36C26219Q0483-0002001.pdf
PDF 121 KB Posted
- Solicitation number
- 36C26219Q0483
About this file
36C26219Q0483 0002 S05 RFI001 with VA response.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| -16683.docx | DOCX document | |
| 36C26219Q0483-0002009.pdf | ||
| 36C26219Q0483-0002007.pdf | ||
| 36C26219Q0483-0002011.pdf | ||
| 36C26219Q0483-0002008.pdf | ||
| 36C26219Q0483-0002006.docx | DOCX document | |
| 36C26219Q0483-0002010.pdf | ||
| 36C26219Q0483-0002004.pdf | ||
| 36C26219Q0483-0002002.pdf | ||
| 36C26219Q0483-0002000.docx | DOCX document | |
| 36C26219Q0483-0002003.pdf | ||
| 36C26219Q0483-0002005.pdf | ||
| 36C26219Q0483-0001001.docx | DOCX document | |
| 36C26219Q0483-0001002.pdf | ||
| 36C26219Q0483-0001000.docx | DOCX document | |
| 36C26219Q0483-003.pdf | ||
| 36C26219Q0483-001.docx | DOCX document | |
| 36C26219Q0483-002.pdf | ||
| 36C26219Q0483-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFI FORM
Contractor Name:
Address:
Phone/Fax:
Send to: cecil.nichols@va.gov
RFI
(REQUEST FOR INFORMATION)
PROJECT NO.:
RFI NO.:
PROJECT NAME:
SERVICE to REPLACE Thermostatic Anti-Scald Mixing Control Valves, VA San Diego
DATE REQUESTED:
03/22/2019
SOLICITATION NO.:
36C26219Q0483
REFERENCE:
DRAWING:
SPECIFICATION
SECTION:
DESCRIPTION OF PROBLEM OR INFORMATION BEING REQUESTED
Please be specific as possible:
1) The RFQ on page 34 of 39, #2 Requirements for Submittal state there is a requirement (h. 2) for a C-36 License. Can the Prime use its Subcontractors License to meet this requirement?
2) To confirm, there is no Bid Bond, performance and payment bond requirements?
3) To confirm, there is no past performance requirement?
4) Is there any work in interstitial spaces?
5) There is a requirement for a third flex line – is it the Contractors responsibility to provide the line or will the Government (VA) be providing it?
6) Can you confirm what percentage of the work will be performed after-hours as this can impact cost?
7) RFQ calls for Infection Control, is it the Government’s (VA) intent that every work location (every sink) have a containment area set-up? If so, what level?
PROJECT MANAGER’S RESPONSE
1) Please reference FBO posted Amendment 0001 which includes Class “B” – General Building Contractor license or C-36 Plumbing license issued by the California State License Board (CSLB). SDVOSBs seeking to submit offers / mailto:cecil.nichols@va.gov quotes are reminded of the Limitations on Subcontracting clauses incorporated as part of this solicitation announcement.
2) This Service based solicitation is a Request for Quote (RFQ), not an Invitation for Bid (IFB). No bonding (bid, performance or payment) is required.
3) Past performance was not a condition of the solicitation or special standards of responsibility stated.
4) There is no work to be performed in the interstitial spaces.
5) If a third flex line is required to be in compliance with current code(s), directives, regulations, industry guidelines / standards, then it is the responsibility of awarded Contractor to provide.
6) Approximately 75% of the work to be conducted after-hours.
7) Per SOW paragraph 13. Risk Control, the Government (VA) COR [Tim Conroy] will submit any required VA “Infection Control Risk Assessment” (ICRA) permit(s).
TRACKING NO.: AMENDMENT NO.:
VA PROJECT ENGINEER/MANAGER:
JUAN HERNANDEZ, Maintenance Mechanic
DATE:
3/28/2019