36E77619B0012-010.pdf
PDF 19 MB Posted
- Attached to
- Radiology Expansion (Construction) Prescott VAMC
- Solicitation number
- 36E77619B0012
About this file
This federal contract opportunity notice provides details for the Radiology Expansion Minor Construction project at the Northern Arizona VA Medical Center. The project scope involves renovating and expanding an existing radiology area by completely demolishing an existing 3000 square foot lab expansion. The new construction and renovation will optimize the department footprint with a centralized waiting room, wide hallways, and sufficiently sized rooms. The work will also provide ground level access for the entire radiology department as well as the structure and utilities for a future second story addition and elevator.
The solicitation for the project will be issued as an Invitation for Bid and follow FAR Parts 14, 19, and 36. Evaluation will also adhere to procedures in the solicitation. The opportunity is set aside as a Service-Disabled Veteran-Owned Small Business and non-SDVOSB offers will be excluded. The NAICS code is 236220 with a $36.5 million size standard. The estimated value is between $5-10 million. The performance period is approximately 425 days from notice to proceed. The solicitation will be issued on August 8, 2019 with all bids due on the specified date and time.
36E77619B0012 Attachment 9 - Elect and Tech Dwgs_Part1.pdf
View the file
Other files
Show 40 more
Latest 50 of 59 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
E
AREA OF
DEMOLITION
BB
AA
BID DEDUCT ALTERNATE #1
SEE BID DEDUCT ALTERNATE NOTE 1.
BID DEDUCT ALTERNATE #2
SEE BID DEDUCT ALTERNATE NOTE 2.
STORAGE
OFFICE
EXISTING MEN'S TOILET
ELECTRICAL
114C
STORAGE
110E OFFICE
110A
OFFICE
110D
OFFICE
110C
OFFICE
110B
OFFICE
OFFICE
CBOC STAGING
STORAGE
LOUNGE
MEN'S TOILET
RECEPTION / WAITING
PHLEBOTOMY
106A MECH
106C
OFFICE
107D
LAB
107A
LOCKER ROOM
OFFICE
TOILET
103A
CLOSET
103B
WOMEN'S TOILET
STORAGE
H.A.C.
PULMONARY FUNCTION
102A
EXAM 1
124 R T WORK AREA
OFFICE
SPUTUM
102B
OFFICE
110A
STORAGE
114B
Corridor
H.A.C.
114A
EXISTING STAIR
OFFICE
SPECIMEN TOILET
106B
Drawing Number
Project Number
Date
Project Title
Building NumberLocation
Checked DrawnAPPROVED: CHIEF ENGINEER
Drawing Title
VA FORM
Office of Construction and Facilities Management
Dwg
CIVIL / STRUCTURAL ENGINEER M.E.P. / T. ENGINEER
APPROVED: DIRECTOR
APPROVED: ASSOCIATE DIRECTOR
APPROVED: ASSISTANT DIRECTOR APPROVED: CHIEF ENGINEER
REVISIONS DATE
CONSULTANTS ARCHITECT
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
H2B
1225 NORTH LOOP WEST, SUITE 900
HOUSTON, TX 77008
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
AZ ARCH REG. NO. 20013-0, EXP. 10/10/2019
AZ ENGR REG. NO. 20015-0, EXP. 10/10/2019
F U
L L Y
S P
R
IN
K L E
R E
D
RADIOLOGY EXPANSIONELECTRICAL LIGHTING
DEMOLITION FLOOR PLAN
649-413
11/01/2018 JGW ABM
107-ELD101
100% CONSTRUCTION DOCUMENTS
DEPARTMENT OF VETERAN AFFAIRS
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 HWY 89N
PRESCOTT AZ, 86313
116 -OF- 148
1/8" = 1'-0"
ELECTRICAL LIGHTING
DEMOLITION FLOOR PLAN
N
1. CONTRACTOR TO VERIFY LOCATIONS OF ALL EXISTING ELECTRICAL
EQUIPMENT, DEVICES, ETC. DEVICES/EQUIPMENT SHOWN MAY NOT
REPRESENT ALL DEVICES/EQUIPMENT AND THE CONTRACTOR SHALL
BE RESPONSIBLE FOR REMOVING/RELOCATING DEVICES/EQUIPMENT
NOT SHOWN AS REQUIRED FOR DEMOLITION.
GENERAL NOTES:
BID DEDUCT ALTERNATE NOTES:
1. BID DEDUCT ALTERNATE #1: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL CIRCUITING AND LIGHTING IN MEETING ROOM 125,
PHYSICAL VIEWING ROOM 119, 122, AND 123, STAFF TOILET 118, PACS
124, ON CALL 126, WORK AREA 120, CHIEF TECHNOLOGIST 120A,
SUPERVISOR 120B AND STAFF LOUNGE 127. EXISTING LIGHTING
SHALL REMAIN IN PLACE. PROVIDE CIRCUITING FOR EXISTING
LIGHTS TO BE TIED INTO 20A BREAKER(S) IN PANELBOARD 107-1A-4.
2. BID DEDUCT ALTERNATE #2: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL CIRCUITING AND LIGHTING IN WOMEN'S TOILET 106,
STORAGE 107, INPATIENT HOLDING 110, INPATIENT HOLDING 112,
STORAGE 113, AND EQUIPMENT ALCOVE 114. EXISTING LIGHTING
SHALL REMAIN IN PLACE. PROVIDE CIRCUITING FOR EXISTING
LIGHTS TO BE TIED INTO 20A BREAKER(S) IN PANELBOARD 107-1A-4.
-1
A X
-5
-1
A X
-6
-1
A X
-8
-1
A X
-7
-1
A -6
107-1AX-31
-1
A -2
-1
A -3
107-1A-5
107-1AX-2
AREA OF
DEMOLITION
(D E
M O
(E T
R
(DEMO)
(DEMO)
(D E
M O
(D E
M O
(D E
M O
(D E
M O
(D E
M O
BB
AA
(DEMO)
107-1A-4
(DEMO)
107-1A-1
(DEMO)
(RELOCATE)
107-1AX-9
1 (ETR)
107-1AX-10
(DEMO)
TEMP.
CONTROL
PANEL
(DEMO)
(E T
D
(E T
D
B L A
N K
P A
N E
L
(E T
R
A C
C O
N T
R O
L (D
E M
O
BID DEDUCT ALTERNATE #1
SEE BID DEDUCT ALTERNATE NOTE 1.
BID DEDUCT ALTERNATE #2
SEE BID DEDUCT ALTERNATE NOTE 2.
(DEMO)
STORAGE
OFFICE
EXISTING MEN'S TOILET
ELECTRICAL
114C
STORAGE
110E
OFFICE
110A
OFFICE
110D
OFFICE
110C
OFFICE
110B
OFFICE
OFFICE
CBOC STAGING
STORAGE
LOUNGE
MEN'S TOILET
RECEPTION / WAITING
PHLEBOTOMY
106A MECH
106C
OFFICE
107D
LAB
107A
LOCKER ROOM
OFFICE
TOILET
103A
CLOSET
103B
WOMEN'S TOILET
STORAGE
H.A.C.
PULMONARY FUNCTION
102A
EXAM 1
124 R T WORK AREA
OFFICE
SPUTUM
102B
OFFICE
110A
STORAGE
114B
Corridor
H.A.C.
114A
EXISTING STAIR
OFFICE
SPECIMEN TOILET
106B
CORRIDOR
Drawing Number
Project Number
Date
Project Title
Building NumberLocation
Checked DrawnAPPROVED: CHIEF ENGINEER
Drawing Title
VA FORM
Office of Construction and Facilities Management
Dwg
CIVIL / STRUCTURAL ENGINEER M.E.P. / T. ENGINEER
APPROVED: DIRECTOR
APPROVED: ASSOCIATE DIRECTOR
APPROVED: ASSISTANT DIRECTOR APPROVED: CHIEF ENGINEER
REVISIONS DATE
CONSULTANTS ARCHITECT
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
H2B
1225 NORTH LOOP WEST, SUITE 900
HOUSTON, TX 77008
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
AZ ARCH REG. NO. 20013-0, EXP. 10/10/2019
AZ ENGR REG. NO. 20015-0, EXP. 10/10/2019
F U
L L Y
S P
R
IN
K L E
R E
D
RADIOLOGY EXPANSIONELECTRICAL POWER DEMOLITION
FLOOR PLAN
649-413
11/01/2018 JGW ABM
107-EPD101
100% CONSTRUCTION DOCUMENTS
DEPARTMENT OF VETERAN AFFAIRS
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 HWY 89N
PRESCOTT AZ, 86313
117 -OF- 148
1/8" = 1'-0"
ELECTRICAL POWER
DEMOLITION FLOOR PLAN
N
1. CONTRACTOR TO VERIFY LOCATIONS OF ALL EXISTING ELECTRICAL
EQUIPMENT, DEVICES, ETC. DEVICES/EQUIPMENT SHOWN MAY NOT
REPRESENT ALL DEVICES/EQUIPMENT AND THE CONTRACTOR SHALL BE
RESPONSIBLE FOR REMOVING/RELOCATING DEVICES/EQUIPMENT NOT
SHOWN AS REQUIRED FOR DEMOLITION.
GENERAL NOTES:
ELECTRICAL PLAN NOTES:#
1. RELOCATE EXISTING FIRE ALARM CONDUIT TO ACCOMMODATE
NEW SWITCHBOARD. COORDINATE EXACT ROUTING WITH FIRE
ALARM CONTRACTOR.
2. DISCONNECT EXISTING IT ROOM EQUIPMENT CIRCUITS TO REMAIN
AND CONNECT TO NEW PANELBOARD. REFER TO SHEET 107-E-401
FOR ADDITIONAL INFORMATION.
BID DEDUCT ALTERNATE NOTES:
1. BID DEDUCT ALTERNATE #1: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL CIRCUITING, RECEPTACLES, AND DISCONNECT SWITCHES.
EXISTING LIGHTING, RECEPTACLES, AND OTHER ELECTRICAL
EQUIPMENT SHALL REMAIN IN PLACE. PROVIDE WIRING AND 20A
BREAKER(S) FOR EXISTING RECEPTACLES TO NEW PANELBOARD
107-1A-4. PROVIDE WIRING AND BREAKER FOR EXISTING FAN
COIL UNIT'S TO NEW PANELBOARD 107-1A-4. NEW RECEPTACLES
SHALL BE PROVIDED IN PACS ROOM PER NEW WORK LAYOUT.
POWER TO NEW MINI-SPLIT SYSTEM SHALL BE PROVIDED.
COORDINATE WITH VA COR FOR EXACT LOCATION OF PACS ROOM.
2. BID DEDUCT ALTERNATE #2: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL CIRCUITING, RECEPTACLES AND DISCONNECT SWITCHES
IN WOMEN'S TOILET 106, STORAGE 107, INPATIENT HOLDING 110,
INPATIENT HOLDING, 112, STORAGE 113, AND EQUIPMENT ALCOVE
114. EXISTING RECEPTACLES SHALL REMAIN IN PLACE. PROVIDE
WIRING AND 20A BREAKER(S) FOR EXISTING RECEPTACLES TO NEW
PANELBOARD 107-1A-4. PROVIDE WIRING FOR NEW SMOKE
DAMPERS TO EXISTING PANELBOARD 107-1AX-9.
PP
A
B
C
D
F
1 2 4 5 6 7
F2 F2 F2 F2 F2
F2 F2 F2E F2 F2
F2F2F2
F2
F2
F2E
F2
9 108
BASEMENT
A.5
A.1
E
E.1
F.1
G
1.1 2.1 4.5
C.2
8.1
B.2
C.1
RC1
107-1A-4 - 43
107-1AX-9 - 30
D.2
D.1
B.1
LV1
Drawing Number
Project Number
Date
Project Title
Building NumberLocation
Checked DrawnAPPROVED: CHIEF ENGINEER
Drawing Title
VA FORM
Office of Construction and Facilities Management
Dwg
CIVIL / STRUCTURAL ENGINEER M.E.P. / T. ENGINEER
APPROVED: DIRECTOR
APPROVED: ASSOCIATE DIRECTOR
APPROVED: ASSISTANT DIRECTOR APPROVED: CHIEF ENGINEER
REVISIONS DATE
CONSULTANTS ARCHITECT
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
H2B
1225 NORTH LOOP WEST, SUITE 900
HOUSTON, TX 77008
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
AZ ARCH REG. NO. 20013-0, EXP. 10/10/2019
AZ ENGR REG. NO. 20015-0, EXP. 10/10/2019
F U
L L Y
S P
R
IN
K L E
R E
D
RADIOLOGY EXPANSIONELECTRICAL LIGHTING
BASEMENT FLOOR PLAN
649-413
11/01/2018 JGW ABM
107-EL-100
100% CONSTRUCTION DOCUMENTS
DEPARTMENT OF VETERAN AFFAIRS
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 HWY 89N
PRESCOTT AZ, 86313
118 -OF- 148
1/8" = 1'-0"
ELECTRICAL LIGHTING
BASEMENT FLOOR PLAN
N
ELECTRICAL PLAN NOTES:#
1. REFER TO DETAIL 3, SHEET 107-E-702 FOR WIRING DIAGRAM OF
BASEMENT LIGHTS WITH SWITCHES AND OCCUPANCY SENSORS.
GENERAL NOTES:
1. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN
THREE CIRCUITS. EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE
GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
2. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF
EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
3. LABEL ALL ELECTRICAL EQUIPMENT AND WIRING DEVICES WITH
PANELBOARD NAME AND CIRCUIT NUMBER. REFER TO
SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
4. REFER TO SHEET 107-GI-001 FOR BID DEDUCT ALTERNATE
DESCRIPTIONS.
A
B
C
D
F
1 2 4 5 6 7
-1
A -6
-1
A -7
9 108
BASEMENT
CT SCANNER EQUIP. RM
(N E
W
(N E
W
SP-2
SP-1
30/2/NF
107-1AX-7 - 1,3
AC-1
VP-1
107-1AX-7 - 9,11,13
107-1AX-7 - 15,17,19
HU
107-1A-7 - 13,15,17
107-1A-6 - 34
RP-4
107-1A-5 - 23,25,27
107-1A-5 - 35,37,39
107-1A-6 - 20
A.5
A.1
E
E.1
F.1
G
1.1 2.1 4.5
C.2
8.1
B.2
C.1
HX
HX
DIV. 23
DIV. 23
DIV. 23 DIV. 23
SDSD
107-1AX-9 - 34
M
107-1A-7 - 21
107-1A-7 - 19 M
(NEW)
HU
100/3
BID DEDUCT ALTERNATE #3
SEE BID DEDUCT ALTERNATE NOTE 1.
AHU-3_TCP-3
VFD
3-1
107-1A-7 - 2,4,6
VFD
2-1
107-1A-7 - 8,10,12
VFD
1-2
VFD
1-1
107-1A-5 - 2,4,6
107-1A-5 - 15,17,19
AHU-1_TCP-1
AHU-2_TCP-2
107-1A-5 - 21
107-1A-7 - 20
107-1A-7 - 22
HU
107-1A-5 - 41,43,45
DIV. 23
DIV. 23
107-1A-5 - 29,31,33
DIV. 23
DIV. 23
CP
3.2
CP
3.1
(NEW)
XFMR-107-117-158
1200/3P/1200
D.2
D.1
B.1
RR
AHU
AHU
30/2/NF
30/2/NF
107-1A-6 - 42,44
107-1A-6 - 46,48
XFMR-107-1A-6
FCU
FCU
107-1AX-7 - 5
30/1/NF
Drawing Number
Project Number
Date
Project Title
Building NumberLocation
Checked DrawnAPPROVED: CHIEF ENGINEER
Drawing Title
VA FORM
Office of Construction and Facilities Management
Dwg
CIVIL / STRUCTURAL ENGINEER M.E.P. / T. ENGINEER
APPROVED: DIRECTOR
APPROVED: ASSOCIATE DIRECTOR
APPROVED: ASSISTANT DIRECTOR APPROVED: CHIEF ENGINEER
REVISIONS DATE
CONSULTANTS ARCHITECT
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
H2B
1225 NORTH LOOP WEST, SUITE 900
HOUSTON, TX 77008
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
AZ ARCH REG. NO. 20013-0, EXP. 10/10/2019
AZ ENGR REG. NO. 20015-0, EXP. 10/10/2019
F U
L L Y
S P
R
IN
K L E
R E
D
RADIOLOGY EXPANSIONELECTRICAL POWER
BASEMENT FLOOR PLAN
649-413
11/01/2018 JGW ABM
107-EP-100
100% CONSTRUCTION DOCUMENTS
DEPARTMENT OF VETERAN AFFAIRS
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 HWY 89N
PRESCOTT AZ, 86313
119 -OF- 148
1/8" = 1'-0"
ELECTRICAL POWER
BASEMENT FLOOR PLAN
N
ELECTRICAL PLAN NOTES:
1. PROVIDE MINIMUM 36" X 24" X 16" POLYMER CONCRETE HANDHOLE
WITH TIER 15 LOCKABLE COVER.
2. CONDUIT SHOWN TO ELECTRICAL ROOM IS DIAGRAMMATIC ONLY.
CONTRACTOR SHALL AVOID ALL EXISTING UTILITIES. REFER TO
107-ES-101 FOR CONTINUATION.
3. PROVIDE PULLBOXES AS REQUIRED.
4. PROVIDE 12" HIGH CONCRETE HOUSEKEEPING PAD BELOW
TRANSFORMER.
BID DEDUCT ALTERNATE NOTES:
1. BID DEDUCT ALTERNATE #3: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL DISCONNECT SWITCHES AND OTHER CONNECTIONS TO
MECHANICAL EQUIPMENT IN THIS AREA. PLUMBING EQUIPMENT
SHALL BE CONNECTED. COORDINATE EXACT EQUIPMENT WITH
MECHANICAL CONTRACTOR.
GENERAL NOTES:
1. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN
THREE CIRCUITS. EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE
GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
2. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF
EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
3. LABEL ALL ELECTRICAL EQUIPMENT AND WIRING DEVICES WITH
PANELBOARD NAME AND CIRCUIT NUMBER. REFER TO
SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
4. INSTALL ALL DISCONNECT SWITCHES FURNISHED BY DIVISION 23.
5. REFER TO SHEET 107-GI-001 FOR BID DEDUCT ALTERNATE
PP
PP
PP
PP
PP
PP
PP
PPPP
PP
PP PP
PP
PP
PP PP
PP
PP
PP
PP
PP
PP
PP
PP
PP
PP
PP
PP
PPPP
PP
PP
PP
PP
PP
A
B
C
D
F
1 2 4 5 6 7
LVD
OS3 OS3
OS3OS3
OS3
LVD
LVD
LVD
LV01
LV01
OS3
LVD
LVD
LVD
OS3
OS3
LVD
LVD
OS3
A1E
A1E
A1
A1 A1
A1 A1 A1E
D1D1
A1
A1
A1
A1D D2
D2
A1D
A1D
A1D
A2D
A1
A1D A1D
A1D A1
A1E
A1
A1
A1
A2D
A2D A2D
A2D
A1E
A1
A1
A1
A1
D1
D1
D1
A1
D1
A1
A2D
D1
A1
A1E
A1
A2D
A2D
A2D
A1A1EA1
A1 A1
A1
A1
A2DA2D
A1A1E
A1
A1
A1
A1A1
A1A1
A1
A1B1D
A1
A1E
A1
A1 A1E
D1
D1 D1
D1
A1
D1D1
A2D
A2D
A2D
A1
A1
A1
A1
A1
A1
A1D
A1D
A1E
A1D
A1
A1D
A1D
A1 A1
A1
A1D
A1E
A1
A1
A1
D1
D1D
D1D
B1D
D1D
B1D
D1D
B1D
D1D
B1D
D1D
B1D
B1D
B1D
B1D
D1D
D1D
D1D
D1D D1D D1D
D1D D1D
A2D
A2D
A2D
A2D
A2D
A2D
D1E
D1E
D1
D1 D1 D1 D1 D1
D1
B1D
D1D B1D
D1D
B1D D1D
B1D D1D
D1D
B1D D1DB1D
D1D
B1D
D1D B1D
D1D
D1D
D1D
D1D
D1
D4D
D4D
D4D
D4D
D4D
D4D
D4D
B1D
B1D
B1D
B1D
B1D
B1D
A1
D3E
A1E A1
A1A1
A1E A1 A1
A2D A2D
F3E
F3E
X1E
X1E
X1E
D1 D1E
D1E D1
X1E
X1E
X1E
X1E
X1E
A2D
OS1
OS1
OS3
OS3
LVD
LVD
LVD
LVD
LVD LVD
LVD
LVD
STAIRWELL
FLUOROSCOPY X-RAY ROOM
CT SCAN ROOM
CT CONTROL
SPECT CT SCAN ROOM
RADIO DROP-OFF
144B
NM "HOT LAB" RADIOPHARMACY
144A
PATIENT DOSE ADMINISTRATION
BONE DENSITOMETRY
MRI PREP/HOLDING
146A
CORRIDOR
NURSE
X-RAY
X-RAY
DRESS
DRESS
WOMEN'S RESTROOM
MEN'S RESTROOM
DRESS
DRESS
SCHEDULING
ENTRY VESTIBULE
NEW ELEC.
WOMEN'S TOILET
STORAGE
INPATIENT HOLDING
STORAGE
EQUIP. ALCOVE
COMMS
STAFF TOILET
CHIEF TECHNOLOGIST
120A
WORK AREA
PHYS. VIEWING ROOM
PHYS. VIEWING ROOM
PHYS. VIEWING ROOM
PACS
SUPERVISOR
120B
MEETING ROOM
ON-CALL ROOM
STAFF LOUNGE/TRAINING
MRI SCAN ROOM
146C
TOILET
111A
HAC
ULTRASOUND
ULTRASOUND
WORKROOM
STAFF TOILET
TOILET
109A
MRI EQUIP. ROOM
RESTROOM
SOILED UTILITY
STRESS
OS3
OS3
OS3
OS3
OS3
OS3
INPATIENT HOLDING
WAITING
OS2 OS2 OS2 OS2 OS2
OS2
OS2
OS2
OS2
OS1
OS1
OS1
OS2
OS2
OS2OS2
OS2
OS2 OS2 OS2
OS2
DS1
DS1
LV2
LV2
OS3
OS3
Z3 Z3
Z2Z2
Z1
B1D
B1D
B1DB1D
D1D
D1D D1D
D1D
D1D
D1D
F3E
F3E
LVD
X1E
LVD
LVD
F1EF1E
LVD
OS3
OS3
OS3
LVD
LVD LVD
LVD
LVDLVD
LVD LVD LVD
LVD
W1
W1
W1
W1 W1
MRI CONTROL ROOM
146B
MRI SUB-WAITING
OS3OS3
D1
LVD
D4D
D4D
MRI DRESS
146E
MRI DRESS
146F
LVD
D1D
F1E F1E
F1E F1E
DS1
DS1
LVD
OS1
LVD LVD
X1E
OS1
OS1
D1
D1
DS1
OS1
DS1
OS1
B1D B1D B1D
B1D
9 10
B1D
RC2
RC3
RC2
RC1
RC1
RC1
RC1
RC1
RC3
RC3
RC1
D1
RC1
D1
OS2
LV1 LVD
X1E
RC2
RC1
RC1
D1
RC1
RC1
RC1
OS1
LV1
RC1
RC1
RC1
X1E
RC1
RC1
RC1
107-1AX-9 - 20
107-1AX-9 - 22
107-1A-4 - 59
(PART)
107-1A-4 - 59
(PART)
107-1A-4 - 59
C1EC1E
107-1AX-2 - 29 107-1AX-2 - 31
(PART)(PART)
OS1
OS1
OS1
RC1
RC1
RC1
4 2
RC1
RC1
RC1
LV1
LV1
107-1A-4 - 49
RC1
LV1
LV1
LV1
RC1
OS3
LIGHTING
CONTROL
LV1
107-1AX-9 - 24
107-1A-4 - 36
LV1
MRIRC
Z2
CORRIDOR
107-1A-4 - 47
107-1A-4 - 45
107-1A-4 - 51 107-1A-4 - 53
107-1A-4 - 55
107-1A-4 - 57
CORRIDOR
A.5
A.1
E
E.1
F.1
G
1.1 2.1 4.5
C.2
8.1
B.2
C.1
LVD
MRIRC
LV1
BID DEDUCT ALTERNATE #1
SEE BID DEDUCT ALTERNATE NOTE 1.
BID DEDUCT ALTERNATE #2
SEE BID DEDUCT ALTERNATE NOTE 2.
BID DEDUCT ALTERNATE #3
SEE BID DEDUCT ALTERNATE NOTE 3.
A1
A1
D.2
D.1
B.1
X1E RC1
Drawing Number
Project Number
Date
Project Title
Building NumberLocation
Checked DrawnAPPROVED: CHIEF ENGINEER
Drawing Title
VA FORM
Office of Construction and Facilities Management
Dwg
CIVIL / STRUCTURAL ENGINEER M.E.P. / T. ENGINEER
APPROVED: DIRECTOR
APPROVED: ASSOCIATE DIRECTOR
APPROVED: ASSISTANT DIRECTOR APPROVED: CHIEF ENGINEER
REVISIONS DATE
CONSULTANTS ARCHITECT
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
H2B
1225 NORTH LOOP WEST, SUITE 900
HOUSTON, TX 77008
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
AZ ARCH REG. NO. 20013-0, EXP. 10/10/2019
AZ ENGR REG. NO. 20015-0, EXP. 10/10/2019
F U
L L Y
S P
R
IN
K L E
R E
D
RADIOLOGY EXPANSIONELECTRICAL LIGHTING
FIRST FLOOR PLAN
649-413
11/01/2018 JGW ABM
107-EL-101
100% CONSTRUCTION DOCUMENTS
DEPARTMENT OF VETERAN AFFAIRS
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 HWY 89N
PRESCOTT AZ, 86313
120 -OF- 148
1/8" = 1'-0"
ELECTRICAL LIGHTING
FIRST FLOOR PLAN
N
ELECTRICAL PLAN NOTES:#
1. REFER TO DETAIL 1, SHEET 107-E-701 FOR WIRING DIAGRAM OF
CHIEF TECHNOLOGIST ROOM 120A AND SUPERVISOR ROOM 120B
LIGHTS WITH SWITCHES, OCCUPANCY SENSORS AND DAYLIGHT
SENSORS.
2. REFER TO DETAIL 2, SHEET 107-E-701 FOR WIRING DIAGRAM OF ALL
TYPICAL ROOM CONTROLLERS WITH SWITCHES AND OCCUPANCY
SENSORS.
3. REFER TO DETAIL 3, SHEET 107-E-701 FOR WIRING DIAGRAM OF
MEETING ROOM 125, WORK AREA ROOM 120 AND STAFF ROOM 117
LIGHTS WITH SWITCHES, OCCUPANCY SENSORS AND DAYLIGHT
SENSORS.
4. REFER TO DETAIL 4, SHEET 107-E-701 FOR WIRING DIAGRAM OF CT
SCAN ROOM 139 AND SPECT CT SCAN ROOM 141 LIGHTS WITH
SWITCHES.
5. REFER TO DETAIL 6, SHEET 107-E-701 FOR WIRING DIAGRAM OF X-
RAY ROOM 137, X-RAY ROOM 137 AND FLUOROSCOPY X-RAY ROOM
135 LIGHTS WITH SWITCHES.
6. REFER TO DETAIL 1, SHEET 107-E-702 FOR WIRING DIAGRAM OF
ENTRY 100 AND RADIO DROP OFF 144B WITH SWITCHES,
OCCUPANCY SENSORS AND DAYLIGHT SENSORS. LOCATE
CONTROLLER IN ADJACENT ACCESSIBLE CEILING.
7. REFER TO DETAIL 3, SHEET 107-E-702 FOR WIRING DIAGRAM OF
CORRIDOR LIGHTS WITH SWITCHES AND OCCUPANCY SENSORS.
8. REFER TO DETAIL 2, SHEET 107-E-701 FOR WIRING DIAGRAM OF NM
"HOT LAB" RADIOPHARMACY LIGHTS WITH SWITCHES. LOCATE
CONTROLLER IN ADJACENT ACCESSIBLE CEILING.
9. REFER TO DETAIL 4, SHEET 107-E-702 FOR WIRING DIAGRAM OF
WORKROOM 105 WITH SWITCHES AND OCCUPANCY SENSORS.
10. TIE CIRCUIT INTO EXISTING BUILDING 117 TIMESWITCH. COORDINATE
WITH GOVERNMENT FOR EXACT LOCATION OF TIMESWITCH.
PROVIDE A NEW CONTACTOR IF NECESSARY.
11. PROVIDE NORMALLY OPEN RELAY WITH A 24 VOLT, DC COIL AND A
STEERING DIODE WIRED OVER THE RELAY COIL TO PROVIDE
CONTROL SIGNAL FOR WARNING LIGHT. REFER TO
MANUFACTURER'S DRAWINGS FOR MORE INFORMATION.
12. ALL CONDUIT, PULLBOXES, ETC. PROVIDED IN MRI SCAN ROOM 146C
SHALL BE ALUMINUM (NON-FERROUS). ALL POWER ENTERING ROOM
SHALL GO THROUGH A RF FILTER. REFER TO MANUFACTURER'S
DRAWINGS FOR EXACT REQUIREMENTS PRIOR TO INSTALLATION.
13. TIE EXISTING LIGHTING IN RESTROOM TO CIRCUIT 107-1A-4- 49.
14. TIE EXISTING LIGHTING IN STAIRWELL TO EXISTING 20A BREAKER(S)
ON LIFE SAFETY PANELBOARD 107-1AX-9.
15. REFER TO DETAIL 4, SHEET 107-E-702 FOR WIRING DIAGRAM OF MRI
SCAN ROOM 146C LIGHTS WITH SWITCHES.
16. REFER TO DETAIL 1, SHEET 107-E-702 FOR WIRING DIAGRAM OF
STAIRWELL 169 LIGHTS WITH SWITCHES, OCCUPANCY SENSORS
AND DAYLIGHT SENSORS. LOCATE CONTROLLER IN BASEMENT.
1. EACH POWER PACK SHALL BE PROVIDED WITH A DIGITAL NETWORK
BRIDGE. THE NETWORK BRIDGES SHALL BE DAISY CHAINED TOGETHER
BEFORE TERMINATING AT THE LIGHTING CONTROL SEGMENT
MANAGER LOCATED IN ELECTRICAL ROOM 103. SUPERVISOR
SOFTWARE SHALL BE INSTALLED ON A DEDICATED CPU SPECIFIED BY
THE GOVERNMENT. COORDINATE EXACT LOCATION OF CPU WITH
GOVERNMENT.
2. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN
THREE CIRCUITS. EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE
GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
3. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF
EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
4. REFER TO SHEET 107-GI-001 FOR BID DEDUCT ALTERNATE
DESCRIPTIONS.
GENERAL NOTES:
BID DEDUCT ALTERNATE NOTES:
1. BID DEDUCT ALTERNATE #1: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL CIRCUITING AND LIGHTING IN MEETING ROOM 125,
PHYSICAL VIEWING ROOM 119, 122, AND 123, STAFF TOILET 118, PACS
124, ON CALL 126, WORK AREA 120, CHIEF TECHNOLOGIST 120A,
SUPERVISOR 120B AND STAFF LOUNGE 127. EXISTING LIGHTING
SHALL REMAIN IN PLACE. PROVIDE CIRCUITING FOR EXISTING
LIGHTS TO BE TIED INTO 20A BREAKER(S) IN PANELBOARD 107-1A-4.
2. BID DEDUCT ALTERNATE #2: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL CIRCUITING AND LIGHTING IN WOMEN'S TOILET 106,
STORAGE 107, INPATIENT HOLDING 110, INPATIENT HOLDING 112,
STORAGE 113, AND EQUIPMENT ALCOVE 114. EXISTING LIGHTING
SHALL REMAIN IN PLACE. PROVIDE CIRCUITING FOR EXISTING
LIGHTS TO BE TIED INTO 20A BREAKER(S) IN PANELBOARD 107-1A-4.
3. BID DEDUCT ALTERNATE #3: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL CIRCUITING AND LIGHTING IN MRI PREP HOLDING 146A, MRI
CONTROL ROOM 146B, MRI SCAN ROOM 146C, AND MRI EQUIPMENT
ROOM 149. PROVIDE (2) F1E STRIP LIGHTS IN MRI EQUIPMENT
ROOM 149 AND LIGHT SWITCH AND PROVIDE (4) F1E STRIP LIGHTS IN
THE MRI SUITE SPACE AND LIGHT SWITCH AND TIE LIGHTS INTO
CIRCUIT 57 IN PANELBOARD 107-1A-4.
DM DM
DM DM DM
J
J
J
J
J
J
J
J
J
J
JJ
J
J
J
A
B
C
D
F
1 2 4 5 6 7
NM "HOT LAB" RADIOPHARMACY
144A
RADIO DROP-OFF
144B
PATIENT DOSE ADMINISTRATION
SPECT CT SCAN ROOM
CT CONTROL
CT SCAN ROOM
FLUOROSCOPY X-RAY ROOM
TOILET
135A
ALCOVE
STAIRWELL
DRESS
DRESS
WOMEN'S RESTROOM
MEN'S RESTROOM
DRESS
DRESS
CORRIDOR
WAITING
SCHEDULING
NEW ELEC.
103ENTRY VESTIBULE
WOMEN'S TOILET
STORAGE
INPATIENT HOLDING
INPATIENT HOLDING
STORAGE
EQUIP. ALCOVE
COMMS
STAFF TOILET
PHYS. VIEWING ROOM
PHYS. VIEWING ROOM
PHYS. VIEWING ROOM
PACS
ON-CALL ROOM
MEETING ROOM
SUPERVISOR
120B
WORK AREA
CHIEF TECHNOLOGIST
120A
STAFF LOUNGE/TRAINING
HAC
TOILET
111A
ULTRASOUND
MRI EQUIP. ROOM
MRI DRESS
146F
MRI SUB-WAITING
MRI PREP/HOLDING
146A
BONE DENSITOMETRY
X-RAY
X-RAY
STRESS
NURSE
SOILED UTILITY
RESTROOM
TOILET
109A
STAFF TOILET
ULTRASOUND
WORKROOM
CORRIDOR
ALCOVE
ALCOVE
ALCOVE
ALCOVE
X-RAY TECH
MRI SCAN ROOM
146C
107-1A-3107-1A-2
PACS
MRI DRESS
146E
MRI CONTROL ROOM
146B
107-E-401
107-1AX-5
SWBD
107-RADI
SWBD
107-117-158 X
F M
R -1
-1
A -4
107-1A-4
107-E-401
EPO EPO
EPO
EPO
EPO
EPO
"ø
2"ø
EPO EPO
9 10
LIGHTING
CONTROL
(ETR) (ETR)
107-1AX-6
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
19VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
107-1A-4 - 8
107-1A-4 - 21 107-1A-4 - 23
107-1A-4 - 25
107-1A-4 - 27
107-1A-4 - 31
107-1A-4 - 10
VAV
107-1A-4 - 4
107-1A-4 - 2
107-1A-4 - 6
107-1A-4 - 12
107-1A-4 - 14
107-1A-4 - 16
107-1A-4 - 18
107-1A-4 - 20 107-1A-4 - 22
107-1A-4 - 15107-1A-4 - 13 107-1A-4 - 9107-1A-4 - 11
107-1A-4 - 34
107-1A-6 - 22
107-1A-6 - 26
107-1A-6 - 12
107-1A-6 - 25
107-1A-6 - 23
107-1A-6 - 17
EPO
107-1A-6 - 7
107-1A-6 - 21
107-1A-6 - 19
107-1A-6 - 1
107-1A-6 - 3
(NEW)
107-1A-6 - 9
107-1AX-2 - 13
(NEW)
(NEW)
(NEW)
(RELOCATE)
107-1AX-2 - 9
107-1AX-2 - 5
107-1AX-2 - 3
107-1AX-2 - 11
107-1A-6 - 11
107-1A-6 - 10
107-1AX-2 - 1
107-1AX-2 - 23
107-1AX-2 - 27
107-1AX-2 - 25
107-1AX-2 - 17
107-1A-6 - 4
107-1AX-2 - 19
107-1A-4 - 30
107-1A-4 - 32
107-1A-4 - 24
107-1AX-2 - 29 107-1AX-2 - 31
107-1A-4 - 17
107-1A-4 - 35
107-1A-4 - 37
(PART) (PART)
VAV
VAV
VAV
VAV
107-1A-6 - 15
VAV
107-1A-6 - 24
107-1A-4 - 39
M
M
M M M
M
M
M
M
M
M
M
M
M
M
M M
M
M M M
M
M
M
M
M
M
M
M M
M
M
M
107-1AX-2 - 21
EPO
107-1AX-9
107-1A-5 - 1
107-1A-6 - 2
107-1A-4 - 5
107-1A-6 - 6
107-1A-6 - 30
VAV
M
VAV
VAV
(ETR)
M M
VAV
VAV
107-1A-6 - 28
107-1A-4 - 33
107-1A-4 - 38
(ETR)
(ETR)
107-1AX-2
107-1AX-7
(NEW)
107-1A-5
2"ø
+60"
VAV
VAV
107-1A-4 - 40
+88"
+88"
107-1A-4 - 29
1 1
3 3
EPO
107-1AX-2 - 15
107-1A-4 - 41
VAV
107-1A-6 - 32
107-1AX-7 - 6
SWBD 107-RADI - 13
107-1A-7 - 1,3,5
SWBD 107-RADI - 10
SWBD 107-RADI - 9 SWBD 107-RADI - 11
SWBD 107-RADI - 12
107-1A-6 - 14
107-1A-6 - 36
107-1A-6 - 38
FCU
107-1A-5 - 5
ACU
ACU
ACU
ACU
M107-1A-4 - 44,46
(PART)
M
107-1A-4 - 48,50
(PART)
107-1A-4 - 52,54
(PART)
M
(PART)
M
M
107-1A-4 - 60,62
(PART)
A.5
A.1
E
E.1
F.1
G
1.1 2.1 4.5
C.2
8.1
B.2
C.1
MAP
AAP
107-1AX-9 - 26107-1AX-9 - 28
ACU
107-1A-4- 64,66
EPO
SD
SD
SD
SD
SD
SD
107-1AX-9 - 32
107-1A-4 - 3
M
107-1A-4 - 7
VAV
107-1A-4 - 1
BID DEDUCT ALTERNATE #1
SEE BID DEDUCT ALTERNATE NOTE 1.
BID DEDUCT ALTERNATE #2
SEE BID DEDUCT ALTERNATE NOTE 2.
BID DEDUCT ALTERNATE #3
SEE BID DEDUCT ALTERNATE NOTE 3.
107-1A-6 - 16
(ETR)
(N E
W
107-1A-5 - 3
D.2
D.1
B.1
R
R
R
RR
R
MM
107-1A-6 - 40
107-1A-4 - 19
107-1A-4 - 63
107-1A-4 - 65
107-1A-6 - 8
ALCOVE
146H
107-1A-4 - 26
107-1A-6 - 13
107-1AX-2 - 7
107-1AX-7 - 2
(PART)
107-1A-6 - 5
107-1A-6 - 18
107-1A-4 - 67
ACV
ACV
1818 18
107-1A-4 - 69
CT SCANNER
MAIN PANEL
BID DEDUCT
ALTERNATE #2
BID DEDUCT
ALTERNATE #2
Drawing Number
Project Number
Date
Project Title
Building NumberLocation
Checked DrawnAPPROVED: CHIEF ENGINEER
Drawing Title
VA FORM
Office of Construction and Facilities Management
Dwg
CIVIL / STRUCTURAL ENGINEER M.E.P. / T. ENGINEER
APPROVED: DIRECTOR
APPROVED: ASSOCIATE DIRECTOR
APPROVED: ASSISTANT DIRECTOR APPROVED: CHIEF ENGINEER
REVISIONS DATE
CONSULTANTS ARCHITECT
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
H2B
1225 NORTH LOOP WEST, SUITE 900
HOUSTON, TX 77008
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
AZ ARCH REG. NO. 20013-0, EXP. 10/10/2019
AZ ENGR REG. NO. 20015-0, EXP. 10/10/2019
F U
L L Y
S P
R
IN
K L E
R E
D
RADIOLOGY EXPANSIONELECTRICAL POWER
FIRST FLOOR PLAN
649-413
11/01/2018 JGW ABM
107-EP-101
100% CONSTRUCTION DOCUMENTS
DEPARTMENT OF VETERAN AFFAIRS
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 HWY 89N
PRESCOTT AZ, 86313
121 -OF- 148
1/8" = 1'-0"
ELECTRICAL POWER
FIRST FLOOR PLAN
N
ELECTRICAL PLAN NOTES:#
1. CHASE/WIREWAY 10" X 5-1/2" ABOVE CEILING. COORDINATE EXACT
ROUTING AND CHASE/WIREWAY SIZE WITH MANUFACTURER PRIOR
TO INSTALLATION.
2. CHASE/WIREWAY 12" X 3-1/2" IN FLOOR, FLUSH WITH TOP.
COORDINATE EXACT ROUTING AND CHASE/WIREWAY SIZE WITH
MANUFACTURER PRIOR TO INSTALLATION.
3. INTERLOCK CIRCUIT BREAKER WITH EACH EPO IN ROOM. REFER TO
SHEET 107-E-601 FOR ADDITIONAL INFORMATION. COORDINATE
EXACT LOCATION WITH EQUIPMENT MANUFACTURER.
4. PROVIDE 120V POWER TO MRI METAL DETECTOR. REFER TO
ARCHITECTURAL FOR EXACT REQUIREMENTS.
5. PROVIDE 120V POWER TO DOOR OPERATOR AND DOORS. REFER TO
ARCHITECTURAL FOR EXACT REQUIREMENTS.
6. PROVIDE 120V POWER TO DOOR OPERATOR AND DOORS.
INTERLOCK CARD READER WITH DOOR OPERATOR. REFER TO
ARCHITECTURAL FOR EXACT REQUIREMENTS.
7. ALL CONDUIT, PULLBOXES, LADDER TRAY, ETC. PROVIDED IN MRI
SCAN ROOM 146C SHALL BE ALUMINUM (NON-FERROUS). ALL
POWER ENTERING ROOM SHALL GO THROUGH A RF FILTER. REFER
TO MANUFACTURER'S DRAWINGS FOR EXACT REQUIREMENTS
PRIOR TO INSTALLATION.
8. TIE EXISTING RECEPTACLES INTO NEW 20A CIRCUIT ON
PANELBOARD 107-1A-4.
9. PROVIDE 120V POWER TO PATIENT LIFT. COORDINATE EXACT
LOCATION WITH EQUIPMENT INSTALLER.
10. PROVIDE 20A HOSPITAL GRADE MRI RECEPTACLE.
11. INTERLOCK RETURN FAN MOTORIZED DAMPER WITH EXHAUST FAN
EF-7. COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT
LOCATION.
12. INTERLOCK DOOR SWITCH WITH POWER EQUIPMENT PER
MANUFACTURER'S RECOMMENDATIONS. REFER TO SHEET 107-E-601
FOR ADDITIONAL INFORMATION.
13. PROVIDE FINAL INTERCONNECTIONS FOR MEDICAL EQUIPMENT AS
REQUIRED BY GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
MEDICAL EQUIPMENT MANUFACTURER’S SHOP DRAWINGS. FINAL
INTERCONNECTIONS TO INCLUDE CONDUIT AND/OR CONDUCTORS
BETWEEN PIECES OF THE MEDICAL EQUIPMENT AND THEIR
CONTROL SYSTEMS INDICATED ON THE MEDICAL EQUIPMENT
MANUFACTURER’S SHOP DRAWINGS. REFER TO CEILING MOUNTED
X-RAY MACHINE MODEL NUMBER N-SRD140015 HIGH PERFORMANCE
ROOM VS CUTSHEETS AND SHOP DRAWINGS FURNISHED BY THE
GOVERNMENT.
14. PROVIDE FINAL INTERCONNECTIONS FOR MEDICAL EQUIPMENT AS
REQUIRED BY GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
MEDICAL EQUIPMENT MANUFACTURER’S SHOP DRAWINGS. FINAL
INTERCONNECTIONS TO INCLUDE CONDUIT AND/OR CONDUCTORS
BETWEEN PIECES OF THE MEDICAL EQUIPMENT AND THEIR
CONTROL SYSTEMS INDICATED ON THE MEDICAL EQUIPMENT
MANUFACTURER’S SHOP DRAWINGS. REFER TO FLUOROSCOPY X-
RAY MACHINE MODEL NUMBER COMBIDIAGNOSTIC R90 SRD
CUTSHEETS AND SHOP DRAWINGS FURNISHED BY THE
GOVERNMENT.
15. PROVIDE FINAL INTERCONNECTIONS FOR MEDICAL EQUIPMENT AS
REQUIRED BY GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
MEDICAL EQUIPMENT MANUFACTURER’S SHOP DRAWINGS. FINAL
INTERCONNECTIONS TO INCLUDE CONDUIT AND/OR CONDUCTORS
BETWEEN PIECES OF THE MEDICAL EQUIPMENT AND THEIR
CONTROL SYSTEMS INDICATED ON THE MEDICAL EQUIPMENT
MANUFACTURER’S SHOP DRAWINGS. REFER TO CT SCANNER
MACHINE MODEL NUMBER DISCOVERY CT SERIES - REV HD CT
CUTSHEETS AND SHOP DRAWINGS FURNISHED BY THE
GOVERNMENT.
16. PROVIDE FINAL INTERCONNECTIONS FOR MEDICAL EQUIPMENT AS
REQUIRED BY GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
MEDICAL EQUIPMENT MANUFACTURER’S SHOP DRAWINGS. FINAL
INTERCONNECTIONS TO INCLUDE CONDUIT AND/OR CONDUCTORS
BETWEEN PIECES OF THE MEDICAL EQUIPMENT AND THEIR
CONTROL SYSTEMS INDICATED ON THE MEDICAL EQUIPMENT
MANUFACTURER’S SHOP DRAWINGS. REFER TO SPECT CT
SCANNER MACHINE MODEL NUMBER DISCOVERY CT - NM 670 DR
CUTSHEETS AND SHOP DRAWINGS FURNISHED BY THE
GOVERNMENT.
17. PROVIDE FINAL INTERCONNECTIONS FOR MEDICAL EQUIPMENT AS
REQUIRED BY GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
MEDICAL EQUIPMENT MANUFACTURER’S SHOP DRAWINGS. FINAL
INTERCONNECTIONS TO INCLUDE CONDUIT AND/OR CONDUCTORS
BETWEEN PIECES OF THE MEDICAL EQUIPMENT AND THEIR
CONTROL SYSTEMS INDICATED ON THE MEDICAL EQUIPMENT
MANUFACTURER’S SHOP DRAWINGS. REFER TO SHOP DRAWINGS
FURNISHED BY THE GOVERNMENT.
18. MOUNT EMERGENCY POWER OFF BUTTON AT HEIGHT
SPECIFIED BY MANUFACTURER.
BID DEDUCT ALTERNATE NOTES:
1. BID DEDUCT ALTERNATE #1: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL CIRCUITING, RECEPTACLES, AND DISCONNECT SWITCHES.
EXISTING LIGHTING, RECEPTACLES, AND OTHER ELECTRICAL
EQUIPMENT SHALL REMAIN IN PLACE. PROVIDE WIRING AND 20A
BREAKER(S) FOR EXISTING RECEPTACLES TO NEW PANELBOARD
107-1A-4. PROVIDE WIRING AND BREAKER FOR EXISTING FAN
COIL UNIT'S TO NEW PANELBOARD 107-1A-4. NEW RECEPTACLES
SHALL BE PROVIDED IN PACS ROOM PER NEW WORK LAYOUT.
POWER TO NEW MINI-SPLIT SYSTEM SHALL BE PROVIDED.
COORDINATE WITH VA COR FOR EXACT LOCATION OF PACS ROOM.
2. BID DEDUCT ALTERNATE #2: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL CIRCUITING, RECEPTACLES AND DISCONNECT SWITCHES
IN WOMEN'S TOILET 106, STORAGE 107, INPATIENT HOLDING 110,
INPATIENT HOLDING, 112, STORAGE 113, AND EQUIPMENT ALCOVE
114. EXISTING RECEPTACLES SHALL REMAIN IN PLACE. PROVIDE
WIRING AND 20A BREAKER(S) FOR EXISTING RECEPTACLES TO NEW
PANELBOARD 107-1A-4. PROVIDE WIRING FOR NEW SMOKE
DAMPERS TO EXISTING PANELBOARD 107-1AX-9. RELOCATE (3)
RECEPTACLES AND CIRCUITING (NOT SHOWN) FROM MEDICAL
EQUIPMENT ALCOVE FOR PORTABLE MEDICAL EQUIPMENT TO
LOCATIONS SHOWN. COORDINATE EXACT LOCATION WITH
GOVERNMENT PRIOR TO ROUGH-IN.
3. BID DEDUCT ALTERNATE #3: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL RECEPTACLES, JUNCTION BOXES, EMERGENCY POWER
OFF BUTTONS, DOOR MONITORS, DISCONNECT SWITCHES, CIRCUIT
BREAKER ENCLOSURES AND CIRCUITING. CIRCUIT BREAKERS
PROVIDED IN NEW PANELBOARDS TO SERVE MRI PREP HOLDING
146A, MRI CONTROL ROOM 146B, MRI SCAN ROOM 146C, AND MRI
EQUIPMENT ROOM 149 SHALL BE PROVIDED. STUB RACEWAYS
FROM PANELBOARDS INTO MRI EQUIPMENT ROOM FOR ALL
CIRCUITS AS SHOWN ON NEW WORK PLANS AND LABEL EACH
RACEWAY ABOVE NEW CEILING FOR FUTURE CIRCUITING. UPDATE
PANELBOARD SCHEDULE TO REFLECT CIRCUIT BREAKERS AS
"FUTURE MRI USE". PROVIDE WIRING AND MOTOR RATED SWITCH
FOR NEW VAV BOX IN MRI PREP/HOLDING 146A.
GENERAL NOTES:
1. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN
THREE CIRCUITS. EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE
GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
2. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF
EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
3. LABEL ALL ELECTRICAL EQUIPMENT AND WIRING DEVICES WITH
PANELBOARD NAME AND CIRCUIT NUMBER. REFER TO
SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
A
C
D
F
1 2 4 5 6 7 9 108
EF
ACC
EF
CU
6.1
WP/WR
WP/WR
WP/WR
WP/WR
WP/WR
EF
CU
7.1
107-1AX-7 - 2
107-1A-5 - 14,16,18
107-1A-5 - 8,10,12
107-1A-4 - 28
107-1A-7 - 14,16,18
CU
CU
107-1A-4 - 48,50
CU
CU
CU
3 1
107-1A-4 - 52,54 107-1A-4 - 56,58
107-1A-4 - 60,62
A.5
A.1
E
E.1
F.1
G
1.1 2.1 4.5
C.2
8.1
B.2
C.1
30/2P
30/2P 30/2P
WP/WR
107-1A-4 - 44,46
DIV. 23
WP/WR
WP/WR
107-1A-4 - 42
EF
EF
EF
EF
EF
BID DEDUCT ALTERNATE #3
SEE DID DEDUCT ALTERNATE NOTE 1.
30/3/NF/3R
CU
6.2
CU
7.2
107-1A-5 - 32,34,36
107-1A-5 - 26,28,30
107-1A-5 - 20,22,24
107-1A-5 - 38,40,42
30/3/NF/3R
30/3/NF/3R 30/3/NF/3R
30/2/NF/3R
30/2/NF/3R
30/3/2/00/3R
B.1
107-1AX-7 - 4
DIV. 23
107-1A-5 - 9 107-1A-5 - 7
DIV. 23
107-1A-5 - 13
DIV. 23
107-1A-4 - 64,66,68
DIV. 23
30/3/2/00/3R 30/3/2/00/3R
30/3/2/00/3R
Drawing Number
Project Number
Date
Project Title
Building NumberLocation
Checked DrawnAPPROVED: CHIEF ENGINEER
Drawing Title
VA FORM
Office of Construction and Facilities Management
Dwg
CIVIL / STRUCTURAL ENGINEER M.E.P. / T. ENGINEER
APPROVED: DIRECTOR
APPROVED: ASSOCIATE DIRECTOR
APPROVED: ASSISTANT DIRECTOR APPROVED: CHIEF ENGINEER
REVISIONS DATE
CONSULTANTS ARCHITECT
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
H2B
1225 NORTH LOOP WEST, SUITE 900
HOUSTON, TX 77008
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
AZ ARCH REG. NO. 20013-0, EXP. 10/10/2019
AZ ENGR REG. NO. 20015-0, EXP. 10/10/2019
F U
L L Y
S P
R
IN
K L E
R E
D
RADIOLOGY EXPANSIONELECTRICAL POWER
ROOF FLOOR PLAN
649-413
11/01/2018 JGW ABM
107-EP-102
100% CONSTRUCTION DOCUMENTS
DEPARTMENT OF VETERAN AFFAIRS
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 HWY 89N
PRESCOTT AZ, 86313
122 -OF- 148
1/8" = 1'-0"
ELECTRICAL POWER
ROOF FLOOR PLAN
N
ELECTRICAL PLAN NOTES:#
1. CONDENSING UNIT LOCATED ON BUILDING 158 ROOF.
BID DEDUCT ALTERNATE NOTES:
1. BID DEDUCT ALTERNATE #3: IF DEDUCT ALTERNATE IS ACCEPTED,
OMIT ALL DISCONNECT SWITCHES AND OTHER CONNECTIONS TO
MECHANICAL EQUIPMENT IN THIS AREA. COORDINATE EXACT
EQUIPMENT WITH MECHANICAL CONTRACTOR.
GENERAL NOTES:
1. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN
THREE CIRCUITS. EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE
GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
2. LABEL ALL ELECTRICAL EQUIPMENT AND WIRING DEVICES WITH
PANELBOARD NAME AND CIRCUIT NUMBER. REFER TO
SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
3. INSTALL ALL DISCONNECT SWITCHES FURNISHED BY DIVISION 23.
107-1A-5
107-1AX-5
107-1AX-2
107-1AX-7
107-1A-4
XFMR-107-1A-4
SWBD
107-117-158
SWBD
107-RADI
LIGHTING
CONTROL
(ETR)
107-1AX-9
(RELOCATE)
(NEW)
(NEW)
(NEW)
(NEW)
(EXISTING)
NEW ELEC.
(NEW)
(NEW)
M
IN
3' - 0"
3' - 9 5/8"
M
IN
COMMS
107-1AX-6
PACS
107-1AX-6 - 3
107-1AX-6 - 5
(NEW)
107-1AX-6 - 1
107-1AX-6 - 7
Drawing Number
Project Number
Date
Project Title
Building NumberLocation
Checked DrawnAPPROVED: CHIEF ENGINEER
Drawing Title
VA FORM
Office of Construction and Facilities Management
Dwg
CIVIL / STRUCTURAL ENGINEER M.E.P. / T. ENGINEER
APPROVED: DIRECTOR
APPROVED: ASSOCIATE DIRECTOR
APPROVED: ASSISTANT DIRECTOR APPROVED: CHIEF ENGINEER
REVISIONS DATE
CONSULTANTS ARCHITECT
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
H2B
1225 NORTH LOOP WEST, SUITE 900
HOUSTON, TX 77008
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
AZ ARCH REG. NO. 20013-0, EXP. 10/10/2019
AZ ENGR REG. NO. 20015-0, EXP. 10/10/2019
F U
L L Y
S P
R
IN
K L E
R E
D
RADIOLOGY EXPANSIONELECTRICAL PARTIAL FLOOR
PLANS
649-413
11/01/2018 JGW ABM
107-E-401
100% CONSTRUCTION DOCUMENTS
DEPARTMENT OF VETERAN AFFAIRS
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 HWY 89N
PRESCOTT AZ, 86313
123 -OF- 148
N 1/4" = 1'-0"
NEW ELEC. ROOM 103
PARTIAL FLOOR PLAN
1/4" = 1'-0"
COMMS ROOM 116
PARTIAL FLOOR PLAN
N
ELECTRICAL PLAN NOTES:
1. PROVIDE 4" HIGH CONCRETE HOUSEKEEPING PAD WITH
DIMENSIONS SHOWN. PROVIDE MINIMUM 3'-0" CLEAR IN FRONT OF
PANELBOARD 107-1A-5.
2. RECONNECT EXISTING IT ROOM EQUIPMENT CIRCUITS. FIELD
VERIFY EQUIPMENT TO REMAIN. UPDATE PANELBOARD SCHEDULE
AT COMPLETION OF PROJECT.
| 114_107-E-000 Electrical Legend |
| 115_107-ES101 Electrical Site Plan |
| 116_107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 117_107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 118_107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 119_107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 120_107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| Sheets |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 121_107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| Sheets |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 122_107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 123_107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 124_107-E-501 Electrical Details |
| 135_107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 136_107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 137_107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| Sheets |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 138_107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 139_107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 140_107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 141_107-TY-101 - SECURITY FIRST FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 142_107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 145_107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 146_107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
| 147_107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| Sheets |
| 107-E-401 - ELECTRICAL PARTIAL FLOOR PLANS |
| 107-EL-100 - ELECTRICAL LIGHTING BASEMENT FLOOR PLAN |
| 107-EL-101 - ELECTRICAL LIGHTING FIRST FLOOR PLAN |
| 107-ELD101 - ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN |
| 107-EP-100 - ELECTRICAL POWER BASEMENT FLOOR PLAN |
| 107-EP-101 - ELECTRICAL POWER FIRST FLOOR PLAN |
| 107-EP-102 - ELECTRICAL POWER ROOF FLOOR PLAN |
| 107-EPD101 - ELECTRICAL POWER DEMOLITION FLOOR PLAN |
| 107-FA-100 - FIRE ALARM BASEMENT FLOOR PLAN |
| 107-FA-101 - FIRE ALARM FIRST FLOOR PLAN |
| 107-FAD101 - FIRE ALARM DEMOLITION PLAN |
| 107-T-401 - TECHNOLOGY ENLARGED FLOOR PLANS |
| 107-TD-101 - TECHNOLOGY DEMOLITION FIRST FLOOR PLAN |
| 107-TI-101 - INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN |
| 107-TM-101 - NURSE CALL FIRST FLOOR PLAN |
| 107-TN-100 - COMMUNICATIONS BASEMENT FLOOR PLAN |
| 107-TN-101 - COMMUNICATIONS FIRST FLOOR PLAN |
| 107-TY-100 - SECURITY BASEMENT FLOOR PLAN |
| 107-TY-101 - SECURITY FIRST FLOOR PLAN |
File details come from the government source that posted it. Updated .