San Diego Water Leak Damage Remediation – 3rd Floor
36E77619B0019
Technical Questions Tracker
9/4/2019
1) Please provide a Haz Mat report for areas where work might occur.
a. See attached report.
2) In reviewing the plumbing drawings, I see that they show the sanitary waste piping as being run on the third floor. See drawings PS101, PS102, PS103, PS104.
Should the piping really be installed in the 2nd floor interstitial space?
If YES, will the abatement be done to make the space safe for plumbers?
A: Sanitary waste piping is shown on the floor plans showing the fixtures. This piping must be sloped in the direction of flow therefore the majority of this piping must be installed below the 3rd floor or in the 2nd floor interstitial space. The 2nd floor interstitial space is a hazardous area and requires appropriate PPE including but not limited to respirators.
D.Harper 2019 Sept 4th, 9/11/2019
A. Please provide a mfg/model number or specification for the patient head walls. Amico is the basis of design, In the Hemodialysis areas, the Futurus wall panel system was the basis of design
B. Arjo is listed as the basis of design for the patient lifts. Which Arjo patient lift is the basis of design? They have several to offer. Maxi sky 2, Attached are the cut sheets of the basis of design for the patient lift system. These drawings serve as the San Diego VAMC facility standard.
Michael Degnan 2019, 9/13
C. What is the maximum weight capacity the lift needs to be? 600 lbs for patient and 750 lbs min.
structure capacity, Michael Degnan 2019, 9/13
D. Please provide a mfg/model for the following CF/CI items listed on AI001:
a. #20 Equipment Rails, Hospital Systems Inc. HIS “F” Type Eclipse Horizontal Equipment Rail
b. #36 Monitor, OFCI
c. #44 Wall Mounted Scale, Stow-A-Weigh Model: 6202
d. #95 Wall Mounted Monitor, OFCI
e. #103 Peerless Ceiling Mounted Hanger for TV, see RFI response to # 4 dated 2019, 9/10. Telehook, Flat screen ceiling mount / Tilt TH-3070-CTLW/CTSW. Michael Degnan 2019, 9/13
E. Is this project sales tax exempt? No, this is not exempt of sales tax. Contractors are required to pay sales and excise tax. Offerors shall include all applicable taxes in accordance with FAR By Reference Clause 52.229-3 “Federal, State and Local Taxes.”
F. Where will the designated laydown & parking area be for workers accessing the construction site? Parking on site will be on a first come first served basis. Parking will be behind the hospital by the North loading dock. Contractors to use Service Elevator P- 3 and/or Elevators S-1, S-3, S-4. Loading and unloading to be done from the Loading Bay directly to the elevators. Contractors to protect tile flooring in front of elevators and keep elevators clean. All deliveries to be done prior to 7:30 AM and construction waste after 4:30 pm. VA will provide an office for the contractor that will be near the project, laydown yards are limited, dumpsters will be provided for general trash, Haz Mat debris to be followed in the specs. Michael Degnan 2019, 9/13
G. Will the government accept the use of the industry leading Procore Project Management software as the primary submittal and data tracking tool for this project? Yes, Michael Degnan 2019, 9/13
H. During construction in an area where the ceilings or fire suppression system will be disrupted, will NFPA 241 apply? Yes, Michael Degnan 2019, 9/13
I. Will the government require additional security measures beyond NFPA code such as fire watch, temporary fire alarms, adjustments to sprinkler heads, etc.
All requirements of the NFPA code (including but not limited to NFPA 101, 13, 25, 72, 241 & 99) will be expected to be followed at all times including the use of fire watches, temporary fire alarms, sprinkler head adjustments, barrier walls, egress paths, daily egress checks, etc.
When a fire protection system (sprinkler) is out of service for more than 10 hours in a 24 hour period or a fire alarm system is out of service for more than 8 hours in a 24 hour period then applicable procedures must be implemented.
J. Who is the fire alarm servicer that the VA is currently work with?
Albireo Energy has the current 5 year contract for the VA Sprinkler Service is Bradshaw Engineering
K. If there is an asbestos report, can the VA release it before the due date? Hazardous Material Report will be provided via amendment to FBO.
L. What is the level of infectious disease control rating for this site?
Refer to specification section 013526 Safety Requirements. Particularly section 1.12.
Class V measures will be required unless written approval is provided by the government.
M. Are there photos available of the Asbestos containing areas? Contractor was given the invitation to bid walk the interstitial, the VA does not have photos to give out. Michael Degnan 2019, 9/13
N. Can the VA publish the site visit, sign in sheet? Yes, refer to contracting officer.
O. Does the VA anticipate and down time between phases? Yes. 45 days. Michael Degnan
2019, 9/13
P. Does the VA have an anticipated NTP date for this project? NTP will be issued after bonding and insurance is received and verified. Anticipated NTP is within 120 calendar days of award.
FUTRUS® MODULAR WALL PANEL SYSTEM
An advanced modular wall system designed to help turn any space into the ultimate sterile, durable and easy to clean environment.
Each panel is made from seamless, bleach cleanable Corian®, which is GREENGUARD® certified to resist microbial growth to help reduce HAIs. Corian® panels also resist chipping, peeling, scratching and staining for greater life cycle. A metal back plate reinforces each panel for greater impact resistance.
Features a patented hanging system for easy panel attachment and removal and interlocking lap joint panel edges to prevent liquid penetration. Available in standard or custom panel sizes, colors and finishes to suit any wall space or design scheme. Can also incorporate services, technology, branding and wayfinding.
futrus.com info@futrus.com
1.877.FUTRUS1 (388.7871)
FUTRUS® MODULAR WALL PANEL SYSTEM
For complete product specifications, visit futrus.com.
©2017 Futrus, LLC. ALL RIGHTS RESERVED. Futrus reserves the right to make changes without notice in design, specifications and models. Corian® is a registered trademark of E. I du Pont de Nemours and Corian are used under license by Futrus LLC. Futrus® is a registered trademark of Futrus LLC.
All Corian® solid surface colors and thicknesses carry the highest “interior finishes” rating, Class I (Class A) of the principle USA building codes.
- Class I (Class A) fire rated
- GREENGUARD Gold for children and schools
- GREENGUARD Indoor Air Quality Certified®
- GREENGUARD listed for Microbial resistance
STANDARD FEATURES
• Panel Depth: 1/2”, 5/8”, 3/4”
• Heights and widths are configurable
• Pre-located, fire rated sub-panels mount to stud-wall for easy layout and installation
• Standard Corian® Colors: Cameo White, Glacier White, Bisque, Bone, Vanilla
• Matte finish
• Futrus® 5-year limited, Corian® 10-year limited warranty
CUSTOMIZATIONS
• Available in any Corian® color & pattern; Exclusive wood grain patterns and customizable print options also available
• Lighting: Panels can be configured to accommodate surface mounted lighting;
offered in a variety of designs or customized for wayfinding, theming or branding
Legend
Light
Sprinkler
Vent
Smoke detector
Existing access trap
Electrical outlet
Access trap required
Exchanger
Turntable
Gate
CURTAIN
IV IV
Wall bracket
Wall post side
Wall post
"T" junction
Curtain track
IV track
Bracket
Joint bracket
Motor/Charger location
(*) Symbol may vary depending of equipment type
Swivel pole
DISTRIBUTOR :
REPRESENTATIVE :
DATE (DD-MMM-YYYY) :
REFERENCE # : PAGE :
INSTALLATION DRAWING
1. The ceiling minimum structure capacity must be able to support the load specified on the installation drawing.
2. Electrical power source outlet already available by the facility at a maximum distance of 3 meters from charging station.
3. Any obstructions such as vents, pipes, lights and sprinklers that could possibly be in the path of the ceiling lifts to be removed or relocated by the facility prior to installation.
4. Modifications of door headers by the facility.
5. Arjohuntleigh reserves the right to slightly modify the track layout if necessary.
6. See the "Agreed Conditions for the Installation of Ceiling Lifts" document included with this quote for important installation details.
7. Arjohuntleigh will not be held responsible for any damages, inconvenience, resulting from hitting any non visible conduits during our installation process.
8. Signed drawings are required prior to ordering and installation of ceiling lifts. This signature of each drawings confirms agreement of all the conditions listed above.
IMPORTANT NOTES
MY SIGNATURE BELOW VERIFIES THAT I HAVE:
Reviewed all ____ pages, with a total quantity of ____ rooms, for the approbation of layout for each room and the approbation of structure for each room. I verify that the answers below are accurate to the best of my knowledge and I understand that the quote produced is dependent upon the conditions below as well as this full drawing set.
Is a load dock available? YES NO
Can facility accept shipment and store until install begins? YES NO
Will a drop trailer be needed? YES NO
Is parking available on site? Is there a fee involved? YES NO
Are there any installation time frame limitations?
What are they? YES NO
Is a level of infectious control required? YES NO
If YES, then what level ___________________________
CUSTOMER
APPROVAL: DATE:
REVISION(S) DATE(S) (D-M-Y)
VA SAN DIEGO
QC-103134MS
03-JAN-2013
ARJOHUNTLEIGH
BILL ASHBROOK
1 / 4
H
E
C S
44"
LISTING OF ROOM NUMBER(S):
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
MINIMUM STRUCTURE CAPACITY:
VA SAN DIEGO
QC-103134MS
03-JAN-2013
usaddsom02 1/4" = 1'
2 / 4
600LBS [272KG]
750LBS [340KG]
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
27.6 MPA [4000 PSI] MIN.
TILE
BLDG 1 RM 2144
A=108"
B=9 1/2"
D=6 1/2"
ECS INSTALLATION
MS2 4F ECS MOTOR
118 " H90
118 "H90
O
A L
H
E
C S
100 " H90
100 " H90
10"
FLUSH MOUNTED TRAVERSING RAIL
UNDER THE FIXED RAILS.
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
MINIMUM STRUCTURE CAPACITY:
VA SAN DIEGO
QC-103134MS
03-JAN-2013
usaddsom02 1/4" = 1'
3 / 4
600LBS [272KG]
750LBS [340KG]
LISTING OF ROOM NUMBER(S):
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
A=108"
B=12 1/2"
F=4"
G=48"
H=4"
G
TILE
BLDG 1 RM 2146
O
A L
H
E
C S
93 " H90
93 " H90
10"
FLUSH MOUNTED TRAVERSING RAIL
UNDER THE FIXED RAILS.
- ALL HARDWARE INCLUDED.
(ACCORDING TO STRUCTURE)
QUANTITY OF ROOMS:
DRAWN BY :
REFERENCE # : PAGE :
SCALE :
DATE CREATED (DD-MMM-YYYY) :
SAFE WORKING LOAD BELOW LIFT:
MINIMUM STRUCTURE CAPACITY:
VA SAN DIEGO
QC-103134MS
03-JAN-2013
usaddsom02 1/4" = 1'
4 / 4
600LBS [272KG]
750LBS [340KG]
LISTING OF ROOM NUMBER(S):
THIS LAYOUT HAS BEEN PREPARED WITH SUPPLIED DATA. NOTE: CUTTING OF RAILS ON SITE ONLY
G
TILE
BLDG 1 RM 2150
A=108"
B=12 1/2"
F=4"
G=48"
H=4"
ECS INSTALLATION
MS2 2F ECS MOTOR
UNIVERSAL TROLLEY FLUSH
GENEIW... NOl'ES
| I. | GENERAL |
| 1. | THIS PRE-APPROVAL IS VAlJD FOR THE EQUIPMENT DESCRIBED IN THESE DRAWINGS |
THROUGHOUT THE STATE OF CAlIFORNIA. AND IS VAlJD FOR EQUIPMENT INSTALLED
AT ANY HEIGHT WITHIN THE BUIWING.
| II. | RESPONSIBIUllES OF' THE STRUCTURAL ENGINEER OF' RECORD |
| 1. | VERIFY MATERIALS AND WORKMANSHIP TO CONFORM WITH THE 2007 EDmON OF THE |
CALIFORNIA BUIWING CODE AND THE REQUIREMENTS OF THIS PRE-APPROVAL DOCUMENT.
2. VERIFY THE ADEQUACY OF THE EXISTING FRAMING TO SUPPORT THE LOADS INDICATED
HEREIN, IN ADDmON TO ALL OTHER LOADS.
| 3. | VERIFY CONCRETE SLAB IS NOT CRACKED. |
| 4. | VERIFY ANCHORS ARE ADEQUATE DISTANCES FROM OPENINGS AND EDGES OF SLABS. |
| 5. | VERIFY ANCHORS ARE ADEQUATE DISTANCES FROM NEW OR EXISTING ANCHORS. |
| 6. | DESIGN ANY SUPPLEMENTARY MEMBER AND THEIR ATTACHMENTS OTHER THAN THOSE |
DETAILED WITHIN THIS PRE-APPROVAL.
7. VERIFY THE EQUIPMENTS WEIGHT, C.G. LOCATION. ANCHOR LOCATIONS AND ANCHOR
DETAILS AGREE WITH THE INFORMATION SHOWN IN THIS PRE-APPROVAL.
| III. | STRUT FRAMING |
| 1. | CHANNEL FRAMING COMPONENTS AND CONNECTORS MANUFACTURED BY UNISTRUT |
CORPORATION, UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
| 2. | CHANNEL FRAMING TO CONFORM TO ASTM A1011, GRADE 33. |
| 3. | INSTALL BRACING WITH NO MORE THAN 10 DEGREE PLAN DEVIATION. |
| N. | MECHANICAL. ANCHORS |
| 1. | WEDGE ANCHORS INTO CONCRETE: USE ZINC PLATED CARBON STEEL HILTI KB-TZ |
(ICC ESR-1917). INSTALL ANCHORS IN ACCORDANCE WITH ICC REPORT AND
OSHPD CAN 2-1912A.l & CAN 2-1916A.8
2. IF REINFORCEMENT IS ENCOUNTERED DURING DRIWNG, ABANDON AND SHIFT THE
HOLE LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM OF 2 ANCHOR
DIAMETERS OR 1 INCH, WHICHEVER IS LARGER, OF SOUND CONCRETE BETWEEN THE
DOWEL AND THE ABANDONED HOLE. FILL THE ABANDONED HOLE WITH NON-SHRINK
GROUT APPROVED BY THE ENGINEER OF RECORD. NOTIFY THE ENGINEER OF RECORD
IF ANY REINFORCING IS DAMAGED.
| 3. | ANCHORS WILL BE PROOF-TESTED BY OWNER'S TESTING AND INSPECTION AGENCY. |
| 4. | IF ANY ANCHOR FAILS TESTING, REPLACE ANCHOR AND TEST ADDmONAL ANCHORS |
OF THE SAME CATEGORY NOT PREVIOUSLY TESTED UNTIL TWENTY (20) CONSECUTIVE
PASS, THEN RESUME INmAL TESTING FREQUENCY.
5. TEST ANCHORS NO SOONER THAN 24 HOURS AFTER INSTALLATION.
6. TEST 50" WEDGE ANCHORS PER THE FOLLOWING METHOD:
A. TORQUE WRENCH METHOD: TEST ANCHORS TO THE TORQUE LOAD INDICATED IN
THE TABLE BELOW WITHIN THE FOLLOWING UMITS:
1. ONE-HALF TURN OF THE NUT.
WEDGE
ANCHOR TORQUE
DIA. (IN) LOAD (FT-LBS)
J/S 25 1/2 40 5/S 60
| V. | ROUGH CARPENlR\' |
| 1. | FRAMING LUMBER: DOUGLAS FlR (COAST REGION) GRADED AND MARKED IN |
ACCORDANCE WITH THE STANDARD GRADING RULES NO. 17 OF THE WEST COAST
LUMBER INSPECTION BUREAU (W.C.LI.B.) OR WESTERN LUMBER GRADING RULES, OF
THE WESTERN WOOD PRODUCTS ASSOCIATION (W.W.PA). USE LUMBER WITH A
MINIMUM GRADE OF D.F. #"
| 2. | ROUGH HARDWARE: |
| A. | NAILS: COMMON WIRE NAILS, FEDERAL SPECIFICATION FF-N-l05B, STANDARD |
LENGTHS U.O.N. USE HOT-DIPPED ZINC-COATED GALVANIZED NAILS FOR EXTERIOR
INSTALLATIONS AND WHEN PENETRATING PRESSURE TREATED OR FlRE-RETARDANT
LUMBER.
B. BOLTS AND THREADED RODS: ASTM Al07, SQUARE OR HEXAGONAL HEAD MACHINE BOLTS WITH ASTM A563 NUTS. USE MALLEABLE IRON WASHERS UNDElR HEAD AND
NUT WHEN IN CONTACT WITH WOOD.
C. LAG SCREWS: ASTM Al07, ANSI/ASME STANDARD B18.2.1. USE ANSI B18.22.1
WASHERS UNDER HEAD WHEN IN CONTACT WITH WOOD.
D. SCREWS: ASTM Al07, ANSI/ASME STANDARD B18.6.1. USE CADMIUM-PLATED PAN
OR ROUND HEADED SCREWS AT STEEL TO WOOD AND WOOD TO WOOD CONNECTIONS.
E. MISCELLANEOUS STEEL: ASTM Al6.
F. FRAMING CUPS, SHEET METAL STRAPS, ETC.: SIMPSON, UNIVERSAL, OR SILVER, WITH
ICC REPORTS. DESIGNATIONS ON DRAWINGS ARE BASED ON SIMPSON CATALOGUE
NUMBERS.
| 3. | BOLT INSTALLATION: |
| A. | DRILL BOLT HOLES A MAXIMUM OF 1/16 INCH LARGER IN DIAMETER THAN THE |
BOLT NOMINAL DIAMETER.
B. DRILL PRE-BORED LEAD HOLES FOR LAG SCREWS AS FOLLOWS.
1. DRILL LEAD HOLE FOR THE SHANK TO A DEPTH EQUAL TO THE LENGTH OF THE
UNTHREADED PORTION IN THE MAIN MEMBER. USE A DRILL BIT OF THE SAME
DIAMETER AS THE LAG SCREW.
2. EXTEND THE LEAD HOLE FOR THE THREADED PORTION OF THE LAG SCREW WITH A
DRILL BIT WHOSE DIAMETER IS 60 PERCENT OF THE NOMINAL LAG SCREW DIAMETER.
| 3. | INSERT LAG SCREW INTO LEAD HOLE BY TURNING. DO NOT DRIVE WITH A HAMMER. |
| 4. | LUBRICATE WITH SOAP OR BEESWAX TO FACIUTATE INSTALlATION. |
| VI. | STRUCTURAL STEEl |
| 1. | STRUCTURAL STEEL TO CONFORM TO THE FOLLOWING UNLESS OTHERWISE NOTED: |
SECTIONS I TYPE I
COW FORMED HOLLOW STRUCTURAL
SECTION (HSS
MACHINE BOLTS
THREADED AND HANGER ROD
NUTS FOR BOLTS AND MACHINE BOLTS
PLAIN WASHERS
ASTM A500 GRADE B
2. HOT DIPPED GALVANIZED IN ACCORDANCE WITH ASTM A123 AND ASTM A153
STRUCTURAL STEEL AND FASTENERS THAT ARE PElRMANENTLY EXPOSED TO WEATHER.
| VII. | STRUCTURAL TESTS. INSPECTIONS. AND OBSERVATIONS |
| 1. | AN INDEPENDENT TESTING AGENCY AND SPECIAL INSPECTORS WILL BE RETAINED BY |
THE OWNER TO PERFORM THE FOLLOWING TESTS AND INSPECTION. PROVIDE ACCESS
AND FURNISH SAMPLES TO THE AGENCY AS REQUIRED.
2. THE FOLLOWING ITEMS REQUIRE TESTS AND INSPECTIONS IN ACCORDANCE WITH THE
REQUIREMENTS OF THE CHAPTER "STRUCTURAL TESTS AND INSPECTIONS· OF THE
CODE.
| 3. | MECHANICAL ANCHORS: |
| A. | VERIFY TYPE OF ANCHOR, ANCHOR DIMENSIONS, CONCRETE TYPE AND COMPRESSIVE |
STRENGTH, PREDRlllED HOLE DIMENSIONS, ANCHOR SPACING, EDGE DISTANCE, SLAB
THICKNESS AND ANCHOR EMBEDMENT.
B. PROOF-TEST AS INDICATED IN THE MECHANICAL ANCHORS SECTION OF THESE
GENERAL NOTES.
VIII. DESIGN CRITERIA
1. APPLICABLE CODE: 2007 CAUFORNIA BUILDING CODE.
2. SEISMIC DESIGN:
SEISMIC FORCE Fp = 2.31w Fpv = 0.385w
WHElRE:
S5 = 289% G WORST CASE ACCEL.
Fa = 1.0 FOR Sd SOIL Rp = 1.5 LOW DEFORMATION
Ip = 1.5 FOR NON-ESSENTIAL EQUIP. ap = 1.0 RIGID COMPONENT
3. CRANE LOADING PER AlSC
TRANSVERSE LOADING = 0.2 (DL+LL)
LONGITUDINAL LOADING = 0.1 (DL+LL)
IX. HOW TO USE THIS PRE-APPROVAL
1. REVIEW AND UNDERSTAND ALL GENERAL NOTES AND FlGURES BEFORE
PROCEEDING.
2. FOR THE SELECTED MAXISKY UNIT, DETERMINE THE TRACK LAYOUT AND
DIMENSIONS.
3. BASED ON THE TRACK LAYOUT AND DIMENSIONS, DETERMINE THE
APPROPRIATE TRACK, THE TRACK BRACING, AND TRACK HANGER
REQUIREMENTS FROM THE TABlES ON SHEET S2.
4. DETERMINE THE MAXIMUM DEMANDS ON THE EXISTING STRUCTURE FROM
THE NEW UNIT FROM THE TABLE ON SHEET S2, AND VERIFY THE
ADEQUACY OF THE EXISTING STRUCTURE WITH THE ENGINEER OF RECORD
FOR THE BUILDING.
SHEET LIST
Sl GENERAL NOTES
S2 TRACK ELEVATION
S3 HANGER CONNECTION DETAILS
S4 HANGER CONNECTION DETAILS
S5 BRACE CONNECTION DETAILS
DEGENKOLB ENGINEERS
235 Montgomery Street, Suite 500 San FranCiSCO, CA 94104
415.392.6952 Phone
415.981.3157 Fax
www.degenkolb.com
A P PRO V E D
Fixed EQuipment Anchorage
Planning and Development
OPA-0611-07
Date
ARJOHUNTLEIGH MAXI SKY CEILING LIFTS
TiHe: Sheet Number
GENERAL NOTES
Drawn: RP Job Number: A5114009.02
Design: RMG Rev.: 2.1
Check: RSP
Date: 4/13/10 1 OF 5 Sheets http:A5114009.02
HANGER~
1/S3 1/s41 /:7·/ ~""7 17
SEE (E) CONC. ON MErAL
CONNECTION DECK/SOLID SLAB OR CONC.
DErAILS BEAM WHERE OCCURS)AND
3/8"9) THRD. HANGER. (TYP.)ROD HANGER. - SEE TABLE
TYP. (PART SPACING
#000.00394).
STIFFENERS
NEEDED @ 18"
ffi'ro §t ~ II
~ II
:;.'2
~ ~ II
:;.'2....,)
II'
T-HANGER
I· TRACK
UNISTRUT Pl000 OR
158-12. OUT-OF-PLANE
BRACE MAX.
HSS 2Xx2XxX6 BRACE
MAX. LENGTH =
HSS 3x3xX6 BRACE
LENGTH == 227"
UNISTRUT P1546 WITH
1/2"9) BOLT & SPRING
NUT OR CHANNEL NUT
EACH END
O.C. WHERE LENGTH 08".
LATERAL BRACE
OCCURS 186".
MAX.
USE 2-3/8"9)
THRD. RODS
FOR MAXISKY
BRACKEr
(PART #700.
11204) FOR
MAXISKY 1000. f------f
TRACK MAX. LIVE LOAD:SECTION X-X SPLICE
MAXISKY 1000 W=1000 Ibs.(LOCATE ONLY AT MAXISKY 600 W=600 IbsOUT-OF-PLANE BRACE) o TRACK ELEVATION MAXISKY 440 W=440 Ibs
THREADED ROD
Max. Transverse Brace Spacing = 2X max. hanger spacing P1000T
* LOADS DO NOT INCLUDE 1.3 INCREASE
FOR ANCHORS
SHEET NOTES:
1. THE STRUCTURAL ENGINEER OF RECORD IS
RESPONSIBLE FOR VERIFYING THE ADEQUACY OF THE SECTION A-ASTRUCTURE FOR APPLIED LOADS INDICATED HEREIN. IN(2) TRACK ELEVATION & DETAILS
ADDITION TO ALL OTHER LOADS.
STRUCTURAL LOADING (lbs.) (ASD LOADING)
LIFT TYPE
Portable 440 600 1000
Thanger 605 814 1307 Tbrace 249 249 281 Vbrace 249 249 281
Weight Lbs 14 28 48 Cal'(]<:;ity Lbs 440 600 1000
2.11 2.07
H180
3.56 4.40
7.84 115.85
3.43 4.25
UNISTRUT 3/8" BOLT
AND P3008 NUT
UNISTRUT P2485
CRADLE CLIP
DEGENKOLB ENGINEERS
235 Montgomery Street, Suite 500 San Francisco, CA 94104
415.392.6952 Phone
415.981.3157 Fax
www.degenkolb.com
Fixed Anchorage Planning and Development
OPA-0611-07
P(e~awoy~ Program UamJQ6t
Al"lihOnyR Pike
(91e, UO·S4TO
ARJOHUNTLEIGH MAXISKY CEILING LIFTS
TRle: Sheet Number
TRACK ELEVATION
A P PRO V E 0
Drawn: RP Job Number: A5114009.02
82Design: RMG Rev.: 2.1
Check: RSP
Date: 4/13/10 2 OF 5 Sheets x
~ .............L~!~.~
FOR
:::.c: g
UNISTRUT
OUT-OF- PLANE
BRACE
ARJOHUNTLEIGH TRACK
BRACKEr PART
#700.11100. TYP.
FOR MAXISKY 1000
USE PART #700.11204
X
TRACK
IN-PLANE BRACING
(1 MIN. EVERY TRACK)
SEE SECTION X-X,
SIM. 30 FT. MAX. O.C.•
TYP.
~ 6063-T54
ALUMINUM
MAXIMUM HANGER SPACING Cinch
LIFT TYPE
Portable 440 600
74 64 143 123
II· i J UNISTRUT Pl000T W/
ROD STIFFENERS @
18" O.C. MAX
ROD STIFFENERS NOT • I
REQ. @ HANGERS W/O
BRACES
48# DEAD
LOAD MAX.
ARJO LIFT
MODULE
170 170 139 steel Min.
11/4"MIN";WTYDP'~~r~1
WASHER~~
3/8"~ THRD. ROD
z
~I ':..:t r<") nl~ :::E
Anchor Diam. Uft Type & Embed Portable 440 600 1000
2-3/8"x 2" NWC ONLY NO NO 2-1f2"x 3 1/4" OK OK NO 2~578"x 4" OK OK OK
L=8" MIN.MIN. EDGE
zZ
':..:tw
DIST. 1.5x
EMBED
12" MAX.
HILTI KWIK BOLT TZ ~
EI
~----- SPRING
EQ.!~(TYP.) SEE TABLE
NUT, CHANNEL NUT, OR SADDLE
1.5x EMBEDMENT LIGHT WEIGHT OR 2500 psi
NORMAL WEIGHT CONCRETE
Portable 440
OK
OK
MINIMUM 3000 psiEDGE DISTANCE MINIMUM 3000 psi
LIGHT WEIGHT OR 2500 psi
NORMAL WEIGHT CONCRETE
HILTI KWIK
BOLT TZ
-'1<-
-'I<---!'/
UNISTRUT P 1 000
OR HILTI 158-12
BASE PL '" HEX-NUT CI SPRING OR CHANNEL
o SOLID CONCRETE SLAB CONSTRUCTION FOR SIZE 1 1/2" MIN l l L/3 'MIN 1T hange~ HANGI:.K KUU UI-'IIUN~
. . FOR 1000 LB UNIT-SEE 1/S2
TYP. 1 1 3/8"~ THRD. ROD
CD SOLID CONCRETE SLAB CONSTRUCTION
MIN. EDGE DIST.
1.5 x EMBED. ~
:::E o w20ga. m
NOTE::::E
w
20ga. MIN.
MTL DECK
SPRING NUT,
HEX-NUT & BASE PL @
HEX-NUT, WASHER HANGER ROD
& BASE PL (TYP.) OPTIONS FOR 1000
1 1/2" MIN.
TYP.
LB UNIT-SEE 1/S2
V 7 J~' 7 I;. A 7 71 7 ::l ;\ I A / 7:"'+- 3000psi MINIMUM
LIGHT WT. OR
WDeck
SEE LOWER FLUTENORMAL WT. CONC.
FOR
z
~~T~~~"""""""~-'I.---,.-l
INSTALLATION
LOW FLUTE FOR ADDITIONALHILTI KWIK BOLT TZ
ROD COUPLER (PART #000.00394) • T hanger HIGH FLUTE (TYP.) SEE TABLE INFORMATION.
OR REDUCER T hanger SIZE & EMBEDMENT
HEX LOWER FLUTE UPPER FLUTE CHANNEL NUT, OR SADDLE NUT UPPER FLUTE INSTALLATION
INSTALLATION INSTALLATION SPRING OR CHANNEL NUT
tIlIESi
1. SEE DETAIL 0/- FOR FLUTE
Anchor Diam. Uft Type & Embed Portable 440 600 1000
1/2"x 3 1/4" OK NO N7A 5/8"x 4" OK OK N7A
NOTE:
DIMENSION REQUIREMENTS.
INSTALL IN HIGH
OR LOW FLUTE.It:;i #~~&0~f~4) LOWER FLUTE INSTALLATION
FLUTE.
2. INSTALL IN HIGH OR LOW
01:=K WI CONC. FILL CONSTRUCTION
Anchor Diam. Uft Type & Embed Portable 440 600 1000
2-1/2"x 3 1/4" OK OK NO 2-5/8"x 4" OK OK OK o METAL DECK WITH CONC. FILL CONSTRUCTION
8 1. THE STRUCTURAL ENGINEER OF RECORD IS RESPONSIBLE FOR VERIFYING THE ADEQUACY OF THE STRUCTURE FOR APPLIED LOADS INDICATED HEREIN, IN ADDITION TO ALL OTHER LOADS. SEE DETAIL 1/S2 FOR STRUCTURAL LOADING.HANGER CONNECTION DETAILS
2. THESE DETAILS ARE NOT USED WITH DIAGONAL BRACING MEMBERS, BUT MAY BE USED FOR VERTICAL HANGERS
BRACED AT LOWER END (PER lA/S2, SECTION X-X) OR FOR UNBRACED HANGERS.
OPA-0611-07
Preo-3PPfoY.,1 Program Manaf:1&r
Anthony 11:, P4ke
(9'6) 441}!I470
ARJOHUNTLEIGH MAXISKY CEILING LIFTS
A P PRO V E D TItle: Sheet Number
Fixed Equipment Anchorage HANGER CONNECTION DETAILS Office of Statewide Health Planning and Development
Drawn: RP Job Number: A5114009.02 DEGENKOLB ENGINEERS 83Design: RMG Rev.: 2.1235 Montgomery Street. Suite 500 San FranciSCO, CA 94104
Check: RSP415.392.6952 Phone
415.981.3157 Fax
www.degenkolb.com Date: 4/13/10 3 OF 5 Sheets http:www.degenkolb.com
-SEE G/S4 l. ~ ; I. . I! / r LI
DOUBLE NUT & WASHER AT HSS
UNISTRUT Pl000
OR HILTI 158-12
SPRING NUT, CHANNEL
1 NUT OR SADDLE NUT
WITH A HEX. NUT &
BASE PL @ SPRING
OR CHANNEL NUT(PART #000.00394)
FOR T hanger HANGER ROD OPTIONS
/1 ' -""
AT
OPTIONS
II~II
HILTI
EQ.
NOTE:
MINIMUM
OF WOOD
@ ---c /~\&)~ :;:; 7.fi. oifiiIIo oHo
2 1/2" MIN. MINIMUM 3000 psi MINIMUM 3000 psi SPAN L L 1/4"xO'-3" LONG " LIGHT WEIGHT OR 2500 psi LIGHT WEIGHT OR 2500 psi
CL 8M.MIN., TYP. MIN. NORMAL WEIGHT CONCRETE NORMAL WEIGHT CONCRETE
7/8"; BOLT, TYP. STRUCTURAL WOOD BUILDING ----"'I
IN 15/16"; HOLE ~.~~B&.~C~I~l GRADE STRUCTURE
NUT & BASE PLt==f STRUT- 12-~:iE NUT & WASHER l/t' SPRING NUT, DETAILS ®.
SEE ANCHORAGE ~
AT HSS
CHANNEL NUT, OR THROUGH ®
(3 l/t' MIN.) STRUT BEAMSADDLE NUT ~ FOR ANCHORAGE SCHEDULE FOR SIZEUNISTRUT Pl000 OR TO STRUCTUREBASE PL @ SPRING
158-12OR CHANNEL NUT ~"; BOLTS1/2" HEX-NUT & SPRING NUT AT STRUT
12"O.C., 4 BOLTS3/8"; THRD. ROD 8ASE PLATE
(PART #000.00394) MIN. @
HEX-NUT & BASE PL @158-12-32BHANGER ROD SPRING OR CHANNEL NUTSTRUT BEAM, SEEFOR 1000 LB UNIT DISTANCE FROM END
TABLE FOR SIZE 3/8"; HANGER
-SEE 1/S2 T hanger MEMBER IS 3 l/t'.
HANGER ROD OPTIONS
FOR HSS BEAM 1000 LB UNIT-SEE 1/S2o WOOD r11'e
CHANNEL
MAX. L = 14"
MIN.
CONSTRUCTION
Trapeze Span (in.)
PORTABLE
UNISTRUT Pl000 29OR HILTI 158-12
UNISTRUT Pl001AW 80
OR HILTI 158-12-B2B
UNISTRUT P5501AW 96
HSS 3"x3"x3/16" 96
Lift Type
KB TZ, SEE TABLE FOR
SIZE
6" MIN. FOR )2"0,
8" MIN. FOR 14"0
BRACKET- TO-BEAM
FOR 1000 LB UNIT - SEE 1/S2USE NUTS &
LOCKING WASHER
ABOVE/BELOW
® CONC. JOIST/BEAM CONSTRUCTION
STRUT BEAM
UNISTRUT P2786 \ , L3x2x3/8 (LLV)x3" MIN.
BEVELED WASHER &
LOCK NUT
UNISTRUT P5000
3/8"; THREADED RODOR HILTI 2716-12
6" MIN. AND 10" MIN.HEX-NUT AND BASE
NUT, OR SADDLE NUT
SPRING NUT,
@ ~"; WITH LWC
CHANNEL NUT
PL @ SPRING OR
STRUT BEAM WITH LOCK3/8"; THRD. ROD o HANGER AT OBSTRUCTION WASHER & NUT, ABOVE(PART #000.00394) T hanger
AND BELOW
HANGER ROD OPTIONS
FOR 1000 LB UNIT
-SEE 1/S2o STEEL CONSTRUCTION DETAILS
SHEET NOlES:
1. THE STRUCTURAL ENGINEER OF RECORD IS RESPONSIBLE FOR VERIFYING THE ADEQUACY OF THE STRUCTURE FOR APPLIED LOADS INDICATED
HEREIN, IN ADDITION TO ALL OTHER LOADS. SEE DETAIL 1/S2 FOR STRUCTURAL LOADING.
2. THESE DETAILS ARE NOT USED WITH DIAGONAL BRACING MEMBERS, BUT MAY BE USED FOR VERTICAL HANGERS BRACED AT LOWER END8 ~T~.NGER CONNECTION DETAILS (PER lA/S2, SECTION X-X) OR FOR UNBRACED HANGERS.
DEGENKOLB ENGINEERS
235 Montgomery Street, Suite 500 San Francisco, CA 94104
415.392.6952 Phone
415.981.3157 Fax
www.degenkolb.com
A P PRO V E 0
Fixed Equipment Anchorage
Office of Statewide Health Planning and Development
OPA-0611-07
P,iIP-appto'olal Program Milf'lsger
AnthOt'ly R Pr.ke
;9'6)440-/1...,0
ARJOHUNTLEIGH MAXISKY CEILING LIFTS
Tide: Sheet Number
HANGER CONNECTION DETAILS
Drawn: RP Job Number: A5114009.02
Design: RMG Rev.: 2.1
Check: RSP
Date: 4/13/10 4 OF 5 Sheets
: IZ
<'l~
SIMPSON A35 7 -
SCREWS TO
UNISTRUT Pl000 48" MAX. -+""7"---:,-'-7/---;.
OR HILTI 158-12
4 • "L
6" MIN. FOR ~~ _--
8" MIN. FOR ;y~
L
1 MAX.
o CONC. JOIST/BEAM CONSTRUCTION
~ FOR INFO NOT SHOWN
/" SEE J/S4
THE ADEQUACY OF
ALL OTHER LOADS.
Anthony R ~ke
A P PRO V E 0
Fixed Equipment Anchorage
Office 01 Statewide Health Planning and Development
OPA-0611-07
Pu.t41pprova! Program Manager
DEGENKOLB ENGINEERS
1916,440-!i4J'1)
235 Montgomery Street, Suite 500 San Francisco, CA 94104
415.392.6952 Phone ( ut:. 4/i<r/'&o{O
415.981.3157 Fax
www.degenkolb.com Dote
ARJOHUNTLEIGH MAXISKY CEILING LIFTS
Title: Sheet Number
BRACE CONNECTION DETAILS
Drawn: RP Job Number: A5114009.02
S5Design: RMG Rev.: 2.1
Check: RSP
Date: 4/13/10 5 OF 5 Sheets
(q CONC. 8EA~ OR SLAB EDGE DISTANCEfc = 2500 pSI MIN.- N.W.C.
8" MIN.fc' = MIN.- LW.C.
•r Ztf)
-tf)
:::::El.J..J : Z <'l~ ......... u
~I lOr-
3/8"rfJ HILTI
KWIK BOLT TZ
P1843W FROMSTRUT BRACE
UNISTRUT
o
SOUD CONCRETE SLAB CONSTRUCTION
MTL DECK
(LWC OR NWC)
DISTANCE
8" MIN.
20go MIN. METAL DECK
3/8"1& HILTI KWIK BOLT TZ
INSTALL IN LOW FLUTE ONLY
P1843W FROM UNISTRUT
STRUT
BRACE
G)
METAL DECK
WITH CONCRETE FILL CONSTRUCTION
8 BRACE CONNECTION DETAILS
N.T.S.
(E) CONC. FILL ON
fc = 3000psi MIN.
EDGE
Zc:l -w :::::Ecn : :::::E...,w
~I~ 1O:::::E
:::::E
T IIlrace
4 1/2" MIN.
FLUTE WIDTH
~r 1A 1Jf~ J~" ~'''~i r v b~ad A { EQ~WQ
SECTION A-A
3/8"1& )( 4" MIN.
LAG SCREW W/ (3 1/2"
1 MIN. SHANK EMBEDMENT)
P1843W FROM UNISTRUT
NOTE:
STRUT
MINIMUM DISTANCE FROM ENDBRACE
OF WOOD MEMBER IS 3 1/2".
o BRACE PARALLEL TO WOOD BEAM
3/4")( 112 PAN HEAD WOOD
DECKING
1/2"
(E) WOOD BEAM
3)( BLKG W/ 3-16d
END NAILS EA. END. MIN.
3/8"rfJ )( 4" MIN.
LAG SCREW W/ (3 1/2"
SHANK EMBEDMENT)
STRUT P1843W FROM UNISTRUT
BRACE
o BRACE PERPENDICULAR TO WOOD BEAM
SHEET NOJES;
1. THE STRUCTURAL ENGINEER OF RECORD IS RESPONSIBLE FOR VERIFYING
THE STRUCTURE FOR APPLIED LOADS INDICATED HEREIN. IN ADDITION TO
SEE DETAIL 1/S2 FOR STRUCTURAL LOADING.
http:A5114009.02 http:www.degenkolb.com