36C26127Q0169.docx

DOCX document 45 KB Posted

Attached to
J012--Dry-Type Fire Suppression System
Solicitation number
36C26127Q0169
Issued by

About this file

This is a Sources Sought Announcement for dry-type fire suppression system maintenance and testing services. The Department of Veterans Affairs Network Contracting Office, located in Fresno, California (zip code 93721), is seeking qualified contractors to provide grease hood cleaning, exhaust fan servicing, and chemical hazardous material shed fire protection system maintenance at three VA Palo Alto Health Care System locations: Palo Alto Main Campus (3801 Miranda Avenue, Palo Alto, CA 94304), Menlo Park Medical Center (795 Willow Road, Menlo Park, CA 94025), and Livermore Medical Center (4951 Arroyo Road, Livermore, CA 94550). The Point of Contact is Contracting Officer Kulvinder Brar (Kulvinder.brar@va.gov). Interested parties must submit capability statements by November 30, 2026, at 3:00 PM Pacific Time, not to exceed ten single-sided, type-written pages using 12-point font or larger.

Contractors must hold a California C-16 contractor license and be certified by the system manufacturer to service Ansul Automatic Fire Control Systems, with equivalent system training documentation acceptable as an alternative. Grease hood cleaning must be performed by International Kitchen Exhaust Cleaning Association (IKECA)-certified Exhaust Cleaning Specialists or personnel demonstrating compliance with NFPA 72 and NFPA 96 standards. The contract is a Firm Fixed Price non-personal services contract requiring semi-annual and annual cleaning and certification services performed during business hours (7:00 AM to 3:30 PM Monday through Friday, excluding federal holidays). The NAICS code is 811310 with a size standard of $12.5 million. As a service acquisition, small business contractors (including SDVOSB and VOSB) are subject to a 50 percent subcontracting limitation per FAR 52.219-14 and FAR 52.219-27. All invoices must be submitted electronically through the VA's Electronic Invoice Presentment and Payment System. This is a preliminary announcement; no formal solicitation is currently available, and the Government will not compensate respondents for submitted information.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SUBJECT*

Dry-Type Fire Suppression System

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
93721
SOLICITATION NUMBER*
36C26127Q0169
RESPONSE DATE/TIME/ZONE
11-30-2026 3PM PACIFIC TIME, LOS ANGELES, USA
ARCHIVE
14 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N

SET-ASIDE

PRODUCT SERVICE CODE*
J012
NAICS CODE*
811310
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Network Contracting Office 21

Fresno CA 93721

POINT OF CONTACT*

Contracting Officer Kulvinder Brar

PLACE OF PERFORMANCE

ADDRESS
VA Palo Alto Health Care System

3801 Miranda Ave.

Palo Alto CA

POSTAL CODE
94304
COUNTRY
USA

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS

EMAIL DESCRIPTION

DESCRIPTION

THIS IS A SOURCES SOUGHT ANNOUNCEMENT ONLY.

No Solicitation is currently available.

All information contained in this Sources Sought Announcement is preliminary, as well as subject to modification, and is in no way binding on the Government. The Government will not pay for any information submitted in response to this request. The information requested will be used solely within the Department of Veterans Affairs to facilitate decision making and will not be disclosed outside of the Government. The determination of a procurement strategy, based upon the comments submitted in response to this Sources Sought Announcement, is solely within the discretion of the Government.

Potential Offerors must be registered in the System for Award Management (SAM) to be eligible for an award (See Internet Site https://www.sam.gov/portal/public/SAM/). Potential Offerors must also have a current Online Representations and Certification Application on file with SAM.

The applicable North American Industry Classification System (NAICS) Code is 811310, Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance and size standard is $12.5 million. NOTE: Please ensure that System For Award Management (SAM) indicates this NAICS code if you are interested in the requirement.

Before responding please carefully read and consider the following:

As this is a service acquisition, the Small Business Administration and the Federal Acquisition Regulation have a Limitations on Subcontracting requirement. For all small businesses, to include SDVOSB and VOSB, “it will not pay more than 50 percent of the amount paid by the Government for contract performance to subcontractors that are not similarly situated entities. Any work that a similarly situated entity further subcontracts will count towards the prime contractor's 50 percent subcontract amount that cannot be exceeded. When a contract includes both services and supplies, the 50 percent limitation shall apply only to the service portion of the contract.” See FAR 52.219-14 and FAR 52.219-27 available in full text at https://www.acquisition.gov/far/html/52_217_221.html

Brief Description of Services

The VA Palo Alto Health Care System (VAPAHCS) has a requirement for Dry-type fire suppression system maintenance and testing of Grease hoods, exhaust fans and chemical Hazmat Sheds. The Government is seeking only qualified kitchen exhaust cleaning specialists who hold current certification through the International Kitchen Exhaust Cleaning Association (IKECA) or an equivalent recognized industry association. Vendors must provide documentation demonstrating compliance with applicable NFPA standards, including NFPA 72 and 96, and furnish all required qualifications, training records, and certifications for personnel performing kitchen exhaust and grease hood cleaning services.

General This is a non-personal services contract to provide Dry-Type Fire Suppression System services for the VA Palo Alto Health Care System (VAPAHCS). The Government shall not exercise any supervision or control over the contract service providers performing the services herein. Such contract service providers shall be accountable solely to the Contractor who, in turn is responsible to the Government.

Place of Performance:

Palo Alto Main Campus 3801 Miranda Ave.

Palo Alto, CA 94304 Menlo Park Medical Center 795 Willow Rd.

Menlo Park, CA 94025 Livermore Medical Center 4951 Arroyo Rd.

Livermore, CA 94550

Contractor Qualifications:

Contractor shall possess a California C-16 contractor license and be certified by the system manufacturer to service and repair Ansul and related Automatic Fire Control Systems, or provide documentation of equivalent system training. Grease hood cleaning shall be performed by International Kitchen Exhaust Cleaning Association (IKECA)-certified or equivalent association Certified Exhaust Cleaning Specialists (CECS), or personnel who can document compliance with all applicable NFPA 72 and NFPA 96 grease hood cleaning qualification and certification requirements. The Government reserves the right to request and review such licenses, certifications, and supporting documentation at any time during the contract period.

Preventative Maintenance and Testing

Contractor shall provide all tools, materials, equipment, labor, and transportation to perform annual and semi-annual cleaning and fire protection services/ certification of the following grease hoods, exhaust fans, and chemical storage sheds at three divisions of the Veterans Administration Palo Alto Health Care System (VAPAHCS). All cleaning shall be done in accordance with NFPA 96 latest edition. All fire protection service/inspections and certifications shall be performed per NFPA 17A, 96, 10 and 72 latest editions.

Capability Statement

The Government requests that only firms seriously interested and truly capable should send their capability information to the Contracting Officer, Kulvinder Brar by email at: Kulvinder.brar@va.gov no later than 3:00 PM Pacific Time, November 30, 2026:

(a) Business Size (Large/Small)

(b) Business Socio-Economic Status (SDVOSB, WOSB, 8(a), HUBZone, etc.)

(c) SAM record (www.sam.gov)

(d) VIP record (SDVOSB/VOSB firms only) (https://www.vip.vetbiz.gov/)

(e) DUNS number

(f) Ability and experience in managing similar projects. Include general information and technical background describing your firm's experience on contracts requiring similar efforts to meet the program objectives.

(g) List of Projects (Government and Commercial) that are similar in scope and size.

(h) Anticipated Teaming Arrangements (if any)

(i) GSA Contract Number if applicable.

(j) Copies of certificates/licenses as identified above under Contractor Qualifications Interested parties shall not submit more than 10 single-sided, type-written pages using 12-point font or larger. Published literature may be any number of pages.

The Government will use this information when determining its business type decision.

*Failure to provide the information requested above (items (a) – (j)) will be considered non-responsive and will not be considered a viable source.

DISCLAIMER

This Sources Sought notice is issued solely for information and planning purposes only and does not constitute a solicitation. All information received in response to this request that is marked proprietary will be handled accordingly. The Government will not compensate an offeror for providing information in response to this sources sought. Furthermore, the Government reserves the right to cancel this requirement at its discretion. This is simply a sources sought notice.

Sources Sought Notice Sources Sought Notice

*= Required Field
Sources Sought Notice

Sources Sought Notice

..Performance Work Statement Dry-type fire suppression system maintenance and testing of Grease hoods, exhaust fans and chemical Hazmat Sheds VA Palo Alto Health Care System Section 1: General Information

1.1 General: This is a non-personal services contract to provide services to the Grease Hoods and Hazmat Shed for the VA Palo Alto Health Care System (VAPAHCS). The Government shall not exercise any supervision or control over the contract service providers performing the services herein. Such contract service providers shall be accountable solely to the Contractor who, in turn is responsible to the Government.

1.3 Place of Performance: Services are required at the following locations. The points of contact (POC) for each location are listed. All work must be coordinated with the COR.

Palo Alto Main Campus 3801 Miranda Ave.

Palo Alto, CA 94304 POC: Anthony StJohn

(650) 493-5000 x64063 Menlo Park Medical Center 795 Willow Rd.

Menlo Park, CA 94025 POC: Ronald Nielson

(650) 493-5000 x27324 Livermore Medical Center 4951 Arroyo Rd.

Livermore, CA 94550 POC: Don Jasch

(925) 373-4700 x35158

1.4 Hours of Operation: All repairs shall be performed during business hours of 7:00 AM to 3:30 PM Monday through Friday, except Federal Holidays. Contractor may work outside normal business hours by arrangement with the COR if such services are provided without additional charge to the government.

1.4.1 Observed Federal Holidays

January 1
New Year’s Day
Third Monday in January
Martin Luther King Jr.’s Birthday
Third Monday in February
President’s Day
Last Monday in May
Memorial Day
June 19
Juneteenth
July 4
Independence Day
First Monday in September
Labor Day
Second Monday in October
Columbus Day
November 11
Veteran’s Day
Fourth Thursday in November
Thanksgiving Day
December
Christmas Day

1.5 Type of Contract: The government will award a Firm Fixed Price contract.

1.6 Invoicing: All invoices from the contractor shall be submitted electronically in accordance with VAAR Clause 852.232-72 Electronic Submission of Payment Requests.

VA’s Electronic Invoice Presentment and Payment System – The FSC uses a third-party contractor, Tungsten, to transition vendors from paper to electronic invoice submission. Please go to this website: http://www.tungsten-network.com/US/en/veterans-affairs/ to begin submitting electronic invoices, free of charge.

More information on the VA Financial Services Center is available at http://www.fsc.va.gov/einvoice.asp.

Vendor e-Invoice Set-Up Information:

Please contact Tungsten at the phone number or email address listed below to begin submitting your electronic invoices to the VA Financial Services Center for payment processing, free of charge. If you have question about the e-invoicing program or Tungsten, please contact the FSC at the phone number or email address listed below:

· Tungsten e-Invoice Setup Information: 1-877-489-6135

· Tungsten e-Invoice email: VA.Registration@Tungsten-Network.com

· FSC e-Invoice Contact Information: 1-877-353-9791

· FSC e-invoice email: vafsccshd@va.gov

1.6.1 Payments: Government only paid for services rendered. Government will not pay on any uncompleted or undelivered work, services, or goods.

Section 2: Definitions & Acronyms

2.1 Definitions:

Contractor. A supplier or vendor awarded a contract to provide specific supplies or service to the government. The term used in this contract refers to the prime.

Subcontractor. One that enters into a contract with a prime contractor. The Government does not have privity of contract with the subcontractor.

Work Day. The number of hours per day the Contractor provides services in accordance with the contract.

Work Week. Monday through Friday, unless specified otherwise.

2.2 Acronyms:

CORContracting Officer Representative
AHJAuthority Having Jurisdiction
NFPANational Fire Protection Association
OEMOriginal Equipment Manufacturer
OSHAOccupational Safety and Health Administration
POCPoint of Contact
PMPreventative Maintenance
PMIPreventative Maintenance Inspection
VAVeterans Affairs
VAPAHCSVeterans Affairs Palo Alto Health Care System

Section 3: Government Furnished Property, Equipment, and Services A. This PWS does not have any government furnished equipment. Contractor shall not use any government own equipment, material, supplies, or tools. Contractor shall furnish all requirements. The government reserves option to terminate the contract in the event that contractor uses government equipment or supplies without written approval from the Contracting Officer and COR.

Section 4: Contractor Furnished Items and Services The Contractor shall provide all equipment, supplies, management, supervision, personnel, and transportation necessary to assure that all services are in accordance with the contract and all applicable laws and regulations. The contractor shall ensure all work meets performance standards specified in this Performance Work Statement (PWS) and referenced documents to include all notes, explanatory material, and appendixes.

4.1 Contractors Qualifications:

A. Contractor shall possess a California C-16 contractor license and be certified by the system manufacturer to service and repair Ansul and related Automatic Fire Control Systems, or provide documentation of equivalent system training. Grease hood cleaning shall be performed by International Kitchen Exhaust Cleaning Association (IKECA)-certified or equivalent association Certified Exhaust Cleaning Specialists (CECS), or personnel who can document compliance with all applicable NFPA 72 and NFPA 96 grease hood cleaning qualification and certification requirements. The Government reserves the right to request and review such licenses, certifications, and supporting documentation at any time during the contract period.

Section 5: Specific Tasks

5.1 Preventative Maintenance and Testing

A. Contractor shall provide all tools, materials, equipment, labor, and transportation to perform annual and semi-annual cleaning and fire protection services/ certification of the following grease hoods, exhaust fans, interconnecting ducts and chemical storage sheds at three divisions of the Veterans Administration Palo Alto Health Care System (VAPAHCS). All cleaning shall be done in accordance with NFPA 96 latest edition. All fire protection service/inspections and certifications shall be performed per NFPA 17A, 96, 10 and 72 latest editions.

B. Alarm System: Alarm System Contractor shall confirm with the COTR or his designee and Supervisor of the Electronics Shop in charge of the Fire Alarm Systems or his designee prior to impairment, disarming, disabling, discharging or shutting down and or reactivation of any system that is monitored by the building fire protection system. Contractor shall be liable for any charges imposed by the responding fire departments related to a “false alarm” due to their actions or failure to verify fire alarm system deactivation prior to start of work, contractor shall document in writing on his field report, time of fire system deactivation and reactivation, verification of operation and VAPAHCS system verification point of contact.

a. Contractor shall verify that all fuel all sources are automatically shut down as per NFPA 72 and 96. Contractor shall document and submit report.

C. Photographic Documentation: Contractor shall take digital photographs of grease hoods and fans prior to and after all cleaning services. Pictures shall be identified as to division location, building location and hood identification.

D. Failed Devices: The contractor shall affix a temporary notification on the failed device indicating failure and verbally notify the P.O.C. and COR of failures of fire protection system or failure to clean all equipment included in this contract on the same business day of failed test. If the device is not immediately correctable, the contractor shall submit a quote to repair to the P.O.C. and COR within 72 hours.

Repair and mandatory replacement parts: Contractor shall only use industry approved repair or maintenance materials and parts during testing and maintenance repair procedures. All fusible links and any other component shall be replaced with new components to meet all NFPA codes and compliance. Contractor shall document model, type, serial number as applicable for all replacement parts. Replacement of parts to perform preventative maintenance for up to $150.00 are included in the service contract by contractor. These parts include but not limited to fusible links, Detection cable, Cartridge/cylinder seals & O-rings, Pull station pins/seals, Micro-switches, Control panel batteries (e.g., Fike Cheetah-XI backup battery), Access panel gaskets/seals, Fan belts (if applicable), Filter retention clips/hardware, etc. are included in PMs at no additional cost to the government. Government shall pay for a difference if total value of parts exceeds $150 after the contractor provides a quote to be approved by the COR.

E. Contractor shall schedule all work 30 days in advance with COR. Any change will be only authorized by COR.

F. Only the contracting officer can make monetary and scope change through modification, which COR has to recommend.

G. Contractor shall provide update information about system upgrade requirements by Federal, State, and local authorities. Contractor shall provide literature of violations and recommendations of upgrades, if any.

5.2 Site Investigation and Conditions Affecting the Work

A. The Contractor acknowledges that it has taken steps reasonably necessary to ascertain the nature and location of the work, and that it has investigated and satisfied itself as to the general and local conditions which can affect the work or its cost, including but not limited to (1) conditions bearing upon transportation, disposal, handling, and storage of materials; (2) the availability of labor, water, eclectic power, and roads; (3) uncertainties of weather, river stages, tides, or similar physical conditions at the site; (4) the conformation and condition of the ground; and (5) the character of equipment and facilities needed preliminary to and during work performance. The Contractor also acknowledges that it has satisfied itself as to the character, quality , and quantity of surface and subsurface materials or obstacles to be encountered insofar as this information is reasonably ascertainable from an inspection of the, including all exploratory work done by the Government, as well as from the drawings and specifications made a part of this contract. Any failure of the Contractor to take the actions described and acknowledged in this paragraph will not relive the Contractor from responsibility for estimating properly the difficulty and cost of successfully performing the work, or for proceeding to successfully perform the work without additional expense to the Government.

B. The Government assumes no responsibility for any conclusions or interpretations made by the Contractor based on the information made available by the Government. Nor does the Government assume responsibility for any understanding reached or representation made concerning conditions which can affect the work by any of its officers or agents before the execution of this contract, unless that understanding or representation is expressly stated in this contract.

5.3 Contract Modifications

A. Throughout the performance of this contract tanks may need to be added or removed from the contract. In the event that the needs change, the Contractor will negotiate with the Contracting Officer to reach a mutually agreeable adjustment to the contract that must be captured in a written modification to the contract.

5.4 Safety:

A. At a minimum contractor, subcontract, and personnel shall wear at all times hard hat, safety glasses, reflective vest, and safety shoes.

B. No shorts or tank tops shall be permitted.

C. Contractor shall adhere to OSHA 10 CFR 1910.

D. Contractor shall be responsible to use appropriate PPE when required by the OSHA and VAPAHCS.

E. Safety plan shall be submit to the COR within 15 days of awarded contract.

F. Contractor shall submit Safety Data Sheet for all chemical used at the VAPAHCS. Chemicals must be approved by COR or Safety Services. Safety Data Sheet shall be kept at work site at all times.

G. Contractor shall comply with Environment Protection Agency standards. No dumping of water or chemical in the storm drains. Contaminates shall be removed from VAPAHCS property and shall be disposed of per all Federal, State, and Local EPA regulation and standards at no additional cost to the government.

a. Any penalties incurred due to unlawful disposal of hazardous material or EPA, State, or Local regulation and standards shall be the responsibility of the Contractor.

5.5 Performance Standards:

A. Contractor shall adhere to the performance standards listed below. Contractor shall adhere to all references in the performance standard to include all notes, explanatory material, and appendixes. The most current edition will be used on all references listed below.

a. NFPA 10: Standards for Portable Fire Extinguishers

b. NFPA 13: Standards for the Installation of Sprinkler Systems

c. NFPA 25: Standards for the Inspection, Testing, and Maintenance of Water-Based Fire Protection System

d. NFPA 96: Standards for Ventilation Control and Fire Protection of Commercial Cooking Operations

e. NFPA 99: Health Care Facilities Code

f. OSHA Standard 29 CFR 1910

B. If a dispute between two codes arises, the most stringent code shall be enforced.

C. If contractor has a different code interpretation than the COR then contractor shall have the opportunity to have the Engineering Compliance office review and make decision, which contractor shall accept. The AHJ shall be the Chief of Engineering of VAPAHCS.

5.6 Documentation Requirements

A. The Contractor shall provide reports to the COR and Compliance Office.

B. Each report shall include a separate document for Grease Hood and HazMat Container.

C. Contract shall use approve reporting form. Contractor shall submit reporting form 15 days from award of contract. COR shall review and approve form. Contractor shall adhere to COR reviews.

D. Submit four (1) hard copies of the completed written report and one (1) PDF version of the report to the Engineering Compliance Office within seven (7) calendar days of completion of inspection and testing.

5.6 Inventory of Equipment

A. Palo Alto

a. Semi-Annual and Annual Cleaning & Certification of two (2) Bldg 100 Main Kitchen Grease Hoods, Ducts & Fans.

b. Semi-Annual and Annual Cleaning & Certification of three (3) Bldg 101 Canteen Grease Hoods, ducts & Fans.

c. Semi-Annual and Annual Service and certification of Automatic Fire Control Systems for buildings, 100 and 101 (total of five (5) hoods.

d. Semi-Annual and Annual Certification of three (3) Chemical Hazardous Material Storage Sheds, self contained fire protection systems.

B. Menlo Park Division:

a. Semi-Annual Cleaning & Cert of one (1) Bldg 329, Main Kitchen Grease Hood, duct & Fan.

b. Semi-Annual and Annual Certification of One (1) Chemical Storage Sheds Automatic Fire Control Systems.

c. Semi Annual and Annual Certification of One (1) Automatic Fire Control Systems buildings 329.

C. Livermore Division:

a. Semi-Annual and Annual Certification of two (2) Chemical Hazardous Material Storage Sheds, self contained fire protection systems

5.7 Security Requirements

A. The Certification and Accreditation requirements do not apply and a Security Accreditation Package is not required for this work.

B. Contractors, contractor personnel, subcontractors, and subcontractor personnel shall be subject to the same Federal laws, regulations, standards, VA directives and handbooks as VA personnel regarding information security under VA Handbook 6500.6, Contract Security, Appendix C.

Section 6: Attachments

1. Equipment Inventory with Maintenance Schedule and Bldg plans.

See attached document: Grease Hood-HAZMAT shed inventory-Schedule- bldg plans 7-24-206.

File details come from the government source that posted it. Updated .