This notice provides details for an upcoming federal construction contract opportunity. The Department of Veterans Affairs intends to solicit fixed-price bids for a Radiology Expansion project at the Northern Arizona VA Medical Center. The scope of work involves renovating and expanding an existing radiology area to optimize workflow and accommodate new equipment. Improvements include a centralized waiting room, wider hallways, and adequately sized rooms. The project also requires ground-level access throughout Radiology and infrastructure to support a future second-floor addition. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and issued on August 8th, with all bids due on the specified due date. The construction value is estimated between $5-10 million. The period of performance is approximately 425 days from notice to proceed. Questions must be submitted in writing to the identified point of contact.
36E77619B0012 Attachment 11 - Struct and Arch Dwgs.pdf
View the file
Other files
Show 40 more
Latest 50 of 59 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES:
1. THE STRUCTURAL DRAWINGS AND SPECIFICATIONS ARE A PORTION
OF THE CONSTRUCTION DOCUMENTS. THE CONTRACTOR AND
SUBCONTRACTORS SHALL REFERENCE AND COORDINATE WITH ALL
OTHER DISCIPLINES' DRAWINGS. ANY DISCREPANCIES OR OMISSIONS
SHALL BE REPORTED TO THE STRUCTURAL ENGINEER AND
ARCHITECT.
2. DESIGN CRITERIA:
A. CODES AND SPECIFICATIONS:
1. GENERAL BUILDING CODE: INTERNATIONAL BUILDING CODE,
2012 EDITION.
2. CONCRETE: BUILDING CODE REQUIREMENTS FOR
STRUCTURAL CONCRETE, AMERICAN CONCRETE INSTITUTE,
ACI 318-11.
3. STRUCTURAL STEEL: SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION,
AISC 360-14.
4. STEEL DECK: STEEL DECK INSTITUTE DESIGN MANUAL FOR
COMPOSITE DECKS, FORM DECKS, ROOF DECKS AND
CELLULAR METAL FLOOR DECK WITH ELECTRICAL
DISTRIBUTION.
5. COLD FORMED STEEL: NORTH AMERICAN SPECIFICATION FOR THE
DESIGN OF COLD FORMED STEEL STRUCTURAL MEMBERS S100-12.
6. UNIFIED FACILITIES CRITERIA: DESIGN OF BUILDINGS TO RESIST
PROGRESSIVE COLLAPSE, DEPARTMENT OF DEFENSE, 2003 WITH
UPDATED CHANGES OF 2016.
7. U.S. DEPARTMENT OF VETERANS AFFAIRS PHYSICAL SECURITY
DESIGN MANUAL FOR MISSION CRITICAL FACILITIES, 2015 EDITION.
B. DESIGN LOADS:
1. DEAD LOADS: ANY CHANGES IN CONSTRUCTION MATERIALS FROM
THOSE SHOWN ON THE ARCHITECTURAL OR STRUCTURAL
DRAWINGS SHALL BE REPORTED BY THE CONTRACTOR TO THE
STRUCTURAL ENGINEER FOR VERIFICATION OF LOAD-CARRYING
CAPACITY OF THE STRUCTURE.
2. LIVE LOADS:
ROOF ----------------------------------------------------------- 20 PSF
STAIRS, EXITWAYS ---------------------------------------100 PSF
CLINICAL SPACE---- --------------------------------------- 80 PSF
PARTITION ---------------------------------------------------- 20 PSF
CORRIDORS ------------------------------------------------ 100 PSF
LOBBIES ----------------------------------------------------- 100 PSF
LIGHT STORAGE ------------------------------------------150 PSF
MECHANICAL -----------------------------------------------150 PSF
FUTURE FLOORS -----------------------------------------100 PSF
LIVE LOAD REDUCTIONS HAVE BEEN APPLIED IN ACCORDANCE
WITH THE BUILDING CODE, UNLESS NOTED.
ARCHITECTURAL BARRIER ACT
ITEM REQUIRED CAPACITY
GRAB BAR ------------------------------------250 POUNDS ANY DIRECTION
TUB OR SHOWER SEAT------------------250 POUNDS ANY DIRECTION
FASTENER & MOUNTING DEVICES--250 POUNDS ANY DIRECTION
3. WIND LOADS:
BASIC WIND SPEED (3 - SECOND GUST) -------- 120 MPH
WIND IMPORTANCE FACTOR (IW) -------------------- 1.0
BUILDING CATEGORY --------------------------------------- IV
WIND EXPOSURE CATEGORY -------------------------- C
INTERNAL PRESSURE COEFFICIENT ------------- ±0.18
WALL COMPONENTS AND CLADDING (EFFECTIVE WIND AREA 50 SF)
INTERIOR ZONE ------------------------------------------ 26 PSF
CORNER ZONE -------------------------------------------- 30 PSF
5’-8” FEET FROM EACH CORNER
ROOF NET UPLIFT (EFFECTIVE WIND AREA 50 SF)
INTERIOR ZONE ------------------------------------------- 25 PSF
EXTERIOR ZONE ------------------------------------------ 35 PSF
CORNER ZONE -------------------------------------------- 40 PSF
5’-8” FEET FROM EACH CORNER
4. SEISMIC LOADS:
SEISMIC IMPORTANCE FACTOR (I) ---------------- 1.5
BUILDING CATEGORY ----------------------------------- IV
MAPPED SPECTRAL RESP ACCEL (Ss/S1) ------ 0.304g/0.089g
SITE CLASS ------------------------------------------------- C
SPECTRAL RESPONSE COEFF (Sds/Sd1) -------- 0.243g/0.1g
SEISMIC DESIGN CATEGORY ------------------------ C
SEISMIC FORCE RESISTING SYSTEM ------------- R=3, STEEL, OMRS
DESIGN BASE SHEAR ---------------------------------- 117K (ELF AND LRFD)
SEISMIC RESPONSE COEFF (Cs) ------------------- 0.887
RESPONSE MODIFICATION FACTOR (R) --------- 3.0
ANALYSIS PROCEDURE -------------------------------- ELF
5. ROOF SNOW LOADS:
GROUND SNOW LOAD (Pg) ---------------------------- 30 PSF FLAT ROOF SNOW LOAD (Pf) ------------------------- 36 PSF SNOW EXPOSURE FACTOR (Ce) --------------------- 1.0
SNOW LOAD IMPORTANCE FACTOR (IS) ----------- 1.2
THERMAL FACTOR (Ct) ---------------------------------- 1.0
6. BLAST LOADS:
PERIMETER WALLS
DESIGN LEVEL VEHICLE THREAT --------------------- W1
STANDOFF DISTANCE ------------------------------------- 50 FT
EXTERIOR DOORS AND WINDOWS
IMPULSE -------------------------------------------- 50.716 PSI-MS
PRESSURE ----------------------------------------------- 13.406 PSI
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SITE CONDITIONS
PRIOR TO FABRICATION/CONSTRUCTION. NOTIFY STRUCTURAL
ENGINEER AND ARCHITECT OF ANY DISCREPANCIES PRIOR TO
FABRICATION/CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR
ALL WORK FITTING AS INTENDED BY THE DRAWINGS AND
SPECIFICATIONS.
4. INSPECTIONS/OBSERVATIONS:
A. SPECIAL INSPECTIONS ARE REQUIRED FOR THIS PROJECT IN
ACCORDANCE WITH INTERNATIONAL BUILDING CODE. REFER TO
PROJECT SPECIFICATIONS AND DRAWINGS.
B. STRUCTURAL OBSERVATION BY STRUCTURAL ENGINEER'S OFFICE.
1. STRUCTURAL OBSERVATION IS VISUAL OBSERVATION OF THE
INPLACE STRUCTURE FOR GENERAL CONFORMANCE TO THE
APPROVED CONSTRUCTION DOCUMENTS AT THE TIME OF THE
OBSERVATION.
2. CONTRACTOR SHALL NOTIFY STRUCTURAL ENGINEER AND
ARCHITECT, PER THE SCHEDULE STATED BELOW, WHEN SUCH
ITEMS HAVE PROGRESSED TO THE POINT WHERE THEY WILL BE
IN PLACE AND READY FOR REVIEW. FAILURE TO NOTIFY MAY
REQUIRE REMOVAL OF COMPLETED CONSTRUCTION.
NOTIFY PRIOR TO THE REQUIRED DAYS
FOLLOWING SCHEDULED TASKS NOTIFICATION
FIRST FOUNDATION POUR ---------------------------------- 7 DAYS
FIRST SLAB ON GRADE POUR ----------------------------- 7 DAYS
LEVEL 2 ELEVATED SLAB POUR -------------------------- 7 DAYS
COVERING METAL ROOF DECK --------------------------- 7 DAYS
C. OBSERVATION BY THE STRUCTURAL ENGINEER'S OFFICE DOES
NOT REPLACE INSPECTIONS AND TESTING BY THE TESTING
AGENCY OR SPECIAL INSPECTOR.
5. SUBMITTALS:
A. REVIEW OF SHOP DRAWINGS AND OTHER SUBMITTALS BY THE
STRUCTURAL ENGINEER DOES NOT RELIEVE THE CONTRACTOR OF THE
RESPONSIBILITY TO REVIEW AND CHECK SHOP DRAWINGS BEFORE
SUBMITTING TO THE STRUCTURAL ENGINEER. THE CONTRACTOR
REMAINS SOLELY RESPONSIBLE FOR ERRORS AND OMISSIONS
ASSOCIATED WITH THE PREPARATION OF SHOP DRAWINGS AS THEY
PERTAIN TO MEMBER SIZES, DETAILS, AND DIMENSIONS SPECIFIED IN
THE CONTRACT DOCUMENTS. ALL SHOP DRAWINGS MUST BE STAMPED
BY THE CONTRACTOR PRIOR TO SUBMITTAL.
B. FABRICATORS AND SUPPLIERS SHALL CLEARLY NOTE AND HIGHLIGHT
CHANGES MADE IN SHOP DRAWINGS, WHICH DO NOT COMPLY WITH
THE CONTRACT DOCUMENTS.
C. SUBMIT ALL SHOP DRAWINGS VIA APPROVED METHOD. A COPY WILL
BE RETURNED TO THE CONTRACTOR. ALL PRINTS REQUIRED BY THE
CONTRACTOR ARE THE RESPONSIBILITY OF THE CONTRACTOR AND
SHALL BE MADE AFTER APPROVED SHOP DRAWINGS ARE
RETURNED. IF ADDITIONAL PRINTS ARE SUBMITTED, THEY WILL BE
RETURNED UNMARKED.
D. SHOP DRAWINGS: THE CONTRACTOR SHALL SUBMIT FOR STRUCTURAL
ENGINEER REVIEW SHOP DRAWINGS FOR THE FOLLOWING ITEMS.
ITEMS MARKED (*) SHALL HAVE SHOP DRAWINGS SEALED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE IN WHICH THE
PROJECT IS LOCATED. ITEMS MARKED (#) SHALL BE SUBMITTED FOR
STRUCTURAL ENGINEER'S RECORD ONLY.
1. STRUCTURAL STEEL (*)
2. CONCRETE REINFORCING
3. STEEL STAIRS (*, #)
4. STEEL DECK
5. CONCRETE MIX DESIGNS
6. CONSTRUCTION JOINT LOCATIONS IN STRUCTURAL FLOORS.
7. ELEVATORS (#)
8. COLD FORMED METAL FRAMING (*, #)
9. EXTERIOR DOORS AND WINDOWS
a. INCLUDE APPLICABLE SPECIFICATION REQUIREMENTS
FROM SPECIFICATION 085653 FOR EXTERIOR DOORS
E. DESIGN CALCULATIONS: THE CONTRACTOR SHALL SUBMIT FOR
STRUCTURAL ENGINEER'S RECORD, DESIGN CALCULATIONS SEALED BY
A PROFESSIONAL ENGINEER REGISTERED IN THE STATE IN WHICH THE
PROJECT IS LOCATED FOR THE FOLLOWING ITEMS.
1. STRUCTURAL STEEL CONNECTIONS AS NOTED IN CONSTRUCTION
DOCUMENTS (*, #)
2. STEEL STAIRS (*, #)
3. COLD FORMED METAL FRAMING (*, #)
4. EXTERIOR DOORS AND WINDOWS
a. DESIGN CALCULATIONS TO BE PREPARED BY A QUALIFIED
BLAST CONSULTANT AND REGISTERED PROFESSIONAL
ENGINEER OF THE STATE IN WHICH THE PROJECT IS LOCATED
6. ALL DETAILS SHOWN ARE TYPICAL. SIMILAR DETAILS APPLY TO SIMILAR
CONDITIONS, UNLESS NOTED.
7. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON
FRAMED FLOORS/ROOFS. IT IS THE CONTRACTOR'S RESPONSIBILITY
TO ENSURE THAT LOADS DO NOT EXCEED THE DESIGN LIVE LOAD.
8. COLUMNS, BEAMS, JOISTS, OR TRUSSES SHALL NOT BE FIELD CUT OR
TRIMMED FOR ANY REASON WITHOUT THE WRITTEN APPROVAL OF THE
ARCHITECT/ENGINEER.
9. HOLES, PIPES, SLEEVES, ETC. NOT SHOWN ON THE DRAWINGS MUST BE
REVIEWED BY THE ARCHITECT/ENGINEER BEFORE PLACEMENT
THROUGH STRUCTURAL MEMBERS.
10. IF MECHANICAL AND ELECTRICAL EQUIPMENT SIZES, WEIGHTS, OR
LOCATIONS DO NOT COINCIDE WITH EQUIPMENT SHOWN ON THE
PLANS, COORDINATE ADJUSTMENTS WITH THE ARCHITECT/ENGINEER.
11. BEAMS, COLUMNS, WALLS AND FOOTING CENTERS SHALL BE
CENTERED UNDER SUPPORTING MEMBERS (TYPICAL UNLESS NOTED
OTHERWISE).
12. CRANES, CONCRETE TRUCKS AND ALL OTHER HEAVILY LOADED
VEHICLES ARE NOT TO BE DRIVEN ACROSS GRADE BEAMS OR BUILDING
SLABS.
13. IF DISCREPANCIES EXIST BETWEEN STRUCTURAL PLANS,
ARCHITECTURAL PLANS, OTHER PLANS OR SPECIFICATIONS, THE
CONTRACTOR OR SUBCONTRACTOR SHALL PROVIDE WRITTEN
REQUEST FOR CLARIFICATION FROM THE ARCHITECT AND/OR
ENGINEER PRIOR TO PROCEEDING WITH THE WORK.
14. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS
REPRESENT THE FINISHED STRUCTURE, AND, EXCEPT WHERE
SPECIFICALLY SHOWN, DO NOT INDICATE THE METHOD OR MEANS OF
CONSTRUCTION. THE CONTRACTOR SHALL SUPERVISE AND DIRECT
THE WORK AND SHALL BE SOLELY RESPONSIBLE FOR ALL
CONSTRUCTION MEANS, METHODS, PROCEDURES, TECHNIQUES, AND
SEQUENCE.
15. THE STRUCTURE HAS BEEN DESIGNED TO RESIST DESIGN LOADS ONLY
AS A COMPLETED STRUCTURE. APPLICATIONS OF CONSTRUCTION
LOADS TO THE PARTIALLY COMPLETED STRUCTURE SHALL BE
CONSIDERED BY THE CONTRACTOR AND SO INCLUDED IN THE DESIGN
OF SHORING, BRACING, FORMWORK, AND ANY OTHER SUPPORTING
ELEMENTS PROVIDED FOR CONSTRUCTION OF THE STRUCTURE.
DURING ERECTION AND UNTIL ALL PERMANENT CONNECTIONS ARE
MADE, THE CONTRACTOR MUST PROVIDE TEMPORARY BRACING TO
BRACE THE STRUCTURE IN ALL DIRECTIONS.
16. THE ENGINEER SHALL NOT HAVE CONTROL OR CHARGE OF, AND SHALL
NOT BE RESPONSIBLE FOR, CONSTRUCTION MEANS, METHODS,
TECHNIQUES, SEQUENCES, OR PROCEDURES FOR CONSTRUCTION OR
SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE
WORK, FOR THE ACTS OR OMISSION OF THE CONTRACTOR,
SUBCONTRACTOR, OR ANY OTHER PERSONS PERFORMING ANY OF THE
WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE
WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
17. THE STRUCTURE AND FOUNDATIONS ARE NOT DESIGNED FOR FUTURE
EXPANSION.
18. TYPICAL DETAILS ARE SHOWN ON SHEETS DESIGNATED “SS-030 AND
SS-050”. THE INCLUDED TYPICAL DETAILS MAY OR MAY NOT BE CUT/
REFERENCED ON PLANS OR SECTIONS, BUT ARE TO BE USED AS
APPLICABLE.
19. NOTE THAT THE GROUND FLOOR SLAB IS A GROUND SUPPORTED SLAB
AT GRADE AS PER THE DESIGN RECOMMENDED IN THE GEOTECHNICAL
REPORT. IT IS NOT A STRUCTURAL SLAB AND AS SUCH IT IS NOT
DESIGNED FOR ANY EXTERNAL UPWARD OR DOWNWARD LOADS. IT IS
INTENDED TO BE ENTIRELY SUPPORTED BY THE PREPARED GROUND
UNDER THE SLAB. THE CONTRACTOR SHOULD NOTE THAT THE
PERFORMANCE OF THE SLAB AS DESIGNED AND INTENDED BY THE
GEOTECHNICAL ENGINEER IS HIGHLY DEPENDENT ON HOW WELL THE
CONTRACTOR FOLLOWS THE SITE PREPARATION INSTRUCTIONS IN THE
GEOTECHNICAL REPORT. THE ARCHITECT SHALL ADVISE THE OWNER
THAT THE PERFORMANCE OF THE SLAB INVOLVES SOME RISKS AND IS
DEPENDENT ON MANY ENVIRONMENTAL CONDITIONS OVER WHICH THE
OWNER HAS CONTROL OF AFTER OCCUPANCY OF THE BUILDING. THE
CONTRACTOR AND THE OWNER SHOULD CONSULT WITH THE
GEOTECHNICAL ENGINEER IF THERE ARE ANY QUESTIONS
CONCERNING CONSTRUCTION, PERFORMANCE AND RISKS INVOLVED IN
GROUND SUPPORTED SLAB AT GRADE CONSTRUCTION.
20. THIS PROJECT CONSISTS OF A MODIFICATION TO AN EXISTING
BUILDING. INFORMATION ON EXISTING CONDITIONS HAS BEEN
TAKEN FROM THE ORIGINAL DESIGN DRAWINGS AND SHOWN
ON THESE DRAWINGS. THESE DRAWINGS WERE ASSUMED TO
BE "AS-BUILT" DRAWINGS SINCE EXISTING CONDITIONS WERE
NOT ACCESSIBLE OR SINCE FIELD OBSERVATION OF EXISTING
CONDITIONS IS BEYOND THE ENGINEER'S SCOPE OF WORK
DURING THE DESIGN PHASE OF THIS PROJECT. THE ACCURACY
OF THIS INFORMATION HAS NOT BEEN VERIFIED. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO VERIFY ALL EXISTING
DIMENSIONS SHOWN ON THESE DRAWINGS AND TO VERIFY THE
LOCATION OF ALL FRAMING MEMBERS AND OTHER
OBSTRUCTIONS WHICH WILL AFFECT THE WORK. AS PART OF
THIS WORK THE CONTRACTOR SHALL PREPARE AN ACCURATE
FIELD SURVEY OF THE LOCATION OF ALL STRUCTURAL MEMBERS
IN THE WORK AREA PRIOR TO BEGINNING SHOP DRAWINGS AND
CONSTRUCTION. THIS SURVEY SHALL BE SUBMITTED TO THE
ARCHITECT WITH VARIANCES NOTED. CLAIMS FOR ADDITIONAL
TIME OR EXTRA COST DUE TO OBSTRUCTIONS AND VARIANCES
IN THE LOCATION OF THE STRUCTURAL MEMBERS WILL NOT BE
HONORED AFTER WORK HAS BEGUN ON THE PROJECT.
EARTHWORK AND FOUNDATION:
1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING
CONDITIONS IN THE FIELD PRIOR TO COMMENCING ANY WORK.
2. CONTRACTOR SHALL NOTIFY OWNER’S REPRESENTATIVE SHOULD ANY
DIMENSIONS OR CONDITIONS VARY FROM THE INTENT OF THE
DRAWINGS.
3. IN AREAS WHERE THERE IS VEGETATION, CONTRACTOR SHALL SCALP
VEGETATION COMPLETELY TO A DEPTH OF 8 INCHES DEEP AT
LEAST FIVE FEET BEYOND THE BUILDING EDGES. STRIPPED MATERIAL
CLASSIFIED AS TOPSOIL SHALL BE STOCKPILED FOR REUSE. OTHER
STRIPPED MATERIAL SHALL BE HAULED OFF OR SPREAD ON SITE AS
DIRECTED BY OWNER.
4. GRADE THE SITE TO PROVIDE POSITIVE DRAINAGE AWAY FROM ALL
BUILDINGS AND SLABS. WATER SHALL NOT BE ALLOWED TO POND
ADJACENT TO OR DRAIN TOWARDS THE BUILDINGS OR SLABS.
5. CONTRACTOR SHALL PROOF ROLL THE SUBGRADE SURFACE TO
DETERMINE LOCATION OF SOFT OR LOOSE SOILS WHICH MUST BE
REMOVED AND REPLACED WITH SELECT FILL.
6. CONTRACTOR SHALL SCARIFY SUBGRADE TO A MINIMUM DEPTH OF 10
INCHES THEN RECOMPACT TO A MINIMUM OF 95 PERCENT OF THE
MAXIMUM DRY DENSITY AS DETERMINED BY THE STANDARD PROCTOR
DENSITY TEST (ASTM D-698). THE MOISTURE CONTENT SHALL RANGE
BETWEEN 0 TO +3 PERCENT OF OPTIMUM MOISTURE CONTENT.
7. STRUCTURAL SELECT FILL SHALL MEET THE SOIL GRADATION LISTED IN
THE GEOTECHNICAL REPORT AND HAVE MAXIMUM PLASTICITY INDEX
(P.I.) OF 10. SELECT FILL SHALL BE PLACED IN MAXIMUM 10 INCH LOOSE
LIFTS AND COMPACTED TO A MINIMUM OF 95 PERCENT OF THE
MAXIMUM DRY DENSITY AS DETERMINED BY THE STANDARD PROCTOR
DENSITY TEST (ASTM D- 698). THE MOISTURE CONTENT SHALL RANGE
BETWEEN 0 TO +3 PERCENT OF OPTIMUM MOISTURE CONTENT.
8. SAND SHALL BE CLEAN, SHARP GRANULAR TYPE, LOCALLY AVAILABLE
AND EASILY COMPACTED FREE OF VEGETATION OR OTHER
DELETERIOUS MATERIAL.
9. FOUNDATION WALL BACKFILL SHALL NOT BE UNBALANCED BY MORE
THAN TWO FEET ON EITHER SIDE AT ANY TIME. BASEMENT WALL AND
RESTRAINED RETAINING WALL BACKFILL SHALL NOT BE PLACED,
UNLESS THE WALL IS ADEQUATELY BRACED. RETAINING WALL AND
BASEMENT WALL BACKFILL SHALL BE FREE DRAINING GRANULAR
BACKFILL ACCEPTABLE TO THE GEOTECHNICAL ENGINEER.
10. ALL FORMWORK SHALL BE PLACED AND SHORED, ALL REINFORCING
STEEL SET AND TIED, ALL CONCRETE PLACED, FINISHED AND CURED
PER THE AMERICAN CONCRETE INSTITUTE LATEST EDITION AND PER
ALL SAFETY PROCEDURES OF THE OCCUPATIONAL SAFETY AND
HEALTH ACT (OSHA).
11. REINFORCING STEEL SHALL BE SET AND CONCRETE PLACED IN PIERS
IMMEDIATELY AFTER DRILLING AND INSPECTION. UNCLEAN SHAFT
BOTTOMS OR SLOUGHED SIDES OF SHAFTS WILL BE CAUSE FOR -
REJECTION.
12. CONTRACTOR SHALL HAND TAMP BOTTOM OF GRADE BEAM
EXCAVATIONS TO A HARD SURFACE BEFORE PLACING REINFORCING
STEEL.
13 . FOUNDATION CONTRACTOR TO ENSURE PROPER ANCHOR ROD
PROJECTION AND THAT ANCHOR RODS ARE HELD SECURELY IN
POSITION PRIOR TO CONCRETE PLACEMENT. STRUCTURAL STEEL
COLUMN ANCHOR RODS SHALL BE SET WITH A TEMPLATE.
14. REINFORCING STEEL SHALL BE LAP SPLICED A MINIMUM OF 42 BAR
DIAMETERS. MINIMUM 10-FOOT LONG CORNER BARS BENT 90-DEGREES
SHALL BE PROVIDED AT ALL GRADE BEAM CORNERS, 5-FEET EACH LEG.
MINIMUM REINFORCING STEEL COVER SHALL BE PROVIDED AS
FOLLOWS:
3” WHERE CONCRETE CONTACTS EARTH
1 ½” WHERE CONCRETE CONTACTS FORM
15. ALL CONCRETE SURFACES SHALL BE PROPERLY CURED AND
SUFFICIENT TIME ALLOWED BEFORE PERMITTING TRAFFIC OR
CONSTRUCTION TO PROCEED. A HARD STEEL TROWEL FINISH SHALL BE
PROVIDED ON ALL CONCRETE.
16. FOOTINGS SHALL BE POURED IMMEDIATELY UPON COMPLETION OF
EXCAVATION AND CLEANING OF FOOTING BEARING SURFACE. ALL
SPOILS FROM THE DRILLED FOOTING EXCAVATIONS SHALL BE
REMOVED FROM THE BUILDING PAD.
17. THIS FOOTING DESIGN IS BASED ON THE GEOTECHNICAL
INVESTIGATION (SOILS REPORT) SUPPLIED BY THE OWNER AND
COMPLETED BY ENGINEERING & TESTING CONSULTANTS INC, PROJECT
NUMBER 9710, DATED NOVEMBER 10,2017. THIS REPORT ASSUMES A
MAXIMUM ALLOWABLE BEARING PRESSURE OF 3,500 PSF FOR TOTAL
LOAD CONDITIONS. THIS BEARING PRESSURE IS FOUND AT A DEPTH OF
4 FEET BELOW EXISTING FINISHED GRADE.
18. PREPARED GRADE AREA UNDER ALL BUILDING SLABS AND GRADE
BEAMS SHALL BE COVERED WITH A 15 MIL WATER VAPOR BARRIER
MEETING THE REQUIREMENTS OF ASTM E 1745, CLASS C OR BETTER
AND SHALL A MAXIMUM WATER PERMEANCE OF 0.01 PERMS WHEN
TESTED IN ACCORDANCE WITH ASTM E96. THE WATER VAPOR BARRIER
SHALL BE INSTALLED AND LAPPED IN ACCORDANCE WITH THE
REQUIREMENTS OF ASTM E 1643. PENETRATIONS SHALL BE SEALED IN
STRICT ACCORDANCE WIT THE MANUFACTURER’S RECOMMENDATIONS
AND REQUIREMENTS.
19. FOUNDATION DETAILING SHOWN ON THE DRAWINGS IS BASED ON A
MINIMUM OF 5 FEET OF SELECT FILL MATERIAL THE FLOOR SLAB AND
EXTENDING 5’-0” MINIMUM BEYOND THE BUILDING.
20. ALL BACKFILL FOR BURIED PIPES AND CONDUIT WITHIN THE BUILDING
PAD AND EXTENDING OUT 5’-0” MINIMUM BEYOND THE BUILDING SHALL
BE BACKFILLED WITH SELECT FILL BACK FILL. DO NOT USE SAND
BACKFILL. A BENTONITE PLUG SHALL BE PROVIDED IN ALL UTILITY
TRENCHES AT THE FACE OF THE BUILDING FOUNDATION.
21. CONDUITS SHALL NOT BE PLACED IN THE CONCRETE SLAB. CONDUITS
SHALL BE PLACED IN THE SELECT FILL MATERIAL BENEATH THE VAPOR
BARRIER. ALL PENETRATIONS IN THE VAPOR BARRIER SHALL BE
SEALED IN STRICT ACCORDANCE WITH THE MANUFACTURER’S
RECOMMENDATIONS AND REQUIREMENTS.
22. SOIL BEARING TESTS SHALL BE PERFORMED BY A GEOTECHNICAL
ENGINEER PRIOR TO INSTALLING FOOTINGS TO ENSURE DESIGN
ALLOWABLE BEARING VALUES ARE MET. IF ACTUAL SITE CONDITIONS
DO NOT SATISFY THESE REQUIREMENTS, COORDINATE ADJUSTMENTS
WITH ARCHITECT/ENGINEER/GEOTECHNICAL ENGINEER.
23. PROVIDE A TREMIE TO PLACE CONCRETE IN DRILLED FOOTINGS SO
THAT CONCRETE DOES NOT FREE FALL OVER 10’-0”.
24. PROVIDE PIER SLEDS TO MAINTAIN 3” MINIMUM CLEAR COVER ON
FOOTING SHAFT REINFORCING. PIER SLEDS SHALL BE STAGGERED
ALONG THE VERTICAL REINFORCING. DO NOT PLACE SLEDS AT THE
SAME LOCATION.
25. QUALITY CONTROL TESTING IS FOR THE OWNER'S BENEFIT AND FOR
HIS ACCOUNT. THE FREQUENCIES AND TYPES OF TESTING SHALL BE
DIRECTED BY THE OWNER OR HIS AGENT IN FULL COOPERATION WITH
AND WITH PRIOR ANNOUNCEMENT TO THE CONTRACTOR.
CONCRETE:
1. CONCRETING OPERATIONS SHALL COMPLY WITH ACI STANDARDS.
2. CONCRETE COMPRESSIVE STRENGTH AT 28 DAYS (PSI), TYPE OF
CONCRETE, MAXIMUM W/C (WATER/CEMENTITIOUS MATERIALS RATIO),
AIR CONTENT, SLUMP AND CONCRETE USE:
STRENGTH TYPE W/C AIR SLUMP USE
3000 NORMAL WT. 0.52 ------- 3"-5" SPREAD FOOTINGS
3000 NORMAL WT. 0.52 4-6% 3"-5" CONCRETE ON
METAL DECK
NORMAL WT. 3"-5" SLAB ON GRADE,
GRADE BEAMS,
PIT WALLS,
SUMP PIT
NORMAL WT.
0.45 3%
3"-5" FOUNDATION WALL4500 0.45 4-5%
3. ALL CONCRETE MIX DESIGNS SHALL HAVE WATER TO CEMENT RATIOS
LESS THAN 0.52, WITH A MAXIMUM 60/40 FINE TO COARSE AGGREGATE
RATIO. CONCRETE MIX DESIGNS THAT DO NOT CONFORM TO THE
ABOVE STANDARD AND/OR CONTAIN WATER REDUCING ADMIXTURES
SHALL BE SUBMITTED WITH APPROPRIATE TEST DATA PER ACI
STANDARDS. ALL CONCRETE SHALL BE IN CONFORMANCE WITH THE
LATEST ACI 301 STANDARD PUBLICATION.
A. LIGHTWEIGHT CONCRETE SHALL HAVE A MINIMUM DRY UNIT WEIGHT
OF 115 PCF.
4. EXTERIOR CONCRETE (FLOOR SLABS, WALLS, ETC) SHALL HAVE 6%
(PLUS/MINUS 1%) ENTRAINED AIR.
5. CHAMFER ALL EXPOSED CONCRETE EDGES ¾” (VERIFY WITH
ARCHITECT).
6. NO ALUMINUM SHALL BE EMBEDDED IN ANY CONCRETE.
7. NO CALCIUM CHLORIDE SHALL BE USED IN CONCRETE.
8. CONTRACTOR SHALL COORDINATE ALL CURING COMPOUNDS WITH
FLOOR FINISH REQUIREMENTS TO ENSURE COMPATIBILITY.
9. THE DESIGN, CONSTRUCTION AND SAFETY OF ALL FORMWORK IS THE
RESPONSIBILITY OF THE CONTRACTOR.
10. ALL CONCRETE IS REINFORCED UNLESS SPECIFICALLY NOTED AS
UNREINFORCED. REINFORCE ALL CONCRETE NOT OTHERWISE SHOWN
WITH THE SAME REINFORCING AS SIMILAR SECTIONS OR AREAS.
11. CONSTRUCTION JOINTS IN GRADE BEAMS, CONTINUOUS FOOTINGS,
AND ALL WALLS THAT DO NOT CHANGE DIRECTION SHALL BE SPACED
NO GREATER THAN 60’-0”. INTERMEDIATE CONTROL JOINTS SHALL BE
SPACED AT 25’-0” MAX FOR WALLS. CONTROL JOINTS IN WALLS SHALL
ALSO BE LOCATED 15’-0” FROM CORNERS AND AT CHANGES IN WALL
THICKNESS.
12. WHERE FRESH CONCRETE IS DEPOSITED AGAINST HARDENED
CONCRETE (GREATER THAN 8 HRS OLD), CLEAN EXISTING SURFACE OF
LAITANCE AND FOREIGN MATERIAL AND DAMPEN THE EXISTING
SURFACE. IF REQUIRED, ROUGHEN EXISTING CONCRETE TO ¼”
AMPLITUDE.
13. SAW CUT JOINTS OR KEYED CONSTRUCTION JOINTS IN SLABS ON
GRADE SHALL BE SPACED TO DIVIDE THE SLAB INTO PANELS NOT TO
EXCEED 225 SQUARE FEET. THE LONGER DIMENSION OF EACH PANEL
SHALL NOT EXCEED THE SHORTER DIMENSION BY MORE THAN 20%.
JOINTS SHALL BE LOCATED AT COLUMN CENTERLINES WHERE
POSSIBLE. CONTRACTOR SHALL SUBMIT JOINT LAYOUT TO ARCHITECT
FOR APPROVAL. REFER TO TYPICAL DETAIL 10/SS-030.
14. REINFORCING BARS: ASTM A615 GRADE 60.
15. WELDED WIRE REINFORCEMENT (WWR): ASTM A185. MINIMUM LAP AND
EMBEDMENT TO BE THE GREATER OF ONE CROSS WIRE SPACING PLUS
2" OR 8". PROVIDE FLAT SHEETS ONLY, NO ROLLS.
16. REINFORCING STEEL SHOWN IN SECTIONS AND DETAILS ARE A
SCHEMATIC INDICATION THAT REINFORCING EXISTS. SEE SCHEDULES,
SECTION NOTES AND GENERAL NOTES FOR ACTUAL REINFORCING
REQUIRED.
17. REINFORCING BAR PLACING ACCESSORIES SHALL BE IN ACCORDANCE
WITH ACI MANUAL OF STANDARD PRACTICE. WHERE CONCRETE IS
EXPOSED IN FINISHED BUILDING, PROVIDE ACCESSORIES WITH
RUSTPROOF LEGS. WHERE CONCRETE IS SAND-BLASTED OR BUSH-
HAMMERED, PROVIDE ACCESSORIES OF STAINLESS STEEL.
18. DETAIL REINFORCEMENT IN ACCORDANCE WITH ACI 315.
REINFORCEMENT SHALL NOT BE WELDED UNLESS NOTED OR
APPROVED BY THE STRUCTURAL ENGINEER.
19. ALL SPLICES SHALL BE CLASS "B" TENSION LAP SPLICE, UNLESS NOTED.
20. ALL REINFORCING MARKED "CONTINUOUS" SHALL BE SPLICED WITH
CLASS "B" TENSION LAP SPLICE, UNLESS NOTED. PROVIDE CORNER
BARS OF SAME SIZE AND SPACING.
21. MINIMUM CONCRETE WALL REINFORCING (WALL 10” OR GREATER)
SHALL BE #5 AT 10” CENTERS EACH WAY, EACH FACE.
22. MINIMUM REINFORCING AROUND CONCRETE WALL OPENINGS 2’-0” OR
GREATER (TYPICAL UNLESS NOTED OTHERWISE): 2-#5, EXTEND REINF
2’-0” PAST OPENINGS. PROVIDE 2-#5 x 4’-0” DIAGONAL BARS AT
CORNERS.
23. SLABS ON GRADE SHALL BE 5” THICK MINIMUM ON 4” OF GRANULAR
FILL. REINFORCE SLAB WITH #3 AT 14 INCHES ON CENTER EACH WAY
IN UPPER 1/3 OF SLAB THICKNESS. AT INTERIOR SLABS, A 15 MIL
WATER VAPOR BARRIER SHALL BE PLACED BETWEEN THE
CONCRETE AND GRANULAR BASE AND CARE SHOULD BE TAKEN
DURING CURING TO PREVENT SLAB CURLING. THIS NOTE SHALL BE
TYPICAL UNLESS NOTED OTHERWISE.
STRUCTURAL STEEL:
1. FABRICATE AND ERECT ALL STRUCTURAL STEEL IN ACCORDANCE WITH
AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND
BRIDGES".
2. THE STRUCTURAL STEEL FABRICATOR SHALL BE AN AISC QUALITY
CERTIFIED COMPANY FOR THE CATEGORY OF WORK IN THIS PROJECT
OR PROVIDE A QUALITY ASSURANCE PLAN AND SPECIAL INSPECTIONS
AS DEFINED IN THE CODE.
3. THE STEEL FRAME IS "NON-SELF-SUPPORTING". ADEQUATE
TEMPORARY SUPPORT MUST BE PROVIDED BY THE CONTRACTOR
UNTIL REQUIRED CONNECTIONS OR ELEMENTS ARE IN PLACE.
A. ALL LATERAL LOAD RESISTANCE AND STABILITY OF THE BUILDING IN
THE COMPLETED STRUCTURE IS PROVIDED AS FOLLOWS:
1. ROOF DIAPHRAGM: STEEL ROOF DECKING
2. COLLECTOR ELEMENTS/DRAG STRUTS: AS NOTED IN FRAMING
PLANS
3. LATERAL LOAD RESISTING SYSTEM: STEEL MOMENT FRAMES
4. STRUCTURAL STEEL: ASTM A992 FOR WIDE FLANGE BEAMS AND
COLUMNS; ASTM A992 FOR S, M AND HP SHAPES AND CHANNELS; ASTM
A36 FOR STIFFENER PLATES, BASE PLATES, COLUMN CAP PLATES,
BEAM CONNECTION PLATES AND STEEL ANGLES.
5. STEEL TUBING: ASTM A500, GRADE B.
6. WELDING SHALL CONFORM TO THE CURRENT AND APPLICABLE AWS
STANDARDS AND BE COMPLETED BY AN AWS CERTIFIED WELDER
A. AWS D1.1 – STRUCTURAL WELDING CODE – STEEL
B. AWS D1.3 – STRUCTURAL WELDING CODE – SHEET STEEL
C. AWS D1.6 – STRUCTURAL WELDING CODE – STAINLESS STEEL
7. WELD SIZES SHALL BE INCREASED TO MEET THE REQUIRED EFFECTIVE
THROAT WIDTH IF GAPS EXIST AT THE FAYING SURFACE.
8. WELDED CONNECTIONS: E70XX ELECTRODES, MINIMUM SIZE FILLET
WELD 3/16".
9. ALL MISCELLANEOUS WELDS (FIELD OR SHOP) SHALL BE MINIMUM SIZE
FILLET ALL AROUND IN ACCORDANCE WITH AISC. WELDING OF
CONTINUOUS MEMBER SHALL BE A MINIMUM OF 2 INCHES OF 3/16 INCH
FILLET STITCH WELDS AT 12 INCHES O.C. STAGGERED EACH SIDE,
UNLESS OTHERWISE NOTED. COLUMN BASE PLATES, CAP PLATES AND
STIFFENER PLATES SHALL BE WELDED ALL AROUND.
10. HEADED ANCHOR RODS: ASTM F1554 GRADE 36 OR GRADE 55 ANCHOR
AND HEAVY HEX NUT, AS INDICATED IN DETAILS.
11. SHEAR CONNECTORS: ASTM A108, GRADE 1015 THROUGH 1020,
HEADED-STUD TYPE, COLD FINISHED CARBON STEEL; AWS D1.1,
TYPE B.
12. HEADED STUDS SHALL BE 3/4" DIAMETER x 5 3/16".
13. PLACE THE NUMBER OF STUDS SHOWN ON PLAN AS FOLLOWS:
A. UNIFORM DISTRIBUTION: FOR BEAMS WHERE ONLY A TOTAL
NUMBER OF STUDS IS SPECIFIED, PLACE STUDS AT A UNIFORM
SPACING BETWEEN THE ENDS OF THE BEAM.
B. SEGMENTED DISTRIBUTION: FOR BEAMS SUPPORTING OTHER
BEAMS, WITH STUDS NOTED BETWEEN BEAM REACTIONS AND/OR
THE ENDS OF THE BEAM, PLACE STUDS AT A UNIFORM SPACING
BETWEEN BEAM REACTIONS AND.OR THE BEAM ENDS.
14. HEADER STUDS SHALL BE PLACED IN A SINGLE ROW WHERE POSSIBLE.
WHERE ADDITIONAL STUDS ARE REQUIRED BEYOND THOSE THAT CAN
BE PLACED IN A SINGLE ROW, PLACE STUDS IN PAIRS STARTING
TOWARDS THE NEAREST END OF THE BEAM, REFER TO STUD
PLACEMENT DIAGRAM 2/SS-050. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR DETERMINING THE PROPER HEADED STUD LAYOUT
FOR EACH BEAM PRIOR TO INSTALLATION OF THE STUDS IN THE FIELD.
15. FOR BEAMS WITH MINIMUM STUDS CALLED OUT ON PLAN, PROVIDE THE
MINIMUM NUMBER OF STUDS AS REQUIRED PER THE MAXIMUM STUD
SPACING REQUIREMENTS SHOWN ON THE SHEAR STUDS PLACEMENT
DIAGRAM.
16. BOLTED CONNECTIONS: BEARING TYPE A325-N IN ACCORDANCE WITH
AISC "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR
A490 BOLTS". BOLTS THROUGH 4" WIDE BEAM FLANGES SHALL BE 5/8"
DIAMETER. OTHER BOLTS SHALL BE 3/4" DIAMETER. USE SNUG TIGHT
BEARING CONNECTIONS FOR ALL BOLTED CONNECTIONS.
17. BOLTS SHOWN IN SECTIONS AND DETAILS ARE A SCHEMATIC
INDICATION THAT BOLTS MAY BE USED. ACTUAL NUMBER, UNLESS
SPECIFIED, TO BE IN ACCORDANCE WITH AISC.
18. ALL STRUCTURAL STEEL CONNECTIONS NOT SPECIFICALLY DETAILED
ON THE STRUCTURAL DRAWINGS SHALL BE DESIGNED BY THE
CONTRACTOR TO RESIST FORCES INDICATED. THE CONTRACTOR'S
CONNECTION DESIGN SHALL BE UNDER THE DIRECT SUPERVISION OF A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE THE
PROJECT IS LOCATED.
19. DESIGN CALCULATIONS FOR THE CONNECTIONS DESIGNED BY THE
CONTRACTOR SHALL BE SUBMITTED FOR THE FILES OF THE ARCHITECT
AND STRUCTURAL ENGINEER. CALCULATIONS SHALL BEAR THE SEAL
OF A PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE
THE PROJECT IS LOCATED. SHOP DRAWINGS CONTAINING
CONNECTIONS FOR WHICH CALCULATIONS HAVE NOT BEEN RECEIVED
WILL BE RETURNED UNCHECKED AS AN INCOMPLETE SUBMITTAL.
20. CONNECTION INFORMATION SHALL BE SHOWN AT EACH DETAILED
CONNECTION ON THE SUBMITTAL DRAWINGS AS FOLLOWS:
A. DESIGN REACTION.
B. CALCULATION PAGE NUMBER.
C. CONNECTION CAPACITY.
21. ALL BEAM CONNECTIONS SHALL BE "SIMPLE SHEAR CONNECTIONS",
UNLESS NOTED OTHERWISE. WHERE BEAM REACTIONS AND/OR DESIGN
FORCES ARE NOT SHOWN ON THE STRUCTURAL DRAWINGS, THE
CONNECTIONS SHALL BE DESIGNED TO SUPPORT A REACTION EQUAL TO
ONE-HALF THE TOTAL UNIFORM LOAD CAPACITY FROM THE MAXIMUM
TOTAL UNIFORM LOAD TABLE MULTIPLIED BY A FACTOR OF 1.2 FOR GIVEN
SHAPE, SPAN, AND GRADE OF STEEL. CONNECTIONS FOR COMPOSITE
BEAMS SHALL HAVE THE STANDARD AISC CAPACITY INCREASED BY
35%.
22. TO THE REACTION LISTED ABOVE, ADD ANY LOADS OR REACTIONS OF
MEMBERS SUPPORTED BY THE BEAM WITHIN THREE FEET OF BEAM
END AND THE VERTICAL COMPONENTS OF FORCES IN BRACE MEMBERS
FRAMING INTO THE BEAM.
23. WHERE BEAM REACTIONS ARE SHOWN ON THE DRAWINGS, THE
CONNECTIONS SHALL DEVELOP THE REACTIONS SHOWN. WHERE
CONNECTIONS ARE SUBJECT TO ECCENTRICITY, SUCH ECCENTRICITY
SHALL BE TAKEN INTO ACCOUNT WHEN DESIGNING AND DETAILING THE
CONNECTION.
24. WHERE STEEL BEAMS ARE CONTINUOUS OVER COLUMNS, PROVIDE
WEB STIFFENER PLATES EACH SIDE OF BEAM WEB, OF THICKNESS
EQUAL TO BEAM FLANGE THICKNESS, LOCATED IN ALIGNMENT WITH
COLUMN WEB, FLANGES OR CENTER LINE OF TUBES AND PIPE
COLUMNS.
25. FABRICATE BRACING MEMBERS WITH SUFFICIENT DRAW TO PREVENT
SAGGING.
26. STEEL BEAMS SHALL BE FABRICATED WITH MILL CAMBER UP.
27. NO COLUMN OR BEAM SPLICES, UNLESS CLEARLY INDICATED ON THE
STRUCTURAL DRAWINGS, WILL BE ALLOWED WITHOUT WRITTEN
APPROVAL OF THE STRUCTURAL ENGINEER.
28. SEE ARCHITECTURAL PLANS FOR FIREPROOFING REQUIREMENTS AND
COORDINATE STEEL COATINGS ACCORDINGLY.
29. GROUT WHERE INDICATED ON PLANS AT BASE PLATES SHALL BE NON-
METALLIC NON-SHRINK WITH A MINIMUM COMPRESSIVE STRENGTH OF
6000 PSI AT 28 DAYS CONFORMING TO ASTM C 1107. 100 PERCENT OF
VOID UNDER ALL BASE PLATE IS TO BE GROUTED. ALL BASE PLATE
WITH A DIMENSION GREATER THAN 24” SHALL HAVE TWO 1” DIAMETER
GROUT HOLES. IF THE SPACE UNDER A COLUMN BASE PLATE IS LESS
THAN ¼”, A PRESSURE INJECTION SYSTEM SHALL BE USED. 10. HEADED
ANCHOR RODS: ASTM F1554 GRADE 36 OR GRADE 55 ANCHOR
AND HEAVY HEX NUT, AS INDICATED IN DETAILS.
30. ALL STEEL FLOOR CONSTRUCTION HAS BEEN DESIGNED IN
ACCORDANCE WITH AISC PROVISIONS NOT TO REQUIRE TEMPORARY
SHORING DURING CONSTRUCTION. HOWEVER, THE STEEL BEAMS WILL
DEFLECT FROM THE WEIGHT OF THE WET CONCRETE. THE
CONTRACTOR IS HEREBY ALERTED THAT THE BEAMS HAVE BEEN
CAMBERED TO ACCOUNT FOR WET CONCRETE DEFLECTIONS.
CONCRETE SHOULD BE PLACED IN EQUAL DEPTH OVER THE ENTIRE
BEAM SPAN.
31. ALL STRUCTURAL STEEL WHICH IS OUTSIDE THE BUILDING ENVELOPE
SHALL BE HOT-DIPPED GALVANIZED. ZINC COATING SHALL MEET THE
REQUIREMENTS OF ASTM 123-73 WITH A MINIMUM COATING CLASS OF
G60 AND SHALL BE APPLIED AFTER FABRICATION. ALL FIELD WELDS
SHALL BE GROUND SMOOTH AND TOUCHED UP WITH ZINC RICH PAINT.
32. ALL BRICK SUPPORT ANGLES ARE DESIGNED TO FULLY SUPPORT THE
BRICK VENEER WITH SOME NORMAL DEFLECTION AS THE BRICK IS
INSTALLED. BRICK SHALL BE INSTALLED WITHOUT SHORING THE
SUPPORT ANGLE DURING CONSTRUCTION. SHORING THE BRICK
DURING CONSTRUCTION CAN RESULT IN HORIZONTAL BED JOINT
CRACKING WHEN THE SHORES ARE REMOVED.
33. THE GENERAL CONTRACTOR AND HIS SUBCONTRACTORS SHALL
COMPLY TO OSHA 29 CFR 1926 SUBPART R, SAFETY STANDARDS FOR
STEEL ERECTION.
34. AS SCOPE AND PERFORMANCE DOCUMENTS, THE DRAWINGS AND
SPECIFICATIONS DO NOT INDICATE OR DESCRIBE ALL THE WORK
REQUIRED FOR THE PERFORMANCE AND COMPLETION OF THIS WORK.
THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE
FABRICATION AND INSTALLATION OF ALL MISCELLANEOUS METAL ITEMS
INDICATED, DESCRIBED OR IMPLIED ON THE STRUCTURAL AND/OR THE
ARCHITECTURAL DRAWINGS. MISCELLANEOUS STEEL ITEMS, WITHIN AN
ASSEMBLY AND NOT ATTACHED TO THE STRUCTURE, ARE THE
RESPONSIBILITY OF THE GENERAL CONTRACTOR AND HIS
SUBCONTRACTORS WHETHER THEY ARE SHOWN OR NOT SHOWN ON
THE ARCHITECTURAL OR STRUCTURAL DRAWINGS. SUCH ASSEMBLIES
INCLUDE BUT ARE NOT LIMITED TO, EXTERIOR AND INTERIOR WALL
ASSEMBLIES, CEILING ASSEMBLIES, PARTITION ASSEMBLIES, SHELF
AND CABINET ASSEMBLIES AND ALL OTHER SIMILAR ASSEMBLIES. ANY
MISCELLANEOUS METAL ITEMS INDICATED ON THE ARCHITECTURAL
DRAWINGS AND NOT SHOWN ON THE STRUCTURAL DRAWINGS SHALL
BE A MINIMUM OF L4x4x1/2”, C7x9.8, 3/8” PLATE OR HSS 4x4x3/8” UNLESS
OTHERWISE APPROVED BY THE STRUCTURAL ENGINEER.
STEEL DECK:
1. STEEL DECK MANUFACTURER SHALL BE A MEMBER OF THE STEEL
DECK INSTITUTE (SDI). ALL METAL DECK TO BE ERECTED PER
MANUFACTURER REQUIREMENTS AND SPECIFICATIONS.
2. DECK PROPERTIES AND ATTACHMENTS SHALL BE IN ACCORDANCE
WITH THE STEEL DECK INSTITUTE.
3. ALL METAL DECK HAS BEEN DESIGNED TO BE CONTINUOUS OVER 3
SPANS MINIMUM AND SHALL BEAR 2” MINIMUM ON STEEL SUPPORTS.
FOR ONE OR TWO SPAN CONDITIONS CONTRACTOR SHALL PROVIDE
SHORING AS REQUIRED OR FURNISH THICKER GAGE DECK TO
SUPPORT ALL APPLICABLE LOADS. CONTRACTOR TO SUBMIT
ALTERNATIVES FOR APPROVAL.
4. DO NOT SHORE DECK, UNLESS NOTED OTHERWISE ON DRAWINGS.
5. DECK SHALL BE WELDED AT SUPPORTS WITH 5/8” PUDDLE WELDS MIN.
AND SIDELAP CONNECTIONS SHALL BE #10 TEK SCREWS MIN (UNO).
6. STEEL DECK SHALL ALWAYS BE INSTALLED WITH DIRECTION OF FLUTES
PERPENDICULAR TO STEEL FRAMING MEMBERS. DECK SHALL BE CUT
TO INSURE A MINIMUM OF THREE SPANS PER DECK WIDTH.
7. PROVIDE REINFORCING CHANNELS, STANDARD CLOSURES, CANT
STRIPS, SUMP PANS, AND OTHER ACCESSORIES AS REQUIRED FOR A
PROPERLY FINISHED JOB, EVEN IF NOT SPECIFICALLY SHOWN ON THE
STRUCTURAL DRAWINGS. PROVIDE BEARING ANGLES WELDED TO
COLUMNS AS REQUIRED TO SUPPORT METAL DECK.
8. ONE OPENING PER DECK SHEET, 6” OR LESS IN DIAMETER, IS
PERMISSIBLE. HOLES LARGER THAN 6” IN DIAMETER OR MORE THAN ONE
HOLE PER DECK SHEET REQUIRES REINFORCING PER SDI. HOLES
LARGER THAN 12” (ROUND OR SQUARE) REQUIRE A STEEL FRAME.
9. OPENINGS IN ROOF DECK TO BE FRAMED WITH L4x4x1/4” ANGLE.
EXTEND ANGLES TO STRUCTURAL SUPPORTS, BLOCK VERTICAL LEGS
AND FIELD WELD. TYPICAL UNLESS NOTED OTHERWISE.
10. COLD-FORMED METAL FRAMING, SUSPENDED CEILINGS, LIGHT
FIXTURES AND DUCTS OR OTHER UTILITIES SHALL NOT BE SUPPORTED
BY THE METAL ROOF DECK.
11. EMBEDDED CONDUIT IS NOT PERMITTED IN CONCRETE SLABS ON
METAL DECK.
12. FLOOR/ROOF DECK:
A. 6¼" THICK CONCRETE SLAB ON STEEL FLOOR DECK. DECK SHALL BE
2" DEEP, 20 GAGE AND G60 GALVANIZED FOR A TOTAL FLOOR DEPTH
8¼" (FY = 40 KSI MINIMUM AND MINIMUM SECTION MODULUS OF 0.73 CU
INCH PER FOOT OF WIDTH), MINIMUM FASTENING PATTERN: 36/4
WITH 5/8" PUDDLE WELDS AND 3 WELDED SIDELAP FASTENERS PER
SPAN (UNO).
B. REINFORCE SLAB WITH 2 LAYERS 6x6-W2.1xW2.1 WWF SUPPORTED
AT LOWER AND UPPER THIRD (SLAB SURFACE TO TOP OF
CORRUGATIONS).
Drawing Number
Project Number
Date
-OF-
Project Title
Building NumberLocation
Checked DrawnAPPROVED: CHIEF ENGINEER
Drawing Title
VA FORM 08-
Office of Construction and Facilities Management
Dwg
CIVIL / STRUCTURAL ENGINEER M.E.P. / T. ENGINEER
APPROVED: DIRECTOR
APPROVED: ASSOCIATE DIRECTOR
APPROVED: ASSISTANT DIRECTOR APPROVED: CHIEF ENGINEER
REVISIONS DATE
CONSULTANTS ARCHITECT
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
H2B
1225 NORTH LOOP WEST, SUITE 900
HOUSTON, TX 77008
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
AZ ARCH REG. NO. 20013-0, EXP. 10/10/2019
AZ ENGR REG. NO. 20015-0, EXP. 10/10/2019
11/01/18
RADIOLOGY EXPANSIONSTRUCTURAL GENERAL NOTES
649-413
11/01/18 SB ED
SS-001
17 148
100% CONSTRUCTION DOCUMENTS
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, AZ 86313
STRUC ABREVIATIONS
+/- PLUS OR MINUS
A.R. ANCHOR ROD
ADDNL ADDITIONAL
ADJ ADJACENT
AESS ARCHITECTURALLY EXPOSED
STRUC STL
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ARCH ARCHITECT OR ARCHITECTURAL
B/ BOTTOM OF
B/W BETWEEN
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
CF COLD FORMED
CHKD CHECKED
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CTR CENTER
db DIA OF REINF BAR, DIA OF BOLT
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DIA DIAMETER
DIAG DIAGONAL
DIR DIRECTION
DWL DOWEL
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ENGR ENGINEER
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EQP EQUIPMENT
EW EACH WAY
EXIST EXISTING
EXT EXTERIOR
F.V. FIELD VERIFY
FLG FLANGE
FLR FLOOR
FND FOUNDATION
FS FAR SIDE
FTG FOOTING
G.C. GENERAL CONTRACTOR
GA GAGE
GALV GALVANIZED
GB GRADE BEAM
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSS HOLLOW STRUCTURAL SECTION
IF INSIDE FACE
INT INTERIOR
JST JOIST
k KIPS (1000 LBS)
LCE COMPRESSION EMBEDMENT
LENGTH
LCS COMPRESSION LAP SPLICE
LENGTH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LTE TENSION EMBEDMENT LENGTH
LTS TENSION LAP SPLICE LENGTH
LW LIGHTWEIGHT
MAS MASONRY
MATL MATERIAL
MNFR MANUFACTURER
MTL METAL
NIC NOT IN CONTRACT
NS NEAR SIDE
NS NON-SHRINK
NTS NOT TO SCALE
O.F. OUTSIDE FACE
OC ON CENTER
OPP OPPOSITE
OVS OVERSIZED
P/C PRECAST
PAF POWDER ACTUATED FASTENER
PEN PENETRATION
PL PLATE
PLF POUNDS PER LINEAL FOOT
PMB PRE-ENGINEERED METAL BUILDING
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
R.F. RIGID FRAME
RC REINFORCED CONCRETE
RE: OR REF REFER TO
REINF REINFORCING
REQD REQUIRED
SC SLIP CRITICAL
SDS SELF DRILLING SCREW
SIM SIMILAR
SLV SHORT LEG VERTICAL
SOG SLAB ON GRADE
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIR STIRRUPS
STL STEEL
SW SHEAR WALL
SYM SYMMETRIC
T&B TOP AND BOTTOM
T/ TOP OF
TOS TOP OF STEEL
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WF WIDE FLANGE
WP WORK POINT
WWF WELDED WIRE FABRIC
COLD FORMED STEEL (SSMA):
1. LIGHT GAUGE FRAMING MEMBERS SHALL HAVE THE FOLLOWING
MINIMUM MATERIAL PROPERTIES: FY = 33 KSI FOR 18 GA AND
LIGHTER MEMBERS, FY = 50 KSI FOR ALL DIAGONAL STRAP BRACING
AND FOR 16 GA AND HEAVIER MEMBERS. ALL MEMBERS SHALL MEET
ASTM A653, G90 SPECIFICATIONS.
2. MINIMUM GAUGE OF STRUCTURAL STUDS SHALL BE 43 MILS (18 GAUGE),
UNLESS NOTED OTHERWISE.
3. TRACKS SHALL BE SECURELY ANCHORED TO THE SUPPORTING
STRUCTURE TO PROPERLY TRANSFER IMPOSED LOADS. MINIMUM
GAUGE OF TRACKS SHALL BE 43 MILS (18 GAUGE). DEFLECTION TRACKS
AT EXTERIOR WALL SHALL BE 16 GA MINIMUM, UNLESS NOTED
OTHERWISE.
4. PROVIDE WALL STUD BRIDGING FOR EACH STUD AS RECOMMENDED
BY THE MANUFACTURER. MAXIMUM SPACING SHALL BE 4’-0”
CENTERS, UNLESS NOTED OTHERWISE.
5. ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR
ATTACHMENTS TO PERPENDICULAR MEMBER. MEMBERS SHALL BE
HELD POSITIVELY IN PLACE UNTIL PROPERLY FASTENED.
6. NOTCHES OR SPLICES IN ANY STRUCTURAL STUDS WILL NOT BE
PERMITTED.
7. DO NOT NOTCH, DRILL OR CUT ANY HOLES IN LOAD BEARING STUDS
FOR ELECTRICAL OR MECHANICAL EQUIPMENT: USE EXISTING
FABRICATED HOLES.
8. ALL WELDING SHALL BE PERFORMED BY WELDERS EXPERIENCED
IN LIGHT GAUGE STEEL FRAMING WORK. TOUCH UP ALL WELDS WITH
GALVANIZE COATING.
9. SCREWS IN LIGHT GAUGE FRAMING SHALL BE INSTALLED WITH MINIMUM
EDGE DISTANCES OF 1/2" AND MINIMUM SPACING BETWEEN SCREWS
OF 3/4".
10. WHERE BACK-TO-BACK STUD COLUMNS ARE USED, ATTACH WITH #10
SCREWS @ 12" O.C. MAX, UNO.
11. PREFABRICATED PANELS SHALL BE SQUARE, WITH COMPONENTS
ATTACHED IN A MANNER AS TO PREVENT RACKING. HANDLING AND
LIFTING SHALL BE DONE IN A MANNER SO AS NOT TO CAUSE
DISTORTION IN ANY MANNER.
12. FASTENING OF COMPONENTS SHALL BE SELF-DRILLING SCREWS OR
WELDS. SCREWS OR WELDS SHALL BE OF SUFFICIENT SIZE TO ENSURE
THE STRENGTH OF THE CONNECTION. WIRE TYING OF COMPONENTS
SHALL NOT BE PERMITTED. ALL WELDS SHALL BE TOUCHED UP WITH A
ZINC-RICH PAINT.
13. RUNNERS SHALL BE SECURELY ANCHORED TO THE SUPPORTING
STRUCTURE. PROPOSED CONNECTION TO BE SUBMITTED FOR APPROVAL.
14. ABUTTING LENGTHS OF TRACK SHALL EACH BE SECURELY ANCHORED TO
A COMMON STRUCTURAL ELEMENT, BUTT-WELDED, OR SPLICED.
15. STUDS SHALL BE PLUMB, ALIGNED AND SECURELY ATTACHED TO FLANGES
OF BOTH UPPER AND LOWER TRACKS.
16. JACK STUDS OR CRIPPLES SHALL BE INSTALLED BELOW WINDOW SILLS,
ABOVE WINDOW AND DOOR HEADDERS, AND WHERE NEEDED TO FURNISH
SUPPORT, AND SHALL BE SECURELY ATTACHED TO CONNECTING MEMBERS.
17. RESISTANCE TO MINOR AXIS BENDING AND ROTATION SHALL BE PROVIDED
BY GYPSUM BOARD OR GYPSUM SHEATHING AND HORIZONTAL STRAP AND
BLOCKING OR COLD-ROLLED CHANNEL BRACING AT THIRD POINTS.
18. PROVIDE A MINIMUM OF (3) #12 SCREWS FOR ALL STUD TO STUD
CONNECTIONS.
19. SSMA STEEL FRAMING CARRIES A FOUR PART CODE THAT IDENTIFIES THE
WEB SIZE, STYLE, FLANGE WIDTH, AND STEEL THICKNESS:
362 S 162-43
WEB SIZE: STYLE FLANGE STEEL
WIDTH THICKNESS
(MIL)
250-2 1/2" 600-6" S-STUD 125-1 1/4" 33
350-3 1/2" 800-8" J-JOIST 137-1 3/8" 43
362-3 5/8" 1000-10" T-TRACK 162-1 5/8" 54
400-4" 1200-12" 200-2" 68 550-5 1/2" 1400-14" 250-2 1/2" 97
#3
#4
#5
#6
#7
#8
#9
BAR
F'c = 3000 psi
EMBEDMENT
8 21
COMPR TENSION (LTE)
OTHER
LAP SPLICE
(LCS) TOP
COMPR TENSION (LTS)
OTHER
HOOK
(LDH)
16 12 28 21 6
22 15 37 28 8
27 19 46 36 10
33 23 56 43 12
48 26 81 62 13
55 30 93 71 15
80 62 34 105 80 17
F'c = 4000 psi
EMBEDMENT
(LCE) TOP
COMPR TENSION (LTE)
OTHER
LAP SPLICE
(LCS) TOP
COMPR TENSION (LTS)
OTHER
HOOK
(LDH)
18 14 12 24 18 6
25 19 15 32 25 7
31 24 19 40 31 8
37 28 23 48 37 10
54 42 26 70 54 12
62 47 30 80 62 13
70 54 34 91 70 15
(LCE)
#10 90 70 38 118 90 19 24 78 60 38 102 78 17
#11 100 77 42 131 100 22 27 87 67 42 113 87 1931
TOP
NOTES (GENERAL):
1. STAGGER ALL SPLICES 12 db MIN, BUT NOT LESS THAN 12"
2. ALL DIMENSIONS INDICATED IN TABLE ARE IN INCHES
3. BARS GREATER THAN #11 SHALL BE MECHANICALLY SPLICED
4. ALL SPLICES SHALL BE WIRED IN CONTACT STACKED
VERTICAL.
MULTIPLIERS:
ALL EMBEDMENT AND LAP SPLICE LENGTHS SHALL BE
INCREASED AS REQD BY THE MULIPLIERS BELOW.
APPLY MULTIPLE MULTIPLIERS IF APPLICABLE.
1.3 -- IF CONC CONTAINS LIGHT WEIGHT AGGREGATES
1.3 -- IF EPOXY COATED REBAR USED
NOTES (PERTAINING TO TABLE):
1. TOP BARS ARE HORIZONTAL BARS THAT HAVE MORE THAN 12"
OF
FRESH CONCRETE CAST BELOW THEM.
2. ALL BARS THAT ARE NOT "TOP BARS" ARE "OTHER" BARS
3. ABBREVIATIONS:
- LCE - COMPRESSION EMBEDMENT LENGTH
- LTE - TENSION EMBEDMENT LENGTH
- LCS - COMPRESSION LAP SPLICE LENGTH
- LTS - TENSION LAP SPLICE LENGTH
- LDH - HOOKED BAR TENSION EMBEDMENT LENGTH
DEVELOPMENT AND LAP SPLICE SCHEDULE
ARRANGE PRIMARY SLAB BARS TO
PASS BY PENETRATIONS. DO NOT
TERMINATE SLAB BARS AT
PENETRATIONS
1#5X5'-0" T&B AT
ENDS AND IN
BETWEEN ALL
PENETRATIONS
1#5X5'-0" T&B EACH
SIDE
LARGER OF ADJACENT
PENETRATION DIAMETERS
D1 & D2 OR 6",
WHICHEVER IS GREATER
ALIGN PENETRATIONS WHERE POSSIBLE
2" TYP2
T Y
P
NOTE:
DETAIL DOES NOT APPLY FOR PENETRATIONS LARGER THAN 12" IN DIAMETER. SEE TYP
SLAB OPENING DETAIL FOR SUCH PENETRATIONS.
TOP BARS
PIPE SLEEVE COORDINATE
LOCATION & SIZE W/ MECH
2' - 0" 2' - 0"
S L A
B S
E E
P L A
N
BOTTOM BARS
2-#6 ADDL. T & B
(4 TOTAL)
DOUBLE STIRRUP
(EACH SIDE OF SLEEVE)
T Y
P
C L R
PIPE SLEEVE
8"
D < 3"
FINISH SLAB
NATURAL SLOPE
1' - 0"
3" < D < 6"
FINISH SLAB
NATURAL SLOPE
LAP MESH 2 SQUARES
LAP BARS 1'-0"
1-#3 CONT. @ EDGE
6" <= D < 10"
FINISH SLAB
NATURAL SLOPE
1-#3 CONT. @ EDGE
LAP MESH 2 SQUARES
LAP BARS 1'-0"
LAP MESH 2 SQUARES
LAP BARS 1'-0"
BEND SLAB REINF. AS
SHOWN. HOOK 12" AT
BOTTOM OF SLAB
1' - 0"
NOTES:
1. COORDINATE DEPTH AND LOCATION OF ALL FLOOR DEPRESSIONS WITH ARCHITECTURAL
DRAWINGS.
2. PROVIDE 1-#4X4'-0" TOP AT INTERIOR CORNERS OF ALL DEPRESSIONS.
2"
D D
D
T.O.C.
T.O.C.
T.O.C.
T.O.C.
T.O.C.
T.O.C.
(S L A
B T
H
IC
K N
E S
S R
E F
T
O P
L A
N
SAW JOINT (SJ) CUT JT. AS
SOON AS EQUIPMENT CAN BE
PLACED ON SLAB WITHOUT DAMAGE
MESH CONT.
SAW CUT JOINT
KEYED CONSTRUCTION JOINT
(CJ) USE BOND BREAKER
NOTE:
THIS DETAIL MAY BE USED IN
LIEU OF SAW CUT JOINT
FORMED KEY (NO
METAL KEY)
(S L A
B T
H
IC
K N
E S
S R
E F
T
O P
L A
N
CUT MESH
AT JOINT
T /2
T /4
T
T T
2 x T 2 x T
3/4" MIN
90.00°
90.00°
CONTROL OR
CONSTRUCTIO
N JOINT
4" M
IN
(TYP)
¼" PREFORMED JOINT
FILLER AROUND COLUMN
AND AT EDGE OF
BLOCKOUT. FILL JOINT
WITH SEALANT (TYP)
EDGE OF SLAB
OR FACE OF
WALL
NOTE:
PROVIDE SONOTUBE BLOCKOUT
WHEN CONTROL /
CONSTRUCTION JOINTS DO NOT
EXTEND FROM ALL CORNERS OF
BLOCKOUT
EDGE OF SLAB
OR FACE OF
WALL
EDGE OF
BLOCK OUT
EDGE OF
BLOCKOUT
INTERIOR COL
EXTERIOR COL
CORNER COL WIDTH + 3'-0"
2'-0" x STAIR #4x1'-5"@16" O.C.
(3) #4 CONT
STAIR WIDTH + 2'-0"
L3x3x5/16"x0'-6" w/(2) 5/8" Ø x 4" EMBED
HILTI KWIK BOLT 3
STAIR STRINGER
SLAB ON GRADE
REINF NOT SHOWN
FOR CLARITY
C L R
END HOOK DIMENSIONS
#3
#4
#5
#6
#7
#8
#9
#10 #11
BAR
SIZE
#14
#18
FINISHED
BEND
DIAMETER D,
(INCHES)
180 ° HOOKS
A OR G'
(INCHES)
A OR G'
(INCHES)J, (INCHES)
2 ¼
3 ¾
4 ½
5 ¼
9 ½
10 ¾
18 ¼
11 ¾
13 ¼
14 ¾
21 ¾
28 ½
90° HOOK
D= INSIDE DIAMETER OF BEND
d b
D
A O
R G d b
DETAILING DIMENSION
90° HOOK
2 1/2"
4db OR
MINIMUM
D
DIMENSION
DETAILING
A OR G
HOOK
J d b
180° HOOK
STIRRUP AND TIE HOOK
#3
#4
#5
BAR
SIZE
1½
2½
4½
5½
D= INSIDE DIAMETER OF BEND
6db FOR #3, #4, #5
12db FOR #6, #7, #8
D E
T A
IL
IN
G D
IM
E
N S
IO
N
D
A OR G
db
D
D E
T A
IL
IN
G D
IM
E
N S
IO
N
A O
R G
H O
O K
A N D
SM
ALLER
6db FO R #8 B
AR
S
D
D db
90° HOOK
135° HOOK
CORNER CONDITIONS-STIRRUP OR TIE
90° HOOK
90° HOOK
BEYOND
135° HOOK
90° HOOK
BEYOND
135° HOOK
135° HOOK
90° HOOK
135° HOOK
GROSS TIE
D
(INCHES)
90° HOOK
A OR G
(INCHES)
135° HOOK
A OR G
(INCHES)
4½
¾" CHAMFER, TYPICAL
BOTTOM REINFORCEMENT,
WHERE SCHEDULED
TOP REINFORCEMENT,
REFER TO SCHEDULE
1-#4 CONTINUOUS AT
PERIMETER WITH 1-#4X4'-0"
AT EXTERIOR CORNERS
AND 1-#4X4'-0" DIAGONAL AT
RE-ENTRANT CORNERS
REFER TO NOTE 1
2'-0"
2" 4' -0
RE-ENTRANT
CORNERS
EXTERIOR
CORNERS
HOUSEKEEPING PAD REINFORCEMENT SCHEDULE
PAD THICKNESS
TOP
REINFORCEMENT
BOTTOM
REINFORCEMENT
T-4" WWR 4x4-W2.9xW2.9 OR #3@12" EACH WAY NONE
4" < T < = 6"
6" < T < = 8"
8" < T < = 12"
12" < T < = 16"
WWR 4x4-W4xW4 OR #4@18" EACH WAY
WWR 4x4-W6xW6 OR #4@12" EACH WAY
#4@18" EACH WAY
#4@12" EACH WAY
NONE
NONE
#4@18" EACH WAY
#4@12" EACH WAY
NOTE:
1. REFER TO ARCHITECTURAL, STRUCTURAL, OR MEP DRAWING FOR HOUSEKEEPING PAD
PLAN DIMENSIONS AND THICKNESS (4" MINIMUM THICKNESS).
2. CONTRACTOR SHALL COORDINATE DIMENSIONS AND OTHER SPECIAL REQUIREMENT WITH
EQUIPMENT MANUFACTURERS AND PROVIDE WHERE REQUIRED WHETHER SHOWN ON
STRUCTURAL DRAWING OR NOT.
3. PROVIDE ADDITIONAL LAYER OF REINFORCING FOR PAD THICKNESS GREATER THAN 18".
DO OPP.
W
FIELD CUT ALTERNATE
HORIZ. BARS EA. FACE
/2
1-1/2"
3/8"
1" 5 1/2"
1/2" DIA X 1'-0" DWLS @ 12" oc
VERTICALLY WITH GREASED SLEEVE
1" EXPANSION
JOINT IN WALL
2"1" 2"
SEALANT BOTH SIDES
W /2
W /2
CORNERSINTERSECTIONS ENDS
DWLS TO
MATCH
HORIZ
REINF SIZE
AND
SPACING
(TYP)
HORIZONTAL BARS
U-BARS TO MATCH SIZE
AND SPACING OF HORIZ
BARS (TYP)
STD HOOK
WALLS WITH 2 LAYERS OF
REINF (10" OR GREATER)
WALLS WITH 1 LAYER OF
REINF (< 10")
L T
S
LTS
STD HOOK
LTS
L T
S
CORNER
BARS. MATCH
HORIZ REINF
SIZE AND
SPACING
DWLS TO MATCH
HORIZ REINF SIZE
AND SPACING. ALT
HOOK DIRECTIONS
(TYP)
BASEMENT FLR
-11' - 0"
EXIST CRAWL
SPACE
-6' - 0"
E.1 F.1
SS-300
2' - 6"
METAL GRATING,
SEE PLAN
SEE PLAN FOR
SLAB DEPTH AND
REINF
# 6 @ 12"O.C.E.W, EA FACE
#6 DOWELS @
12" O.C. EA FACE
#6 DOWELS @
8" O.C. EA FACE
#6 @ 8"O.C.E.W, TOP & BOT
#6 @ 8" O.C.E.W, EA FACE
R E
:A R
C H
CONT. L4x4x¼ w/ ¾"Ø HILTI KWIK
BOLT 3 @ 2'-0" O.C.
w/ 6" OF EMBED.
SLOPE: RE ARCH .SLOPE: RE ARCH
SEE PLAN
SEE PLAN
3" CLR
#4 DWLS
@ 15" O.C.
EA SIDE
FTG. BRG. EL.
SEE PLAN
SEE 7/SS-201
FOR REINF.
15' - 0"
IN
T
E R
IO
R
E X
T E
R
IO
R
Drawing Number
Project Number
Date
-OF-
Project Title
Building NumberLocation
Checked DrawnAPPROVED: CHIEF ENGINEER
Drawing Title
VA FORM 08-
Office of Construction and Facilities Management
Dwg
CIVIL / STRUCTURAL ENGINEER M.E.P. / T. ENGINEER
APPROVED: DIRECTOR
APPROVED: ASSOCIATE DIRECTOR
APPROVED: ASSISTANT DIRECTOR APPROVED: CHIEF ENGINEER
REVISIONS DATE
CONSULTANTS ARCHITECT
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
H2B
1225 NORTH LOOP WEST, SUITE 900
HOUSTON, TX 77008
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
AZ ARCH REG. NO. 20013-0, EXP. 10/10/2019
AZ ENGR REG. NO. 20015-0, EXP. 10/10/2019
11/01/18
RADIOLOGY EXPANSIONTYPICAL DETAILS - CONCRETE
649-413
11/01/18 SB ED
SS-030
18 148
100% CONSTRUCTION DOCUMENTS
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, AZ 86313
NTS
2 SPLICE & DEVELOPMENT SCHEDULE
NTS
8 TYPICAL ALIGNED CIP SLAB PENETRATIONS
NTS
9 CONCRETE BEAM PENETRATION DETAIL
NTS
11 TYPICAL DETAIL SLAB ON GRADE AT FLOOR DEPRESSION
NTS
4 TYPICAL SOG CONTROL JOINTS
NTS
5 SOG JOINTS AT COLUMNS
NTS
6 TYPICAL THICKENED SLAB AT STAIR STRINGER DETAIL
NTS
3 TYPICAL END HOOK TYPES
NTS
1 TYPICAL STIRRUP AND TIE HOOK TYPES
NTS
10 TYPICAL HOUSEKEEPING PAD OVER SLAB-ON-GRADE
1/2" = 1'-0"
7 CONC WALL JOINTS
1/2" = 1'-0"
13 CONC WALL CORNERS
1/2" = 1'-0"
14 MECHANICAL WALL SECTION
1'-4" MAX
4" MIN
36" MAX
4½" MIN
COLUMN OR BEAM
COLUMN OR
BEAM FLANGE
M
IN
M
A X
M A
X
½
M
IN
1" MIN
1" MIN
3" MIN
3" M
IN
1" MIN
SINGLE LINE SPACING
MULTIPLE LINE SPACING PLAN
WHERE MULTIPLE LINE
SPCG. IS REQ'D. AT A BM.
w/ A FLANGE WIDTH LESS
THAN 5" SPACE THUS.
STUDS SHALL BE
ATTACHED DIRECTLY OVER
WEB UNLESS THE BM.
FLANGE THICKNESS IS 0.3
OR THICKER FOR ¾" DIA.
STUDS.
STUDS SHALL BE TYPE S3L, ¾" DIA.
AS MFG. BY NELSON STUD DIVISION,
OR APPROVED EQUAL. STUDS SHALL
HAVE PROPER FERRULES FOR WELD-
THRU DECK APPLICATIONS.
STUD (AFTER WELDING) SHALL PROJECT
A MIN. OF 1½" ABOVE TOP METAL DECK
AND THERE SHALL BE A MIN. OF 1"
CONCRETE ABOVE STUDS. STUDS SHALL
BE WELDED PER MANUFACTURERS
RECOMMENDATIONS.
TOWARDS
SUPPORTS
TOWARDS
SUPPORTS
MID-SPAN OF BEAM
PLACE STUD AWAY FROM
MID-SPAN OF BEAM. CLOSER
TOWARDS THE SUPPORTS.
STRONG SIDE OF FLUTES
MIN
1"
3" 3" MIN
1"
3x3/8x0'-5"
CHORD SPLICE
PLATE
CHORD ANGLE
PER PLAN AND
DETAILS
3/16 2
3/16 2
TYP
¼
¼
L e v L e v
"S
S P
A C
IN
G
(N
"D
D
IA
A
-N B
O L
T S
BEAM N
W8, W10 2
W12, W14 3
W16 4
W18 5
W21, W24 6
NOTES:
3" DIM. TYP. EXCEPT AS
RECOMMENDED BY AISC FOR
W8 & SMALLER BEAMS OR
FOR LARGERBEAMS.
FACE OF : BEAM WEB, COL.
FLG., OR COL. WEB
.1
L 3½ x 3½ x 5/16"
DBL ANGLE CONN
(GA = 4½" MIN)2
VARIABLES:
Lev = 1½" D = ¾"
N = PER TABLE
S = 3"
NOTE:
INFORMATION PROVIDED IN THIS DETAIL
IS TO COMMUNICATE THE GENERAL INTENT
OF THE CONNECTIONS. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR DESIGNING
THE STEEL CONNECTIONS PER THE
GENERAL NOTES.
L e v
S
S P
A C
IN
G
(N
"D
D
IA
A
-N B
O L
T S
L e v
1/2"
Leh
Leh
¼
¼ F. WELD AT
EMBED
PLATES
5/16" TAB PL.
WIDTH = 2 x Leh+½"
DEPTH AS REQ'D.
WF BEAM PER PLAN
HOLES MAY BE HORIZ. SHORT
SLOTS AS REQ'D.
NOTES:
3" DIM. TYP. EXCEPT AS
RECOMMENDED BY AISC FOR
W8 & SMALLER BEAMS OR
FOR LARGERBEAMS.
FACE OF : BEAM WEB, COL.
FLG., COL. WEB, OR EMBED
PLATE.
VARIABLES:
Lev = 1½" Leh = 1½" D = ¾"
N = PER TABLE
S = 3"
BEAM N
W8, W10 2
W12, W14 3
W16 4
W18 5
W21, W24 6
NOTE:
INFORMATION PROVIDED IN THIS DETAIL
IS TO COMMUNICATE THE GENERAL INTENT
OF THE CONNECTIONS. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR DESIGNING
THE STEEL CONNECTIONS PER THE
GENERAL NOTES.
MAX
9"
½" FROM MASONRY JAMB
STOP LINTEL ANGLE
BRACE ANGLE - SEE SCHEDULE
(WELD ALL CONNECTIONS)
48" O.C. (MAX)
TO GRADE
MASONARY STACKED
3/8" MASONRY
CONTROL JOINT
CONT LINTEL ANGLE
(HOT DIPPED GAVANIZED)
MASONRY SUPPORTED
BY ROOF OR FLOOR
PLAN VIEW
SEE SECTION FOR OTHER
NOTES AND DETAILS
NOTE:
WHERE MASONRY IS SUPPORTED BY
SREEL TUBES WITHOUT HANGERS AND
BRACES, THE NOTES PRETAINING TO
LINTEL. ANGLES SHALL STILL APPLY.
BRACE ANGLE SCHEDULE
BRACE ANGLE HEADER ANGLE SIZE MAX LENGTH
L 3x3x¼" L 4x4x5/16" 9'-6"
L 4x4x¼" L 5x5x5/16" 13'-3"
L 5x5x5/16" L 6x6x3/8" 16'-6"
L 6x6x5/16" L 6x6x3/8" 20'-0"
CONSULT ENGINEER CONSULT ENGINEER OVER 20'-0"
SIZE OF ALL BRACE ANGLE IN COMPRESSION SHALL BE
DETERMINED BY STEEL FABRICATOR BASED ON THEIR
UNBRACED LENGTH AS SCHEDULED.
IF BRACE ANGLE DOES NOT HIT
JOIST (OR BEAM). PROVIDE
L4x4x5/16" HEADER WELDED TO
JOIST OR BEAM
Drawing Number
Project Number
Date
-OF-
Project Title
Building NumberLocation
Checked DrawnAPPROVED: CHIEF ENGINEER
Drawing Title
VA FORM 08-
Office of Construction and Facilities Management