SOW – SERVICE TO PERFORM PM OF CHLORINE DIOXIDE GENERATOR SERVICE BLDG.#525
Statement of Need: The VAGLAHS requires the weekly, quarterly monthly and annual service of one
(1) Dioxide Pacific CDEB-2.5 chlorine dioxide generator for the purpose of maintaining chlorine dioxide residual levels in the domestic hot and cold water systems between 0.3-0.6ppm in building #525
VAGLAHS.
Statement of Work:
Service of CLO2 Generator:
1.1 Provide weekly verification of proper operation of chlorine dioxide generator. Use provided regular maintenance checklist log sheet.
1.2 Provide weekly verification of proper chlorine dioxide residual levels.
1.3 Provide weekly verification of 25% sodium chlorite levels.
1.4 Perform weekly, monthly, quarterly and annual preventive maintenance to comply with manufacturer recommendations and ensure proper operation.
General Requirements:
2.1 Contractor is responsible for supplying and filling chlorine dioxide generator with 25% Sodium Chlorite
2.2 Chlorine dioxide residual levels are to be between 0.3-0.6ppm.
2.3 Chlorine dioxide residual levels are to be measured at the generator and at 25%, 50%, 75% and 100% of plumbing outlet distance.
2.4 Report is to be emailed to COR or designee same day as service. Must include completed regular maintenance checklist log sheet.
Place of Performance:
11301 Wilshire Blvd. Los Angeles, CA 90073 Building #525
Hours of Operation:
Monday-Friday 8AM-2PM
Period of Performance: One year from date of award
BASE + 4 OPTION YEARS