S01 36C26223Q1510 0001_1 Amend-Questions.pdf
PDF 139 KB Posted
- Solicitation number
- 36C26223Q1510
About this file
This document contains answers to questions regarding solicitation number 36C26223Q1510 for preventative maintenance and repair of low voltage systems and fire suppression systems at a Department of Veterans Affairs facility. Services required include testing and maintenance of the fire alarm system comprising 24 control panels, 1322 appliances and speakers, 356 smoke detectors, and 184 waterflow switches across 16 buildings. The fire suppression system includes 2 pre-action and 1 wet sprinkler system, as well as maintenance and testing of 1 fire pump. The contractor will also be responsible for battery replacements, detector repairs, and service calls. Pricing is set forth in CLINs 0002, 1002, 2002, 3002, and 4002 for any above and beyond repairs, with historical data on these expenses unavailable. The response date has been extended to September 12, 2023.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26223Q1510 0001.docx | DOCX document | |
| S01 36C26223Q1510 Solicitation.pdf | ||
| 36C26223Q1510_1.docx | DOCX document | |
| W-9 Form.pdf | ||
| VA10091.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE 7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO. 1. CONTRACT ID CODE
FACILITY CODE CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30 PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243
(Type or print) (Type or print)
(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code)
(If other than Item 6)
(Specify type of modification and authority)
(such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
1 5
36C262
NCO 22
Department of Veterans Affairs NCO 22 - Gilbert Network Contracting 335 East Germann Road Gilbert AZ 85297
36C262
NCO 22
Department of Veterans Affairs NCO 22 - Gilbert Network Contracting 335 East Germann Road Gilbert AZ 85297
To all Offerors/Bidders
36C26223Q1510
09-06-2023
X x x
See CONTINUATION Page
Preventative Maintenance and Repair of Low Voltage System and Fire Suppression System
The purpose of this amendment is:
1. Answer questions received prior to cutoff.
2. Extend the date of the solicitation to September 12, 2023 at 12:00 pm (noon).
Anita Amodia Contracting Officer
VA-VHA-RPOW-2023-0052
CONTINUATION PAGE
Answers to Questions Submitted Fire Management
1. Section C of the SOW List of device such as waterflows, tampers, smoke detectors, etc.
Can VA provide device quantities for all device listed in EP 1-19?
Answer:
Main Fire Alarm Control Panels 24
NAC Power Supplies 29
NAC Appliances & speaker/strobes 1322
Batteries 78
Modcom Modem 1
Smoke Detectors 356
Heat Detectors 58
Releasing Device 47
Duct Detectors 147
Pull Stations 135
FM200 1
Waterflows 184
Tampers 268
Pre-Action 2
Kitchen Hoods 3
Fire Pumps 1
Off-site Notification 6
Supervisory 5
AHU Fan Shutdown 64
Post Indicator Valves (PIVs) 3
Fire Department Connections 12
Fire Hydrants 14
2. Are kitchen hood systems to be tested on this contract? If so can you provide the number of tanks and systems to be tested? When can systems be tested?
Answer: Yes, systems need to be tested starting at 5 pm at night; usually takes 2 hours
3. Are standpipes to be tested under this contract? How many standpipes? When was the last 5 year inspection completed?
Answer: Yes, 11/3/2021
4. How many fire pumps are to be tested? Can you provide size (gpm)?
Answer: 1, 750 GPM
5. Can elevator recall/shunt trip be tested during normal hours? If not can they be tested on weekends?
Answer: Partially Elevators S1, 2, and 3 need to be test prior 0700
6. Will the VA coordinate for their elevator contractor to be onsite to reset the elevators after testing? If not, can the VA provide the contact information for the VA Elevator Contractor?
Answer: No, should be part of the contract
7. After duct detectors are tested/reset to verify HVAC Shutdown will VA Mechanical staff be responsible for restarting the HVAC Equipment that does not automatically restart?
Some equipment might require manual restart from HVAC Personnel
Answer: Yes
8. What areas of the VA require after hours fire alarm testing such as OR, CATH Lab, SPD? Can the VA provide a list of areas that requires after hour testing? Also indicate any area that requires weekend testing
Answer: Thursday 0600 for OR. SPS and Cath Lab anytime
9. What is the estimated number of fire alarm service calls annually?
Answer: average 33 service calls a year over last 4 years
10. When batteries, smoke detectors, duct detectors fail during testing will the contractor be able to provide a quote to make repair? IAW with the latest NFPA 72 batteries have to meet a higher standard which will result in more failures
Answer: Part of the contract to supply parts and materials
11. Can you provide a previous contract number?
Answer: 36C25819C0021
12. Can you give previous contract award information?
Answer: Climatec 10/01/2018 – 09/30/2023
13. How many buildings are in the complex?
Answer: 16
14. How many and type of fire alarm systems are there?
Answer: 1-EST
15. How many and type of fire sprinkler systems are there?
Answer: 2, pre-action, wet
16. How many, type and size of fire pumps are there?
Answer: 1, PRNTAIR, model 4-491-11C, 750 GPM, 3560 RPM, horizontal shaft
17. How many flow switches are there?
Answer: Approximate 184
18. How many and brand of each type of device are there?
Answer: Unknown
19. How many repairs and type of repairs were made in the previous five years?
Answer: Unknown
20. How are service calls paid? Under what CLIN?
Answer: Service and emergency calls are part of the contract
21. How are parts and repairs paid? Under what CLIN?
Answer: Only above and beyond parts and repairs get paid.
22. CLINs 0002, 1002, 2002, 3002, and 4002 state over and above repairs and services.
What does this entail, and what is the historical data on this? We cannot just bid on something where no information is provided. That would give one company (the incumbent) a huge competitive advantage over everyone else, unless we leave that blank and the Government is going to give everyone the same number for that CLIN.
Answer: Well, that is a $0 dollar line and over and above would have to get approved and verified by the COR and the contractor. Then a modification would get done to get funds approve to get the above and beyond repairs corrected.
23. I am already set up in Tungsten as I service other VA fire systems, do I need to include another 10991 in my submittal package?
Answer: Yes. Each location has their own system which will need to be updated.