The 151st Intelligence Support Squadron requires procurement and installation of replacement raised access computer floor tiles in Building 302, Room 110. The project involves removing 700 existing aged floor tiles and installing 700 new concrete-filled tiles and 100 perforated airflow tiles into the existing raised access flooring system understructure. The concrete-filled tiles must be 24" x 24" with an all-steel welded shell filled with a cementitious core, Class A flame spread rating, gray color, and specified load capacities (Design Load: 1250 lbs, Uniform Load: 300 lbs, Ultimate Load: 2500 lbs, Impact Load: 150 lbs, Rolling Load: 1000 lbs for 10 passes / 800 lbs for 10,000 passes). The perforated airflow tiles must also be 24" x 24", all-steel with cross-punch perforation, at least 25% open area for airflow, Class A flame spread rating, gray color, and fully compatible with the integrated floor system load-bearing requirements. Both tile types must include at least a standard manufacturer warranty. The contractor must extract and remove existing tiles, install new tiles ensuring seamless and level fit, cut holes for data and power cables with industry standard grommets, seal all cut tiles, and haul away all old tiles in accordance with local regulations. All cutting occurs in a designated staging area outside the installation space. Workers must clear security restrictions for the classified area and will be escorted at all times. Delivery is anticipated no later than 90 days after receipt of award, with the vendor required to state alternate timelines if unable to meet this deadline. The vendor must provide all tools, equipment, and personnel for installation and disposal during UTANG operating hours of 0600-1630 Monday through Thursday. Delivery and installation will occur at 765 N 220 W Salt Lake City, UT 84116.

View the file

Other files

File Type Posted
SOURCES SOUGHT.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIFICATIONS

Bldg 302 Rm 110 Bullpen Area Tile Replacement

BACKGROUND: The 151st Intelligence Support Squadron (ISS), located at the Roland R.

Wright Utah Air National Guard Base in Salt Lake City, UT, has a requirement to acquire and replace the existing raised access computer floor tiles located in building 302, room 110 bullpen area.

This project is strictly for the procurement and installation of the new replacement tiles into the existing, currently installed raised access flooring system understructure. It does not involve installing a new pedestal or grid network understructure.

The scope of work requires the contractor to:

1. Extract and remove the existing aged floor tiles.

2. Install the new concrete-filled and perforated airflow tiles into the existing grid system, ensuring a seamless, level, and flush fit. Cut holes as needed for data and power cables and supply industry standard gourmets for holes. Seal all cut tiles to industry standards.

All cutting will be done outside the space in a designated staging area. Workers must clear security restrictions for working in a classified area and will be always escorted.

3. Completely remove, haul away, and properly dispose of all old, replaced tiles off-site in accordance with local regulations.

EQUIPMENT: The following specifications delineate the required criteria for each of the items needed. The proposed products shall meet the stated salient characteristics to be considered acceptable.

1) Concrete Filled Floor Tile

QTY: 700

Salient Characteristics-

• Shall All-steel welded shell filled with a cementitious core.

• Shall be 24" x 24" (standard panel size).

• Shall be high strength, solid walk feel.

• Shall Class A flame spread, non-combustible.

• Design Load: 1250 lbs• Uniform Load: 300 lbs• Ultimate Load: 2500 lbs• Impact

Load: 150 lbs• Rolling Load: 1000 lbs (10 passes) / 800 lbs (10,000 passes).

• Shall have at least a standard manufacturer warranty.

• Shall be gray in color to closely match existing building tiles as much as possible.

2) Perforated Airflow Tile

QTY: 100

Salient Characteristics-

• Shall be all-steel with cross-punch perforation pattern.

• Shall be 24" x 24" (standard panel size).

• Shall have at least 25% open area for air flow.

• Shall be Class A flame spread, non-combustible.

• Shall be fully compatible with the load-bearing requirements of the integrated floor system.

• Shall have at least a standard manufacturer warranty.

• Shall be gray in color to closely match existing building tiles as much as possible.

DELIVERY, REMOVAL/DISPOSAL, & INSTALLATION: Shipment and delivery of these items is anticipated to be no later than 90 days after receipt of award. If this delivery timeline cannot be met, the vendor shall state the best alternate delivery timeline they can provide. The vendor shall provide all tools, equipment, and personnel needed for installation of the tiles and disposal as per federal guidelines, setting the new tiles in place, cutting edge tiles to fit and access holes, during UTANG operating hours of 0600-1630 Monday through Thursday. Delivery and installation will take place at: 765 N 220 W Salt Lake City, UT 84116.

**END SPECIFICATIONS**