Project No. 22015.2030 rev2 August 2015

BUILDING 205 – MHC (VACANT) BUILDING

Building No. 205 is the MHC (vacant) building and was built in 1937. The building has one floor and is 53,047 ft2 in size. The interior wall and ceiling finishes include a mix of drywall, plaster and concrete walls with drop-in ceiling panels, 12”x12” ceiling tiles, plaster and drywall hard lids. The interior flooring finishes include 12”x12” vinyl floor tiles, carpeting, terrazzo and concrete floors. The exterior is composed of a slab-on grade foundation with concrete and stucco walls and a terra cotta pitched roof. The HVAC system is comprised of a forced air system with three air handling units located along the exterior perimeter of the building.

Historical Data:

An asbestos survey was conducted by others. The data from this survey is listed below. The findings of this survey noted the following materials as being ACM:

Transite panels (at radiators);

TSI debris, Basement crawl space below pool (5 SF), Room 14 (5 SF), Room 14B (1 SF);

Duct insulation (aircell);

2” Pipe run insulation, Room 9 (1

LF);

2” Pipe joint insulation, Room 3” Pipe run insulation, Room 9, Southwest pipe basement (61 LF);

3” Pipe joint insulation, Room 9, Room 16, Southwest pipe basement (24 Each);

4” Pipe run insulation, Room 16

(20 LF);

5” Pipe run insulation, Room 17 (2

LF);

Plaster composite, Hall by room

207 (770 SF);

12”x12” White w/ brown RFT & mastic, Room 5, Room 120 (7,340 SF);

12”x12” Yellow RFT & mastic, Room

8A (1,815 SF);

12”x12” White w/ beige streaks RFT & mastic, Room 16, Room 223, Room

214 (7,700 SF);

12”x12” Multicolor, black, brown spots RFT & mastic, Stairwell basement, Room 214, Room 218

(9,855 SF);

12”x12” Beige w/ copper streaks RFT & mastic, Hall by room 207 (5,200 SF);

and 12”x12” Gray w/ white & tan streaks RFT & mastic, Room 218 (5,200 SF).

Project No. 22015.2030 279 rev2 August 2015

Historical Data on LBP –

Beige plaster walls in rooms 132, 211 & 212 (800 SF) (4.1-7.6 mg/cm2) (Intact);

White plaster walls in rooms 2-10 (75 SF) (3.5 mg/cm2) (Poor);

Brown plaster walls in rooms 2-11 (525 SF) (4.9-6.3 mg/cm2) (Intact to poor);

White plaster window sills in room 127 (48 SF) (1.7-1.8 mg/cm2) (Poor); and Green Ceramic Tile Wall located in Room 129, (250 SF) (6.8 mg/cm2) (Poor).

The following materials were removed from the building:

No abatement/removal records available.

Millennium’s Data:

ACM was detected in the resilient sheet flooring. Millennium discovered lead-based paint in the plaster and ceramic wall tiles and concrete window sills.

The details of location, condition, color, substrate analytical results are provided in the appendix of this report.

Prior to making inferences and interpretations of these data, please refer to the Limitations section of this report.

The total ACM/Lead removal costs for building 205 are $496,550. The total asbestos removal cost is $468,800 and lead-based paint removal costs for building 205 are $27,750. Please refer to Tables 1-3 included herein.

EMSL Analytical, Inc 2235 Polvorosa Ave , Suite 230, San Leandro, CA 94577 Phone/Fax: (510) 895-3675 / (510) 895-3680 http://www.EMSL.com sanleandrolab@emsl.com

091401468 CustomerID: MECA62 CustomerPO: 8543 ProjectID:

EMSL Order:

Attn: Front Desk Millennium Consulting Associates, Inc.

620 Contra Costa Blvd.

Suite 102 Pleasant Hill, CA 94523

Received: 01/31/14 12:30 PM

22015.2030 VA WLA Bldg 205

Fax: (925) 808-6708 Phone: (925) 808-6700

Project:

2/3/2014Analysis Date:

1/31/2014Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

201-205-001-RFT

091401468-0001

RM103 Brown/Beige Non-Fibrous Homogeneous

Chrysotile<1%Non-fibrous (other)100%

201-205-001-Mastic

091401468-0001A

RM103 Black Non-Fibrous Homogeneous

Chrysotile6%Non-fibrous (other)94%

201-205-002-RFT

091401468-0002

RM14B Tan/Beige Non-Fibrous Homogeneous

Chrysotile<1%Non-fibrous (other)100%

201-205-002-Mastic

091401468-0002A

RM14B Black Non-Fibrous Homogeneous

Chrysotile8%Non-fibrous (other)92%

201-205-003-RFT

091401468-0003

RM235 Brown None Detected Non-Fibrous Homogeneous

Non-fibrous (other)100%

201-205-003-Mastic

091401468-0003A

RM235 Black Non-Fibrous Homogeneous

Chrysotile4%Non-fibrous (other)96%

201-205-004-RFT

091401468-0004

RM3A White/Blue/Pink None Detected

Black mastic was not submitted in the sample bag.

Non-Fibrous Homogeneous

Non-fibrous (other)100%

201-205-004-Mastic

091401468-0004A

RM3A Yellow None Detected Non-Fibrous Homogeneous

Non-fibrous (other)100%

1Test Report PLM-7.28.9 Printed: 2/3/2014 3:09:57 PM

Baojia Ke, Laboratory Manager or other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc San Leandro, CA NVLAP Lab Code 101048-3, WA C884

Initial report from 02/03/2014 13:31:44

Matthew Batongbacal (20)

Phone/Fax: (510) 895-3675 / (510) 895-3680 http://www.EMSL.com sanleandrolab@emsl.com

091401468 CustomerID: MECA62 CustomerPO: 8543 ProjectID:

EMSL Order:

Attn: Front Desk Millennium Consulting Associates, Inc.

620 Contra Costa Blvd.

Suite 102 Pleasant Hill, CA 94523

Received: 01/31/14 12:30 PM

22015.2030 VA WLA Bldg 205

Fax: (925) 808-6708 Phone: (925) 808-6700

Project:

2/3/2014Analysis Date:

1/31/2014Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

201-205-005-RFT

091401468-0005

RM127 White None Detected Non-Fibrous Homogeneous

Non-fibrous (other)100%

201-205-005-Mastic

091401468-0005A

RM127 Yellow None Detected Non-Fibrous Homogeneous

Non-fibrous (other)100%

201-205-006-Cove Base 091401468-0006

RM14B Brown None Detected Non-Fibrous

Homogeneous

Non-fibrous (other)100%

201-205-006-Mastic

091401468-0006A

RM14B Brown None Detected Non-Fibrous Homogeneous

Fibrous (other)4% Non-fibrous (other)96%

201-205-007-Carpet Adhesive 091401468-0007

RM252 Tan None Detected Non-Fibrous

Homogeneous

Non-fibrous (other)100%

201-205-008-ACT

091401468-0008

RMH14 Gray/White None Detected Fibrous Homogeneous

Cellulose15% Min. Wool75%

Non-fibrous (other)10%

201-205-008-Mastic 091401468-0008A

RMH14 Brown None Detected Non-Fibrous

Homogeneous

Fibrous (other)4% Non-fibrous (other)96%

201-205-008-Mastic 091401468-0008B

RMH14 Tan None Detected Non-Fibrous

Homogeneous

Non-fibrous (other)100%

2Test Report PLM-7.28.9 Printed: 2/3/2014 3:09:57 PM

Baojia Ke, Laboratory Manager or other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc San Leandro, CA NVLAP Lab Code 101048-3, WA C884

Phone/Fax: (510) 895-3675 / (510) 895-3680 http://www.EMSL.com sanleandrolab@emsl.com

091401468 CustomerID: MECA62 CustomerPO: 8543 ProjectID:

EMSL Order:

Attn: Front Desk Millennium Consulting Associates, Inc.

620 Contra Costa Blvd.

Suite 102 Pleasant Hill, CA 94523

Received: 01/31/14 12:30 PM

22015.2030 VA WLA Bldg 205

Fax: (925) 808-6708 Phone: (925) 808-6700

Project:

2/3/2014Analysis Date:

1/31/2014Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

201-205-009-ACP

091401468-0009

RMH14 Gray/White None Detected Fibrous Homogeneous

Cellulose20% Min. Wool70%

Non-fibrous (other)10%

201-205-010-ACP

091401468-0010

RM127 Gray/White None Detected Fibrous Homogeneous

Cellulose65% Min. Wool20%

Non-fibrous (other)15%

201-205-011-Plaster Ceiling 091401468-0011

RMH14 Gray/White None Detected Non-Fibrous

Homogeneous

Non-fibrous (other)100%

201-205-011-Mastic

091401468-0011A

RMH14 Brown Non-Fibrous Homogeneous

Chrysotile<1%Non-fibrous (other)100%

3THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 2/3/2014 3:09:57 PM

Baojia Ke, Laboratory Manager or other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc San Leandro, CA NVLAP Lab Code 101048-3, WA C884