36C26224Q0364 Questions.docx

DOCX document 17 KB Posted

Attached to
J044--PIPE INSULATION & REPAIR SCA Required Federal contract opportunity
Solicitation number
36C26224Q0615
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22

About this file

This combined synopsis/solicitation requests quotations for pipe insulation and repair services. The Department of Veterans Affairs seeks a contractor to insulate piping for 65 lavatories and repair insulation on 10 to 15 existing piping systems at the VA La Jolla Medical Center in San Diego, California. Interested offerors must provide pricing to meet the requirements outlined in the statement of work by February 20, 2024. The associated NAICS code is 238220 for plumbing, heating, and air-conditioning contractors with a small business size standard of $19 million. The contracting office is NCO 22, Department of Veterans Affairs, located in Tucson, Arizona.

View the file

Other files for this federal contract opportunity

Other files attached to J044--PIPE INSULATION & REPAIR SCA Required, newest first.
File Type Posted
VA10091.pdf PDF
36C26224Q0615_1.docx DOCX document
FMS Vendor File Update Request Form.pdf PDF
RFQ - 36C26224Q0615 - Pipe Insulation.docx DOCX document
W-9 Form.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Previously Submitted Questions (36C26224Q0364)

1. Please provide photos or schematics of the scope of work needed.

Insulation is in easily accessible areas of the hospital.

2. Will there be a schedule site visit or job walk to evaluate what is needed?

There will not be a site visit for this contract.

3. What is the linear feet and diameter of pipe that need to be insulation and repair?

Approximately 100-120 linear ft. 0.5 inch & 1.5-inch diameter piping.

4. Are there any valves that need openings for operating in enclosed with doors for adjustments?

The valves are easily accessible and will not require openings.