This document package includes an electrical drawing and schedule for a federal construction project along with the corresponding solicitation notice. The solicitation is for construction services to build an air handling tower at a Veterans Affairs medical center in Omaha, Nebraska. The project is set aside for service-disabled veteran-owned small businesses. Responses are due based on the solicitation number 36C26321R0102 issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23. The electrical drawing and schedule provide details on the circuiting and load information to support the construction of the air handling tower.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BRANCH CIRCUIT WIRING KEY
WIRE
ID 2 WIRE 3 WIRE 4 WIRE
THHW/THWN COPPER
CONDUCTORS
EQUIPMENT
GROUNDING
CONDUCTOR CONDUIT
A# 2#12 3#12 4#12 1#12 3/4"
B# 2#10 3#10 4#10 1#10 3/4"
C# 2#8 3#8 4#8 1#10 3/4"
D# 2#6 3#6 4#6 1#10 1"
E# 2#4 3#4 4#4 1#8 1 1/4"
G# 2#2 3#2 4#2 1#8 1 1/4"
H# 2#1 3#1 4#1 1#6 1 1/2"
J# 2#1/0 3#1/0 4#1/0 1#6 2"
ALL BRANCH CIRCUITS SHALL INCLUDE THE EQUIPMENT GROUND
CONDUCTOR
F# 2#3 3#3 4#3 1#8 1 1/4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID SET
C R e v it L o c a l F ile s \M
E P
T
.0
-V A
-O m a h a -A
H U
T o w e r_
C z a c h a ry .r
.r o s s .r v t
/2
/2
:3
:5
P
M
E502
ELECTRICAL SCHEDULES NWIHCS - CONSTRUCT
AIR HANDLING TOWER
OMAHA, NE
636-18-303
05/28/21 RICVED KRISPI15744
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2020 IMEG CORP.
2882 106TH STREET
DES MOINES, IA 50322
515.334.9906 FAX: 515.334.9908
www.imegcorp.com
19004249.01
[Key*:]
Total Amps: 61.97 31.54 56.64
Total Load: 7.03 kVA 3.79 kVA 6.4 kVA
-- 59 SPACE -- -- -- 0 0 -- -- -- SPACE 60 --
-- 57 SPACE -- -- -- 0 0 -- -- -- SPACE 58 --
-- 55 SPACE -- -- -- 0 0 -- -- -- SPACE 56 --
-- 53 SPACE -- -- -- 0 0 -- -- -- SPACE 54 --
51 SPARE 20 A 1 -- 0 0 -- -- -- SPACE 52 --
49 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 50
47 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 48
45 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 46
43 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 44
41 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 42
39 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 40
37 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 38
35 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 36
33 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 34
31 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 32
29 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 30
27 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 28
25 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 26
23 SPARE 20 A 1 -- 0 0.57 -- -- -- -- 24 --
21 SPARE 20 A 1 -- 0 0.57 2 20 A SP-1 22
19 AHU-1A-LIGHTS 20 A 1 1 0.68 1 20 A Lighting 20
17 AHU-BA-LIGHTS 20 A 1 1 1 1 20 A AHU-BB-LIGHTS 18
15 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 16
13 SPARE 20 A 1 -- 0 0.83 1 20 A FCU-1 14
11 FCU-1 20 A 1 0.83 1 1 20 A AHU-1B-LIGHTS 12
9 CRS-2 20 A 1 0.67 0.83 1 20 A FCU-1 10
7 CRS-1 20 A 1 1.13 1.13 1 20 A CRS-1 8
5 AHU-1B-HEAT WHEEL 20 A 1 1 1 1 20 A AHU-BB-HEATWHEEL 6
3 RECEPTACLES 20 A 1 0.72 1 1 20 A AHU-1A-HEATWHEEL 4
1 AHU-BA-HEATWHEEL 20 A 1 1 1.26 1 20 A RECEPTACLES 2
CKT
NO. LOAD DESCRIPTION
OVERCURRENT
PROTECTION
AMPS P
WIRE
ID
A B C
WIRE
ID
OVERCURRENT
PROTECTION
P AMPS LOAD DESCRIPTION
CKT
NO.
Panel Notes: ALL WIRING IS 2#12 & 1#12 GND IN 3/4" C. UNLESS OTHERWISE NOTED.
LOCATION: BASEMENT FLOOR DEMAND: 17.21 kVA
SCCR: WIRE: 4
FED FROM: US-2 GROUND BUS PHASE: 3
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye
TYPE: BOLT-ON MAIN: 200 A/MLO
PANEL NAME: LB CONNECTED 17.2 kVA
[Key*:]
Total Amps: 44.05 25.37 0
Total Load: 4.88 kVA 2.64 kVA 0 kVA
-- 41 SPACE -- -- -- 0 0 -- -- -- SPACE 42 --
-- 39 SPACE -- -- -- 0 0 -- -- -- SPACE 40 --
-- 37 SPACE -- -- -- 0 0 -- -- -- SPACE 38 --
-- 35 SPACE -- -- -- 0 0 -- -- -- SPACE 36 --
33 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 34
31 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 32
29 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 30
27 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 28
25 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 26
23 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 24
21 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 22
19 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 20
17 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 18
15 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 16
13 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 14
11 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 12
9 Lighting 20 A 1 0.64 10
7 RECEPTACLES 20 A 1 1.44 1.44 1 20 A RECEPTACLES 8
5 FCU-1 20 A 1 0 0 1 20 A FCU-1 6
3 AHU-2B-LIGHTS 20 A 1 1 1 1 20 A AHU-2B-HEATWHEEL 4
1 AHU-2A-LIGHTS 20 A 1 1 1 1 20 A AHU-2A-HEATWHEEL 2
CKT
NO. LOAD DESCRIPTION
OVERCURRENT
PROTECTION
AMPS P
WIRE
ID
A B C
WIRE
ID
OVERCURRENT
PROTECTION
P AMPS LOAD DESCRIPTION
CKT
NO.
Panel Notes: ALL WIRING IS 2#12 & 1#12 GND IN 3/4" C. UNLESS OTHERWISE NOTED.
LOCATION: SECOND FLOOR DEMAND: 7.52 kVA
SCCR: WIRE: 4
FED FROM: US-2 GROUND BUS PHASE: 3
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye
TYPE: BOLT-ON MAIN: 200 A/MLO
PANEL NAME: L2 CONNECTED 7.5 kVA
[Key*:]
Total Amps: 31.51 22.61 15
Total Load: 3.66 kVA 2.59 kVA 1.8 kVA
-- 41 SPACE -- -- -- 0 0 -- -- -- SPACE 42 --
-- 39 SPACE -- -- -- 0 0 -- -- -- SPACE 40 --
-- 37 SPACE -- -- -- 0 0 -- -- -- SPACE 38 --
-- 35 SPACE -- -- -- 0 0 -- -- -- SPACE 36 --
33 SPARE 20 A 1 -- 0 0 -- -- -- SPACE 34 --
31 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 32
29 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 30
27 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 28
25 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 26
23 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 24
21 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 22
19 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 20
17 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 18
15 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 16
13 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 14
11 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 12
9 Lighting 20 A 1 0.39 0.2 1 20 A Lighting 10
7 FCU-1 20 A 1 0.83 0.83 1 20 A FCU-1 8
5 RECEPTACLES 20 A 1 0.9 0.9 1 20 A RECEPTACLES 6
3 AHU-3B-LIGHTS 20 A 1 1 1 1 20 A AHU-3B-HEATWHEEL 4
1 AHU-3A-LIGHTS 20 A 1 1 1 1 20 A AHU-3A-HEATWHEEL 2
CKT
NO. LOAD DESCRIPTION
OVERCURRENT
PROTECTION
AMPS P
WIRE
ID
A B C
WIRE
ID
OVERCURRENT
PROTECTION
P AMPS LOAD DESCRIPTION
CKT
NO.
Panel Notes: ALL WIRING IS 2#12 & 1#12 GND IN 3/4" C. UNLESS OTHERWISE NOTED.
LOCATION: THIRD FLOOR DEMAND: 8.05 kVA
SCCR: WIRE: 4
FED FROM: US-2 GROUND BUS PHASE: 3
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye
TYPE: BOLT-ON MAIN: 200 A/MLO
PANEL NAME: L3 CONNECTED 8.1 kVA
[Key*:]
Total Amps: 29.4 20.93 16.67
Total Load: 3.46 kVA 2.44 kVA 2 kVA
-- 41 SPACE -- -- -- 0 0 -- -- -- SPACE 42 --
-- 39 SPACE -- -- -- 0 0 -- -- -- SPACE 40 --
-- 37 SPACE -- -- -- 0 0 -- -- -- SPACE 38 --
-- 35 SPACE -- -- -- 0 0 -- -- -- SPACE 36 --
33 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 34
31 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 32
29 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 30
27 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 28
25 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 26
23 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 24
21 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 22
19 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 20
17 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 18
15 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 16
13 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 14
11 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 12
9 Lighting 20 A 1 0.44 0 -- 1 20 A SPARE 10
7 RECEPTACLES 20 A 1 0.9 0.9 1 20 A RECEPTACLES 8
5 AHU-5B-LIGHTS 20 A 1 1 1 1 20 A AHU-5B-HEATWHEEL 6
3 AHU-5A-LIGHTS 20 A 1 1 1 1 20 A AHU-5A-HEATWHEEL 4
1 FCU-1 20 A 1 0.83 0.83 1 20 A FCU-1 2
CKT
NO. LOAD DESCRIPTION
OVERCURRENT
PROTECTION
AMPS P
WIRE
ID
A B C
WIRE
ID
OVERCURRENT
PROTECTION
P AMPS LOAD DESCRIPTION
CKT
NO.
Panel Notes:
LOCATION: FIFTH FLOOR DEMAND: 7.9 kVA
SCCR: WIRE: 4
FED FROM: US-2 GROUND BUS PHASE: 3
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye
TYPE: BOLT-ON MAIN: 200 A/MLO
PANEL NAME: L5 CONNECTED 7.9 kVA
[Key*:]
Total Amps: 32.61 20.9 13.83
Total Load: 3.8 kVA 2.39 kVA 1.66 kVA
-- 41 SPACE -- -- -- 0 0 -- -- -- SPACE 42 --
-- 39 SPACE -- -- -- 0 0 -- -- -- SPACE 40 --
-- 37 SPACE -- -- -- 0 0 -- -- -- SPACE 38 --
-- 35 SPACE -- -- -- 0 0 -- -- -- SPACE 36 --
33 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 34
31 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 32
29 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 30
27 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 28
25 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 26
23 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 24
21 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 22
19 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 20
17 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 18
15 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 16
13 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 14
11 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 12
9 Lighting 20 A 1 0.39 0 -- 1 20 A SPARE 10
7 RECEPTACLES 20 A 1 0.9 0.9 1 20 A RECEPTACLES 8
5 FCU-1 20 A 1 0.83 0.83 1 20 A Power 6
3 AHU-4B-LIGHTS 20 A 1 1 1 1 20 A AHU-4B-LIGHTS 4
1 AHU-4A-LIGHTS 20 A 1 1 1 1 20 A AHU-4A-HEATWHEEL 2
CKT
NO. LOAD DESCRIPTION
OVERCURRENT
PROTECTION
AMPS P
WIRE
ID
A B C
WIRE
ID
OVERCURRENT
PROTECTION
P AMPS LOAD DESCRIPTION
CKT
NO.
Panel Notes: ALL WIRING IS 2#12 & 1#12 GND IN 3/4" C. UNLESS OTHERWISE NOTED.
LOCATION: FOURTH FLOOR DEMAND: 7.85 kVA
SCCR: WIRE: 4
FED FROM: US-2 GROUND BUS PHASE: 3
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye
TYPE: BOLT-ON MAIN: 200 A/MLO
PANEL NAME: L4 CONNECTED 7.9 kVA
[Key*:] H- HANDLE LOCK
Total Amps: 12.06 21.09 11.42
Total Load: 1.44 kVA 2.52 kVA 1.37 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 LIGHTING 20 A 1 0 0.5 1 20 A FACP 8 *H
5 Receptacles 20 A 1 0.54 0.83 1 20 A FCU-1 6
3 RECEPTACLES 20 A 1 1.26 1.26 1 20 A RECEPTACLES 4
1 LIGHTING 20 A 1 0.59 0.35 1 20 A LIGHTING 2
CKT
NO. LOAD DESCRIPTION
OVERCURRENT
PROTECTION
AMPS P
WIRE
ID
A B C
WIRE
ID
OVERCURRENT
PROTECTION
P AMPS LOAD DESCRIPTION
CKT
NO.
Panel Notes:
LOCATION: FUTURE MECHANICAL 1104A DEMAND: 5.33 kVA
SCCR: WIRE: 4
FED FROM: GROUND BUS PHASE: 3
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye
TYPE: BOLT-ON MAIN: 200 A/MLO
PANEL NAME: L1 CONNECTED 5.3 kVA
Revisions: Date:
Revised for Addendum 7/27/2021
| Sheets |
| E502 - ELECTRICAL SCHEDULES |
| EP100 - BASEMENT PLAN - POWER |
| EP108 - EIGHTH LEVEL FLOOR PLAN - POWER |
File details come from the government source that posted it. Updated .