This is a Sources Sought Notice for annual medical gas testing and certification services at the Phoenix Veterans Affairs Healthcare System. The Department of Veterans Affairs' Phoenix VA Health Care System, located at 650 East Indian School Road in Phoenix, Arizona, is seeking qualified vendors to provide annual medical gas testing and certification along with annual master alarm testing. The requirement covers testing and certification of medical gas systems including Oxygen, Medical Air, Vacuum, Waste Anesthesia, and Nitrous Oxide across four facilities: the Phoenix VA Medical Center (Building 1), Community Living Center (Building 16), Ambulatory Care Center (Building 8), and Dental Clinic (Building 29). Contractors must complete NFPA 99C Medical Gas Certifier training, test 100% of outlets at each location, verify minimum flow rates (100 liters per minute for standard outlets, 142 lpm for surgical outlets, and 85 lpm for medical vacuum), test for suspended particulate matter, and provide a comprehensive Medical Gas Campus Overview book within 30 days of the initial site visit.
Responses to this sources sought announcement must be submitted in writing by February 25, 2026 at 10:00 AM Mountain Time to Felicia Simpson, Contracting Officer, at Felicia.Simpson@va.gov. The solicitation number is 36C26226Q0387, with a NAICS code of 541380 and Product Service Code H165. This is a pre-solicitation announcement with a set-aside consideration for Service-Disabled Veteran Owned Small Businesses, though the Government may pursue alternate set-asides or full and open competition if SDVOSB responses prove inadequate. Interested vendors must provide company name, address, point of contact, phone/fax/email, DUNS number, CAGE Code, Tax ID Number, small business classification, and a detailed capability statement. All respondents must be registered in SAM.gov and complete ORCA; veteran-owned businesses must also register with the SBA Dynamic Small Business Search Registry. The Government is not obligated to issue a formal solicitation, pay for response costs, or award a contract based on this notice.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sources Sought Notice Sources Sought Notice
| SUBJECT* |
| Annual Medical Gas-Testing Certification |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 85297 |
| SOLICITATION NUMBER* |
| 36C26226Q0387 |
| RESPONSE DATE/TIME/ZONE |
| 02-25-2026 10:00AM MOUNTAIN TIME, DENVER, USA |
| ARCHIVE |
| 10 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
| SET-ASIDE |
| SDVOSBC |
| PRODUCT SERVICE CODE* |
| H165 |
| NAICS CODE* |
| 541380 |
| CONTRACTING OFFICE ADDRESS |
| NCO 22 |
Department of Veterans Affairs Mesa Annex 4135 S. Power Rd #103 RM 116 Mesa, AZ 85212
POINT OF CONTACT*
Contracting Officer Felicia Simpson Felicia.Simpson@va.gov
PLACE OF PERFORMANCE
| ADDRESS |
| Phoenix Veteran Affairs Healthcare System |
650 East Indian School Road
Phoenix AZ
| POSTAL CODE |
| 85012 |
COUNTRY
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
This is a SOURCES SOUGHT ANNOUNCEMENT ONLY. It is neither a solicitation announcement nor a request for proposals or quotes and does not obligate the Government to award a contract. Requests for a solicitation will not receive a response. Responses to this source sought must be in writing. The purpose of this sources sought announcement is for market research to make appropriate acquisition decisions and to gain knowledge of potential qualified Service-Disabled Veteran Owned Small Businesses, Veteran Owned Small Businesses, 8(a), HubZone and other Small Businesses interested and capable of providing the services described below. Documentation of technical expertise must be presented in sufficient detail for the Government to determine that your company possesses the necessary functional area expertise and experience to compete for this acquisition. Responses to this notice shall include the following: (a) company name (b) address (c) point of contact (d) phone, fax, and email (e) DUNS number (f) Cage Code (g) Tax ID Number (h) Type of small business, e.g. Services Disabled Veteran Owned small Business, Veteran-owned small business, 8(a), HUBZone, Women Owned Small Business, Small disadvantaged business, or Small Business HUBZone business and (i) must provide a capability statement that addresses the organizations qualifications and ability to perform as a contractor for the work described below.
The Department of Veteran Affairs, Phoenix VA Health Care System located at 650 East Indian School Road, Phoenix Arizona has a requirement for the vendor to provide Annual Medical Gas testing and certification, and Annual Master Alarm testing.
Important information: The Government is not obligated to, nor will it pay for or reimburse any costs associated with responding to this source sought synopsis request. This notice shall not be construed as a commitment by the Government to issue a solicitation or ultimately award a contract, nor does it restrict the Government to a particular acquisition approach. The Government will in no way be bound to this information if any solicitation is issued. The VA is mandated by Public Law 109-461 to consider a total set-aside for Service-Disabled Veteran Owned Small Business set aside. However, if response by Service-Disabled Veteran Owned Small Business firms proves inadequate, an alternate set-aside or full and open competition may be determined. No sub-contracting opportunity is anticipated. The North American Classification System (NAICS) code for this acquisition is 541380 ($19 Million dollars).
Notice to potential offerors: All offerors who provide goods or services to the United States Federal Government must be registered in the System for Award Management (SAM) at www.sam.gov and complete Online Representations and Certifications Application (ORCA). Additionally, all Service-Disabled Veteran Owned Businesses or Veteran Owned Businesses who respond to a solicitation on this project must be registered with the SBA-Dynamic Small Business Search (DSBS) Registry located at https://dsbs.sba.gov. All interested Offerors should submit information by e-mail to felicia.simpson@va.gov All information submissions to be marked Attn: Felicia Simpson, Contract Specialist and should be received no later than 10:00 am MST on February 25, 2026.
Testing and Certification of the Medical Center’s Medical Gas systems shall comply with Engineering Policy Memorandum No. FS/138-1027. This policy shall be used to schedule, monitor and document the testing and maintenance of the Medical Center’s Medical Gas systems. These systems include Oxygen, Medical Air, Vacuum, Waste Anesthesia and Nitrous Oxide.
All critical components of the piped Medical Gas system including Bulk Oxygen tanks, Medical Vacuum systems, Medical Air systems, Waste Anesthesia Vacuum system, Dental Air, Dental Vacuum, Oxygen H tank supply manifolds, Nitrous H tank supply manifolds, master alarm signal panels, area alarms, automatic pressure switches, shutoff valves, flexible connectors and outlets shall be tested, inspected and maintained in compliance with NFPA standards by the contractor.
The Prime Contractor shall have completed NFPA 99C Medical Gas Certifier training and provide current certificates of qualification.
The Contractor shall provide Annual Medical Gas testing and certification of 100% of Oxygen, Medical Air, Vacuum, Waste Anesthesia and Nitrous outlets at the Phoenix VA Medical Center (Building 1), the Community Living Center (Building 16), the Ambulatory Care Center (Building 8) and Dental Clinic (Building 29).
The Contractor on the initial Inspection and Certification visit, shall complete an accurate inventory of Medical Gas outlets of all Buildings covered by this contract and provide a current Medical Gas Campus Overview book within 30 days of the initial site visit.
The Contractor shall check flow rate at each outlet. Oxygen, Medical Air and Nitrous Oxide must deliver a minimum of 100 liters per minute (1PM). Surgical outlets must deliver a minimum of 142 lpm. Medical Vacuum outlets must provide a minimum of 85 lpm.
The Contractor shall test each outlet (except Medical Vacuum) for suspended particulate by passing a gas stream through a particulate filter at a maximum flow rate for 5 seconds. Any presence of discoloration or visible particulate matter shall be documented.