Updated - 598-18-108 Renovate SPS Drawings Part 2 - 5.6.21.pdf
PDF 17 MB Posted
- Attached to
- Y1DZ-- Renovate Sterile Processing Service Project # 598-18-108 NRM Construction - Little Rock, AR
- Solicitation number
- 36C77621R0035
About this file
This document provides details for a federal contract solicitation to renovate the Sterile Processing Services areas at the John L. McClelland Veterans Affairs Medical Center in Little Rock, Arkansas. The solicitation will be issued as a Request for Proposal and evaluated according to procedures outlined. It is a total Service-Disabled Veteran-Owned Small Business set-aside under NAICS code 236220 with a size standard of $39.5 million. The solicitation period of performance is approximately 365 calendar days from the notice to proceed for renovating approximately 15,763 gross square feet of interior space. The magnitude of construction is estimated between $5 million to $10 million. Questions must be submitted in writing by the specified due date.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STORAGE,
STERILE
DURABLES
GE-113
CLEAN
WORKROOM
INSTRUMENT SET
ASSEMBLY
GE-111
AUTOMATED
CART WASH
GE-113D
ANTEROOM,
SCOPE
PROCESSING
GE-112A
SCOPE
PROCESSING /
HLD ROOM
GE-112
WATER
TREATMENT &
DETERGENT
GE-107D
ANTEROOM,
SOILED
DROP-OFF/TRANSITION
GE-107A
DECONTAMINATION
WORK AREA
GE-107
WOMEN
GE-108
ALCOVE, PPE
GE-107F
TRAINING ROOM
GE-106
MEN
GE-109
CASE CART
STERILE AREA
GE-114
HAZARD
STORAGE
GE-107E
QH401
F1
CHASE
CH
AS
E
CHASE
CHASE
PIPE
CHASE
CHASE
CH
AS
E
CHASE
CHASE
PIPE
CHASE
LOGISTICS
AIR-LOCK
GD-124QH403
F3
ALCOVE, PPE
GE-107B
JANITOR
GE-107C
STERILIZER
ROOM
GE-110
STEAM
STERILIZATION
CHASE
GE-110A
QH402
F1
QH403
C3
SPS BREAKDOWN
ROOM
GD-122
EUSS ROOM
GD-125
CORRIDOR
CG-38A
R
N
L
K
J
H
STERILIZATION
CHASE
GE-110B
V
W
X
ALCOVE, PPE
5B-120A
CH
AS
E
SCOPE
PROCESSING /
HLD ROOM
5B-119
ANTEROOM,
SCOPE
PROCESSING
5B-119A
DECONTAMINATION
WORK AREA
5B-120
QH404
F5
SCOPE STORAGE
AREA
5B-118
SCOPE STORAGE
VEST
5B-118A
W
V
X
CH
AS
E
EQUIPMENT LEGEND
CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
VA FURNISHED,
VA INSTALLED
VA FURNISHED,
CONSTRACTOR INSTALLED
JOINT SCHEDULE
NUMBER REFERS TO
EQUIPMENT LISTED
IN 'MIL-STD 1691
MASTER EQUIPMENT
LIST' DOCUMENT
CC
VV
VC
JSN
NEW UNRATED PARTITION
NEW / EXISTING 2-HOUR BARRIER
EXISTING PARTITION, TO BE
REMOVED
EXISTING PARTITION, TO REMAIN
INDICATES AREA NOT IN
CONTRACT
NEW / EXISTING 1-HOUR BARRIER
PLUMBING TRENCHES
U.S. Department of Veterans Affairs
CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
Revisions: Date:
VA FORM 08 - 6231
FULLY SPRINKLERED
MISSION CRITICAL
CONSTRUCTION DOCUMENTS
5/ 3/
:5
3:
A M
C :\U se rs
\jc or de ll\
R ev it Lo ca l\5
-1
8-
8_
SP
S_ Ar ch F in al
S ub m is si on
_A D
D _J
AC
O
B.
C
O R
D
EL
L.
rv t
EQUIPMENT PLANS CONSTRUCTION
DOCUMENTS SUBMISSION
RENOVATE SPS / INSTALL
STERILIZERS
JLM MEMORIAL VETERANS HOSPITAL
2021.04.30 JDM JDB
598-18-108
QH101
JLM
JDA PROJECT #: D-18-02
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
1/8" = 1'-0"F3 EQUIPMENT PLAN - GROUND LEVEL
FIRE PROTECTION
LACEY FIRE PROTECTION
ENGINEERING, LLC
P.O. BOX 723
GREENBRIER AR 72058
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
EQUIPMENT SCHEDULE - QH101
JSN # DESCRIPTION
JSN_VA ACQ/INS
ASSIGNMENT
A - ARCHITECTURAL
A1012 A1012 - Telephone, Wall Mounted, 1 Line 12'' x 12'' VV A1014 A1014 - Telephone, Wall Mounted, 1 Line, With Speaker 12"x 12" VV A1020 A1020 - Telephone, Conferencing System 12 x 12 VV A1030 A1030 - Locker, 2 Person, Over Under CC A1066 A1066 - Mirror, Float Glass CC A1067 A1067 - Mirror, Float Glass, ADA Accessible CC A1080 A1080 - Mirror, Posture, Wall Mounted 28"x 6 CC A1195 A1195 - Counter, Cleanup, With 2 or 3 Sinks VV A5075 A5075 - Dispenser, Soap VV A5077 A5077 - Dispenser, Hand Sanitzer, Hands free VV A5080 A5080 - Dispenser, Paper Towel VV A5082 A5082 - Dispenser, Paper Towel, Sensor, Hands Free VV A5090 A5090 - Dispenser, Sanitary Napkin, SS, Surface Mounted VV A5106 A5106 - Waste_Disposal Unit, Sharps with Glove Dispenser VV
A5109.1 A5109 - 42" Grab Bar, 1-1/4" Dia., SS, 2 Wall, W/C Accessible CC A5109.2 A5109 - 36" Grab Bar, 1-1/4" Dia., SS, 2 Wall, W/C Accessible CC A5135 A5135 - Shelf w Mop Broom Holders VV A5145 A5145 - Hook, Garment, Double CC A5160 A5160 - Shelf, 8 in Depth, SS, Surface Mounted CC A5200 A5200 - Dispenser, Toilet Tissue, SS, 2-Roll, Surface Mntd CC A5212 A5212 - Bracket, Television, Wall-Mounted, Tilt/Angle 32"x 4" VV
C - FIXED CASEWORK
CT050.1 CT050 - Countertop, Stainless Steel 24"x 24" CC CT050.2 CT050 - Countertop, Stainless Steel 72"x 24" CC CT050.3 CT050 - Countertop, Stainless Steel 36"x 24" CC CT050.4 CT050 - Countertop, Stainless Steel 96"x 24" CC CT050.5 CT050 - Countertop, Stainless Steel 48"x 24" CC
F - FURNITURE AND FURNISHINGS
F0220 F0220 - Chair, Conference CC F0500 F0500 - Cart, Janitor's VV F0505 F0505 - Bucket, Mop, With Wringer, 26 Quart VV F0540 F0540 - Cart, Scope, Transport VV F0601 F0601 - Credenza, Performance 120"x 26" CC F0765 F0765 - Table, Folding_Nesting CC F2000 F2000 - Basket, Wastepaper VV F2010 F2010 - Basket, Waste Paper, Step-On VV F2020 F2020 - Can, Trash, 44 Gallon VV F2700 F2700 - Reader, Bar Code, Hand Held, With Interface VV F3200 F3200 - Clock, Battery, 12in Dia VV
K - FOOD SERVICE EQUIPMENT
K2020 K2020 - Dispenser, Detergent, Automatic 10"x 7" VV K6300 K6300 - Sink, Cooks, 1 Compartment CC
M - MISCELLANEOUS
M0506 M0506 - Television, Flat Screen VV M0507 M0507 - Video Teleconferencing System VV M1801 M1801 - Computer with Flat Panel Monitor VV M1803 M1803 - Workstation, Computer, Wall Mounted VV M2035 M2035 - Rack, Storage, Wire, CRS VV M2080 M2080 - Shelving, Storage, Solid, CRS VV M2600 M2600 - Vacuum, Wet/Dry, HEPA Filtration 22"x 24" VV M2650 M2650 - Scrubber, Floor, Automatic, Rechargeable VV M3072 M3072 - Frame, Infectious Waste Bag with Lid VV M3160 M3160 - Cabinet, Storage, Hanging Scopes VV
P - PLUMBING FIXTURES
P2000 P2000 - Eyewash, Wall Mounted, Hands-Free CC P3200 P3200 - Lavatory, Viteous China, Slab Type WSens Op Fauc CC P4700 P4700 - Sink, Mop, Molded Stone CC P5210 P5210 - Shower, Safety, Freestanding, With Eye-Face Wash CC P6150 P6150 - Sink, Cage Washing, SS, Single Compartment, FS CC P9050 P9050 - Toilet, Wall Hung, Siphon Jet CC
S - STERILIZERS AND ASSOCIATED EQUIPMENT
S0440 S0440 - Caviwave Ultrasonic Console VV S0442 S0442 - Evolution Sterilizer,VAC,54in,Stm,Dd Hng,Lr,R2W,480V 38 Wide VV S0495 S0495 - Loading Car & Transfer Carriage, 24x36x48 Chamber VV S0940 S0940 - Washer-Disinfector,STM,1DO,RSCD1WLL,26X24X24 Cham VV S1905 S1905 - Window, Sliding Service CC S2615 S2615 - Endoscope Reprocessing System VV
S2615A S2615A - Automatic Endoscope Reprocessor VV S2627 S2627 - Washer, Fiber Scope VV S2635 S2635 - Innowave Ultrasonic SNGL Chamber CAB F-S VV S5505 S5505 - Sterilizer, Hydrogen Peroxide Gas, 3.5 cu ft Cham 33Inches VV
U - USER SPECIFIC ITEMS
U0040 _0040 - Trophon Disinfectant Processor VV U0042 _0042 - Incubator, Biological Indicator 12"x 12" VV U0049 _0049 - Micro Scrubber, Floor, Automatic 12"x 12" VV U0053 _0053 - Dispensing System, Cleaning Solution 12"x 12" VV U0070 U0070 - Accu Hold System - Wall Mounted / 3 Container VV U0071 U0071 - Wall Mounted / 3 Container 2 VV U0080 U0080 - SCS Load/Unload Conveyor System, Single Load VV U0081 U0081 - Loading Car & Transfer Carriage VV U0082 U0082 - SCS Motorized Return Conveyor System VV U0090 U0090 - System, Deionized, Water VV
1/8" = 1'-0"F1 EQUIPMENT PLAN - 5B
PLAN
NORTH
A E
BC
D
KEY PLAN
F
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
GROUND LEVEL F.F.E. = 378.00'FIFTH LEVEL F.F.E. = 464.67'
GRAPHIC LEGEND
M2035
F2020
A5160
CT050.3
A5077
A1014
A5075
F2010
A1066
P3200
A5080
F0540
M1801
CT050.2
K2020
U0090
F0505
F0500
M2650
M2080
U0049
M2600
U0053
A5077
A5106
F2010
F2020 M3072
P5210
A1195
A1195
F2020
A5080
A5075 P3200 A5077
K6300
M1803
M1801
F2700
CT050.4
M3072 S2635
CT050.4
F0540
A1195M1803
M1801
M3072
A5080
P3200 A5075
A5077
A5106 P5210
A1195
ANTEROOM,
SCOPE
PROCESSING
GE-112A
SCOPE
PROCESSING /
HLD ROOM
GE-112
WATER
TREATMENT &
DETERGENT
GE-107D
DECONTAMINATION
WORK AREA
GE-107
ANTEROOM,
SOILED
DROP-OFF/TRANSITION
GE-107A
AUTOMATED
CART WASH
GE-113D
DUMBWAITER
CHASE
CHASE
CHASE
PIPE
CHASE
F0540
S0495
HAZARD
STORAGE
GE-107E
CLEAN
WORKROOM
INSTRUMENT SET
ASSEMBLY
GE-111
A1014
A5160
A5106
A5160
S1905
STERILIZER
ROOM
GE-110
S0495
JANITOR
GE-107C
ALCOVE, PPE
GE-107B
P4700
P3200
A5080
A5075
A5145
S0442
P2000
P3200
P5210
M1801
CT050.5
S1905 x4
S0495 S0495
S0495 S0495
S2627
CT050.5
S2615AS2615A
A5077
A5075 F2010
P3200
A5080
P5210
S0442
S0442
STEAM
STERILIZATION
CHASE
GE-110A
A5080
A5075
A5135
A5075
F2010
R
NN
LL
S0940 S0940
A1014
TRAINING ROOM
GE-106
ALCOVE, PPE
GE-107F
MEN
GE-109
CORRIDOR
CG-38A
S1905
SCRUB EX SCRUB EX
A5080
U0042
A1014
U0040U0040U0040
CH
AS
E
FEC
FEC
FEC
U0071U0071
U0070U0070
U0080 U0080
U0080U0080
U0081 U0081
U0081U0081
U0082
FEC
STERILIZATION
CHASE
GE-110B
A5080 P3200
A5075
P2000 M1801 M1803
S5505 S5505
S0440 S0440
A1195A1195
P3200
P2000
EQUIPMENT LEGEND
CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
VA FURNISHED,
VA INSTALLED
VA FURNISHED,
CONSTRACTOR INSTALLED
JOINT SCHEDULE
NUMBER REFERS TO
EQUIPMENT LISTED
IN 'MIL-STD 1691
MASTER EQUIPMENT
LIST' DOCUMENT
CC
VV
VC
JSN
NEW UNRATED PARTITION
NEW / EXISTING 2-HOUR BARRIER
EXISTING PARTITION, TO BE
REMOVED
EXISTING PARTITION, TO REMAIN
INDICATES AREA NOT IN
CONTRACT
NEW / EXISTING 1-HOUR BARRIER
PLUMBING TRENCHES
NOTES:
1. P2000 AND P5210 FIXTURES ALSO REQUIRE "P2450 - VALVE, MIXING,
THERMOSTATIC" COMPONENTS FOR EACH INSTANCE. G.C. RESPONSIBLE
FOR PROVIDING AND INSTALLING FOR EACH INSTANCE WHERE A P2000
OR P5210 FIXTURE IS REQUIRED; P2450 - "CC".
2. A1014 ALSO REQUIRES "A1010 - TELECOMMUNICATIONS OUTLET" FOR
EACH INSTANCE. G.C. RESPONSIBLE FOR PROVIDING AND INSTALLING
A1010 - "CC".
3. A5212 WILL ALSO REQUIRE "A5220 - BRACKET, TELEVISION, WALL
BACKING." G.C. RESPONSIBLE FOR PROVIDING AND INSTALLING AT EACH
INSTANCE; A5220 - "CC".
4. GC RESPONSIBLE FOR COORDINATING ALL ACCESSORIES, FIXTURES, AND
EQUIPMENT BETWEEN FLOOR PLANS, RCPs, INTERIOR ELEVATIONS, EQUIPMENT PLANS, AND ALL OTHER DISCIPLINE SPECIFIC (MEP,FP)
DRAWINGS AS WELL.
5. GC RESPONSIBLE FOR COORDINATING ALL WALL MOUNTED EQUIPMENT
WITH "EQUIPMENT MOUNTING LEGEND" LOCATED IN GI DRAWINGS.
6. FEC - FIRE EXTINGUISHER CABINET; REF SPECIFICATIONS.
7. GC TO COORDINATE ALL WALL PENETRATIONS AND ROUGHT OPENINGS
PRIOR TO INSTALLATION OF RESINOUS WAINSCOT.
U.S. Department of Veterans Affairs
CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
Revisions: Date:
VA FORM 08 - 6231
FULLY SPRINKLERED
MISSION CRITICAL
CONSTRUCTION DOCUMENTS
5/ 3/
:5
4:
A M
C :\U se rs
\jc or de ll\
R ev it Lo ca l\5
-1
8-
8_
SP
S_ Ar ch F in al
S ub m is si on
_A D
D _J
AC
O
B.
C
O R
D
EL
L.
rv t
ENLARGED EQUIPMENT PLANS @
GROUND FLOOR SPS
CONSTRUCTION
DOCUMENTS SUBMISSION
RENOVATE SPS / INSTALL
STERILIZERS
JLM MEMORIAL VETERANS HOSPITAL
2021.04.30 JDM JDB
598-18-108
QH401
JLM
JDA PROJECT #: D-18-02
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
FIRE PROTECTION
LACEY FIRE PROTECTION
ENGINEERING, LLC
P.O. BOX 723
GREENBRIER AR 72058
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
1/4" = 1'-0"F1 EQUIPMENT PLAN - GROUND LEVEL - SPS
EQUIPMENT SCHEDULE - QH401
JSN # DESCRIPTION
JSN_VA ACQ/INS
ASSIGNMENT
A - ARCHITECTURAL
A1014 A1014 - Telephone, Wall Mounted, 1 Line, With Speaker 12"x 12" VV A1066 A1066 - Mirror, Float Glass CC A1195 A1195 - Counter, Cleanup, With 2 or 3 Sinks VV A5075 A5075 - Dispenser, Soap VV A5077 A5077 - Dispenser, Hand Sanitzer, Hands free VV A5080 A5080 - Dispenser, Paper Towel VV A5106 A5106 - Waste_Disposal Unit, Sharps with Glove Dispenser VV A5135 A5135 - Shelf w Mop Broom Holders VV A5145 A5145 - Hook, Garment, Double CC A5160 A5160 - Shelf, 8 in Depth, SS, Surface Mounted CC
C - FIXED CASEWORK
CT050.2 CT050 - Countertop, Stainless Steel 72"x 24" CC CT050.3 CT050 - Countertop, Stainless Steel 36"x 24" CC CT050.4 CT050 - Countertop, Stainless Steel 96"x 24" CC CT050.5 CT050 - Countertop, Stainless Steel 48"x 24" CC
F - FURNITURE AND FURNISHINGS
F0500 F0500 - Cart, Janitor's VV F0505 F0505 - Bucket, Mop, With Wringer, 26 Quart VV F0540 F0540 - Cart, Scope, Transport VV F2010 F2010 - Basket, Waste Paper, Step-On VV F2020 F2020 - Can, Trash, 44 Gallon VV F2700 F2700 - Reader, Bar Code, Hand Held, With Interface VV F3200 F3200 - Clock, Battery, 12in Dia VV
K - FOOD SERVICE EQUIPMENT
K2020 K2020 - Dispenser, Detergent, Automatic 10"x 7" VV K6300 K6300 - Sink, Cooks, 1 Compartment CC
M - MISCELLANEOUS
M1801 M1801 - Computer with Flat Panel Monitor VV M1803 M1803 - Workstation, Computer, Wall Mounted VV M2035 M2035 - Rack, Storage, Wire, CRS VV M2080 M2080 - Shelving, Storage, Solid, CRS VV M2600 M2600 - Vacuum, Wet/Dry, HEPA Filtration 22"x 24" VV M2650 M2650 - Scrubber, Floor, Automatic, Rechargeable VV M3072 M3072 - Frame, Infectious Waste Bag with Lid VV
P - PLUMBING FIXTURES
P2000 P2000 - Eyewash, Wall Mounted, Hands-Free CC P3200 P3200 - Lavatory, Viteous China, Slab Type WSens Op Fauc CC P4700 P4700 - Sink, Mop, Molded Stone CC P5210 P5210 - Shower, Safety, Freestanding, With Eye-Face Wash CC
S - STERILIZERS AND ASSOCIATED EQUIPMENT
S0440 S0440 - Caviwave Ultrasonic Console VV S0442 S0442 - Evolution Sterilizer,VAC,54in,Stm,Dd Hng,Lr,R2W,480V 38 Wide VV S0495 S0495 - Loading Car & Transfer Carriage, 24x36x48 Chamber VV S0940 S0940 - Washer-Disinfector,STM,1DO,RSCD1WLL,26X24X24 Cham VV S1905 S1905 - Window, Sliding Service CC
S2615A S2615A - Automatic Endoscope Reprocessor VV S2627 S2627 - Washer, Fiber Scope VV S2635 S2635 - Innowave Ultrasonic SNGL Chamber CAB F-S VV S5505 S5505 - Sterilizer, Hydrogen Peroxide Gas, 3.5 cu ft Cham 33Inches VV
U - USER SPECIFIC ITEMS
U0040 _0040 - Trophon Disinfectant Processor VV U0042 _0042 - Incubator, Biological Indicator 12"x 12" VV U0049 _0049 - Micro Scrubber, Floor, Automatic 12"x 12" VV U0053 _0053 - Dispensing System, Cleaning Solution 12"x 12" VV U0070 U0070 - Accu Hold System - Wall Mounted / 3 Container VV U0071 U0071 - Wall Mounted / 3 Container 2 VV U0080 U0080 - SCS Load/Unload Conveyor System, Single Load VV U0081 U0081 - Loading Car & Transfer Carriage VV U0082 U0082 - SCS Motorized Return Conveyor System VV U0090 U0090 - System, Deionized, Water VV
PLAN
NORTH
A E
BC
D
KEY PLAN
F
SCALE: 1/4" = 1'-0"
0 2' 4' 8'
GROUND LEVEL F.F.E. = 378.00'
STORAGE,
STERILE
DURABLES
GE-113
CASE CART
STERILE AREA
GE-114
P2000
P3200
19 2116
SPS BREAKDOWN
ROOM
GD-122
EUSS ROOM
GD-125
F2010
A5075
NN
LL
KK
JJ
AUTOMATED
CART WASH
GE-113D
CLEAN
WORKROOM
INSTRUMENT SET
ASSEMBLY
GE-111
STERILIZER
ROOM
GE-110
DECONTAMINATION
WORK AREA
GE-107
ANTEROOM,
SCOPE
PROCESSING
GE-112A
STERILE/CLEAN
DUMBWAITER CHASE
FEC
FEC
NOTES:
1. P2000 AND P5210 FIXTURES ALSO REQUIRE "P2450 - VALVE, MIXING,
THERMOSTATIC" COMPONENTS FOR EACH INSTANCE. G.C. RESPONSIBLE
FOR PROVIDING AND INSTALLING FOR EACH INSTANCE WHERE A P2000
OR P5210 FIXTURE IS REQUIRED; P2450 - "CC".
2. A1014 ALSO REQUIRES "A1010 - TELECOMMUNICATIONS OUTLET" FOR
EACH INSTANCE. G.C. RESPONSIBLE FOR PROVIDING AND INSTALLING
A1010 - "CC".
3. A5212 WILL ALSO REQUIRE "A5220 - BRACKET, TELEVISION, WALL
BACKING." G.C. RESPONSIBLE FOR PROVIDING AND INSTALLING AT EACH
INSTANCE; A5220 - "CC".
4. GC RESPONSIBLE FOR COORDINATING ALL ACCESSORIES, FIXTURES, AND
EQUIPMENT BETWEEN FLOOR PLANS, RCPs, INTERIOR ELEVATIONS, EQUIPMENT PLANS, AND ALL OTHER DISCIPLINE SPECIFIC (MEP,FP)
DRAWINGS AS WELL.
5. GC RESPONSIBLE FOR COORDINATING ALL WALL MOUNTED EQUIPMENT
WITH "EQUIPMENT MOUNTING LEGEND" LOCATED IN GI DRAWINGS.
6. FEC - FIRE EXTINGUISHER CABINET; REF SPECIFICATIONS.
7. GC TO COORDINATE ALL WALL PENETRATIONS AND ROUGHT OPENINGS
PRIOR TO INSTALLATION OF RESINOUS WAINSCOT.
EQUIPMENT LEGEND
CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
VA FURNISHED,
VA INSTALLED
VA FURNISHED,
CONSTRACTOR INSTALLED
JOINT SCHEDULE
NUMBER REFERS TO
EQUIPMENT LISTED
IN 'MIL-STD 1691
MASTER EQUIPMENT
LIST' DOCUMENT
CC
VV
VC
JSN
NEW UNRATED PARTITION
NEW / EXISTING 2-HOUR BARRIER
EXISTING PARTITION, TO BE
REMOVED
EXISTING PARTITION, TO REMAIN
INDICATES AREA NOT IN
CONTRACT
NEW / EXISTING 1-HOUR BARRIER
PLUMBING TRENCHES
U.S. Department of Veterans Affairs
CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
Revisions: Date:
VA FORM 08 - 6231
FULLY SPRINKLERED
MISSION CRITICAL
CONSTRUCTION DOCUMENTS
5/ 3/
:5
4:
A M
C :\U se rs
\jc or de ll\
R ev it Lo ca l\5
-1
8-
8_
SP
S_ Ar ch F in al
S ub m is si on
_A D
D _J
AC
O
B.
C
O R
D
EL
L.
rv t
ENLARGED EQUIPMENT PLAN @
STORAGE & PACKAGE PREP
CONSTRUCTION
DOCUMENTS SUBMISSION
RENOVATE SPS / INSTALL
STERILIZERS
JLM MEMORIAL VETERANS HOSPITAL
2021.04.30 JDM TSS
598-18-108
QH402
JLM
JDA PROJECT #: D-18-02
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
FIRE PROTECTION
LACEY FIRE PROTECTION
ENGINEERING, LLC
P.O. BOX 723
GREENBRIER AR 72058
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
1/4" = 1'-0"F1 EQUIPMENT PLAN - GROUND LEVEL - STORAGE @ PACKAGE PREP
PLAN
NORTH
A E
BC
D
KEY PLAN
F
SCALE: 1/4" = 1'-0"
0 2' 4' 8'
EQUIPMENT SCHEDULE - QH402
JSN # DESCRIPTION
JSN_VA
ACQ/INS
ASSIGNMENT
A - ARCHITECTURAL
A5075 A5075 - Dispenser, Soap VV A5082 A5082 - Dispenser, Paper Towel, Sensor, Hands
Free
VV
F - FURNITURE AND FURNISHINGS
F2010 F2010 - Basket, Waste Paper, Step-On VV
P - PLUMBING FIXTURES
P2000 P2000 - Eyewash, Wall Mounted, Hands-Free CC P3200 P3200 - Lavatory, Viteous China, Slab Type
WSens Op Fauc
CC
GROUOND FLOOR F.F.E. = 374.00'
EQUIPMENT LEGEND
CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
VA FURNISHED,
VA INSTALLED
VA FURNISHED,
CONSTRACTOR INSTALLED
JOINT SCHEDULE
NUMBER REFERS TO
EQUIPMENT LISTED
IN 'MIL-STD 1691
MASTER EQUIPMENT
LIST' DOCUMENT
CC
VV
VC
JSN
A5160
M2035
F2020
F0601
M0507
F2000
F0220
F0220F0220
F0220
F0220
F0220
A1020 F0765F0765 P5210
P3200 x4
TRAINING ROOM
GE-106
ALCOVE, PPE
GE-107F
MEN
GE-109
WOMEN
GE-108
CORRIDOR
CG-38A
F3200
A1030
F2000
A1080 A1012
A5075
P3200
A1067 F2010
A5090
A5200
A5200
A1012
A1080 F2000
A1030
A5075 P3200
A1067
A5082
F2010 x9 x9
P9050
P9050
A5082
RR
A5145
A5145
DECONTAMINATION
WORK AREA
GE-107
HAZARD
STORAGE
GE-107E
A5075
A5145
A5082
A5109.2
A5109.1
A5077
M0506
A5212
MILWORK, SINK AND ICE MACHINE
RELOCATED TO THIS LOCATION
SCRUB EX EQUIPMENT
TO BE REINSTALLED
A5109.1
A5109.2
FEC
STERILIZATION
CHASE
GE-110B
LOGISTICS
AIR-LOCK
GD-124
SPS BREAKDOWN
ROOM
GD-122
EUSS ROOM
GD-125
18 1917
HH
STORAGE,
STERILE
DURABLES
GE-113
CASE CART
STERILE AREA
GE-114
EX
IS
TI
N
G V
ER
TI
C
AL
FI
LE
S
TO
R
AG
E
SY
ST
EM
FEC
NEW UNRATED PARTITION
NEW / EXISTING 2-HOUR BARRIER
EXISTING PARTITION, TO BE
REMOVED
EXISTING PARTITION, TO REMAIN
INDICATES AREA NOT IN
CONTRACT
NEW / EXISTING 1-HOUR BARRIER
PLUMBING TRENCHES
NOTES:
1. P2000 AND P5210 FIXTURES ALSO REQUIRE "P2450 - VALVE, MIXING,
THERMOSTATIC" COMPONENTS FOR EACH INSTANCE. G.C. RESPONSIBLE
FOR PROVIDING AND INSTALLING FOR EACH INSTANCE WHERE A P2000
OR P5210 FIXTURE IS REQUIRED; P2450 - "CC".
2. A1014 ALSO REQUIRES "A1010 - TELECOMMUNICATIONS OUTLET" FOR
EACH INSTANCE. G.C. RESPONSIBLE FOR PROVIDING AND INSTALLING
A1010 - "CC".
3. A5212 WILL ALSO REQUIRE "A5220 - BRACKET, TELEVISION, WALL
BACKING." G.C. RESPONSIBLE FOR PROVIDING AND INSTALLING AT EACH
INSTANCE; A5220 - "CC".
4. GC RESPONSIBLE FOR COORDINATING ALL ACCESSORIES, FIXTURES, AND
EQUIPMENT BETWEEN FLOOR PLANS, RCPs, INTERIOR ELEVATIONS, EQUIPMENT PLANS, AND ALL OTHER DISCIPLINE SPECIFIC (MEP,FP)
DRAWINGS AS WELL.
5. GC RESPONSIBLE FOR COORDINATING ALL WALL MOUNTED EQUIPMENT
WITH "EQUIPMENT MOUNTING LEGEND" LOCATED IN GI DRAWINGS.
6. FEC - FIRE EXTINGUISHER CABINET; REF SPECIFICATIONS.
7. GC TO COORDINATE ALL WALL PENETRATIONS AND ROUGHT OPENINGS
PRIOR TO INSTALLATION OF RESINOUS WAINSCOT.
U.S. Department of Veterans Affairs
CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
Revisions: Date:
VA FORM 08 - 6231
FULLY SPRINKLERED
MISSION CRITICAL
CONSTRUCTION DOCUMENTS
5/ 3/
:5
5:
A M
C :\U se rs
\jc or de ll\
R ev it Lo ca l\5
-1
8-
8_
SP
S_ Ar ch F in al
S ub m is si on
_A D
D _J
AC
O
B.
C
O R
D
EL
L.
rv t
ENLARGED EQUIPMENT PLANS @
MISC. ROOMS
CONSTRUCTION
DOCUMENTS SUBMISSION
RENOVATE SPS / INSTALL
STERILIZERS
JLM MEMORIAL VETERANS HOSPITAL
2021.04.30 JDM TSS
598-18-108
QH403
JLM
JDA PROJECT #: D-18-02
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
FIRE PROTECTION
LACEY FIRE PROTECTION
ENGINEERING, LLC
P.O. BOX 723
GREENBRIER AR 72058
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
PLAN
NORTH
A E
BC
D
KEY PLAN
F
SCALE: 1/4" = 1'-0"
0 2' 4' 8'
1/4" = 1'-0"C3 EQUIPMENT PLAN - GROUND LEVEL - TRAINING ROOM / RESTROOMS
1/4" = 1'-0"F3 EQUIPMENT PLAN - GROUND LEVEL - LOGISTICS ANTEROOM
GRAPHIC LEGEND
EQUIPMENT SCHEDULE - QH403
JSN # DESCRIPTION
JSN_VA
ACQ/INS
ASSIGNMENT
A - ARCHITECTURAL
A1012 A1012 - Telephone, Wall Mounted, 1 Line 12'' x 12'' VV A1020 A1020 - Telephone, Conferencing System 12 x 12 VV A1030 A1030 - Locker, 2 Person, Over Under CC A1067 A1067 - Mirror, Float Glass, ADA Accessible CC A1080 A1080 - Mirror, Posture, Wall Mounted 28"x 6 CC A5075 A5075 - Dispenser, Soap VV A5077 A5077 - Dispenser, Hand Sanitzer, Hands free VV A5082 A5082 - Dispenser, Paper Towel, Sensor, Hands Free VV A5090 A5090 - Dispenser, Sanitary Napkin, SS, Surface Mounted VV
A5109.1 A5109 - 42" Grab Bar, 1-1/4" Dia., SS, 2 Wall, W/C Accessible CC A5109.2 A5109 - 36" Grab Bar, 1-1/4" Dia., SS, 2 Wall, W/C Accessible CC A5145 A5145 - Hook, Garment, Double CC A5160 A5160 - Shelf, 8 in Depth, SS, Surface Mounted CC A5200 A5200 - Dispenser, Toilet Tissue, SS, 2-Roll, Surface Mntd CC A5212 A5212 - Bracket, Television, Wall-Mounted, Tilt/Angle 32"x 4" VV
F - FURNITURE AND FURNISHINGS
F0220 F0220 - Chair, Conference CC F0601 F0601 - Credenza, Performance 120"x 26" CC F0765 F0765 - Table, Folding_Nesting CC F2000 F2000 - Basket, Wastepaper VV F2010 F2010 - Basket, Waste Paper, Step-On VV F2020 F2020 - Can, Trash, 44 Gallon VV F3200 F3200 - Clock, Battery, 12in Dia VV
M - MISCELLANEOUS
M0506 M0506 - Television, Flat Screen VV M0507 M0507 - Video Teleconferencing System VV M2035 M2035 - Rack, Storage, Wire, CRS VV
P - PLUMBING FIXTURES
P3200 P3200 - Lavatory, Viteous China, Slab Type WSens Op Fauc CC P5210 P5210 - Shower, Safety, Freestanding, With Eye-Face Wash CC P9050 P9050 - Toilet, Wall Hung, Siphon Jet CC
GROUND FLOOR F.F.E. = 374.00'
GROUND FLOOR F.F.E. = 374.00'
V
W
X
SCOPE STORAGE
AREA
5B-118
MED GAS
TOWER
CH
AS
E
SCOPE
PROCESSING /
HLD ROOM
5B-119
DECONTAMINATION
WORK AREA
5B-120
ALCOVE, PPE
5B-120A
ANTEROOM,
SCOPE
PROCESSING
5B-119A
M2035
F2020 A5160
F3200
M1801
CT050.5
S2627
A5077
A5075 F2010
A1066
A5080 P3200
A5077
A5075
F2010 P3200A1066
M3072 P3200
P6150
P2000
A5106
A5080
A5075
A5077
M1801
S1905
S1905
P5210 x3
CT050.1
A5080
A1066
P6150
P3200 A1066
A5075 A5077
A1014
SCOPE STORAGE
VEST
5B-118A
F2010
A1014 A5080
WW
VV
XX
CH
AS
E
S2615
S2615
S2615
M3160
M3160
M3160
S2615
WORK STATION
A5145A5145A5145
EQUIPMENT LEGEND
CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
VA FURNISHED,
VA INSTALLED
VA FURNISHED,
CONSTRACTOR INSTALLED
JOINT SCHEDULE
NUMBER REFERS TO
EQUIPMENT LISTED
IN 'MIL-STD 1691
MASTER EQUIPMENT
LIST' DOCUMENT
CC
VV
VC
JSN
NEW UNRATED PARTITION
NEW / EXISTING 2-HOUR BARRIER
EXISTING PARTITION, TO BE
REMOVED
EXISTING PARTITION, TO REMAIN
INDICATES AREA NOT IN
CONTRACT
NEW / EXISTING 1-HOUR BARRIER
PLUMBING TRENCHES
NOTES:
1. P2000 AND P5210 FIXTURES ALSO REQUIRE "P2450 - VALVE, MIXING,
THERMOSTATIC" COMPONENTS FOR EACH INSTANCE. G.C. RESPONSIBLE
FOR PROVIDING AND INSTALLING FOR EACH INSTANCE WHERE A P2000
OR P5210 FIXTURE IS REQUIRED; P2450 - "CC".
2. A1014 ALSO REQUIRES "A1010 - TELECOMMUNICATIONS OUTLET" FOR
EACH INSTANCE. G.C. RESPONSIBLE FOR PROVIDING AND INSTALLING
A1010 - "CC".
3. A5212 WILL ALSO REQUIRE "A5220 - BRACKET, TELEVISION, WALL
BACKING." G.C. RESPONSIBLE FOR PROVIDING AND INSTALLING AT EACH
INSTANCE; A5220 - "CC".
4. GC RESPONSIBLE FOR COORDINATING ALL ACCESSORIES, FIXTURES, AND
EQUIPMENT BETWEEN FLOOR PLANS, RCPs, INTERIOR ELEVATIONS, EQUIPMENT PLANS, AND ALL OTHER DISCIPLINE SPECIFIC (MEP,FP)
DRAWINGS AS WELL.
5. GC RESPONSIBLE FOR COORDINATING ALL WALL MOUNTED EQUIPMENT
WITH "EQUIPMENT MOUNTING LEGEND" LOCATED IN GI DRAWINGS.
6. FEC - FIRE EXTINGUISHER CABINET; REF SPECIFICATIONS.
7. GC TO COORDINATE ALL WALL PENETRATIONS AND ROUGHT OPENINGS
PRIOR TO INSTALLATION OF RESINOUS WAINSCOT.
U.S. Department of Veterans Affairs
CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
Revisions: Date:
VA FORM 08 - 6231
FULLY SPRINKLERED
MISSION CRITICAL
CONSTRUCTION DOCUMENTS
5/ 3/
:5
5:
A M
C :\U se rs
\jc or de ll\
R ev it Lo ca l\5
-1
8-
8_
SP
S_ Ar ch F in al
S ub m is si on
_A D
D _J
AC
O
B.
C
O R
D
EL
L.
rv t
ENLARGED EQUIPMENT PLANS -
5B
CONSTRUCTION
DOCUMENTS SUBMISSION
RENOVATE SPS / INSTALL
STERILIZERS
JLM MEMORIAL VETERANS HOSPITAL
2021.04.30 JDM JDB
598-18-108
QH404
JLM
JDA PROJECT #: D-18-02
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
FIRE PROTECTION
LACEY FIRE PROTECTION
ENGINEERING, LLC
P.O. BOX 723
GREENBRIER AR 72058
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
1/4" = 1'-0"F5 ENLARGED PLAN - 5B EQUIPMENT LAYOUT
EQUIPMENT SCHEDULE - QH404
JSN # DESCRIPTION
JSN_VA
ACQ/INS
ASSIGNMENT
A - ARCHITECTURAL
A1014 A1014 - Telephone, Wall Mounted, 1 Line, With Speaker 12"x 12" VV A1066 A1066 - Mirror, Float Glass CC A5075 A5075 - Dispenser, Soap VV A5077 A5077 - Dispenser, Hand Sanitzer, Hands free VV A5080 A5080 - Dispenser, Paper Towel VV A5106 A5106 - Waste_Disposal Unit, Sharps with Glove Dispenser VV A5145 A5145 - Hook, Garment, Double CC A5160 A5160 - Shelf, 8 in Depth, SS, Surface Mounted CC
C - FIXED CASEWORK
CT050.1 CT050 - Countertop, Stainless Steel 24"x 24" CC CT050.5 CT050 - Countertop, Stainless Steel 48"x 24" CC
F - FURNITURE AND FURNISHINGS
F2010 F2010 - Basket, Waste Paper, Step-On VV F2020 F2020 - Can, Trash, 44 Gallon VV F3200 F3200 - Clock, Battery, 12in Dia VV
M - MISCELLANEOUS
M1801 M1801 - Computer with Flat Panel Monitor VV M2035 M2035 - Rack, Storage, Wire, CRS VV M3072 M3072 - Frame, Infectious Waste Bag with Lid VV M3160 M3160 - Cabinet, Storage, Hanging Scopes VV
P - PLUMBING FIXTURES
P2000 P2000 - Eyewash, Wall Mounted, Hands-Free CC P3200 P3200 - Lavatory, Viteous China, Slab Type WSens Op Fauc CC P5210 P5210 - Shower, Safety, Freestanding, With Eye-Face Wash CC P6150 P6150 - Sink, Cage Washing, SS, Single Compartment, FS CC
S - STERILIZERS AND ASSOCIATED EQUIPMENT
S1905 S1905 - Window, Sliding Service CC S2615 S2615 - Endoscope Reprocessing System VV S2627 S2627 - Washer, Fiber Scope VV
PLAN
NORTH
A E
BC
D
KEY PLAN
F
SCALE: 1/4" = 1'-0"
0 2' 4' 8'FIFTH LEVEL F.F.E. = 464.67'
U.S. Department of Veterans Affairs
CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
Revisions: Date:
VA FORM 08 - 6231
FULLY SPRINKLERED
MISSION CRITICAL
CONSTRUCTION DOCUMENTS
5/ 3/
:5
5:
A M
C :\U se rs
\jc or de ll\
R ev it Lo ca l\5
-1
8-
8_
SP
S_ Ar ch F in al
S ub m is si on
_A D
D _J
AC
O
B.
C
O R
D
EL
L.
rv t
AXONS - FA1 EQUIPMENT
LAYOUTS
CONSTRUCTION
DOCUMENTS SUBMISSION
RENOVATE SPS / INSTALL
STERILIZERS
JLM MEMORIAL VETERANS HOSPITAL
2021.04.30 JDM JDB
598-18-108
QH901
JLM
JDA PROJECT #: D-18-02
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
FIRE PROTECTION
LACEY FIRE PROTECTION
ENGINEERING, LLC
P.O. BOX 723
GREENBRIER AR 72058
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
C7 FA1 - AXON - SW - CSDE1 - DECONTAMINATION WORK AREA - GROUND LEVELC1 FA1 - AXON - NW - CSDE1 - DECONTAMINATION WORK AREA - GROUND LEVEL
E1
FA1 - AXON - SW - CSCR1 - ANTEROOM, SOILED DROP-OFF/TRANSITION - GROUND
LEVEL E6 FA1 - AXON - SW - CSPE1 - ALCOVE, PPE - GROUND LEVEL
F1 FA1 - AXON - SE - JANC2 - JANITOR - GROUND LEVEL F6 FA1 - AXON - NW - CSWT1 - WATER TREATMENT & DETERGEANT - GROUND LEVEL
WASTE DISPOSAL UNIT SHARPS
WITH GLOVE DISPENSER
STAINLESS STEEL 3 SINKS
COUNTERTOP UNIT
CABINET WITH SLOPING TOP
STAINLESS STEEL COUNTERTOP
COMPUTER WITH FLAT PANEL
MONITOR
WALL MOUNTED WORKSTATION ARM
44 GALLON TRASH CAN
HANDHELD BAR CODE READER
STAINLESS STEEL 3 SINKS
COUNTERTOP UNIT
WASTE DISPOSAL UNIT SHARPS
WITH GLOVE DISPENSER
CABINET WITH SLOPING TOP
STAINLESS STEEL 3 SINKS
COUNTERTOP UNIT
CLOCK 12" DIA.
44 GALLON TRASH CAN
COMPUTER WITH FLAT PANEL
MONITOR
WALL MOUNTED WORKSTATION ARM
PAPER TOWEL DISPENSER
WALL MOUNTED SINK
HAND SANITIZER DISPENSER,
HANDS FREE
SOAP DISPENSER
44 GALLON TRASH CAN
WASTE DISPOSAL UNIT SHARPS
WITH GLOVE DISPENSER
INFECTIOUS WASTE BAG
FRAME WITH LID
HANDS FREE EYE WASH
STEP ON WASTE PAPER
BASKET
PAPER TOWEL DISPENSER
SOAP DISPENSER
SHELVING STORAGE
W/ADJUSTABLE SHELVES
DEIONIZED WATER
SYSTEM
AUTOMATIC DETERGENT
DISPENSER
WINDOWS, SLIDING
SERVICE
WINDOWS, SLIDING
SERVICE
E4
FA1 - AXON - NW - CSCR1 - ANTEROOM, SOILED DROP-OFF/TRANSITION - GROUND
LEVEL E9 FA1 - AXON - NE - CSPE1 - ALCOVE, PPE - GROUND LEVEL
WALL MOUNTED SINK
SURFACE MOUNTED
SHELVING
TRASH CAN
DOUBLE GARMET
HOOK
FREE STANDING
SAFETY SHOWER
WITH EYE-FACE
WASH
F4 FA1 - AXON - NW- JANC2 - JANITOR - GROUND LEVEL
JANITOR'S CART
MOP SINK
MOP BUCKET WITH
WRINGER
AUTOMATIC FLOOR
MICRO SCRUBBER
CLEANING SOLUTION
DISPENSING SYSTEM
SOLID STORAGE
SHELVING
EXISTING SOILED DUMB WAITER
SOAP DISPENSER
INFECTIOUS WASTE BAG HOLDER
INFECTIOUS WASTE BAG HOLDER
COMPUTER WITH FLAT PANEL
MONITOR
WALL MOUNTED WORKSTATION ARM
VERIFY EXACT LOCATION
WALL MOUNTED ACCU HOLD
SYSTEM W/ 3 CONTAINER BASE
PAPER TOWEL DISPENSER
SOAP DISPENSER
WALL MOUNTED SINK
HAND SANITIZER DISPENSER,
HANDS FREE
F9 FA1 - AXON - SW - CSWT1 - WATER TREATMENT & DETERGEANT - GROUND LEVEL
CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
Revisions: Date:
VA FORM 08 - 6231
FULLY SPRINKLERED
MISSION CRITICAL
CONSTRUCTION DOCUMENTS
5/ 3/
:5
5:
A M
C :\U se rs
\jc or de ll\
R ev it Lo ca l\5
-1
8-
8_
SP
S_ Ar ch F in al
S ub m is si on
_A D
D _J
AC
O
B.
C
O R
D
EL
L.
rv t
AXONS - FA2-FA3 EQUIPMENT
LAYOUTS
CONSTRUCTION
DOCUMENTS SUBMISSION
RENOVATE SPS / INSTALL
STERILIZERS
JLM MEMORIAL VETERANS HOSPITAL
2021.04.30 JDM JDB
598-18-108
QH902
JLM
JDA PROJECT #: D-18-02
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
FIRE PROTECTION
LACEY FIRE PROTECTION
ENGINEERING, LLC
P.O. BOX 723
GREENBRIER AR 72058
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
C1 FA2 - AXON - SW - CSSD1 - DECONTAMINATION ROOM - GROUND LEVEL C8 FA2 - AXON - NW - CSST1 - SCOPE STAGING ROOM - GROUND LEVELC5 FA2 - AXON - NE - CSSD1 - DECONTAMINATION ROOM - GROUND LEVEL
D5 FA2 - AXON - NE - CSAR1 - ANTEROOM, SCOPE PROCESSING - GROUND LEVEL
F1 FA2 - AXON - NE - CSSP1 - SCOPE PROCESSING / HLD ROOM - GROUND LEVEL
WASTE DISPOSAL UNIT SHARPS
WITH GLOVE DISPENSER
INFECTIOUS WASTE BAG
FRAME WITH LID
PAPER TOWEL DISPENSER
WALL MOUNTED SINK
HAND SANITIZER DISPENSER,
HANDS FREE
SOAP DISPENSER
STAINLESS STEEL 3 SINKS
COUNTERTOP UNIT
FREESTANDING SAFETY SHOWER
WITH EYE-FACE WASH
CLOCK 12" DIA.
COMPUTER WITH FLAT PANEL
MONITOR
WALL MOUNTED WORKSTATION ARM
SCOPE TRANSPORT CART
STAINLESS STEEL 3 SINKS
COUNTERTOP UNIT
FREE STANDING SAFETY
SHOWER WITH EYE-FACE WASH
SCOPE TRANSPORT CART
STAINLESS STEEL
COUNTERTOP
WASHER DISINFECTORCAVIWAVE ULTRASONIC
CLEANER
STAINLESS STEEL SHELF
INNOWAVE ULTRASONIC CLEANER
WALL MOUNTED SINK
HAND SANITIZER DISPENSER,
HANDS FREE
SOAP DISPENSER
STEP ON WASTE PAPER
BASKET
FLOAT GLASS MIRROR
PAPER TOWEL DISPENSER
WALL MOUNTED SINK
HAND SANITIZER DISPENSER,
HANDS FREE
SOAP DISPENSER
WALL MOUNTED TELEPHONE
WITH SPEAKER
STEP ON WASTE PAPER
BASKET
FLOAT GLASS MIRROR
CLOCK 12" DIA.
COMPUTER WITH FLAT
PANEL MONITOR
SCOPE TRANSPORT CART
STAINLESS STEEL
COUNTERTOP
AUTOMATIC ENDOSCOPE
REPROCESSOR
FIBER SCOPE
WASHER WINDOWS, SLIDING SERVICE
D1 FA2 - AXON - SW - CSST1 - SCOPE STAGING ROOM - GROUND LEVEL
EXISTING RELOCATED
STAINLESS STEEL 3 SINKS
COUNTERTOP UNIT
EXISTING RELOCATED
STAINLESS STEEL 3 SINKS
COUNTERTOP UNIT
SLIDING SERVICE
WINDOW
FREESTANDING SAFETY SHOWER
WITH EYE-FACE WASH
D8 FA2 - AXON - SE - CSAR1 - ANTEROOM, SCOPE PROCESSING - GROUND LEVEL
STEP ON WASTE PAPER
BASKET
FLOAT GLASS MIRROR
WALL MOUNTED SINK
PAPER TOWEL DISPENSER
WALL MOUNTED TELEPHONE
WITH SPEAKER
F5 FA2 - AXON - NW - CSSP1 - SCOPE PROCESSING / HLD ROOM - GROUND LEVEL
CLOCK 12" DIA.
COMPUTER WITH FLAT PANEL MONITOR
WALL MOUNTED TELEPHONE
WITH SPEAKER
STAINLESS STEEL COUNTERTOP
STAINLESS STEEL COUNTERTOP
AUTOMATIC ENDOSCOPE
REPROCESSOR
WINDOWS, SLIDING SERVICE
TROPHON, WALL MOUNTED
FIRE EXTINGUISHER CABINET
STAINLESS STEEL COUNTERTOP
CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
Revisions: Date:
VA FORM 08 - 6231
FULLY SPRINKLERED
MISSION CRITICAL
CONSTRUCTION DOCUMENTS
5/ 3/
:5
6:
A M
C :\U se rs
\jc or de ll\
R ev it Lo ca l\5
-1
8-
8_
SP
S_ Ar ch F in al
S ub m is si on
_A D
D _J
AC
O
B.
C
O R
D
EL
L.
rv t
AXONS - FA2-FA3 EQUIPMENT
LAYOUTS
CONSTRUCTION
DOCUMENTS SUBMISSION
RENOVATE SPS / INSTALL
STERILIZERS
JLM MEMORIAL VETERANS HOSPITAL
2021.04.30 JDM JDB
598-18-108
QH903
JLM
JDA PROJECT #: D-18-02
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
FIRE PROTECTION
LACEY FIRE PROTECTION
ENGINEERING, LLC
P.O. BOX 723
GREENBRIER AR 72058
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
B1 FA2 - AXON - SW - CSST1 - SCOPE STAGING ROOM - FIFTH LEVEL B9 FA2 - AXON - NW- CSSP1 - SCOPE PROCESSING / HLD ROOM - FIFTH LEVEL
D3 FA2 - AXON - SE - CSAR1 - ANTEROOM, SCOPE PROCESSING - FIFTH LEVEL D9 FA2 - AXON - SW - CSPE1 - ALCOVE, PPE - FIFTH LEVEL
B3 FA2 - AXON - N - CSDE1 - DECON AREA - FIFTH LEVEL
D1 FA2 - AXON - NE - CSSP1 - SCOPE PROCESSING / HLD ROOM - FIFTH LEVEL D6 FA2 - AXON - SW - CSAR1 - ANTEROOM, SCOPE PROCESSING - FIFTH LEVEL
F1 FA2 - AXON - NW - CSPE1 - ALCOVE, PPE - FIFTH LEVEL
B6 FA2 - AXON - SE - DECON AREA - FIFTH LEVEL
PAPER TOWEL DISPENSER
FLOAT GLASS MIRROR
SOAP DISPENSER
HANDS FREE HAND
SANITIZER DISPENSER
WALL MOUNTED SINK
STEP ON WASTE PAPER
BASKET
SILIDING SERVICE WINDOW SINK W/ CLEANUP COUNTER
COMPUTER WITH FLAT PANEL MONITOR
STAINLESS STEEL COUNTERTOP
HANDSFREE WALL MOUNTED EYEWASH
SILIDING SERVICE WINDOW
SHARPS WASTE DISPOSABLE
UNIT WITH GLOVES
INFECTIOUS WASTE BAG FRAME
WITH LID
FIBER SCOPE WASHER
ENDOSCOPE
REPROCESSOR SYSTEM
CLOCK
PAPER TOWEL DISPENSER
FLOAT GLASS MIRROR
SOAP DISPENSER
HANDS FREE HAND
SANITIZER DISPENSER
WALL MOUNTED SINK
STEP ON WASTE PAPER BASKET
FREE STANDING SAFETY SHOWER WITH
EYE-FACE WASH
COMPUTER WITH FLAT
PANEL MONITOR
STAINLESS STEEL COUNTERTOP
FLOAT GLASS MIRROR
SOAP DISPENSER
WALL MOUNTED SINK
STEP ON WASTE PAPER
BASKET
PAPER TOWEL DISPENSER
WALL MOUNTED TELEPHONE
SURFACE MOUNTED SHELF
44 GALLON TRASH CAN
WIRE STORAGE RACK
DOUBLE GARMENT HOOK (x3)
HANDS FREE PAPER
TOWEL DISPENSER
FLOAT GLASS MIRROR
SOAP DISPENSER
HANDS FREE HAND
SANITIZER DISPENSER
WALL MOUNTED SINK
HANDS FREE HAND
SANITIZER
DISPENSER
ENDOSCOPE
REPROCESSOR SYSTEM
FLOAT GLASS MIRROR
SOAP DISPENSER
WALL MOUNTED SINK
STEP ON WASTE PAPER
BASKET
DISPENSER, PAPER
TOWEL
EXISTING PASS THROUGH
WINDOW
CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
Revisions: Date:
VA FORM 08 - 6231
FULLY SPRINKLERED
MISSION CRITICAL
CONSTRUCTION DOCUMENTS
5/ 3/
:5
6:
A M
C :\U se rs
\jc or de ll\
R ev it Lo ca l\5
-1
8-
8_
SP
S_ Ar ch F in al
S ub m is si on
_A D
D _J
AC
O
B.
C
O R
D
EL
L.
rv t
AXONS - FA4-FA6 EQUIPMENT
LAYOUTS
CONSTRUCTION
DOCUMENTS SUBMISSION
RENOVATE SPS / INSTALL
STERILIZERS
JLM MEMORIAL VETERANS HOSPITAL
2021.04.30 JDM JDB
598-18-108
QH904
JLM
JDA PROJECT #: D-18-02
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
FIRE PROTECTION
LACEY FIRE PROTECTION
ENGINEERING, LLC
P.O. BOX 723
GREENBRIER AR 72058
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
C5 FA6 - AXON - SE - CFR01 - TRAINING ROOM - GROUND LEVEL C8 FA6 - AXON - SW - CSPE1 - ALCOVE, PPE - GROUND LEVELC1 FA4 - AXON - SW - CSSS1 - STERILIZATION ROOM - GROUND LEVEL
E5 FA6 - AXON - SE - TSSU1 - MEN - GROUND LEVEL
F1 FA6 - AXON - NE - TSSU1 - WOMEN - GROUND LEVEL
RELOCATED
MILLWORK W/
SINK & ICE MAKER
FLAT SCREEN TELEVISION
WALL MOUNTED TELEVISION BRACKET
PERFORMANCE CREDENZA
VIDEO TELECONFERENCING
SYSTEM
CONFERENCE CHAIRS
CONFERENCE CHAIRS
TELEPHONE CONFERENCING
SYSTEM
STAINLESS STEEL 8" SHELF
WIRE STORAGE RACK
STAINLESS STEEL FLOAT GLASS
MIRROR WITH SHELF
36" GRAB BAR
WALL HUNG TOILET
SOAP DISPENSER
HANDS FREE PAPER
TOWEL DISPENSER
STAINLESS STEEL
FLOAT GLASS MIRROR
WITH SHELF
WALL MOUNTED SINK
STEP ON WASTE PAPER
BASKET
36" GRAB BAR
SANITARY NAPKIN
DISPOSAL
WALL HUNG TOILET
2 ROLL TOILET TISSUE
DISPENSER
FOLDING TABLE WALL MOUNTED SINK
SOAP DISPENSER
HANDS FREE PAPER
TOWEL DISPENSER
E1 FA6 - AXON - SE - CSPE1 - ALCOVE, PPE - GROUND LEVEL
FREE STANDING SAFETY
SHOWER WITH EYE-
FACE WASH
44 GALLOON TRASH CAN
DOUBLE GARMET HOOK
x4
STEP ON WASTE PAPER
BASKET
WALL MOUNTED POSTURE
MIRROR
WALL MOUNTED
TELEPHONE
BATTERY CLOCK
HANDS FREE PAPER TOWEL
DISPENSER
WALL MOUNTED SINK
SURFACE MOUNTED TOILET
TISSUE DISPENSER
E8 FA6 - AXON - NW - TSSU1 - MEN - GROUND LEVEL
DOUBLE GARMET HOOK
OVER UNDER 2 PERSON LOCKER
x9
WASTE PAPER BASKET
SOAP DISPENSER
F5 FA6 - AXON - NE - TSSU1 - WOMEN - GROUND LEVEL Copy 1
WALL MOUNTED POSTURE
MIRROR
WALL MOUNTED
TELEPHONE
BATTERY CLOCK
DOUBLE GARMET HOOK
OVER UNDER 2 PERSON LOCKER
x9
WASTE PAPER BASKET
WASTEPAPER BASKET
SOAP DISPENSER
PAPER TOWEL DISPENSER
WALL MOUNTED SINK
LOADING CART &
TRANSFER CARRIAGE
STERILIZER
HYDROGEN PEROXIDE
STERILIZER
WALL MOUNTED
EYEWASH HANDS
FREE
HANDSANITZER
DISPENSER HANDSFREE
EXISTING SCRUB EX DISPENSER
FREE STANDING SAFETY
SHOWER WITH EYE-
FACE WASH
42" GRAB BAR
42" GRAB BAR
WASTE PAPER BASKET
FIRE EXTINGUISHER
FIRE ALARM NOTES:
F
P-C-D
F
P-C-D
951/4
P-C-D P-C-D
P-C-D
F
SLC
LEGEND:
FIRE ALARM 4" CEILING SPEAKER / STROBE
(WATT, CD, CIRCUITS)
FIRE ALARM 4" CEILING SPEAKER (WATT,
CIRCUIT)
FIRE ALARM WALL MOUNT STROBE (CD, CIRCUIT,
WP=WEATHER PROOF DEVICE AND SURFACE
MOUNT BACK BOX)
FIRE ALARM DIRECTIONAL LOUDSPEAKER (WATT,
CIRCUIT)
FIRE ALARM MANUAL PULL STATION (CIRCUIT)
NEW EST APS10A AUXILIARY POWER SUPPLY
WITH TWO AA30 AMPLIFIER CARDS, MODULES,
AND BATTERIES
FIRE ALARM NOTES:
1. FIRE ALARM SPEAKERS HAVE BEEN SELECTED
BASED ON ROOM SURFACES AND BACKGROUND
NOISE.
2. SPEAKERS WILL BE ADDED TO ENSURE AUDIBILITY
IN ALL AREAS.
3. CONTRACTOR SHALL ALLOW FOR ADJUSTING TAP
(WATTAGE) ONCE INSTALLED TO ACHIEVE BEST
INTELLIGIBILITY.
4. STIPA INTELLIGIBILITY READINGS SHALL BE TAKEN
TO ACHIEVE BEST RESULTS BASED ON WATTAGE
ONCE SPACE IS OCCUPIED.
5. STROBES HAVE BEEN SELECTED FOR THE ROOM
ENVIRONMENT AND CLEANING. WEATHER
RESISTANT (OUTDOOR) DEVICES WITH BACK
BOXES FOR SURFACE MOUNT HAVE BEEN
SELECTED IN DIRTY / WET AREAS.
6. DIRECTIONAL LOUDSPEAKERS HAVE BEEN
SELECTED FOR USE IN CERTAIN AREAS BASED ON
ANTICIPATED BACKGROUND NOISE AND
REFLECTIVE SURFACES.
7. A NEW STROBE AND AUDIO AMPLIFIER CABINET
WILL BE INSTALLED TO PROVIDED CIRCUITS FOR
THE SPS SMOKE ZONE. THE NEW PANEL WILL BE
LOCATED WHERE INDICATED.
8. TWO-HOUR CIRCUITS ARE NOT REQUIRED BASED
ON VA ALTERNATIVE DESIGN OF CONDUIT IN
SPRINKLERED BUILDING.
9. CONTRACTOR SHALL PROVIDE A NEW EST-APS10A
PANEL WITH TWO EST AA30 AMPLIFIER CARDS,
AND MODULES TO SERVE STROBES AND
SPEAKERS IN GROUND FLOOR SPS.
10. PROVIDE AN EST ZONED AUDIO AMPLIFIER/NAC
CARD WITHIN EXISTING EST PANEL 3 SERVING
AREA 5B TO SERVE NEW DEVICES IN 5B SPS.
11. CONTRACTOR TO RUN NEW 120VAC CIRCUIT FROM
EMERGENCY CABINET SHOWN FOR GROUND
PANEL.
12. EXISTING DEVICES SHALL BE REMOVED WHILE
MAINTAINING EXISTING CIRCUITS SERVING OTHER
AREAS / ZONES. PROVIDE STAINLESS STEEL
COVER PLATES ON EXISTING JUNCTION BOXES IN
FINISHED AREAS.
GENERAL FIRE PROTECTION NOTES:
1. FIRE PROTECTION COMPONENTS INCLUDING
SPRINKLERS, FIRE ALARMS, EXTINGUISHERS, ETC.
SHALL BE BASED ON CRITERIA OF VA FIRE
PROTECTION DESIGN MANUAL - 2015, NFPA 13 -
2016, NFPA 72 - 2016, NFPA 10-2018, NFPA 101 - 2018,
AND NFPA 99 - 2018.
2. FIRE PROTECTION AREAS OF WORK MAY EXTEND
OUTSIDE OF ARCHITECTURAL AREAS OF WORK.
REVIEW PLANS CLOSELY.
3. ALL CONSTRUCTION RELATED ACTIVITIES SHALL
FOLLOW NFPA 241 STANDARD FOR
SAFEGUARDING CONSTRUCTION, ALTERATION,
AND DEMOLITION OPERATIONS - 2013. ALL
CONTRACTORS SHALL BE VERSED IN AND FOLLOW
CRITERIA OF THIS STANDARD.
4. FIRE ALARM AND SPRINKLER SYSTEMS SHALL BE
ZONED TO COINCIDE WITH SMOKE
COMPARTMENTS IN ACCORDANCE WITH NFPA 99 -
2018. CURRENT SPRINKLER SYSTEM DOES
COINCIDE WITH SPS SMOKE ZONE. FIRE ALARM
DOES NOT APPEAR TO CURRENTLY MATCH.
FIRE ALARM VA DESIGN MANUAL NOTES:
1. DO NOT COMBINE FIRE ALARM CIRCUITS WITH
OTHER SYSTEMS SUCH AS BUILDING AUTOMATION,
ENERGY MANAGEMENT, SECURITY, ETC.
2. ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED IN
METAL RACEWAY SEPARATE FROM OTHER
SYSTEMS.
3. RED CONDUIT SHALL BE USED FOR FIRE ALARM
CIRCUITS.
4. WIRING INSTALLED IN METAL RACEWAY WITHIN
SPRINKLERED BUILDING HAS BEEN APPROVED AS
AN ALTERNATIVE TO 2-HOUR PATHWAY
SURVIVABILITY LEVEL 2 IN ACCORDANCE WITH
NFPA 72. AS SUCH, 2-HOUR CI CABLE IS NOT
REQUIRED.
5. FIRE ALARM CIRCUITS SHALL BE:
5.1. INITIATING DEVICE CIRCUITS: CLASS B
5.2. SIGNALING LINE CIRCUITS: CLASS B
5.2.1. T-TAPPING ADDRESSABLE CIRCUITS IS
ALLOWED
5.3. NOTIFICATION APPLIANCE CIRCUITS: CLASS B
5.4. COMMUNICATION BETWEEN FACU AND
NETWORK PANELS: CLASS X
5.5. CIRCUITS RUN BETWEEN PANELS IN
DIFFERENT BUILDINGS SHALL BE FIBER AND
CLASS X.
5.6. COORDINATE AND MATCH EXISTING COLORS
OF CIRCUITS AND WIRE TYPE FOR ALL FIRE
ALARM CIRCUITS.
ACTION PERFORMED >>
INITIATION SOURCE: .
GENERAL FIRE EVAC
WATER FLOW
SMOKE DETECTOR COMMON AREA
MANUAL PULL (FIRE)
DUCT DETECTOR
NA
SPRINKLER ISOLATION TAMPER
SHORT/GROUND/FAULT
NA
NA
R
E
L
E
A
S
E
D
O
R
L
C
K
S
T
R
O
U
B
I
G
N
A
T
M
N
P
N
M
O
T
E
F
I
A
E
A
K
R
O
B
E
S
A
L
A
G
N
F
S
I
N
I
T
O
R
I
N
G
E
X
T
E
R
I
W
T
A
U
R
I
G
O
W
N
A
S
H
S
P
E
C
T
I
H
A
C
R
E
L
E
A
H
L
D
O
P
O
R
S
S
U
P
E
R
V
I
S
O
Y
G
N
N
M
O
T
E
N
A
N
A
F3
OPERATION MATRIX
NOT TO SCALE
NEW FIRE ALARM STROBE / VOICE PANEL
BATTERY BATTERY
POWER
SUPPLY &
STROBES
MODULE
MODULE
AMPLIFIER CARD
EST AA30
CIRCUIT SPS-A1-?
D6
NEW EST APS10A FOR GROUND SPS AREA
NOT TO SCALE
AMPLIFIER CARD
EST AA30
CIRCUIT: SPS-A2-?
NAC1 (+)
NAC1 (-)
NAC2 (+)
NAC2 (-)
NAC3 (+)
NAC3 (-)
NAC4 (+)
NAC4 (-)
CIRCUIT SPS-V1-#; CALCULATED AT
1.5 AMPS AND 17.1 EOL VOLTAGE
CIRCUIT SPS-V2-#; CALCULATED AT
1.2 AMPS AND 17.9 EOL VOLTAGE
CIRCUIT SPS-V3-#; CALCULATED AT
1.0 AMPS AND 18.2 EOL VOLTAGE
CIRCUIT SPS-V4 - SPARE
F7
STROBE CIRCUITS FROM APS10A
NOT TO SCALE
SPS VISUAL CIRCUITS
3.7 STROBE AMPS
I N
P U
T
A
X
C
R
C U
I T
S
CIRCUIT SPS-A1-#; CALCULATED AT
7.75 WATTS WITH 22.25W SPARE
SPS AUDIO CIRCUITS
17 WATT USED,
43 WATTS AVAILABLE
CIRCUIT SPS-A1-#; CALCULATED AT
9.2 WATTS WITH 20.8W SPARE
PANEL NOTES:
1. PROVIDE NEW 12OVAC POWER
WITH SURGE PROTECTION TO NEW
AUDIO / VISUAL PANEL.
2. PROVIDE CONNECTIONS BETWEEN
PANELS PER MFG.
3. SYSTEM IS NOT CURRENTLY
CONFIGURED FOR ZONED
EVACUATION, BUT WILL BE IN THE
FUTURE. THUS, ALL NEW WORK
SHALL BE PROVIDED TO FACILITATE
FUTURE ZONED NOTIFICATION AND
RELOCATION.
4. PRODUCT BRAND AND MODEL IS
REQUIRED AS CALLED OUT FOR
COMPATIBILITY WITH EXISTING
SYSTEM.
5. LOCATE WHERE SHOWN ON
DRAWINGS.
6. DO NOT MIX POWER LIMITED AND
NON-POWER LIMITED CIRCUITS
(INCLUDING AC CIRCUITS WITH DC
CIRCUITS).
7. PANEL SHALL BE ON EMERGENCY
POWER AC CIRCUIT.
8. PROVIDE CIRCUIT BREAKER LOCK
AND LABEL IN ACCORDANCE WITH
NFPA 72.
9. PROVIDE BATTERIES SIZED TO
PROVIDE MINIMUM 15 MINUTES
ALARM UPON LOSS OF POWER.
EMERGENCY GENERATOR WILL
PROVIDE REMAINDER.
DEMOLITION NOTES:
1. THERE ARE A FEW EXISTING FIRE ALARM DEVICES
WITHIN THE EXISTING AREAS TO BE RENOVATED.
THOSE IDENTIFIED ARE INDICATED ON SHEET
FA-101.
2. CONTRACTOR TO REMOVE ANY EXISTING
NOTIFICATION DEVICES WITHIN FIRE ALARM AREA
OF WORK THAT WERE MISSED AND ARE NOT
IDENTIFIED.
3. EXISTING NOTIFICATION DEVICES SHALL BE
REMOVED WITHOUT IMPACTING OTHER DEVICES
ON THE EXISTING CIRCUITS. AS SUCH, CIRCUITS
SHALL REMAIN AND JUNCTION BOXES COVERED
WITH BLANK STAINLESS STEEL COVER.
4. EXISTING JUNCTION BOXES SHALL REMAIN
ACCESSIBLE FOR SERVICE. IF THEY ARE IN A
LOCATION WHERE THEY MUST BE REMOVED OR
RELOCATED, ENSURE THEY ARE ACCESSIBLE
SUCH AS ABOVE THE CEILING. NO ELECTRICAL
JUNCTION BOXES SHALL BE HIDDEN IN ANY WALL.
5. EXISTING MANUAL PULL STATIONS MAY BE
RE-USED / RELOCATED FOR NEW CONFIGURATION.
6. CONTRACTOR TO MAINTAIN AND TEST ALL
EXISTING CIRCUITS. THIS INCLUDES TESTING
DEVICES OUTSIDE WORK AREA FOR ANY IMPACT.
PROVIDE SURGE PROTECTION
ON EMERGENCY 120VAC
CIRCUIT.
PROVIDE MFG DATE ON
BATTERIES PER NFPA 72, NOT
INSTALLATION DATE
TEMPORARY WATER SUPPLY TO PARKING LOT TRAILERS:
1. CONTRACTOR SHALL PROVIDE TEMPORARY PIPED
PROTECTION TO SPS TRAILERS IN PARKING LOT.
2. TRAILERS ARE PROVIDED WITH SPRINKLERS AND WILL
HAVE A SINGLE POINT OF CONNECTION PROVIDED BY MFG.
3. PROVIDE SCHEDULE 40 BLACK STEEL, PAINTED.
4. COORDINATE WITH TRAILER PROVIDER FOR POINT OF
CONNECTION.
5. CONTRACTOR SHALL PROVIDE A CITY METER AND
BACKFLOW PREVENTER FOR HYDRANT USE. SPRINKLERS
SHALL BE SUPPLIED FROM HYDRANT ADJACENT TO
TRAILERS.
6. CONTRACTOR TO PROVIDE HEAT TRACING WITHIN
FIBERGLASS INSULATION WRAP, COVERED BY GALVANIZED
METAL WRAP.
7. INSULATION AND HEAT TRACING TO INCLUDE HYDRANT AND
METER WITH ACCESS TO HYDRANT VALVE AND METER FOR
CITY READINGS.
8. PROVIDE INSULATED BOX CONSTRUCTED OF EXTERIOR
GRADE PLYWOOD OVER HYDRANT WHICH CAN BE READILY
REMOVED TO ACCESS HYDRANT.
8.1. PAINT BOX RED TO MATCH FIRE HYDRANT.
9. CONTRACTOR SHALL PROVIDE ELECTRICAL POWER FOR
HEAT TRACING ON DEDICATED BREAKER.
ADDITIONAL SPRINKLER NOTES:
FIRE ALARM MONITORING OF TEMPORARY TRAILERS:
1. TEMPORARY TRAILERS WILL BE PROVIDED IN PARKING
LOT FOR SPS FUNCTIONS. CONTRACTOR SHALL
PROVIDE FOR TEMPORARY MONITORING OF FIRE ALARM
SYSTEM PROVIDED WITH TRAILERS.
2. PROVIDE SLC FROM MAIN BUILDING IN MINIMUM 3/4"
ELECTRICAL PLASTIC CONDUIT WITH CABLE LISTED FOR
WET LOCATIONS.
2.1. ROUTE CONDUIT UNDER/WITH WALKWAY BETWEEN
BUILDING AND TRAILERS.
2.2. FIELD COORDINATE BEST ROUTING AND ENTRY/EXIT
POINTS WITH USER AND TRAILER MFG.
2.3. FIELD COORDINATE WITH USER POINT OF
CONNECTION TO EXISTING SLC WITHIN MAIN
BUILDING.
3. PROVIDE ISOLATION MODULE AND SURGE PROTECTION
ON SLC AT POINT OF ENTRY TO MAIN VA BUILDING.
4. PROVIDE MONITORING MODULES TO MONITOR ALARM,
SUPERVISORY, AND TROUBLE OF TRAILER ALARM
CONDITION.
U.S. Department of Veterans Affairs
CONSULTANTS ARCHITECT/ENGINEER OF RECORD
STAMP
Office of
Construction and Facilities
Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
Revisions: Date:
VA FORM 08 - 6231
FULLY SPRINKLERED
CONSTRUCTION
DOCUMENTS SUBMISSION
RENOVATE SPS / INSTALL
STERILIZERS
JLM MEMORIAL VETERANS HOSPITAL
2020.01.06 JM SWL
598-18-108
JLM
JDA PROJECT #: D-18-02
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
FIRE PROTECTION
LACEY FIRE PROTECTION
ENGINEERING, LLC
P.O. BOX 723
GREENBRIER, AR 72058
CONSTRUCTION DOCUMENTS SUBMISSION
MISSION CRITICAL
37345
SCOTT WADE
LACEY
R e g i s t e r e d
P r o f e s s i o n a l Eng in e e r
F i r e
P r o t e c t i o n
C
E
R
T
I
F
I C
A
T
E
N
O
D A
T
E
S
I
G N
E
D
A
R
I
Z
O
N A
U
S
A
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
900 S. SHACKLEFORD, SUITE 300
LITTLE ROCK, AR 72211
FIRE ALARM NOTES & DETAILS
FA001
AutoCAD SHX Text 01/06/2020
NEW UNRATED PARTITION
NEW / EXISTING 2-HOUR BARRIER
EXISTING PARTITION, TO BE REMOVED
(SEE ARCH)
EXISTING PARTITION, TO REMAIN
INDICATES AREA NOT IN CONTRACT
NEW / EXISTING 1-HOUR BARRIER
MEN
GE-109
CLEAN
WORKROOM
INSTRUMENT SET
ASSEMBLY
GE-111
SCOPE
PROCESSING /
HLD ROOM
GE-112
WATER
TREATMENT &
DETERGENT
GE-107D
STORAGE,
STERILE
DURABLES
GE-113
ANTEROOM,
SOILED
DROP-OFF/TRANSITION
GE-107A
DECONTAMINATION
WORK AREA
GE-107
AUTOMATED
CART WASH
GE-113D
ALCOVE, PPE
GE-107F
C O
R R
I D
O R
C G
A
TRAINING ROOM
GE-106
WOMEN
GE-108
CASE CART
STERILE AREA
GE-114
ANTEROOM,
SCOPE
PROCESSING
GE-112A
LOGISTICS
AIR-LOCK
GD-124
HAZARD
STORAGE
GE-107E
STERILIZER
ROOM
GE-110
ALCOVE, PPE
GE-107B
JANITOR
GE-107C
STEAM
STERILIZATION
CHASE
GE-110A
SPS BREAKDOWN
ROOM
GD-122
EUSS ROOM
GD-125
V
W
X
DECONTAMINATION
WORK AREA
5B-120
ALCOVE, PPE
5B-120A
SCOPE STORAGE
AREA
5B-118
C H
A S
E
ANTEROOM,
SCOPE
PROCESSING
5B-119A
SCOPE
PROCESSING /
HLD ROOM
5B-119
SCOPE STORAGE
VEST
5B-118A
W
V
F
S P
S V
S P
S A
1W
P
F
SPS-V3-9
F
SPS-V3-7
WP
WP
F
S
P
S
A
WP
F
S
P
S
A
F
S
P
S
A
F
S P
S V
F
S P
S V
F
S P
S V
WP WP
WP
751/4
SPS-V3-5
SPS-A2-14
151/8
SPS-V3-8
SPS-A2-12
151/4
SPS-V3-2
SPS-A2-17
151/4
SPS-V3-3
SPS-A2-16
951/4
SPS-V1-3
SPS-A1-3
951/4
SPS-V1-1
SPS-A1-1
951/4
SPS-V1-2
SPS-A1-2
951/4
SPS-V2-4
SPS-A2-4
SPS-V2-9 EOL
SPS-A2-9
SPS-V2-6
SPS-A2-7
1/4
SPS-A2-5
1/4
SPS-A2-2
1/4
SPS-A1-4
1/4
SPS-A2-19 EOL
151/4
SPS-V3-4
SPS-A2-15
151/8
P-C-D P-C-D
151/8
P-C-D P-C-D
151/8
P-C-D P-C-D
151/8
P-C-D P-C-D
F
SLC
F
SLC
F
SLC
SPS-V1-7
SPS-A1-8
SPS-V1-6
SPS-A1-7
POD-D
POD-E
POD-C
POD-E
POD-E
POD-B
151/4
SPS-V3-1
SPS-A2-18
F
SLC
POD BOUNDARY AS INDICATED ON VA
DRAWINGS EVEN THOUGH RATED WALL IS
OTHER SIDE OF CORRIDOR.
F
SLC
F
SLC
F
30 1/4
SPS-V2-7
SPS-A2-8
WP
F
SPS-V2-8
WP
151/8
P-C-D P-C-D
EXISTING 24VDC
POWER SUPPLIES,
MISC FA PANELS
EXIST NETWORK EQUIP
EXISTING
HEAD-END FACU
120 VAC EMERGENCY
BREAKERS, PROVIDE NEW
BREAKER AND CIRCUIT TO NEW
FA PANEL.
1/4
SPS-A1-11
SPS-V1-8
SPS-A1-9
151/2
SPS-V1-9
SPS-A1-10
SPS-V2-5
SPS-A2-6
151/4
SPS-V1-10
SPS-A1-12
151/4
SPS-V1-11
SPS-A1-14
151/4
SPS-V1-12 EOL
SPS-A1-15 EOL
SPS-V1-5
SPS-A1-6
SPS-V1-4
SPS-A1-5
1/4
SPS-A1-13
NEW EST APS10A CABINET
RELOCATE EXISTING ELECTRICAL
BOX TO SIDE OF COLUMN
PROVIDE NECESSARY CIRCUITS
BETWEEN HEAD-END FACU AND NEW
APS10A CABINET AND CARDS FOR
VOICE, STROBE TRIGGER, AND
MONITORING TROUBLES.
EXISTING PULL STATION AND SPEAKER TO REMAIN
EXISTING FA
NOTIFICAITON TO BE
REMOVED AND
COVERED
EXISTING FA
NOTIFICATION TO
BE REMOVED
EXISTING PULL TO
BE RELOCATED,
REMOVE
NOTIFICATION
NEW PULL LOCATION
FIRE ALARM SCOPE:
NOTE THAT THE AREA OF FIRE ALARM WORK IS LIKELY DIFFERENT THAN THE
AREA OF ARCHITECTURAL WORK OR OTHER DISCIPLINES. CONTRACTOR
SHALL PAY CLOSE ATTENTION TO DRAWINGS AND UPGRADE RESPECTIVE
AREAS SHOWN.
F
S P
S V
S P
S A
PROVIDE AN EST ZONED
AUDIO AMPLIFIER / NAC CARD
WITHIN EXISTING EST PANEL 3
SERVING AREA 5B TO SERVE
NEW DEVICES IN 5B SPS.
CONTRACTOR TO IDENTIFY
BEST CIRCUIT ROUTE FOR 5B
DEVICES ON NEW CIRCUIT.
1/8" = 1'-0"
F1
FIRE ALARM PLAN - SPS GROUND LEVEL
1/8" = 1'-0"
C8
FIRE ALARM PLAN - AREA 5B ON FIFTH FLOOR
U.S. Department of Veterans Affairs
CONSULTANTS ARCHITECT/ENGINEER OF RECORD
STAMP
Office of
Construction and Facilities
Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
Revisions: Date:
VA FORM 08 - 6231
FULLY SPRINKLERED
CONSTRUCTION
DOCUMENTS SUBMISSION
RENOVATE SPS / INSTALL
STERILIZERS
JLM MEMORIAL VETERANS HOSPITAL
2020.01.06 JM SWL
598-18-108
JLM
JDA PROJECT…
This is the start of the file's text. The full file is on GovTribe.