This document is a Hazardous Materials Investigation Report for the Eielson Air Force Base (EAFB) Combined Heat and Power Plant (CHPP) Black Start Generator Upgrade Project. The report provides the results of limited sampling and assessment of asbestos-containing materials, lead-based paint, and settled dust within the project area. Key findings include:
No asbestos-containing materials were identified, but dust on horizontal surfaces contained low levels of lead contamination. Lighting fixtures may contain mercury and PCBs. The project area is located within a known soil/groundwater contamination source area, requiring special approval and handling procedures prior to soil disturbance. The report provides recommendations for contractor notification, worker protection, dust cleaning, and waste characterization prior to demolition and construction activities. An overview of the related federal contract opportunity indicates it is a pre-solicitation for architect-engineering services to replace the CHPP generators at Eielson AFB, with a solicitation due date of June 18, 2024.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUSTAINABLE ENVIRONMENT, ENERGY,
HEALTH & SAFETY PROFESSIONAL SERVICES
Https://Nortechinc.Sharepoint.Com/00-Jobs/2018/1026/Shared Documents/Reports/Drafts/Blackstartgenerator-Hazmatreport-Final.Docx
NORTECH, Inc.
Accounting Office:
2400 College Rd
Fairbanks, AK 99709 907.452.5688
907.452.5694 Fax
3105 Lakeshore Drive Suite A106
Anchorage, AK 99517 907.222.2445
907.222.0915 Fax
5438 Shaune Drive Suite B
Juneau, AK 99801 907.586.6813
907.586.6819 Fax
www.nortechengr.com
January 23, 2019 Sent via email to:
Electric Power Systems, Inc. jrowland@espinc.com 3305 Arctic Boulevard, Suite 200 Anchorage, AK 99503
Attn: Jason Rowland, PE
RE: Hazardous Materials Investigation and Design Repair Black Start Generator, Building 6203, EAFB CHPP / FTQW 12-1012
Jason:
NORTECH Sustainable Environment, Energy, Health & Safety Professional Services is pleased to provide Electric Power Systems (EPS) with this Limited Hazardous Materials Investigation Report for the Eielson Air Force Base (EAFB) Combined Heat and Power Plant (CHPP) Design Repair Black Start Generator Project. The following is a brief synopsis of the background, scope of work, methodology, field activities, and sampling results with discussion, including conclusions and recommendations where appropriate.
Background and Scope of Work EAFB selected the EPS team to perform the investigation and design of upgrades to the CHPP Black Start Generator. The specific goals of the project are to replace the existing Black Start Generator, repairing heating and ventilation in the Black Start room.
The 2.5 MW diesel-powered Black Start Generator is housed on the lower level, inside the CHPP on EAFB. This unit provides a “black start” capability for restoring electrical power without relying on the external electric power transmission network in the event of a total power outage. The current Black Start generator was manufactured by Electro-Motive Division (EMD) of the General Motors Corporation and was installed in 1987 as part of a major plant upgrade.
Due to excessive emissions, Eielson’s Air Permit includes operational limits for the unit. The Black Start generator is not allowed to consume more than 157,000 gallons of fuel in any rolling 12-month period and the peak output is limited to 1,800 kW. The current Black Start Generator was used for peak load shaving, but due to the fuel and output limits, the practice is no longer possible.
NORTECH’s scope of work is to provide limited hazardous material investigation services. This included sampling suspect asbestos containing building material, analyzing paint for lead content, and sampling settled dust for asbestos, and lead contamination within project areas of this phase of the project.
Methodology Project efforts were completed in accordance with NORTECH Hazardous Material Standardized Methodologies (v17). Project work was performed by an experienced Health and Safety Professional with current EPA AHERA inspector certification
Hazardous Materials Investigation and Design Repair Black Start Generator EAFB CHPP/ FTQW 12-1012
Page 2Https://Nortechinc.Sharepoint.Com/00-Jobs/2018/1026/Shared Documents/Reports/Drafts/Blackstartgenerator-Hazmatreport-Final.Docx utilizing industrial hygiene inspection practices dedicated to the anticipation, recognition, evaluation and control of those materials within workplaces. Work was reviewed and signed off by a registered Professional Engineer.
All samples were sent to EMSL Analytical, Inc. (EMSL), a laboratory certified through the National Voluntary Laboratory Accreditation Program (NVLAP). The suspected asbestos samples were analyzed by Phase Light Microscopy (PLM) using the EPA Method 600 or ASTM 6480. Lead dust samples were analyzed by Flame AAS (SW 846 3050B/7000B). This method measures lead loading, the amount of lead dust on a specific surface area.
Field Activities On October 19, 2018, Hilary Clifton and Jeanette Daniel of NORTECH completed the hazardous materials investigation for the CHPP Black Start Generator. The main scope of work for the project is to replace the existing Black Start Generator and repair the heating and ventilation system in the existing generator room. The following summarizes field activities by category of hazardous material.
Asbestos Containing Material (ACM) Sampling Building materials suspected of containing asbestos included joint compound, gypsum wallboard, generator caulking, floor covering and mastic, roof caulking, insulation, pipe wrap thermal system insulation (TSI) and pipe caulking. A total of 8 samples were collected from both interior and exterior locations and submitted for laboratory analysis to determine the percent content of asbestos by the polarized light microscopic (PLM) method. Sample locations are shown on Figure 3.
Lead Based Paint (LBP) A handheld NITON XLP-303A X-Ray fluorescence spectrometer (XRF) was used to analyze 21 various paint locations for lead in paint. This included the generator scheduled for replacement along with interior supporting structures such as I-beams and walls, and exterior components that will be affected. The specific locations, materials, and colors are shown in Figure 3.
Dust Sampling Visible accumulations of dust were observed on horizontal surfaces, including the floor inside of the Black Start generator room. Lead in settled dust was suspected due the facility burning coal and asbestos contamination was suspect due to the historical use of thermal systems insulation (TSI) and other ACM materials throughout the facility.
To quantify the amount of dust present, the inspector used a scale from 1 to 5 with the following descriptions:
1 – low to no visual dust or debris present 2 – low dust, substrate is visible 3 – moderate dust, substrate is partially obstructed 4 – heavy dust, substrate is no longer visible 5 – extensive dust, non-uniform distribution, accumulations of ≥ 0.25” of dust and debris
A visual assessment determined that a low to moderate amount of settled dust (rated 2-3) is present on top of horizontal surfaces throughout the facility scope of work area. A representative dust sample for lead was collected from the top of blue/green tank and the Black Start generator. A representative dust sample for asbestos was collected from the top of the blue metal compressor and from the Black Start Generator. Sample locations are shown on Figure 3.
Page 3Https://Nortechinc.Sharepoint.Com/00-Jobs/2018/1026/Shared Documents/Reports/Drafts/Blackstartgenerator-Hazmatreport-Final.Docx
Universal Waste and Other Materials Requiring Special Handling Lighting in the Black Start room will require removal as part of this project. The lights could not be accessed for the inspection, however, based on lighting observed elsewhere in the CHPP, mercury fluorescent bulbs, high pressure sodium (HPS) lamps, HID, or LED fixtures may be present. Fluorescent tubes and HPS lamps contain mercury and light fixtures with magnetic ballasts can contain PCBs.
Environmental Concerns Soil and groundwater samples were not collected as part of this investigation. Information regarding previous investigations in the vicinity of the project area was provided by EAFB for review. Additional information available on the Alaska Department of Environmental Conservation (ADEC) Contaminated Sites online database was also reviewed. This information is summarized in the Sample Results and Discussion section below.
Sample Results with Discussion Sample locations and summary tables are depicted on the attached project figures. A copy of all laboratory results is attached. The following is a discussion of sample results with analysis by hazardous material type.
Asbestos No ACM was identified in the CHPP Black Start Generator scope of work area. No materials had an asbestos content in excess of 1%, the regulatory threshold of a building material to be considered ACM. ACM samples, descriptions, locations and results are presented in Figure 3.
Since no ACM is present, no abatement of ACM is necessary prior to construction and demolition (C&D). The waste stream will be considered non-ACM.
Demolition will be required to meet the general demolition NESHAP of no visible dust emissions during demolition.
Lead Based Paint XRF sample results above the EPA Housing and Urban Development (HUD) limit of 1.0 mg/cm2 were not observed. Sample results ranged from 0.0 to 0.11 mg/cm2. Due to the minimal amount of lead in paint observed, the debris waste stream is considered non-hazardous for leachable lead.
Painted surfaces and finishes that contain lead at any concentration also represent a potential hazard for workers who are performing lead trigger tasks such as burning, sanding or grinding.
Demolition design documents should provide contractor notification of the lead content of the lead containing materials as a potential work hazard. The approved demolition work plan should document lead hazard reduction practices, proper PPE used, lead awareness training for onsite workers, and other safety measures to be implemented during building demolition.
Settled Dust The dust samples collected within the Black Start Generator room are a non-detect for asbestos fibers. Precleaning of the Black Start Generator scope of work area can be completed without concern for asbestos exposure and cleaning material can be disposed of as non-asbestos containing.
Page 4Https://Nortechinc.Sharepoint.Com/00-Jobs/2018/1026/Shared Documents/Reports/Drafts/Blackstartgenerator-Hazmatreport-Final.Docx
The current federal lead dust hazard and clearance standards (see below) were incorporated into regulations by the U.S. EPA Housing and Urban Development (HUD). The HUD lead hazard standard for floors is ≥ 40 µg/ft2. There are not currently lead standards for commercial and industrial buildings.
The surface dust samples collected from horizontal surfaces within the Black Start room indicate deposits of lead ranging from 21 µg/ft2 to 110 µg/ft2. The tabulated results and sample locations are shown in Figure 3.
In summary, dust on and around the Black Start Generator are non-detect for asbestos fibers but do contain low concentrations of lead. Additionally, previous sampling events throughout the CHPP building have confirmed the presence of RCRA-8 metals in dust as well.
In addition, OSHA regulations are set to protect worker inhalation exposure, and are not correlated to surface dust concentrations. The worker inhalation permissible exposure level for airborne lead is 50 µg/m3.
Electrical panels, transformers, conduit, the Black Start Generator and other horizontal surfaces with settled dust that will be disturbed during project efforts should be precleaned before demolition begins. Precleaning efforts should be performed by qualified workers who at a minimum have taken lead awareness training and avoid lead trigger tasks.
All dust, PPE, and other materials generated during the dust cleaning activities may be lead hazardous. A lead toxicity characteristic leaching procedure (TCLP) sample is recommended to characterize project PPE and cleaning materials following dust cleaning to determine appropriate handling and disposal requirements.
Universal Waste Universal waste was found to be consistent with items typically found in commercial and industrial buildings. Lighting in the building was observed to consist of fixtures that mercury containing fluorescent light bulbs and HPS lamps. These items should be removed from the project area as necessary and properly disposed of before renovation or demolition. All light ballasts and transformers should be inspected before disposal to ensure they say “no-PCB” or other markings indicating there is no PCB fluid in the ballast.
Environmental Concerns Project work will require the excavation of soil in the vicinity of the Black Start Generator for the installation of supplementary equipment for the new engine. Information provided by EAFB suggests that previous sampling events have identified contaminants in soil in areas likely to be impacted by the project work. The following is a summary of known conditions near the project area:
Based on drawings provided by EAFB dated October 2018, Source Area ST048 (ADEC File # 107.38.070) encompasses the exterior areas adjacent to the Black Start Generator room.
Contaminants of concern have been identified as fuel-related and include benzene, toluene, ethylbenzene, and xylenes (BTEX). Gasoline range organics (GRO) and diesel range organics (DRO) were also identified in groundwater in the area. The source of the contamination is former buried fuel pipelines that are no longer in use and were abandoned in place.
Page 5Https://Nortechinc.Sharepoint.Com/00-Jobs/2018/1026/Shared Documents/Reports/Drafts/Blackstartgenerator-Hazmatreport-Final.Docx
Prohibitions and restrictions within Source Area ST048 state that any activity that may result in the disturbance of soil requires approval by Installation Management (CES/CEI). Completion of Form 103 (Base Civil Engineering Work Clearance), and approval prior to commencing any work. Contaminated soil removed from the Site must be treated or disposed in accordance with state and federal regulations. Source Area ST048 has a 200-foot buffer around it until better delineation of the release can be defined. A contaminated soil specification should be included in the project design documents.
Additionally, during a sewer line excavation performed in May 2016, it was determined through sampling that PAH compound benzo(a)pyrene is present above cleanup levels in that specific project area. This project was located relatively close to the proposed Black Start project area.
Conclusions and Recommendations Based on the findings of the hazardous material assessment, the following conclusions and recommendations have been developed regarding the EAFB Black Start Generator Upgrade Project:
Asbestos Containing Material
No ACM was identified
Lead Based Paint No LBP was observed in excess of 1.0 mg/cm2 Materials containing lower concentrations of lead are also present Lead trigger tasks and appropriate controls should be identified in the Contractor’s
Demolition Work Plan
Settled Dust
Dust on horizontal surfaces is non-detect for asbestos fibers Dust on horizontal surfaces show lead contamination both above and below the EPA
HUD standard o It is recommended horizontal surfaces are cleaned and abated/decontaminated using a project specific work plan o The work plan should include lead abatement work practices, engineering controls, HEPA filtration, no visible emissions and PPE Data collected in other areas of the CHPP indicates the presence of RCRA-8 metals in dust o All dust, PPE, and other materials generated during the cleaning activities may be lead/metal hazardous o A TCLP sample should be collected from project PPE and cleaning materials following dust cleaning to determine handling and disposal requirements
Universal Waste Mercury containing fluorescent light bulbs and HPS lamps, PCB light ballasts and transformers involved in the project work scope should be removed from the building and properly disposed of before renovation or demolition
Environmental Concerns
The project area is located within Source Area ST048 with known contamination and long term monitoring
Page 6Https://Nortechinc.Sharepoint.Com/00-Jobs/2018/1026/Shared Documents/Reports/Drafts/Blackstartgenerator-Hazmatreport-Final.Docx o This area has restrictions related to the disturbance of soil and/or groundwater The appropriate forms and permissions must be approved prior to beginning work A contaminated soil specification should be included in project design documents
This hazardous building materials assessment was conducted to identify the potential hazards in preparation of the EAFB Black Start Generator Upgrade Project. All information about hazardous material associated with the building should be made available to employees, contractors and/or abatement/demolition contractors associated with the renovation or demolition of the Black Start project. Specific abatement work practices may require additional sampling by the contractor to comply with OSHA worker exposure regulatory guidelines.
If you have any questions or require additional professional services or advice, please let us know. We thank you for the opportunity to work with you on this project and appreciate your confidence in our Firm.
Sincerely, NORTECH
Jeanette Daniel Peter Beardsley, PE Environmental Health & Safety Professional Principal
Attachments: Figures
Photo Pages Lab Results
Methodology
Attachment
AutoCAD SHX Text
PROJECT LOCATION
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
PROJECT:
AutoCAD SHX Text
DWG. NO.:
AutoCAD SHX Text
FIGURE
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
PROJ MGR:
AutoCAD SHX Text Location Map
AutoCAD SHX Text CHPP Black Start Generator
AutoCAD SHX Text Eielson, Alaska
AutoCAD SHX Text 11/16/2018
AutoCAD SHX Text
HNC
AutoCAD SHX Text
KAO
AutoCAD SHX Text
1" = 1/2 MILE
AutoCAD SHX Text 18-1026
AutoCAD SHX Text 181026a(01)
AutoCAD SHX Text
AutoCAD SHX Text
ANAKTUVUK PASS
AutoCAD SHX Text
ATQASUK
AutoCAD SHX Text
KAKTOVIK
AutoCAD SHX Text
NUIQSUT
AutoCAD SHX Text
POINT LAY
AutoCAD SHX Text
WAINWRIGHT
AutoCAD SHX Text
BERING
AutoCAD SHX Text
ARCTIC OCEAN
AutoCAD SHX Text Juneau
AutoCAD SHX Text
UNITED STATES
AutoCAD SHX Text R U S S I A
AutoCAD SHX Text
KODIAK
AutoCAD SHX Text
TANANA
AutoCAD SHX Text
CANTWELL
AutoCAD SHX Text
SEA
AutoCAD SHX Text
KOTZEBUE
AutoCAD SHX Text
NOME
AutoCAD SHX Text Anchorage
AutoCAD SHX Text
HOMER
AutoCAD SHX Text
SITKA
AutoCAD SHX Text
PACIFIC OCEAN
AutoCAD SHX Text
EAGLE
AutoCAD SHX Text
HEALY
AutoCAD SHX Text
VALDEZ
AutoCAD SHX Text
SEWARD
AutoCAD SHX Text
GLENNALLEN
AutoCAD SHX Text
TOK
AutoCAD SHX Text Fairbanks
AutoCAD SHX Text
NENANA
AutoCAD SHX Text
CIRCLE
AutoCAD SHX Text
STATES
AutoCAD SHX Text
UNITED
AutoCAD SHX Text
CANADA
AutoCAD SHX Text
HAINES
AutoCAD SHX Text
BARROW
AutoCAD SHX Text
BAY
AutoCAD SHX Text
PRUDHOE
AutoCAD SHX Text
WRANGELL
AutoCAD SHX Text Koyukuk
AutoCAD SHX Text River
AutoCAD SHX Text Yukon
AutoCAD SHX Text Kuskokwim
AutoCAD SHX Text River
AutoCAD SHX Text Yukon
AutoCAD SHX Text River
AutoCAD SHX Text
BETHEL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Miles
AutoCAD SHX Text 2400 College Road, Fairbanks, AK. 99709, 907-452-5688
AutoCAD SHX Text 3105 Lakeshore Dr., Anchorage, AK. 99517 907-222-2445
AutoCAD SHX Text 5438 Shaune Dr., Juneau, Alaska 99801 907-586-6813
AutoCAD SHX Text
ENVIRONMENT, ENERGY, HEALTH & SAFETY CONSULTANTS
AutoCAD SHX Text Eielson
PROJECT LOCATION
AREA SHOWN IN FIGURES 3 AND 4
AutoCAD SHX Text
INDUSTRIAL DRIVE
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
PROJECT:
AutoCAD SHX Text
DWG. NO.:
AutoCAD SHX Text
FIGURE
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
PROJ MGR:
AutoCAD SHX Text Vicinity Map
AutoCAD SHX Text CHPP Black Start Generator
AutoCAD SHX Text Eielson, Alaska
AutoCAD SHX Text 11/16/2018
AutoCAD SHX Text
HNC
AutoCAD SHX Text
KAO
AutoCAD SHX Text 1" = 100'
AutoCAD SHX Text 18-1026
AutoCAD SHX Text 181026a(02)
AutoCAD SHX Text
AutoCAD SHX Text 2400 College Road, Fairbanks, AK. 99709, 907-452-5688
AutoCAD SHX Text 3105 Lakeshore Dr., Anchorage, AK. 99517 907-222-2445
AutoCAD SHX Text 5438 Shaune Dr., Juneau, Alaska 99801 907-586-6813
AutoCAD SHX Text
ENVIRONMENT, ENERGY, HEALTH & SAFETY CONSULTANTS
N
< ²
≥ ²
Lead Dust Data Table Surveyed by Nortech: October 2018
Sample ID Location Lead (μg/ft²)
L1 Square Station 110
L2 Generator 21
Lead Data Table Surveyed by Nortech: October 2018
Sample ID Color Location Substrate Lead 3242 Tan Wall Concrete 0.0
3243 Red Floor Concrete 0.0
3244 White I-Beam Steel 0.03
3245 Blue Compressor Metal 0.02
3246 Blue/Green Tank Metal 0.0
3247 Red Curb Concrete 0.0
3248 Blue Blackstart Metal 0.0
3249 Tan Bulletin Board Wood 0.0
3250 Tan Column Concrete 0.0
3251 Red Steps Concrete 0.0
3252 Tan Door Metal 0.0
3253 Tan Door Frame Metal 0.0
3255 Tan Door Frame Metal 0.0
3256 Yellow Battery Stand Metal 0.0
3257 Gray Blackstart Metal 0.01
3258 Tan Main Floor Control Metal 0.0
3259 Tan Siding Metal 0.0
3260 Tan Condenser Support Metal 0.11
3261 Tan Side of Condenser Metal 0.05
3262 Tan Bollard Concrete 0.0
3263 Red Overhang Metal 0.0
Asbestos Dust Data Table Surveyed by Nortech: October 2018
Sample ID Location Asbestos (structures/cm²)
A1 Square Station ND
A2 Generator ND
Asbestos Data Table Surveyed by Nortech: October 2018
Sample ID Description Result A3 gray caulking ND
A4 white floor sheet ND
A5 brown/white gwb ND
A6 black caulking ND
R1 gray caulking ND
R2 gray caulking ND
R3 gray/blue caulking ND
E1 gray insulation ND
E2 black pipe wrap ND
AutoCAD SHX Text LEAD BASED PAINT SAMPLE NEGATIVE (< 1 mg/cm²)(HUD) 1 mg/cm²)(HUD))(HUD)
AutoCAD SHX Text LEAD BASED PAINT SAMPLE POSITIVE ( 1 mg/cm²)(HUD) 1 mg/cm²)(HUD))(HUD)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text
ASBESTOS SAMPLE LOCATIONS NEGATIVE (<1% ASBESTOS)
AutoCAD SHX Text
ASBESTOS SAMPLE LOCATIONS POSITIVE ( 1% ASBESTOS)>= 1% ASBESTOS)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EJ
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
MH
AutoCAD SHX Text
MH
AutoCAD SHX Text
MH
AutoCAD SHX Text
MH
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A5
AutoCAD SHX Text A4
AutoCAD SHX Text R1
AutoCAD SHX Text R2
AutoCAD SHX Text A6
AutoCAD SHX Text A2
AutoCAD SHX Text L2
AutoCAD SHX Text
AutoCAD SHX Text R3
AutoCAD SHX Text E2
AutoCAD SHX Text E1
AutoCAD SHX Text A1
AutoCAD SHX Text L1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A3
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
PROJECT:
AutoCAD SHX Text
DWG. NO.:
AutoCAD SHX Text
FIGURE
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
PROJ MGR:
AutoCAD SHX Text Basement Lead Sample Locations and Results
AutoCAD SHX Text CHPP Black Start Generator
AutoCAD SHX Text Eielson, Alaska
AutoCAD SHX Text 11/16/2018
AutoCAD SHX Text
HNC
AutoCAD SHX Text
KAO/SPH
AutoCAD SHX Text 1" = 10'
AutoCAD SHX Text 18-1026
AutoCAD SHX Text 181026a(03)
AutoCAD SHX Text
AutoCAD SHX Text 2400 College Road, Fairbanks, AK. 99709, 907-452-5688
AutoCAD SHX Text 3105 Lakeshore Dr., Anchorage, AK. 99517 907-222-2445
AutoCAD SHX Text 5438 Shaune Dr., Juneau, Alaska 99801 907-586-6813
AutoCAD SHX Text
ENVIRONMENT, ENERGY, HEALTH & SAFETY CONSULTANTS
AutoCAD SHX Text N
NOTE: SAMPLE A5 WAS COLLECTED FROM THE MAIN FLOOR AT THE OPENING NEAR THE DAY TANK.
Https://Nortechinc.Sharepoint.Com/00-Jobs/2018/1026/Shared Documents/Reports/Drafts/Doc1.Docx
Black Start Generator EAFB CHPP/ FTQW 12-1012 Report
November 19, 2018
Photo 1: Black Start Generator inside of EAFB CHPP
Photo 2: Black Start Generator Insulated Asbestos Free Labeled Ducting
Page 2 Https://Nortechinc.Sharepoint.Com/00-Jobs/2018/1026/Shared Documents/Reports/Drafts/Doc1.Docx
Photo 3: Blue Metal Compressor, Asbestos Wipe Sample Area
Photo 4: Blue/Green Metal Tank, Lead Wipe Sample Area
Page 3 Https://Nortechinc.Sharepoint.Com/00-Jobs/2018/1026/Shared Documents/Reports/Drafts/Doc1.Docx
Photo 5: Black Start Generator, Lead Wipe Sample Area
Photo 6: Black Start Generator, Asbestos Wipe Sample Area
Page 4 Https://Nortechinc.Sharepoint.Com/00-Jobs/2018/1026/Shared Documents/Reports/Drafts/Doc1.Docx
Photo 7: CHPP Exterior Black Start Components
Photo 8: CHPP Exterior Black Start Components
EMSL Analytical, Inc.
200 Route 130 North Cinnaminson, NJ 08077
Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
041831811EMSL Order:
Customer ID: NORT69
Customer PO: 18-1026
Project ID:
Attention: Phone:Jeanette Daniel (907) 452-5688
Fax:Nortech Environmental & Engineer Cnslt. (907) 452-5694
Received Date:2400 College Road 10/23/2018 9:20 AM
Analysis Date:Fairbanks, AK 99709 10/31/2018
Collected Date: 10/18/2018
Project:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
A3
041831811-0003
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Generator - Caulking
A4-Floor Sheet
041831811-0004
None DetectedNon-fibrous (Other)90%Synthetic10%White
Fibrous
Homogeneous
Floor Sheet
A4-Mastic
041831811-0004A
None DetectedNon-fibrous (Other)100%Yellow/Green
Non-Fibrous
Homogeneous
Yellow Mastic
A5
041831811-0005
None DetectedNon-fibrous (Other)77%Cellulose
Glass
15%
8%
Brown/White
Fibrous
Homogeneous
GWB
A6
041831811-0006
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Roof-Exterior Pipe
Caulking
R1
041831811-0007
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Roof Caulking
R2
041831811-0008
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Roof Caulking
R3
041831811-0009
None DetectedNon-fibrous (Other)100%Gray/Blue
Non-Fibrous
Homogeneous
Roof Caulking
E1
041831811-0010
None DetectedNon-fibrous (Other)20%Glass80%Gray
Fibrous
Homogeneous
Exterior Insulation
(Friable)
E2
041831811-0011
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Exterior-Pipe Wrap
Analyst(s)
Amy Johnson (10) Benjamin Ellis, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NVLAP Lab Code 101048-0, AIHA-LAP, LLC-IHLAP Lab 100194, NYS ELAP 10872, NJ DEP 03036, PA ID# 68-00367
Initial report from: 10/31/2018 08:37:03
Page 1 of 1ASB_PLM_0008_0001 - 1.78 Printed: 10/31/2018 8:37 AM
200 Route 130 North Cinnaminson, NJ 08077
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
EMSL Analytical, Inc.
041831811EMSL Order:
NORT69Customer ID:
18-1026Customer PO:
Project ID:
Attention: Phone: (907) 452-5688Jeanette Daniel
Nortech Environmental & Engineer Cnslt. Fax: (907) 452-5694
2400 College Road Received Date: 10/23/2018 9:20 AM
Fairbanks, AK 99709 Analysis Date: 10/31/2018
Collected Date: 10/18/2018
Test Report: Asbestos Analysis of Dust Samples Using Method ASTM 6480
Sample ID
Area
Sampled
(cm²)
Asbestos
Type
Asbestos
Structures
Sensitivity
(str/cm²)
Concentration
(str/cm²) Comments
None
Detected
523 <1560<2.99A1 Due to excessive particulate the target analytical sensitivity of 260 str/cm² was not reached.
041831811-0001
None
Detected
250 <748<2.99A2
041831811-0002
Analyst(s):
Ted Young (2) Benjamin Ellis, Laboratory Manager or other approved signatory
EMSL maintains liability to cost of analysis . This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted.
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ
Initial report from: 10/31/2018 08:53:52
ASB_TEMMV_0014 Printed 10/31/2018 8:53:53AM Page 1 of 1
Client Sample Description ConcentrationLab ID Analyzed Area Sampled Lead
Collected
EMSL Analytical, Inc.
200 Route 130 North, Cinnaminson, NJ 08077 Phone/Fax: (856) 303-2500 / (856) 786-5974 http://www.EMSL.com cinnaminsonleadlab@emsl.com
Attn: Jeanette Daniel Nortech Environmental & Engineer Cnslt.
2400 College Road Fairbanks, AK 99709
Received: 10/23/18 10:00 AM Fax: (907) 452-5694 Phone: (907) 452-5688
10/18/2018Collected:
Test Report: Lead in Dust by Flame AAS (SW 846 3050B/7000B)*
201812361 CustomerID: NORT69 CustomerPO: 18-1026 ProjectID:
EMSL Order:
Site: Square Station 201812361-0001L1 1 110 µg/ft²ft²10/29/201810/18/2018
Site: Generator 201812361-0002L2 1 21 µg/ft²ft²10/29/201810/18/2018
Phillip Worby, Lead Laboratory Manager or other approved signatory
Test Report ChmSnglePrm/nQC-7.32.3 Printed: 10/30/2018 9:36:15 AM
*Analysis following Lead in Dust by EMSL SOP/ Determination of Environmental Lead by FLAA. Reporting limit is 10 µg/wipe. ug/wipe =µg/ft² x area sampled in ft². Unless noted, results in this report are not blank corrected. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities (such as volume sampled) or analytical method limitations. Samples received in good condition unless otherwise noted. The lab is not responsible for data reported in µg/ft² which is dependent on the area provided by non-lab personnel. The test results contained within this report meet the requirements of NELAC unless otherwise noted. "<" (less than) results signifies that the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. The QC data associated with the sample results included in this report meet the recovery and precision requirements unless specifically indicated otherwise. Definitions of modifications are available upon request.
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NELAP Certifications: NJ 03036, NY 10872, PA 68-00367, AIHA-LAP, LLC ELLAP 100194, A2LA 2845.01
Initial report from 10/30/2018 09:36:15 http://www.EMSL.com mailto:cinnaminsonleadlab@emsl.com
File details come from the government source that posted it. Updated .