S06 36C26225Q0007 0005 - Amendment.pdf
PDF 278 KB Posted
- Attached to
- J041--Chiller Preventative Maintenance - SAVAHCS Federal contract opportunity
- Solicitation number
- 36C26225Q0007
About this file
This document is an amendment to a solicitation (Solicitation Number: 36C26225Q0007) for chiller preventative maintenance services at the Southern Arizona Veterans Affairs Health Care System (SAVAHCS). The amendment responds to questions asked by potential offerors regarding the contract requirements, including the scope of work, pricing structure, and repair thresholds. Key details include:
This is a full coverage agreement that covers preventative maintenance, refrigerant, and repairs on the listed equipment. Emergency service calls 24/7 are part of the preventative maintenance agreement, and the contractor will be responsible for minor repairs up to $2,500, while major repairs over $2,500 will require a quote and approval from the government. The contractor will be expected to provide a 90-day parts warranty and 60-day labor warranty. No Eddy Current testing has been performed in the last 5 years, and the government may allow a deficiency assessment period for the awarded contractor to inspect the equipment and provide repair quotes. Historical data on the equipment will not be provided. The solicitation does not include any ancillary equipment such as cooling towers or pumps.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26225Q0007_7.docx | DOCX document | |
| S06 36C26225Q0007 0004 - Amendment.pdf | ||
| 36C26225Q0007_6.docx | DOCX document | |
| S06 36C26225Q0007 0003 - Amendment.pdf | ||
| 36C26225Q0007_5.docx | DOCX document | |
| S06 36C26225Q0007 0002 - Amendment.pdf | ||
| 36C26225Q0007_4.docx | DOCX document | |
| S02 36C26225Q0007_1 Updated.pdf | ||
| 36C26225Q0007_3.docx | DOCX document | |
| S02 36C26225Q0007_1.pdf | ||
| 36C26225Q0007_2.docx | DOCX document |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE 7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO. 1. CONTRACT ID CODE
FACILITY CODE CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30 PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243
(Type or print) (Type or print)
(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code)
(If other than Item 6)
(Specify type of modification and authority)
(such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
1 4
08/27/2024
None
36C262
Department of Veterans Affairs
NCO 22 - Network Contracting
3601 S. 6th Avenue
Tucson AZ 85723
36C262
Department of Veterans Affairs
NCO 22 - Network Contracting
3601 S. 6th Avenue
Tucson AZ 85723
To all Offerors/Bidders
36C26225Q0007
08-12-2024
X
X X
X 1
The purpose of this amendment is to respond to the questions asked related to this solicitation on pages 2-4 of this.
amendment.
No further questions will be answered.
Rochelle Bennett
Contracting Officer
Chiller Preventative Maintenance - SAVAHCS
36C26225Q0007
Q: Given the periodicity of the Eddy Current testing is 3 years, how would the government like contractors to quote for Eddy Current testing? Is it possible to add a separate CLIN for Eddy Current testing given it would be not be required in all years. Additionally, in what year is the Eddy Current testing expected to be done? With regards on the subject solicitation, may I ask the expected weight for laundry services per CLIN weekly?
A: We have not had an Eddy Current test for the chillers in the last 5 years. They can perform the test when they want to. A separate CLIN will be added for each year for Emergency/Over and Above Maintenance and Repairs.
Q: Is this a full coverage agreement that covers preventative maintenance, refrigerant and repairs on the equipment listed?
A: Yes.
Q: Are 24 hours a day and 7 days a week emergency service calls part of preventative maintenance agreement?
A: Yes.
Q: Are emergency or after-hours service calls billable?
A: Yes.
Q: What does your team consider over and above repairs?
A: If the repair job is over $2500. The contractor will give us a quote for the repairs and wait for an approval from appropriate Maintenance & Operations staff before doing the work.
Q: Can the government confirm that the eddy testing is in years three and five of the contract and not some other sequence based upon the incumbent?
A: There has been no eddy testing done for our chillers in the last 5 years by our incumbent contractor.
Q: Does the facility currently have rental equipment requirements that have not yet been filled?
A: No.
Q: Does the government have planned outages that require rental equipment in the future?
A: No.
Q: Can the government please provide a clear expectation for when the awarded contractor will be requested to quote a repair?
A: Yes, any repair over $2500.
Q: Would this be considered major repairs (e.g., centrifugal chiller motor replacements, compressor rebuilds, major chiller component replacement, compressor replacement and overhauls?).
A: Yes, major repairs (compressors etc.)
Q: Does the government consider the dollar amount of the repair when making a determination on whether or not to request a quotation?
A: Yes, any repair over $2500.
Q: Can the government please provide a clear expectation for when the awarded contractor will NOT be financial or responsible for repairs?
A: The awarded contractor is responsible for minor repairs if it’s a major repair Maintenance and
Operations approving authority (M & O) will request a quote and approval from M & O to do the repair.
Q: Will the awarded contractor be expected to provide a 90 day parts warranty for components not warranted by the original equipment manufactured for 90 days?
A: Yes.
Q: Can the government please provide labor warranty expectations?
A: 60 days.
Q: When was Chiller Annual service last performed? Should the awarded contractor expect to execute the service during the base year, year 2 and year 4?
A: The program office does not have the exact date.
Q: When was the Eddy Current testing on the condenser tubes last performed? Should the awarded contractor expect to execute the service during the base year and option year 3?
A: No date, there has not been an eddy test done in the last 5 years.
Q: When was the Eddy Current testing on the evaporator tubes last performed? Should the awarded contractor expect to execute the service only during the base year of the contract?
A: No date, there has not been an eddy test done in the last 5 years.
Q: Would the government consider a deficiency assessment period for the awarded contractor to perform in depth inspections and quote the government for repairs?
A: Yes.
Q: Can the government please provide a detailed deficiency list for each individual piece of equipment listed in Section 14 “list of equipment”.
A: Program office is not able to provide list at the moment.
Q: Can the government please provide historical data on each individual piece of equipment. Including repairs, maintenance records, run hours and factory recommendations that have not been executed by the VA.
A: Program office is not able to provide historical data at the moment.
Q: Can the government please confirm that no ancillary equipment such as cooling towers, pumps, cooling tower VFD’s, pump VFD’s and BMS are associated with this Solicitation.
A: Yes, no ancillary equipment with this solicitation.
Q: Can the government please provide an example of how over and above repairs has been applied in the past?
A: Building 40 cooling tower #4 the contractor had to replace a 40 HP motor, building 60, the contractor replaced a bad chiller compressor motor.
Q: Can over and above repairs be applied to minor and major repairs?
A: Major repairs.
Q: Can the government please provide an instance where a price quotation for repair was requested as opposed to the awarded contractor completing the repair as part of the contract.
A: Replaced cooling tower motor for B-40 and replaced bad chiller compressor motor for B-60.
Q: If the compressor motor fails on a Trane chiller RTHC or a chiller. Is the mechanical contractor responsible for replacing the compressor motor under the service agreement at no additional charge to the VA hospital? Will the VA hospital generate a purchase order and pay the mechanical contractor to replace the compressor motor?
A: No, the compressor would be a “major repair” and the contractor would put in a quote for the repair. Once approved by M & O approval authority then the contractor would do the repair.
Yes, the VA would get a purchase order and pay the mechanical contractor to replace the compressor motor.
NOTE: Any questions not answered is due to it not having any relevancy to the current solicitation and or is public information in which a contractor may request a FOIA.