36C26118R0048-00004001.pdf

PDF 94 KB Posted

Attached to
Project: #654-16-614 Water Safety Dead Leg Removal
Solicitation number
36C26118R0048
Issued by

About this file

36C26118R0048 00004 654-16-614 AMENDMENT 00004- Question-Answers - May 23 2018.pdf

View the file

Other files

File Type Posted
36C26118R0048-0008001.pdf PDF
36C26118R0048-0008000.docx DOCX document
36C26118R0048-00007000.docx DOCX document
36C26118R0048-00007001.pdf PDF
36C26118R0048-00006000.docx DOCX document
36C26118R0048-00005001.pdf PDF
36C26118R0048-00005000.docx DOCX document
36C26118R0048-00004000.docx DOCX document
36C26118R0048-00003000.docx DOCX document
36C26118R0048-00002000.docx DOCX document
36C26118R0048-00002001.pdf PDF
36C26118R0048-00001001.pdf PDF
36C26118R0048-00001000.docx DOCX document
36C26118R0048-021.pdf PDF
36C26118R0048-005.xlsx XLSX spreadsheet
36C26118R0048-018.pdf PDF
36C26118R0048-013.pdf PDF
36C26118R0048-022.pdf PDF
36C26118R0048-015.pdf PDF
36C26118R0048-014.pdf PDF
36C26118R0048-010.pdf PDF
36C26118R0048-020.pdf PDF
36C26118R0048-017.pdf PDF
36C26118R0048-006.pdf PDF
36C26118R0048-012.pdf PDF
36C26118R0048-011.pdf PDF
36C26118R0048-019.pdf PDF
36C26118R0048-003.pdf PDF
36C26118R0048-016.pdf PDF
36C26118R0048-009.pdf PDF
36C26118R0048-008.pdf PDF
36C26118R0048-007.pdf PDF
36C26118R0048-004.pdf PDF
36C26118R0048-002.pdf PDF
36C26118R0048-001.docx DOCX document
36C26118R0048-000.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT NO. 00004

Solicitation 36C26118R0048

Project 654-16-614 Water Safety Piping Revisions

General

The following changes, additions or deletions shall be made to the following Contract Documents.

All other conditions shall remain the same.

1. SPECIFICATIONS

a. N/A

2. DRAWINGS

a. N/A

3. BIDDER QUESTIONS AND CLARIFICATIONS

a. Question 1: What areas/spaces are considered to be confined space?

b. Response: VASNHCS has a list of areas that are considered permitted and nonpermitted confined spaces. In this project a crawlspace will be considered a confined space. A list of the specific areas at the medical center that are confined spaces and an SOP will be provided to the contractor after contract is awarded.

c. Question 2: Are we to expect any lead or asbestos material in or around the pipes to be removed? And, if so, what are our procedures to address these materials?

d. Response: Asbestos abatement is not included in this construction project.

Previous sampling has not found pipe insulation that contains asbestos in the areas covered in this contract or the asbestos has already been abated. Any materials that are found to have asbestos will be abated per applicable codes and requirements.

e. Question 3: Where exactly will we be cutting off the ‘dead leg’?

f. Response: Must be cut within 1-1/2 diameters of the dead leg pipe. Example; If the dead leg pipe is a 1” diameter pipe, the dead leg must be terminated within 1.5”.

g. Question 4: How many dead legs go back to isolation valves that do not require a shutdown of the water system? Please provide location, size, and quantity.

h. Response: Most, if not all require a shutdown.

i. Question 5: Are there special requirements to de-water the dead legs? Can the water be routed into the sewer system? Please advise and/or provide specification/procedure.

j. Response: Water can be routed to waste water system.

k. Question 6: Is there any requirement for disinfection? If so, to what extent?

l. Response: Yes. Per AWWA C651 and International Plumbing Code.

m. Question 7: According to the dead leg inventory, it appears #185 on the 2nd floor resides behind a restroom/toilet. Can the VA provide information on where that pipe runs with respect to this restroom? Perhaps a picture or plan of the restroom where the pipe is running would be helpful.

n. Response: Specific piping details or existing conditions are not available. Walk through of the project was to be used by the contractor to identify specific as-built details or existing conditions for bidding purposes.

o. Question 8: According to the dead leg inventory, it appears #219, 220, 261, 262, 263, and 264 reside behind walls. Can the VA provide information on where these pipes run with respect to the walls? Perhaps a picture of plan of the wall vicinity where these pipes run would be helpful.

p. Response: Specific piping details or existing conditions are not available. Walk

q. Question 9: Are there any dead legs that penetrate a floor that will require floor demolition and repair? If so, please provide location, quantity, and size of pipe.

r. Response: Specific piping details or existing conditions are not available. Walk

s. Question 10: Is there any restriction on how many dead legs can be worked on at one time?

t. Response: As many as can get completed, sanitized and the domestic water system placed back in service for the following work day as to not interfere with patient care.

-END OF AMENDMENT NO. 00004-