE REMOTE ANNUNCIATER FOR GENERATOR. CONFIRM FINAL LOCATION OF RA WITH OWNER BEFORE
FINAL INSTALLATION.
2. RE-USE DEMOLISHED ATS ENCLOSURE AS A JUNCTION BOX FOR NEW FEEDER FOR PANEL "EM". REUSE
CONDUIT RETAINED FROM DEMOLITION FOR NEW FEEDER WIRE.
3. PROVIDE NEW BREAKERS IN PANEL "EM" AS SHOWN ON PANEL SCHEDULE ON SHEET E-400.
4. PROVIDE NEW LIGHTING INVERTER FOR EGRESS LIGHTS. REFER TO PANEL SCHEDULE ON SHEET E-400 FOR
BRANCH CIRCUITS THAT NEED TO BE MOVED TO INVERTER.
5. PROVIDE FEEDERS AND BRANCH CIRCUITS ASSOCIATED WITH GENERATOR. REFER TO SHEET E-101 FOR MORE INFORMATION. ROUTE NEW FEEDER AND BRANCH CIRCUITS ABOVE CEILING IN STORAGE SPACE ON LEVEL
BELOW ELECTRICAL ROOM. STUB INTO ELECTRICAL ROOM AS INDICATED ON PLANS.
6. DATA CLOSET ROOM LOCATED ON THIRD FLOOR NEXT TO MAIN ELEVATOR. REMOVE EXISTING FOLDING TABLE
FROM DATA CLOSET TO ALLOW FOR INSTALLATION SPACE OF NEW LIGHTING INVERTER.
DATA CLOSET RM 3241
E-100 SCALE: 1/4" = 1'-0"
EX. TAP BOX
UP
EXISTING PANEL "EM"
EXISTING
JUNCTION BOX
EXISTING
CONDUITS
EX. UNDERGROUND
TUNNEL
E
E
E
E
E
E
E
E
E
EX. UTILITY XFMR
NEW 250kW/300kVA
OPTIONAL STAND-BY
GASEOUS GENERATOR
EXISTING
PANEL "MDP"
EXISTING
SERVICE
ENTRANCE
ECBEXISTING
ATS
EXISTING
J-BOX
e e
EM-13
EM-2,4
NEW RA
EPO
EXISTING
SPD
M
AX - 182"
35" M
IN
35" M
IN
ELECTRICAL SITE PLAN - NEW WORK
SCALE: 1/8"= 1'-0"
E-101
ELECTRICAL
NEW WORK
SITE PLAN
E-101
KEYED NOTES NEW WORK:
1. REFER TO SHEET E-001 FOR ADDITIONAL GENERAL NOTES.
GENERAL NOTES:
1. PROVIDE NEW OPTIONAL STAND-BY GENERATOR. NEW STAND-BY GENERATOR IS REQUIRED TO FIT IN EXISTING SPACE AS SHOWN. REFER TO PLAN DIMENSIONS FOR SIZE REFERENCES. REFER TO RISER
DIAGRAM AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. PROVIDE EQUIPMENT PAD FOR GENERATOR PER DETAIL ON THIS SHEET.
3. TURN UP ON EXTERIOR OF BUILDING WITH CONDUITS ASSOCIATED WITH NEW GENERATOR. TURN INTO
BUILDING ABOVE CEILING OF GROUND FLOOR.
4. PROVIDE FEEDER TO ATS AND BRANCH CIRCUITS FOR GENERATOR BLOCK HEATER AND BATTERY
CHARGER.
5. PROVIDE NEW BRANCH CIRCUIT TO SERVE BATTERY CHARGER AND CONNECT TO EXISTING SPARE
BREAKER IN EXISTING PANEL "EM" . REFER TO RISER DIAGRAM FOR CIRCUIT SIZE.
6. PROVIDE NEW BRANCH CIRCUIT AND CONNECT TO NEW BREAKER IN EXISTING PANEL "EM". PROVIDE NEW TWO-POLE, 30A, BREAKER IN PANEL "EM" TO SERVE BLOCK HEATER. REFER TO PANEL SCHEDULE AND
RISER DIAGRAM FOR ADDITIONAL INFORMATION.
7. TURN UP CONDUITS UP FROM BELOW (BASEMENT) TO FIRST FLOOR IN SECONDARY ELECTRICAL ROOM.
CONTINUE ROUTING CONDUITS TO FINAL DESTINATION ON FIRST FLOOR AS SHOWN ON RISER AND FLOOR
PLANS.
8. PROVIDE CONCRETE BOLLARDS AROUND GENERATOR TO PREVENT ACCIDENTAL DAMAGE TO EQUIPMENT.
REFER TO BOLLARD DETAIL.
9. PROVIDE SURFACE MOUNT REMOTE ANNUNCIATOR FOR GENERATOR. COORDINATE WITH OWNER ON FINAL LOCATION. PROVIDE ADDITIONAL 200' OF 3/4"C AND CABLING TO REACH THE RECEPTIONIST DESK.
ALL CONDUIT WILL BE EXPOSED OR ABOVE ACT TILE. ALL EXPOSED CONDUIT SHALL BE PAINTED WHITE TO
MATCH EXISTING EXPOSED CONDUITS.
10. GENERATOR SHALL BE INSTALLED SUCH THAT EXHAUST IS PLACED AWAY FROM BUILDING AND ACCESS TO TERMITE PLUGS IS MAINTAINED. COORDINATE FINAL PLACEMENT OF GENERATOR WITH ACCESS
REQUIREMENTS.
C
B
A
SHEET NO.
D
E
APPROVED BY
CHECKED BY
REVISIONS
TITLE
DRAWN BY
0' 8' 16'4' 1/8" = 1'-0"
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KEY PLAN
SCALE
SEAL
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T C
EN
TE
R O
PT
IO
N
AL
S
TA
N D
-B Y
G
EN
ER
AT
O R
R
EP
LA
C
EM
EN
T
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T
H
IL
LC
R
ES
T D
R
SA
N
FO
R
D , N
C
A
TYPICAL SECTION
(DIRECT BURIAL)
24"
MAGNETIC CABLE
MARKING TAPE
3"
3" LAYER OF
COMPACT
SAND (TYP.)
FINAL
BACKFILL
3"
1-1/2" CONDUIT
(TYP. UNLESS NOTED
OTHERWISE)2"
2" MINIMUM BETWEEN
CONDUITS ON ALL SIDES
(TYP. FOR ALL CONDUITS)
2"
SECTION A
(DIRECT BURIAL)
2-1/2"C FOR GEN
POWER2-1/2"C FOR GEN
POWER
2-1/2"C FOR GEN
POWER
1 " C FOR BATTERY
CHARGER
1 " C FOR CTRLS
AND RA
DIRECT BURY SECTIONS
SCALE: NTS
E-101
NEW GENERATOR
STUB-UP AREA. PROVIDE CONDUCTOR
LENGTHS INTO STUB-UP AREA AS
REQUIRED .
20' CONCRETE ENCASED BARE COPPER
ELECTRODE NOT SMALLER THAN 4 AWG
PER NEC 250.52(A)(3).
GROUND ROD WITH EXOTHERMIC WELDED
CONNECTIONS TO GROUNDING CONDUCTORS
TYPICAL
#3/0 BARE COPPER
CONDUCTOR IN CONDUIT
TO EQUIPMENT OPENING
GENERATOR ENCLOSURE
AS REQUIRED BY MANUFACTURER
CONCRETE PAD
AS
R
EQ
'D
B Y
M
AN
U F.
6"
6"
6"
6"
AS REQUIRED BY MANUFACTURER
#4 @ 8" O.C. EACH WAY
3"
3"
#4 @ 8" O.C. EACH WAY
12"Ø
30" 24"
2"
54"
PROVIDE CONC. OVERFILL
TO CREATE DOME CAP
6" SCHEDULE 40 BLACK
STEEL PIPE, FILL W/ 3000
PSA CONC., PAINT ENTIRE
ASSEMBLY YELLOW
CONC. 3000 PSI, W/ 3/4"
CHAMFER
3/4" STUD, WELD TO
PIPE, TYP. FOR THREE
EQUALLY SPACED
ROUND PIPE
GENERATOR BASE - GROUNDING AND STRUCTURAL DETAIL
SCALE: NTS
E-101
BOLLARD DETAIL
SCALE: NTS
E-101
NOTE:
BOLLARD SHALL BE POWDER COATED, SHERWIN WILLIAMS POWDURA COATING
OR APPROVED EQUAL, TO PROVIDE WEATHER RESISTANCE.
NON-SEPARATELY DERIVED GENERATOR
BONDING BUSHING
W/METAL RACEWAYS
NCBA
G
NEW OPTIONAL
STANDBY PNL
MDP
NEW SERVICE
ENTRANCE ECB
NEW OPTIONAL
STANDBY
ATS
GROUNDING
ELECTRODE
CONDUCTOR
5 WIRES
W
IR
ES
5 WIRES-INCLUDING
NEUTRAL AND EQUIPMENT
GROUND CONDUCTOR (EGC)
EGC
5 WIRES
G
A
C N
B A
C N
B
LEVEL 1
ENCLOSURE
BRANCH CIRCUIT
JUNCTION BOX
UNIT CIRCUIT
BREAKERS
CONCRETE BASE
SEE DETAILS
GENERATOR
CONTROL BOX
POWER TO "ATS"
TO EPO
LOAD BANK
CIRCUIT BREAKER
TO EXISTING PNL "EM"
CONTROLS TO NEW ATS
GENERATOR DETAIL
SCALE: NTS
E-101
NCBA
G
GENERATOR GROUNDING
SCALE: NTS
E-101
1 " C FOR BLOCK
HEATER
ELECTRICAL
DEMOLITION AND
NEW WORK
RISER DIAGRAMS
E-300
NEW ELECTRICAL EQUIPMENT
EXISTING ELECTRICAL PANEL, EQUIPMENT AND FEEDERS TO REMAIN
EXISTING ELECTRICAL EQUIPMENT TO BE REMOVED
C
B
A
SHEET NO.
D
E
APPROVED BY
CHECKED BY
REVISIONS
TITLE
DRAWN BY
Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KEY PLAN
SCALE
SEAL
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T C
EN
TE
R O
PT
IO
N
AL
S
TA
N D
-B Y
G
EN
ER
AT
O R
R
EP
LA
C
EM
EN
T
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T
H
IL
LC
R
ES
T D
R
SA
N
FO
R
D , N
C
DEMAND LOADDESCRIPTION
TOTAL LOAD= 279.6 KVA
LOAD SUMMARY EXISTING SERVICE
223.68 KW
LOAD ADDED: NEW GENERATOR - HEATER,
CHARGER
NEW SOURCE CAPACITY= 1000 AMPS
METERING LOAD DATA PROVIDED BY OWNER
FROM UTILITY COMPANY. METERED LOAD BY DUKE
ENERGY OVER THE LAST 24 MONTHS.
2.5 KW
768 @ 208/120V, 3PH
KEYED NOTES DEMO:
1. CONTRACTOR SHALL DEMOLISH EXISTING GENERATOR LOAD CENTER. REMOVE ALL WIRING BETWEEN LOAD CENTER AND SOURCE.
CONDUIT SHALL REMAIN, CAP OFF AND LABEL. TURN SOURCE BREAKER OFF AND LABEL AS SPARE. REPRINT EXISTING PANEL SCHEDULE
WITH UPDATED CIRCUIT NAMES.
2. CONTRACTOR SHALL DEMOLISH EXISTING FEEDERS. CONDUIT FROM GENERATOR TO ATS SHALL REMAIN, CAP OFF AND LABEL. CONDUIT
BETWEEN ATS, PLANELBOARD, AND SWITCHBOARD SHALL BE REUSED FOR NEW WORK.
3. DEMOLISH EXISTING WALL MOUNTED ATS. RETAIN EXISTING ENCLOSURE FOR NEW WORK. REMOVE ALL LABELING ON EXTERIOR OF ATS
THAT INDICATE TYPE OF EQUIPMENT.
4. DEMOLISH ALL CONNECTIONS TO EXISTING GENERATOR AND ABANDON IN PLACE. REFER TO PLUMBING PLANS FOR DEMOLITION TO GAS
LINES.
#KEYED NOTES NEW WORK:
1. PROVIDE NEW 250KW NATURAL GAS GENERATOR FOR OPTIONAL STAND-BY
LOADS. REFER TO FLOOR PLAN FOR LOCATION OF GENERATOR. REFER TO
SPECIFICATIONS FOR MORE INFORMATION ON GASEOUS GENERATOR.
2. PROVIDE NEW FEEDER FOR GENERATOR POWER SOURCE IN ATS.
3. PROVIDE NEW BRANCH CIRCUITS FOR GENERATOR HEATER AND BATTERY
CHARGER. REFER TO FLOOR PLAN FOR ADDITIONAL INFORMATION.
4. REUSE DEMOLISHED ATS ENCLOSURE RETAINED DURING DEMOLITION AS A
JUNCTION BOX FOR NEW FEEDER.
5. PROVIDE NEW FEEDER FOR PANEL EM. REUSE EXISTING CONDUIT RETAINED
DURING DEMOLITION.
6. PROVIDE NEW FEEDER FOR NEW LIGHTING INVERTER. REFER TO PANEL
SCHEDULE FOR INFORMATION ON LOADS BEING RELOCATED TO LIGHTING
INVERTER.
7. PROVIDE NEW 12.5KVA, 208/120V, THREE PHASE INVERTER FOR LIFE SAFETY
LOADS.REMOVE EXISTING BRANCH CIRCUITS SERVING EXIT SIGNS AND LIGHTING
CIRCUITS FROM PANEL 3E AND EXTEND THE BRANCH CIRCUITS (3#12-3/4"C) TO
LIGHTING INVERTER. CONNECT TO NEW CIRCUIT BREAKERS PROVIDED IN
INVERTER. REFER TO E-400 FOR ADDITIONAL INFORMATION ON RELOCATED
CIRCUITS.
8. LABEL NEW MDP, ENCLOSED CIRCUIT BREAKER, AND GENERATOR DISCONNECT:
"BUILDING SERVED BY 2 SOURCES OF POWER: "UTILITY SE-ECB (MAIN
ELECTRICAL ROOM), OPTIONAL STAND-BY GENERATOR (YARD)."
9. REMOVE EXISTING BRANCH CIRCUITS SERVING EXIT SIGNS AND LIGHTING
CIRCUITS FROM PANEL EM AND EXTEND THE BRANCH CIRCUITS (3#12-3/4"C) TO
NEW LIGHTING INVERTER ON THIRD FLOOR. CONNECT TO NEW CIRCUIT
BREAKERS PROVIDED IN INVERTER . REFER TO E-400 FOR ADDITIONAL
INFORMATION ON RELOCATED CIRCUITS.
10. PROVIDE A NEW 60A, 3P BREAKER IN EXISTING PANEL 3E. REFER TO PANEL
SCHEDULE FOR ADDITIONAL INFORMATION.PARTIAL DEMOLITION WORK RISER DIAGRAM
SCALE: N.T.S.
E-300
EX.
GEN
208Y/120V
106 HILLCREST DR.
LEVEL 1
LEVEL 2
MDP
208/120V
3PH, 4W
MCB
PNL
EM
208Y/120V 400A
MCB
EMERGENCY
ATS
"ATS-LS"
208/120V 400A
PNL
GEN CTRL
208Y/120V
60A
PARTIAL NEW WORK RISER DIAGRAM
SCALE: N.T.S.
E-300
EX.
GEN
208Y/120V
106 HILLCREST DR.
LEVEL 1
LEVEL 2
EXTERIOR YARD
MDP
208/120V
3PH, 4W
MCB
PNL
EM
208Y/120V 400A
MCB
EMERGENCY
NEW GEN
250KW
300KVA
208/120V
3PH
4-500KCMIL, 1#3G
IN 4"C
3 SETS OF 4-300KCMIL, 1#1/0G IN 2-1/2"C EA SET
2 SETS OF
2#10, #10G IN 1"C EA SET
2 SETS OF: 4-300KCMIL, 1#3G IN
4"C
4-500KCMIL, 1#3G IN 4"C
800A
LINETYPE LEGEND:
106 HILLCREST DR.
SE ECB
1000A 208/120V
3PH
NEMA 1
SE ECB
1200A 208/120V
3PH
NEMA 1
3/4"C FOR ATS CTRLS
RA
1"C FOR REMOTE
ANNUCIATOR & CTRLS
SPD
SPD
J
3/4"C FOR ATS CTRLS
ATS 208/120V
3PH, 3P
1200A
NEMA 1
ATS 208/120V
3PH, 3P
1000A
NEMA 1
LEVEL 3
12.5KVA
LIGHTING
LINV
208/120V
3PH
PNL
3E
208Y/120V 100A
MLO
EMERGENCY
3#6, #6N, #10G, IN 1"C 6
EX.
100A
LOAD ADDED: GENERATOR LOAD CENTER -2.5 KW
EXISTING LOAD AT 125%= 960 AMPS
J TO EXISTING
1ST AND 2ND FLOOR
EGRESS LIGHTING
CIRCUITS
#3/0CU
ELECTRICAL
DEMOLITION AND
NEW WORK
PANEL SCHEDULE
E-400
B
A
SHEET NO.
D
E
APPROVED BY
CHECKED BY
REVISIONS
TITLE
DRAWN BY
Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KEY PLAN
SCALE
SEAL
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T C
EN
TE
R O
PT
IO
N
AL
S
TA
N D
-B Y
G
EN
ER
AT
O R
R
EP
LA
C
EM
EN
T
LE
E
C O
U N
TY
G
O
VE
R N
M
EN
T
H
IL
LC
R
ES
T D
R
SA
N
FO
R
D , N
C
EXISTING PANEL EM SCHEDULE
SCALE: N.T.S.
E-400
LIGHTING INVERTER "LINV" SCHEDULE
SCALE: N.T.S.
E-400
EXISTING PANEL 3E SCHEDULE
SCALE: N.T.S.
E-400
PLUMBING
SYMBOLS &
ABBREVATIONS
P-001
B
A
SHEET NO.
D
E
APPROVED BY
CHECKED BY
REVISIONS
TITLE
DRAWN BY
0' 4' 8'2' 1/4" = 1'-0"
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KEY PLAN
SCALE
SEAL
L E
E C
O U
N T
Y G
O V
E R
N M
E N
T C
E N
T E
R O
P T
IO
N
A L
S T
A N
D -B
Y G
E N
E R
A T
O R
R E
P
LA
C E
M E
N T
L E
E C
O U
N T
Y G
O V
E R
N M
E N
T
H
IL
L C
R E
S T
D R
S
A N
F O
R D
, N C
ABBREVIATIONS - PLUMBING
BLV GLOBE VALVE
BTV BUTTERFLY VALVE
BV BALL VALVE
CKV CHECK VALVE
DN DOWN
FBO FURNISHED BY OWNER
G NATURAL GAS
INV INVERT ELEVATION
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
PRV PRESSURE REDUCING VALVE
TYP TYPICAL
1. PROVIDE ALL MATERIALS AND LABOR NECESSARY FOR A COMPLETE PLUMBING
SYSTEM. WARRANTY ALL WORK AND MATERIAL FOR A PERIOD OF AT LEAST ONE
YEAR AFTER ACCEPTANCE BY OWNER.
2. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST
EDITIONS OF:
A. NORTH CAROLINA PLUMBING CODE
B. ANSI
C. UNDERWRITERS LABORATORIES (UL)
D. ALL STATE AND LOCAL CODES AND ORDINANCES
E. NORTH CAROLINA GAS CODE
3. DO NOT SCALE DRAWINGS. OBTAIN ROUGH-IN DIMENSIONS FROM
ARCHITECTURAL DRAWINGS OR FROM MANUFACTURERS PRINTED
INSTRUCTIONS AND RECOMMENDATIONS ONLY. CONTRACTOR SHALL
COORDINATE EXACT LOCATIONS OF ALL EQUIPMENT, CONNECTIONS AND LINES
WITH THE OWNER PRIOR TO INSTALLATION OF ANY PIPING.
4. COORDINATE PLUMBING SYSTEMS WITH ALL TRADES TO AVOID INTERFERENCE
AND CONFLICTS PRIOR TO INSTALLATION OF PIPING, FIXTURES, AND
EQUIPMENT.
5. COORDINATE WITH AND OBTAIN PERMITS AND INSPECTIONS FROM THE LOCAL
AUTHORITY HAVING JURISDICTION.
6. PROVIDE OWNER WITH CERTIFICATES OF FINAL INSPECTION FROM THE LOCAL
AUTHORITY HAVING JURISDICTION.
7. WHENEVER THE WORD "PROVIDE" IS USED, IT SHALL MEAN FURNISH AND
INSTALL COMPLETE AND READY FOR USE.
8. UNLESS OTHERWISE SHOWN OR NOTED, ALL PIPING SHALL BE ROUTED
CONCEALED IN WALLS, CHASES AND/OR ABOVE CEILINGS.
9. ALL SUSPENDED PIPING SHALL BE SUPPORTED FROM FLOOR AND/ OR ROOF
STRUCTURAL MEMBERS. IN NO CASE SHALL PIPING BE SUSPENDED FROM
FLOOR OR ROOF DECKING.
10. UNLESS OTHERWISE INDICATED PLUMBING CONTRACTOR IS RESPONSIBLE FOR
ALL CUTTING, CORE DRILLING, AND PATCHING REQUIRED TO INSTALL PLUMBING
WORK.
11. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE NOT INTENDED TO
SHOW EXACT LOCATIONS AND/OR SIZES OF EXISTING PLUMBING, MECHANICAL,
OR ELECTRICAL OR STRUCTURAL FEATURES, ETC. CONTRACTORS SHALL FIELD
VERIFY EXISTING CONDITIONS BEFORE THE START OF CONSTRUCTION.
CONTRACTORS SHALL COORDINATE WITH OTHER TRADES TO AVOID CONFLICTS
DURING CONSTRUCTION. CONTRACTORS SHALL CONSULT SPECIFICATIONS FOR
CONSTRUCTION MATERIALS AND STANDARDS.
12. WHERE AFFECTED BY THE NEW WORK CONTRACTOR SHALL RELOCATE ANY
EXISTING PIPING, COMPONENTS OR SYSTEMS THAT ARE REQUIRED TO REMAIN
IN ORDER TO KEEP EXISTING SYSTEM OPERATIVE.
GENERAL NOTES - PLUMBING PLUMBING PIPING SYMBOLS
SYMBOL DESCRIPTION
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
CONTROL VALVE
3-WAY CONTROL VALVE
GATE VALVE
GLOBE VALVE
PRESSURE REGULATING VALVE
PIPE TURN UP
PIPE TURN DOWN
PIPE BOTTOM TAKE OFF
PIPE TOP TAKE OFF
PIPE CAP OR PLUG
PIPE UNION
NATURAL GAS
G
TNA
CCC
CCC
EX. TAP BOX
EXISTING PANEL "EM"
EXISTING
JUNCTION BOX
EXISTING
CONDUITS
EX. UNDERGROUND
TUNNEL
NEW 4KVA INVERTER
EX. UTILITY XFMR
NEW 230kW OPTIONAL
STAND-BY GASEOUS
GENERATOR
NEW PANEL
"MDP"
NEW SERVICE
ENTRANCE
ECB
NEW ATS
J-BOX
NEW RA
EPO
NEW SPD
G
G
G
6 7
PLUMBING
NEW WORK
SITE PLAN
P-101
KEYED NOTES NEW WORK:
1. REFER TO P-001 FOR PLUMBING GENERAL NOTES.
GENERAL NOTES:
1. COORDINATE WITH THE UTILITY PROVIDER TO REPLACE THE EXISTING METER TO SUPPORT THE NEW
NATURAL GAS DEMAND AND SUPPLY PRESSURE. UTILITY PROVIDER TO REPLACE NATURAL GAS METER
AND UTILITY SUPPLY AS NECESSARY TO ACCOMMODATE. SUPPLY PRESSURE TO BUILDING SHALL BE 2.0
PSI.
2. UPSIZE EXISTING SUPPLY PIPING DOWNSTREAM TO MATCH SUPPLY SIZE INDICATED ON PLAN FOR
GENERATOR.
3. PROVIDE NEW CONNECTION AND ROUTE ON WALL SURFACE TO NEW GENERATOR LOCATION GOING
ABOVE AND AROUND THE DOOR FRAME.
4. CONTRACTOR TO REPLACE THE EXISTING PRESSURE REGULATING VALVE SERVING THE EXISTING BOILER
(300 CFH) INSIDE THE BUILDING FOR ONE THAT ACCEPTS THE NEW 2.0 PSI INLET AND REDUCES THE
PRESSURE DOWN TO THE NECESSARY RANGE OF EXISTING EQUIPMENT (ASSUMED TO BE 0.5 PSI).
5. EXISTING DIESEL FUEL TANK TO REMAIN.
6. CUT AND CAP BOTH ENDS OF UNDERGROUND DIESEL FUEL SUPPLY PIPING ABOVEGROUND. PRIOR TO
CAPPING BOTH ENDS AND ABANDONING UNDERGROUND PIPING IN PLACE, FULLY EVACUATE ALL DIESEL
FUEL FROM UNDERGROUND PIPING AND FILL PIPING WITH FLOWABLE FILL. CAP AND WATERPROOF FUEL
LINE CONNECTION AT TOP OF TANK.
7. DISCONNECT AND REMOVE ALL DIESEL FUEL SUPPLY PIPING, AND ASSOCIATED SUPPORTS, ROUTED UP
BUILDING EXTERIOR, ALONG ROOF, UP TO AND INCLUDING FINAL CONNECTION TO EXISTING GENERATOR
IN ROOM LOCATED ON ROOF. EVACUATE DIESEL FUEL FROM HOLDING TANK AT GENERATOR AND CAP AND
SEAL FUEL LINE CONNECTION. REFER TO ELECTRICAL SHEETS FOR ADDITIONAL INFORMATION.
C
B
A
SHEET NO.
D
E
APPROVED BY
CHECKED BY
REVISIONS
TITLE
DRAWN BY
0' 8' 16'4' 1/8" = 1'-0"
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KEY PLAN
SCALE
SEAL
L E
E C
O U
N T
Y G
O V
E R
N M
E N
T C
E N
T E
R O
P T
IO
N
A L
S T
A N
D -B
Y G
E N
E R
A T
O R
R E
P
LA
C E
M E
N T
L E
E C
O U
N T
Y G
O V
E R
N M
E N
T
H
IL
L C
R E
S T
D R
S
A N
F O
R D
, N C
NATURAL GAS PIPE SIZING CRITERIA:
EXISTING NATURAL GAS DEMAND = 300.0 CFH.
NEW NATURAL GAS DEMAND = 3000.0 CFH.
TOTAL NATURAL GAS DEMAND = 3300.0.
LONGEST PIPE LENGTH ~ 50 FT.
PIPING SIZED IN ACCORDANCE WITH TABLE 402.4(5) OF THE
NC FUEL GAS CODE. EACH PIECE OF EQUIPMENT SHALL BE
PROVIDED WITH A PRESSURE REGULATOR.
NATURAL GAS REGULATOR AND METER DETAIL
SCALE: NTS
GRADE
PLUG/BLEED
VALVE (TYP)
SCHEDULE 40
GALVANIZED STEEL PIPE
SERVICE REGULATOR BY GAS
COMPANY, REFER TO SITE
PLAN FOR TOTAL DEMAND
CFH AND DEVELOPED LENGTH
SERVICE LINE RISER
WITH ANODE
TRANSITION FITTING
UNDERGROUND PIPING
EXISTING GAS
SERVICE TO BUILDING
UNION (TYP)
GAS METER
CONNECTION TO
EMERGENCY GENERATOR
NATURAL GAS VALVE ASSEMBLY DETAIL
SCALE: NTS
G
GAS PRESSURE REGULATOR WITH INTERNAL OVER PRESSURE
DEVICE
SPRING RANGE: 6 TO 14" W.C.
MAX. OUTLET PRESSURE: 13" W.C.
AUTOMATIC GAS SAFETY SHUTOFF VALVE
PER NFPA 37, 5,2,1(3), TYPICAL OF 2
TEE FITTING FOR CONNECTING
DOWNSTREAM PRESSURE-MEASURING
DEVICE
MIN. 10 PIPE DIAMETERS
TEE FITTING WITH THREADED OPENING
POSITIONED TO ALLOW FOR CONNECTION OF A
PRESSURE-MEASURING DEVICE & TO SERVE AS A
SEDIMENT TRAP
-6 TO 10 FOOT LENGTH-
EXCESS FLOW
VALVE ON GAS
SERVICE
STRAINER
1 1/4" NG
EX 3/4" NGSEE PLANS FOR CONTINUATION
2.0 PSI GAS MAIN FROM METER,
SEE PLAN FOR SIZE
TNA
CCC
CCC
| 2025.09.19 - Lee County Generator Replacement - Permit Set - Electrical |
| CS-1 |
| E-001 Legend |
| E-100 ELECTRICAL FLOOR PLAN |
| E-101 ELECTRICAL SITE PLAN |
| E-300 ELECTRICAL RISER |
| E-400 PANEL SCHEDULES |
2025.09.19 - Lee County Generator Replacement - Permit Set - Plumbing
| 2025-09-19T11:43:24-0700 | |
| Digitally verifiable PDF exported from www.docusign.com |
File details come from the government source that posted it. Updated .