This is a Statement of Work for elevator maintenance and repair services at White City VA Medical Center located at 8495 Crater Lake Highway, White City, OR 97503. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 20 is soliciting a contractor to provide comprehensive maintenance and repair services for all elevators at the facility. The solicitation number is 36C26027Q0121, with questions due by November 27, 2026 at 5:00 PM PST and offers due by December 4, 2026 at 5:00 PM PST.
The specific scope of work, elevator inventory, maintenance requirements, and performance standards are detailed in the full Statement of Work document. Interested contractors must review the complete SOW in its entirety to understand all requirements, service level agreements, response protocols, and deliverables expected under this maintenance services contract with the VA Medical Center.
View the file
Other files
On GovTribe
Work with this file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK (SOW)
Centric Elevators as of 9/1/2026
1. Contract Title. Elevator Maintenance and Repair
2. Background.
Contractor shall provide White City VA Medical Center (VA SORCC), 8495 Crater Lake Highway, White City, OR 97503, with maintenance and repairs to all elevators listed below in the Statement of Work. This includes O&M manuals, VA personnel training, and expectations of the customer. Contractor shall have been in business a minimum of ten years, with the core business being dedicated to maintenance and repair of elevators. Contractor’s elevator technicians must be properly license and must be able to meet the one-hour callback requirement listed in section four.
3. Scope.
This section covers full maintenance and repair, which includes emergency callback services, regular and systematic inspections and preventive maintenance of each of the elevators listed below. The Contractor shall accomplish all work needed to troubleshoot, clean, lubricate, test, adjust, repair, dismantle, and assemble, when necessary, to provide complete care and upkeep needed to maintain the elevators in good operating condition (except as excluded elsewhere in the specifications). Maintenance tasks for each car shall be performed per the manufacturer’s recommended specifications. All equipment, materials, and installations shall conform to the following codes:
a) The American National Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks- ANSI/ASME, A17.1/CSA B44, 2007.
b) Guide for Inspection of Elevators, Escalators, and Moving Walks ANSI/ASME A17.2, 2007.
Manufacturer
Model
S/N
Location
Innovation Industries Hydraulic
906088
B201
Innovation Industries Hydraulic
None
B224
Esco
PXH10822
B208
PXH12338
B240
ThyssenKrupp
Hydraulic
EAA461
B202
ThyssenKrupp
Tac22
EAT
B204A
Tac32
EBF211
B205A
EBH536
B201A #1
EBH537
B201A #2 Lift Solutions/Centric
MCE
B210
ThyssenKrupp*
B225
*(B225 elevator not on maintenance until OY2, OY3, OY4) All work performed shall be within this Scope of Work to the extent it applies to the types, size and locations of the elevators listed above. The successful bidder shall provide one (1) set of O&M manuals for the above listed elevators and shall provide the preventive maintenance program for each elevator per the manufacturer’s O&M manuals. Both shall be provided to the Contracting Officer’s Representative (COR) within 30 days of acceptance of this service contract.
2.1 Inspections:
1. Maintenance Schedule/Inspections- Preventive and recurring maintenance shall be accomplished in accordance with the manufacturer’s recommendation. Completed maintenance checklists shall be furnished to the COR at the time of monthly invoicing. The following checklists from the American Society of Mechanical Engineers (ASME) shall be used: Checklist for Inspection of Electric Elevators, Checklist for Inspection of Hydraulic Elevators, Checklist for Inspections of Escalators and Moving Walks, and the manufacturer’s Operation and Maintenance manuals for preventive maintenance tasks, as applicable.
2. All passenger and service type elevators shall be inspected monthly and maintenance performed. A minimum of one hour, per elevator, per maintenance and inspection is required.
3. The Contractor shall provide an estimated time and cost for work or repairs not covered in this service contract. Any work that increases the cost to the Government shall be approved, in writing, by the Contracting Officer prior to performance. All repair work shall be in accordance with the normal commercial practices using parts specified by the elevator manufacturer or items of equal or better quality. Downtime of the elevator will be kept to an absolute minimum. The Contractor shall notify the customer of all projected downtime and estimated time for repair.
4. Work required under this contract shall include, but is not limited to, a thorough check of and replacement or repair of items suck as control panels, main machine governors, safeties, car hatchways, accessories in pits, relays, contacts, contact leads, switched, selectors or associated parts.
2.2 Maintenance Service
Contractor shall maintain all elevator equipment using trained and certified persons directly employed and supervised by the Contractor. These persons shall be qualified to keep the equipment properly adjusted and shall use all reasonable care to maintain equipment in proper and safe operating conditions:
1. As needed, examine, adjust, clean, lubricate and, when conditions warrant, repair or replace: machine, motor and controller parts including worms, gears, thrusts, bearings, brake magnate, brake shoes, brushes, field and armature windings, commutators, rotating elements, coils, contacts, resistors, magnate frames, solid state electrical components and other electro-mechanical parts.
2. Selector and dispatching equipment relay printing circuit boards, SCR controls, condenser, transformers, contacts, leads, timing devices, computer devices and traveling cable.
3. Governor, governor sheaves and assembly, bearings, contacts, governor jaws, governor cables, and car safeties.
4. Deflector or secondary sheaves, bearing, car and counterweight buffers, car and counterweight shoes, including rollers or gibes, top and bottom limit switches, governor tension sheaves assembly, compensating sheave assembly, hoist ropes, governor ropes, compensating ropes and chains. Load weighing equipment, car frame, car safety mechanism, platform, wooden platform flooring.
5. Door operator, clutch assembled, pick-up rollers, interlocks, hoist way door hangers, bottom door guides, safety edges, electric eyes, astragal, auxiliary door closing devices, hatch indicators, vanes, car and hall lanterns, fixtures, power fans, position indicators, access switched and inspection stations.
6. Keep the guide rail clips properly lubricated where required. Renew guide shoe gibs or guide rollers as applicable to assure smoother and quitter operation.
7. As needed, examine all safety devices and governors and equalize the tension on all hoisting ropes.
8. Furnish and supply manufacturer’s approved parts and lubricants or equal or better quality.
9. As needed, examine, adjust, clean, lubricate, and, when conditions warrant, repair or replace: pumps, pump motors, operating valves, valve motors, motor windings, leveling valves, plunger packing's, exposed piping, hydraulic fluid tanks on hydraulic elevators and furnish hydraulic fluid.
10. Power plant, consisting of its enclosure, pump, motor, power transmission elements between the pump and motor, valves (of every kind), strainers, mufflers, gaskets and all other accessories.
11. Entire controller and motor starter including accessories.
12. All hoist way equipment of every kind, including fastenings to the building. All electrical wiring, conduit, ducts, traveling cables, etc., from and beyond the elevator equipment of every kind to the main line disconnect switches and hoist way outlets.
13. All piping, fittings and accessories (such as vibration dampeners, silencers, etc.) between the pumping plant and the jack unit (unless buried underground).
14. Emergency lighting, firemen's service equipment, automatic power door operators, landing and car door hangers, landing and car door contacts, door protective devices, hoist way door interlocks, bottom door guides, manual door closer and auxiliary door closing devices.
15. Re-lamp all inoperative signals during regular examinations, all other miscellaneous equipment, materials, solid state components, etc. not mentioned above or the makeup of the complete elevator or elevators.
2.3 Lubrication/Adjustment Service.
The Contractor shall furnish all lubricants, hydraulic fluid, cleaning supplies and tools necessary to perform the work described above. All lubricants shall be as recommended by the manufacturer of the equipment.
1. As required, the machines, brakes, motors, controllers, relay panels, selectors, leveling devices, operating devices, switches on car and hoist way, hoist way door and car door or gate operating devices, interlocks and contact guide shoes, or roller guides, guide grooves in hoist way and car door sills, hangers for all doors and car doors or gates, signal system, car safety devices, governors, tension frames and sheaves in pit shall be lubricated and adjusted in accordance with manufacturers recommendations: (See SHUTDOWN OF ELEVATORS).
2. All hoisting ropes, where applicable, shall be examined quarterly and tension equalized, and a written report of rope condition furnished to the COTR upon completion of adjustment. When Contractor's recommendation to replace hoisting ropes is approved, the Contractor shall renew all hoisting ropes and governor ropes. The exterior of the machinery and any other parts of the equipment, subject to rust, shall always be kept properly painted and presentable. The motor windings shall be periodically treated with proper insulation compound. The guide rails shall be kept free of rust, where roller guides are used and properly lubricated where sliding guides are used. Guide shoe roller and gibs shall be renewed as required to insure smooth and satisfactory operation. All electrical wiring and conductors extending from elevators and machine rooms into the hoist ways shall be repaired and for replaced when required. Circuit breakers on main line switches, together with main line fuses, are excluded.
2.4 BREAKDOWNS: The Contractor shall repair all breakdowns in full and the elevator shall be returned to service as soon as possible. All callback trouble calls and repairs shall be accomplished under the basic contract at no additional cost to the Government.
2.5 Parts to be Furnished and Installed or Repaired: The Contractor shall furnish and install or repair when and as necessary, machine hydraulic pumps, motor generators, controllers, selectors, worms, gears, thrusts, windings, commutators, hydraulic pump 'VEE" belts and pulleys, hydraulic valve components and coils, circuits, magnet frames, relays, contractors, control fuses, cams, car door and hoist way door hangers, tracks and door guides, door operating devices, interlocks and contacts, car gates, safety devices, governors, push but1ons, annunciators, hail lanterns and indicators, lamp replacements in signal systems and all other elevator signal and accessory equipment complete. All parts shall be of the original manufacturer's design and specification or approved equal.
2.6 Inventory: Contractor shall own and maintain or have ready access to an efficient stock of replacement parts, by the original manufacturer or approved equal, to maintain the equipment in a first-class and safe operating condition. All diagnostic equipment, microprocessor printed circuit boards, solid-state circuitry parts and reprogramming capabilities shall be of the original manufacturer’s parts only.
2.7 Cleaning Services: All parts, equipment, sheaves and beams, counterweights, frame, top of cars, bottom of platforms, hatchways, pits and machines room floors shall be kept clean. Contractor shall clean, remove dirt, hydraulic fluid, lint, excessive grease on or about the machines, motors, controls and associated equipment and accessories. Car tops and pits are to be cleaned at least each time the machine is inspected, serviced or repaired. Pit cleaning shall include removal of rubbish, debris, spillage and drippings. Contractor shall wipe down all machinery and keep it free of dust. Oily rags shall be removed from the premises and disposed of after each service visit. Material safety Data Sheets (MSDS's) shall also be maintained at the worksite for cleaning and maintenance supplies.
2.8 Lamp Replacement: Car top lights, pit lights, hoist way lights, floor signal lights and operational control lights are to be kept operational by the Contractor. Contractor shall check all lamps at the time of required inspection and shall immediately replace those found to be out of order.
4. Specific Tasks.
EMERGENCY CALLBACK SERVICE: Emergency callback service shall be provided within one (1) hour of receipt of requests (telephone or otherwise) from the VA covering shutdowns or any emergency trouble arising between scheduled service calls. This callback service shall be rendered at any hour of any day of the week at no additional charge to the Government, except when cause is other than Contractor's responsibility. If a serviceman is not immediately available, the office receiving the call must notify the Medical Center stating the length of time of delay. They will be advised at that time if service call can be deferred. The contractor shall commence work within one (1) hour and if the job cannot be completed, due to lack of parts, he is to notify the COR, Facilities Management Service Maintenance Supervisor or the boiler plant. The Government reserves the right to procure services from a non-contract source and bill the costs to the Contractor if response time from the Contractor is determined inadequate.
REPORT OF SERVICES: Immediately upon completion of each inspection or emergency call, a copy of the Contractor's service report, initialed by the VA employee in charge of the equipment shall be furnished to the COR. At night, weekends, or holidays, the Contractor shall deliver service or repair tickets to the boiler plant. Additionally, Contractor shall provide Maintenance Supervisor, by email, copies of all service tickets and call back tickets for the previous month by no later than the 5th of the following month.
SHUTDOWNS OF ELEVATORS: Shutdown of elevators for cleaning, lubrication and adjustment shall be performed during off-peak hours or as determined by COR. Contractor shall notify the COR, or his/her designee, twenty-four (24) hours in advance of date scheduled for equipment shutdowns. Signs must be posted at each floor to inform personnel that elevator is down for service or repairs. (NOTE: Interruption of service by shutdown is work requiring shutdown for more than one (I) hour at any one time.)
5. Performance Monitoring.
All work shall commence within one (I) hour after receipt of telephonic notification unless other arrangements are made and are acceptable with the VA, after which work shall proceed progressively to accomplishment without undue delay. Upon arrival at the VA Medical Center White City, Contractor's technician shall report to 8229, Facilities Management Service and check in with Maintenance Supervisor or COR, sign in and receive a contractor's badge prior to commencing repairs or maintenance.
Contractor agrees to maintain the following minimum requirements of the elevators designated below:
a) Speed: Plus or minus 5% under any loading condition.
b) Capacity: Safety lower, stop and hold up to 125% rated load.
c) Leveling: Plus or minus 3/8" under any loading condition.
d) Door closing time, thrust and kinetic energy shall comply with all ANSI code.
e) Floor to floor performance time: Per manufacturer's specification from time door starts closing at one floor to fully opened and level on successive typical floor, regardless of loading conditions or direction of travel. If not feasible, contractor must contact the COR or Maintenance Supervisor with recommendations for compliance.
In accomplishing the above requirements, Contractor shall maintain a comfortable ride with smooth acceleration, retardation, and a soft stop. Door operation shall be quiet and positive with smooth checking at the stream of travel.
Perform the following test on the elevator equipment:
a) Test of the car and counterweights safeties, governors, buffers and all other safety devices. The car balance will be checked and the governor set. If required, the governor will be recalibrated and sealed for proper tripping speed. Annual no-load and five-year full load code required testing will be complied with.
b) Code required yearly relief valve test and cylinder leakage test on all hydraulic elevators.
c) All tests performed on the elevator equipment described will be in accordance with the most recent ANSI/ASME A17.1 and A17.2 code requirements.
6. Security Requirements.
The contractor employees shall not have access to VA sensitive or computer information and will not require routine access to VA Facilities. The contractor employees shall require intermittent access only and will be escorted by VA employees while at VA Facilities. No background investigation is required.
7. Government-Furnished Equipment/Government-Furnished Information.
Manufacturer
Model
S/N
Location
Innovation Industries Hydraulic
906088
B201
Innovation Industries
B224
PXH10822
B208
PXH12338
B240
ThyssenKrup
EAA461
B202
Tac22
EAT
B204A
EBF211
B205A
EBH536
B201A #1
EBH537
B201A #2 Lift Solutions/Centric
MCE
B210
ThyssenKrupp*
B225
*(B225 elevator not on maintenance until OY2, OY3, OY4)
8. Other Pertinent Information or Special Considerations.
1. Quality Assurance Surveillance Plan
a. This Quality Assurance Surveillance Plan (QASP) has been developed to evaluate contractor actions while implementing this Statement of Work (SOW). It is designed to provide an effective surveillance method of monitoring contractor performance for each listed objective in the maintenance contract.
b. The QASP provides a systematic method lo evaluate the services the contractor is required to furnish.
c. This QASP is based on the premise the government desires to maintain a quality standard in operating, maintaining and repairing facilities and that a service contract to provide the service is the best means of achieving that objective.
d. The contractor and not the government, is responsible for management and quality control actions to meet the terms of the contract. The role of the government is quality assurance to ensure contract standards are achieved.
| Performance Objective |
| Performance Threshold |
| Perform Preventive Maintenance: |
| 95% of elevators are operational at all times |
Repair Service Calls:
Repairs are made in timely manner; Customers are informed of expected repair time; Response and repair is made within the specified time.
Response to and repairs of service calls are timely 95% of the time
Submit Maintenance and Repair Reports:
Immediately upon completion of each inspection 95% of all reports are timely and accurate
In this contract the quality control program is the driver for product quality. The contractor is required to develop a comprehensive program of inspections and monitoring actions. The first major step 10 ensuring a "self-correcting" contract is to ensure that the quality control program approved at the beginning of the contract provides the measures needed to lead the contractor to success. Once quality control program is approved, careful application of the process and standards presented in the remainder of this document will ensure a robust quality assurance program.
2. Surveillance: The government QA will evaluate the performance objectives through contractor metrics, periodic inspections during each service month, customer feedback and outage reports.
3. Standard: The contractor shall perform all work required in a satisfactory manner in accordance with the appropriate SOW paragraph. The QA shall not consider the services complete until all deficiencies have been corrected.
4. Procedures/Remedies: The COTR will inspect all contract performance objectives at least semi-annually to ensure contractor compliance with the appropriate paragraphs of the SOW. In addition, they will record results of inspection, noting the date and time of inspection. If inspection indicates unacceptable performance, they notify the contract manager or the contractor's Quality Control Inspector (QCI) of the deficiencies for correction. The contractor shall be given two hours after notification to correct the unacceptable performance or the COTR may approve additional time if the COTR considers additional time appropriate. CONTRACTOR WTLL REPERFORM SERVICE AT NO ADDITIONAL COST TO THE GOVERNMENT. If deficiencies are not corrected within the required time frame the COTR will notify the Contracting Officer for action. ff these percentages are not met, the COTR will contact the Contracting Officer to seek resolution and reach mutual agreement.
9. Risk Control Contractor shall NOT:
a) Make renewals or repairs necessitated by damage of the equipment by persons other than the Contractor by reason by other damage beyond control of the Contractor, unless approved, in writing, by the Contracting Officer.
b) Install, without purchase order authority, new attachments as may be recommended or directed by inspection firms or by Federal, State, and Municipal or other Government authorities.
c) Be responsible for repair or replacement of building items, hoist way or machine room walls or floors, car enclosures, car finish, floor materials, hoist way entrance frames, doors and sills and signal fixture face plates.
d) Be responsible for machine and auxiliary disconnect switches, fuses and feeders to control panels.
e) Be required to make renewals or repair necessitated by fluctuations in the building AC power systems, extreme variations in machine room (allowable variations to be between 65 degrees Fahrenheit and 95 degrees Fahrenheit temperature) or tampering with the-elevator equipment by unauthorized personnel.
10. Place of Performance.
White City VA Medical Center (VA SORCC) 8495 Crater Lake Highway White City, OR 97503 Buildings: B201, B224, B208, B240, B202, B204A, B205A, B201A #1, and B201A #2, B210, and B225.
All services shall be performed during normal business hours from 8:00 a.m.- 4:30 p.m., Monday – Friday.
11. Period of Performance.
Base Year: 10/01/2026 – 09/30/2027 Option Year 1: 10/01/2027 – 09/30/2028 Option Year 2: 10/01/2028 – 09/30/2029 Option Year 3: 10/01/2029 – 09/30/2030 Option Year 4: 10/01/2030 – 09/30/2031