VANCH MATHER BUILDING 700 SEMI ANNUAL AND QSP.pdf
PDF 2 MB Posted
- Attached to
- J012--Fire Sprinkler Testing and Maintenance and Repairs for VA Northern California Health Care System
- Solicitation number
- 36C26123Q0259
About this file
This document includes a fire sprinkler system inspection report and related federal contract opportunity. The inspection report details the semi-annual inspection of the fire sprinkler system at the Vanch Mather Building 700 located in Rancho Cordova, California. It provides information on six sprinkler risers, inspection and testing results for sprinkler components, control valves, waterflow alarms, and backflow preventers. Deficiencies were noted but corrections are not specified.
The related federal contract opportunity is solicitation number 36C26123Q0259 for fire sprinkler testing, maintenance, and repair services for the VA Northern California Health Care System. The opportunity was posted by the Department of Veterans Affairs Veterans Health Administration VISN 21. The solicitation seeks a contractor to provide regular inspection, testing, and maintenance in accordance with NFPA standards for the fire protection systems within the health care system's facilities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| VANCH MATHER BUILDING 726 SEMI ANNUAL AND QSP.pdf | ||
| Clarifiying Questions 36C26123Q0259.docx | DOCX document | |
| 36C26123Q0259 0001.docx | DOCX document | |
| VANCH MATHER BUILDING 700 ANNUAL AND QSP.pdf | ||
| Attachment 1 - Tamper Flow Consolidated List.xlsx | XLSX spreadsheet | |
| 36C26123Q0259.docx | DOCX document | |
| Attachment 3 - Wage Determiantion Alameda Contra Costa.pdf | ||
| Attachment 4 - Wage Determination Solono.pdf | ||
| Attachment 2 - Wage Determination El Dorado Placer Sacramento Yolo.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AES 1 Sept. 3, 2013
Inspection, Testing, and Maintenance Cover Sheet NFPA25 as amended by CCR, Title 19
Property Information:
Name: VANCH MATHER BUILDING 700 Occupancy/Use: LIGHT/ORD
Address: 10535 HOSPITAL WAY Construction Type: WOOD/CONCRETE
City: RANCHO CORDOVA, CA No. Stories: 6
ZIP: 95655 Year Constructed: N/A
Contact: DOUG GAMBRELL
Telephone: (440)319-2479
Contractor Information: Number of System Risers 6
Copy sent to:
Name: Owner Date:
Address Fire AHJ Date:
City: Contractor Date:
State: NOTES:
1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011 edition as amended by California Code of Regulations, Title 19, §901 to §906.
2) Inspection items may be performed by the owner in accordance with California Code of Regulations, Title 19, §904.1(a)
Telephone:
CA License#: 905493
Job #: HURTVET 3626120P1265
Performed by:
Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.
Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass
Automatic Sprinkler System 5 1
Standpipe and Hose System 6
Private Water Supply System 7
Fire Pump 8
Water Storage Tank 9
Water Spray System 10
Foam Water Sprinkler System 11
Water Mist System 12
Concerns that are Not Deficiencies (i.e. Non-Sprinklered Areas) Yes No
*See "Deficiencies and Comments" section at end of each respective form.
8/24/2021
Wet Pipe Fire Sprinkler System
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and SEMI Annual
Report
Property Information Contractor or Licensed Owner Information
Building VANCH MATHER BUILDING 700 Address 10535 HOSPITAL WAY
City RANCHO CORDOVA, CA License # 905493 Contact DOUG GAMBRELL SFM Job # HURTVET 3626120P1265 Phone
(440)319-2479
CSLB
Misc. SEMI ANNUAL Quarterly Sprinkler Inspection
Riser Information Main Drain Test (Annual) Riser No. Location
Riser Diameter
Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure P,F,N/A
1 1ST FLOOR (STAIRWELL 2) 2 ½ ’’ 1 ½ ‘’ 140 PSI N/A N/A P
2 2ND FLOOR(STAIRWELL 2) 2 ½ ’’ 1 ¼ ‘’ 131 PSI N/A N/A P
3 3RD FLOOR(STAIRWELL 2) 2 ½ ’’ 1 ¼ ‘’ 128 PSI N/A N/A P
4 4TH FLOOR(STAIRWELL 2) 2 ½ ’’ 1 ¼ ‘’ 121 PSI N/A N/A P
5 5TH FLOOR(STAIRWELL 2) 2 ½ ’’ 1 ¼ ‘’ 116 PSI N/A N/A P
6 6TH FLOOR (STAIRWELL 2) 2 ½ ’’ 1 ¼ ‘’ 108 PSI N/A N/A P
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable Item Description NFPA 25 CA ed.
Reference Date Date Date Date
7-20-21
1.1 I Control Valves – Identification Sign 13.3.1 P
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 P
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 P
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 P
1.9 I Hydraulic Design Information Sign
(For Hydraulically Designed Systems) 5.2.6 P
1.10 I
General Information Sign (Not Required for System prior to 2007 Edition of NFPA 13)
5.2.8 P
1.11 I Heat Tape 5.2.7 NA
1.12 I Spare Sprinklers 5.2.1.4 P
1.13 I Fire Department Connections 13.7 P
1.14 I Alarm Valves – Exterior Inspection 13.4.1 P
1.15 I Pressure Reducing Valves 13.5.1.1 N
1.16 I Backflow Preventers 13.6.1 P
1.17 I Small Hose Connections - Hose Valve* 5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
Quarterly Inspections EP 2 EXCEPT WHERE NOTED
EP 10
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe systems.
Wet Pipe Fire Sprinkler System
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and SEMI Annual
Report
Property Information Contractor or Licensed Owner Information
Building VANCH MATHER BUILDING 700 Name
Address 10535 HOSPITAL WAY Job # HURTVET 3626120P1265 City RANCHO CORDOVA, CA Misc. SEMI ANNUAL Quarterly
Sprinkler Inspection
SEMI ANNUAL INSPECTION, TESTING, AND MAINTENANCE
Include ALL Quarterly Inspections
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference Date Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 7-20-21 N
1.20 I Buildings (Freeze Protection) 4.1.1.1 7-20-21 Owner’s Responsibility N
1.21 I Pipe and Fittings 5.2.2 7-20-21 N
1.22 I Hangers 5.2.3 7-20-21 N
1.23 I Seismic Braces 5.2.3 7-20-21 N
2.1 T Field Service Test Required (Send
Report to Fire Code Official)
5.3.1 7-20-21 If REQUIRED, Enter 'F' until results are returned from Lab N
2.2 T Recalled Sprinklers
If not present = Pass; If present = Fail Title 19 904.1(c) 7-20-21 N
2.3 T Water Flow Alarm Devices 90
sec. maximum - (Enter Time )
5.3.3 13.2.6
7-20-21 90 sec. P
2.4 T Main Drain Test
(Enter Data on Page 1 of this Form)
13.2.5 13.3.3.4
7-20-21 P
2.5 T Control Valve - Position 13.3.3.2 7-20-21 P
2.6 T Control Valve – Operation 13.3.3.1 7-20-21 P
2.7 T Supervisory Devices 13.3.3.5 7-20-21 P
2.8 T Backflow Preventer Assemblies 13.6.2 7-20-21 P
2.9 T Small Hose Connections* w/PRV Hose
Valves – Partial Flow Test
13.5.2.3 13.5.3.3
7-20-21 N
2.10 T PRV – Fire Sprinkler Systems 13.5.1.3 7-20-21 N
3.1 M Control Valves 13.3.4 7-20-21 P
3.2 M Small Hose Connections* 13.5.6.3 7-20-21 N
3.3 M
Obstruction Investigation required (If “Yes”, see Deficiencies and Comments Section for Results.)
14.3 7-20-21 Yes
No N
3.4 M System Returned to Service 4.5.3 7-20-21 Yes
No P
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe systems.
EP 9
VHAMACForemM Highlight
Wet Pipe Fire Sprinkler System
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and SEMI Annual
Report
Property Information
Contractor or Licensed Owner Information
Building VANCH MATHER BUILDING 700
Name Address 10535 HOSPITAL WAY Job # HURTVET 3626120P1265 City RANCHO CORDOVA, CA Misc. SEMI ANNUAL Quarterly
Sprinkler Inspection
D = Deficiency C = Comment (Indicate type )
Item Date Riser D C Deficiencies and Comments Indicate all equipment, devices and parts that were repaired or replaced
*****SEMI ANNUAL QUARTERLY SPRINKLER INSPECTION*****
Notes:
END OF REPORT
Check here if additional Deficiencies and Comments are listed on Form AES9.
See Correction Form AES 10 for corrected deficiencies.
Number attached Number attached
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Check box if Annual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Quarter 1st - SEMI Annual 2nd - Annual 3rd - Annual 4th - Annual Date 7-20-21
Print Name TY KELL Signature TY KELL