Contract Opportunity Presolicitation Notice

CLASSIFICATION CODE

SUBJECT

CONTRACTING OFFICE'S

ZIP-CODE

SOLICITATION NUMBER

RESPONSE DATE (MM-DD-YYYY)

ARCHIVE

DAYS AFTER THE RESPONSE DATE

RECOVERY ACT FUNDS

SET-ASIDE

NAICS CODE

CONTRACTING OFFICE

ADDRESS

POINT OF CONTACT

(POC Information Automatically Filled from User Profile Unless Entered)

DESCRIPTION

See Attachment

AGENCY'S URL

URL DESCRIPTION

AGENCY CONTACT'S EMAIL

ADDRESS

EMAIL DESCRIPTION

ADDRESS

POSTAL CODE

COUNTRY

ADDITIONAL INFORMATION

GENERAL INFORMATION

PLACE OF PERFORMANCE

* = Required Field Contract Opportunity Presolicitation Notice H344 Service | Boiler Water Monthly Chemical Testing/Analysis Black Hills VAMC, Fort Meade, South Dakota Base plus 4 option year contract 57741 36C26320Q0234 02-14-2020 N

VSA

238220 Department of Veterans Affairs Network 23 Contracting Office (NCO 23) 113 Comanche Rd.

Fort Meade SD 57741 David A. Raad david.raad@va.gov Department of Veterans Affairs Black HIlls VAMC 113 Comanche Rd.

Fort Meade, South Dakota 57741

USA

SCOPE OF WORK

Fort Meade Boiler Water Chemical Testing Vendor will provide chemicals and monthly chemical testing/analysis for SULFITE, AMINE, ALKALINITY, TDS or MICRO-MHON, PPM FOR BOILER WATER SOLIDS for three high pressure boilers located in Bldg. 137 at the VA BHHCS Fort Meade Medical Center. All services will be performed during normal working hours, 8am—4pm.

Water test parameter limits are as follows

Boilers
Feedwater
Condensate
RO
Conductivity as mmhos:
1,800-2,200
50 Max
60 Max
60 Max
Sulfite PPM as SO3
20-60
Polymer
40-60

Hardness, Total PPM as CACO3

1 Max

Iron (Fe)

0.15 Max

pH

8.0-9.5

Vendor will test/calibrate equipment monthly and advise additions/deletions to the boilers. One copy of the water report will include equipment tested, report number and for the person completing the test, the specific tests conducted, test results, test parameters, and recommended actions.

Vender will also provide controllers, ball valves, pumps, sample coolers, injection quills, feed manifolds, and chemical storage containers necessary for chemical testing and chemical.

introduction as required for chemicals used in the water conditioning program. Vendor will provide MSDS information for all chemicals provided.

Chemicals provided will be in such amounts to treat the boiler water continuously for a 60month period. Chemicals will be delivered to Bldg. 137. Billings will be made monthly for testing services and chemical costs.

Water conditioning/testing chemicals to be provided include at a minimum the following labeled chemicals:

· B-731

· B-663

· SC-60

· B-750

· Hardness Reagent TE424-53 (Code 424-53)

· Starch Acid Indicator TE105-Q (Code 40)

· Iodate –Iodide TE14961-01 (#14961-01)

· Sulfuric Acid TE14389-01 (#14389-01)

· EDTA Salt TE14399-01 (#14399-01)

· Phenophthalein TE393-H (Code 32)

· BCG – Indicator TE943-99

· Polymer Reagent #1 TE7438-H

· Polymer Reagent #2 TE7439-H

· Hardness Indictor TE257-V (Code 20)