Text Box Okay to lower Air flow by 20% of indicated for administrative areas per Mech EOR to reduce noise level in Animal holding rooms. Coordinate with COR

VHASFCBRAZEC

Change to 10 ACH to animal holding rooms. Provide proposed CFMs to COR prior to execution.

VHASFCBRAZEC

New existing sound attenuators not shown