S02 Drawings - Boise VAMC Biomed HVAC - CD Set.pdf
PDF 3 MB Posted
- Solicitation number
- 36C26025R0066
About this file
These are architectural and engineering drawings for a mechanical systems upgrade project at the Boise Veterans Affairs Medical Center (VAMC) Biomedical Building, specifically detailing HVAC system renovations. The comprehensive drawing set (designated 531-24-107) includes multiple sheets covering mechanical demolition plans, new mechanical system layouts, energy compliance calculations, mechanical schedules, control schematics, and electrical power and distribution plans for Building 27. Key technical elements include installing new multi-port heat pump systems with indoor and outdoor units, an energy recovery unit, and associated ductwork, electrical infrastructure, and control systems. The drawings are dated 05 MAR 2025 and prepared at 100% Construction Document (CD) stage, indicating the project is in final design preparation prior to construction bidding.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26025R0066 0001.docx | DOCX document | |
| 531-24-107 HVAC Biomed Sign In Site Walk.pdf | ||
| 531-24-107 Install New HVAC Biomed RFI and Responses 05.15.2025.docx | DOCX document | |
| S02 EXHIBIT A Project Information Sheet for Contractors.pdf | ||
| 36C26025R0066.docx | DOCX document | |
| S02 EXHIBIT B Past Performance Reference Form.docx | DOCX document | |
| S02 Specifications - Boise Biomed HVAC CD Set.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
BUILDING 27
531-24-107
BOISE, ID 83702
Au to de sk
D oc s:
//2
- B oi se
V
AM
C B
IO
M
ED
/2
4- El ec C en tra l.r vt
3/ 5/
2:
:3
PM
CS001
COVER SHEET Boise VAMC BIOMED
05 MAR 2025 WNF PMS
100% CD
SHEET INDEX
SHEET NUMBER SHEET NAME
CS001 COVER SHEET
M001 MECHANICAL COVER SHEET
M002 ENERGY COMPLIANCE & MECHANICAL LOAD CALCS
M100 MECHANICAL DEMOLITION PLAN
M101 MECHANICAL NEW PLAN
M500 MECHANICAL DETAILS
M600 MECHANICAL SCHEDULES
M700 MECHANICAL CONTROLS
EE001 ELECTRICAL COVER SHEET
EE701 TYPICAL MOUNTING DETAILS
EE702 TYPICAL LABELING DETAILS
ED101 LEVEL 1 ELECTRICAL DEMOLITION PLAN
EP100 OVERALL POWER PLAN - FOR REFERENCE ONLY
EP101 LEVEL 1 POWER PLAN
EP601 ONE-LINE DIAGRAM & ELECTRICAL SCHEDULES
DIRECTOR
ASSOCIATE DIRECTOR / ADMINISTRATIVE OPERATIONS
CHIEF OF STAFF
ASSOCIATE DIRECTOR / PATIENT SERVICES
ASSOCIATE DIRECTOR / CLINICAL OPERATIONS
FINANCIAL MANAGEMENT SERVICE
Boise VAMC BIOMEDBoise VAMC BIOMED 531-24-107531-24-107
DEPARTMENT OF VETERANS AFFAIRS BOISE VAMC
500 W FORT ST
BOISE, ID 84702
100% CD
05 MAR 2025
SCALE: NTS
SITE PLAN1
NORTH
Revisions: Date:
03/05/2025
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BUILDING 27
531-24-107
BOISE, ID 83702
Au to de sk
D oc s:
//2
- B oi se
V
AM
C B
IO
M
ED
/2
4- M ec h
C en tra l.r vt 3/
5/
2:
:3
PM
M001
MECHANICAL COVER SHEET Boise VAMC BIOMED
05 MAR 2025 CLD DDL
100% CD
ABBREVIATIONS
NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
(E) EXISTING
(F) FUTURE
AC AIR CONDITION(-ING,-ED)
APD AIR PRESSURE DROP
BD BALANCING DAMPER
BHP BRAKE HORSE POWER
BTU BRITISH THERMAL UNIT
BTUH BTU/HOUR
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CV CONTROL VALVE
DB DRY BULB TEMPERATURE
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RECIRC
DP DEPTH, DEEP, OR DROP IN PRESSURE
EA EXHAUST AIR
EER ENERGY EFFICIENCY RATIO
EFF EFFICIENCY
ELEC ELECTRIC
ELEV ELEVATION
ENT ENTERING
EVAP EVAPORAT(-E, -ING, -ED, -OR)
EWT ENTERING WATER TEMPERATURE
EXT EXTERNAL
FD FIRE DAMPER
FLA FULL LOAD AMPS
FPI FINS PER INCH
FPM FEET PER MINUTE
FPS FEET PER SECOND
FSD FIRE SMOKE DAMPER
GE GREASE EXHAUST
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HD HEAD
HG MERCURY
HP HORSEPOWER
HR HOUR
HTG HEATING
HZ HERTZ (FREQUENCY)
IN INCH
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LH LATENT HEAT
LRA LOCKED ROTOR AMPS
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPS
MFR MANUFACTUR(-ER, -ED)
NC NORMALLY CLOSED OR NOISE CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DIAMETER
OZ OUNCE
PD PRESSURE DROP OR DIFFERENCE
PG PROPOLENE GLYCOL
PH PHASE
PPM PARTS PER MILLION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIA PSI ABSOLUTE
PSIG PSI GAUGE
RA RETURN AIR
RECIRC RECIRCULATE (-ER, -ED, -ING)
REFR REFRIGERATION
REQD REQUIRED
RLA RATED LOAD AMPS
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SCFM STANDARD CUBIC FEET PER MINUTE
SCW SOFT COLD WATER
SH SENSIBLE HEAT
SP STATIC PRESSURE
SPEC(S) SPECIFICATION(S)
SQ SQUARE
SS SANITARY SEWER, SOIL, WASTE
STD STANDARD
TA TRANSFER AIR
TD TEMP. DROP OR DIFF.
TEMP TEMPERATURE
TOT TOTAL
TSTAT THERMOSTAT
TYP TYPICAL
V VOLT, VOLTAGE OR VENT
VAC VACUUM
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VENT VENT, VENTILATION
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
VTR VENT THROUGH ROOF
WB WET BULB TEMP
WC WATER COLUMN
WG WATER GAUGE
WPD WATER PRESSURE DROP
WTR WATER
SHUT OFF VALVE
SYMBOL LEGEND - PIPING
DESCRIPTIONSYMBOL
NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
GATE VALVE
CHECK VALVE
AUTOMATIC 2-WAY VALVE
AUTOMATIC 3-WAY VALVE
GLOBE VALVE
BALL VALVE
RELIEF VALVE
PRESSURE REDUCING VALVE
BUTTERFLY VALVE
SOLENOID VALVE
ANGLE VALVE
S
VENTURI VALVE
BALANCING OR PLUG COCK
FLOW SETTER
EXPANSION VALVE
GAS COCK
MAV MANUAL AIR VENT
STRAINER
GAUGE COCK
FLEXIBLE CONNECTION
PRESSURE GAUGE
THERMOMETER
PIPE REDUCER
REFRIGERANT SITE GLASS
REFRIGERANT STRAINER
90 DEGREE ELBOW UP
90 DEGREE ELBOW DOWN
90 DEGREE TEE UP
90 DEGREE TEE DOWN
PIPE UNION
PIPE CAP
PIPE ANCHOR
FLOAT AND THERMOSTATIC TRAP
REFRIGERANT FILTER DRIER
SYMBOL LEGEND - DUCTWORK
DESCRIPTION
NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
RECTANGULAR SUPPLY DUCT UP
RECTANGULAR SUPPLY DUCT DOWN
RECTANGULAR RETURN DUCT UP
RECTANGULAR RETURN DUCT DOWN
RECTANGULAR EXHAUST DUCT UP
RECTANGULAR EXHAUST DUCT DOWN
ROUND SUPPLY DUCT UP
ROUND SUPPLY DUCT DOWN
ROUND RETURN DUCT UP
ROUND RETURN DUCT DOWN
ROUND EXHAUST DUCT UP
ROUND EXHAUST DUCT DOWN
OVAL SUPPLY DUCT UP
OVAL SUPPLY DUCT DOWN
OVAL RETURN DUCT UP
OVAL RETURN DUCT DOWN
OVAL EXHAUST DUCT UP
OVAL EXHAUST DUCT DOWN
SPIRAL OVAL DUCT
SPIRAL ROUND DUCT
DUCT INSULATION
DUCT LINING
90° RECTANGULAR ELBOW
WITH TURNING VANES
90° ROUND RADIUS ELBOW
GORED OVAL RADIUS ELBOW
DUCT SIZE OR SHAPE TRANSITION
SYMBOL
PIPING LEGEND
DESCRIPTIONABBREVIATION
NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
FIRE PROTECTION
HEATING HOT WATER SUPPLY
HEATING HOT WATER RETURN
NITROUS OXIDE
REFRIGERANT LIQUID
REFRIGERANT GAS
SNOW MELT RETURN
SNOW MELT SUPPLY
CHILLED WATER SUPPLY
CHILLED WATER RETURN
COMPRESSED AIR
CONDENSATE DRAIN
GLYCOL SUPPLY
GLYCOL RETURN
MEDICAL AIR
LIQUID PROPANE GAS
NATURAL GAS
OXYGEN
VACUUM
CHWR
CHWS
CA
CD
CWR
CWS
FP
GR
GS
HHWR
HHWS
LPG
MA
NG
NO
O
RL
RG
SMR
SMS
VAC
FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL VENT
FOR
FOS
FOV
MEDIUM PRESSURE CONDENSATE
HIGH PRESSURE CONDENSATEHPC
MPC
HIGH PRESSURE STEAM
LOW PRESSURE CONDENSATELPC
HPS
LOW PRESSURE STEAM
MEDIUM PRESSURE STEAMMPS
LPS
PUMPED CONDENSATEPC
SYMBOL LEGEND - MISC
DESCRIPTIONSYMBOL
VIEW OR DETAIL INDICATOR: # INDICATES DETAIL NUMBER,
SHEET INDICATES DRAWING SHEET WHERE VIEW OR DETAIL
IS SHOWN.
REFERENCE LINES AND SYMBOLS
ELEVATION OR SECTION INDICATOR: # INDICATES VIEW
NUMBER, SHEET INDICATES DRAWING SHEET WHERE VIEW IS
SHOWN.
NAME
### ROOM / SPACE INDICATOR
# KEYNOTE INDICATOR
# REVISION INDICATOR
XX-##
XX-##
TAG
CFM
PLUMBING FIXTURE INDICATOR
EQUIPMENT INDICATOR
REGISTER, GRILLE, OR DIFFUSER INDICATOR
BREAKLINE
MATCHLINE INDICATOR
CONTRACT LIMIT LINE: DASHDOT, WIDE LINE
NEW CONNECTION TO EXISTING
POINT OF DEMOLITION
OR
MATCH LINE
SEE XX/XXX
SQUARE OR RECTANGULAR
SUPPLY DIFFUSER
SYMBOL LEGEND - MECH
DESCRIPTIONSYMBOL
NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
DUCT HIGH EFFICIENCY TAKE OFF
WITH BALANCING DAMPER
SQUARE OR RECTANGULAR
RETURN DIFFUSER
SQUARE OR RECTANGULAR
EXHAUST DIFFUSER
ROUND DIFFUSER
SIDEWALL GRILLE OR REGISTER
BALANCING DAMPER
FIRE DAMPER
FIRE / SMOKE COMBINATION
DAMPER
LINEAR SLOT GRILLE OR DIFFUSER
FLEXIBLE DUCT
C02 CARBON DIOXIDE
T S H THERMOSTAT - SENSOR - HUMIDISTAT
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
THE MECHANICAL DRAWINGS SHOW THE GENERAL DESIGN, ARRANGEMENT,
& EXTENT OF THE MECHANICAL SYSTEM. BECAUSE OF THE SMALL SCALE OF
THE DRAWINGS, THESE DRAWINGS DO NOT SHOW ALL OFFSETS, BENDS, OR
ELBOWS NECESSARY FOR THE COMPLETE INSTALLATION IN THE SPACE
PROVIDED. CONTRACTOR SHALL MAKE ALTERATIONS AS MAY BE
NECESSARY TO MAKE THE SYSTEM COMPLETE & OPERATIONAL IN
ACCORDANCE WITH THE DESIGN INTENT.
MAJOR DEVIATIONS SUCH AS CHANGES IN SIZES, WEIGHTS, QUANTITIES, OR
MATERIAL REQUIRE PRIOR APPROVAL BY THE DESIGN ENGINEER.
THE DRAWINGS & SPECIFICATIONS HAVE BEEN PREPARED TO SUPPLEMENT
EACH OTHER & SHALL BE INTERPRETED AS AN INTEGRAL UNIT WITH THE
ITEMS SHOWN ON ONE & NOT THE OTHER BEING FURNISHED & INSTALLED
AS THOUGH SHOWN AND CALLED OUT IN BOTH DOCUMENTS.
THE ENTIRE MECHANICAL INSTALLATION SHALL CONFORM TO THE
REQUIREMENTS OF THE MOST RECENTLY ADOPTED BUILDING CODES,
MECHANICAL CODE, PLUMBING CODE, ELECTRICAL CODE, & ALL OTHER
APPLICABLE CITY, COUNTY, STATE, & FEDERAL CODES & REGULATIONS IN
EFFECT.
THE ENTIRE MECHANICAL INSTALLATION SHALL CONFORM TO ALL CODES,
RULES, REGULATIONS, & REQUIREMENTS OF THE BUILDING OWNER.
ALL MECHANICAL COMPONENTS AND EQUIPMENT SHALL BE INSTALLED TO
CONFORM WITH ANY APPLICABLE LOCAL SEISMIC REQUIREMENTS.
PRIOR TO FABRICATION & INSTALLATION OF ANY MECHANICAL COMPONENT
THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL
MECHANICAL WORK WITH ALL OTHER BUILDING TRADES, INCLUDING
BUILDING TRADES HIRED DIRECTLY BY THE OWNER. WHERE CONFLICTS
MAY OCCUR, THEY SHALL BE RESOLVED PRIOR TO INSTALLATION.
VERIFY ALL REQUIRED SERVICE CONNECTIONS, INCLUDING ELECTRICAL
CHARACTERISTICS, FOR ALL EQUIPMENT PRIOR TO ORDERING OR
FABRICATING MECHANICAL EQUIPMENT AND COMPONENTS.
THE SPACE ABOVE CEILINGS IS LIMITED. CAREFUL COORDINATION IS
REQUIRED WITH ALL TRADES BEFORE ANY PIPE, DUCT, OR EQUIPMENT IS
ORDERED &/OR INSTALLED. ANY CONFLICTS &/OR CHANGES FOUND DURING
INSTALLATION THAT RESULTS FROM THE LACK OF COORDINATION BY THE
CONTRACTORS DURING THE SHOP DRAWING PROCESS ARE THE
RESPONSIBILITY OF THE CONTRACTOR.
ALL MECHANICAL INFORMATION IS NOT SHOWN ON THE MECHANICAL
DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION
OF ALL INFORMATION ON ALL OTHER CONSTRUCTION DOCUMENTS.
THE CONTRACTOR SHALL BE RESPONSIBLE TO REVIEW & USE, WHERE
APPROPRIATE, ALL THE MECHANICAL DETAILS SHOWN ON THE DRAWINGS.
DETAILS MAY OR MAY NOT BE CALLED OUT ON THE DRAWINGS WITH
SYMBOLS OR KEYED NOTES. ANY CHANGES RESULTING FROM FAILURE TO
INSTALL THE MECHANICAL SYSTEM WITHOUT USING THE INCLUDED DETAILS
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
ALL EQUIPMENT SHALL BE INDEPENDENTLY SUPPORTED FROM
STRUCTURAL MEMBERS. STRUCTURAL ELEMENTS SHOWN IN DETAILS MAY
OR MAY NOT PERTAIN TO ANY PORTION OF THE BUILDING. COORDINATE ALL
MOUNTING REQUIREMENTS WITH ARCHITECTURAL & STRUCTURAL
DRAWINGS AND SPECIFICATIONS.
ALL MECHANICAL COMPONENTS AND EQUIPMENT SHALL BE INSTALLED IN
ACCORDANCE WITH ALL MANUFACTURER RECOMMENDATIONS.
ALL SIMILAR EQUIPMENT SHALL BE OF THE SAME MANUFACTURER. AIR
INLETS & OUTLETS OF SIMILAR TYPES SHALL BE OF THE SAME
MANUFACTURER.
ANY PART OF THE MECHANICAL INSTALLATION THAT FAILS, IS DEEMED
UNFIT, OR BECOMES DAMAGED DURING CONSTRUCTION SHALL BE
REPAIRED OR REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO
THE OWNER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR EQUIPMENT
CHECK-IN, SAFEKEEPING, & DAMAGE.
COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT
LOCATION OF ALL CEILING DIFFUSERS & GRILLES.
CONTRACTOR SHALL OPERATE INSTALLED &/OR MODIFIED SYSTEMS &
DEMONSTRATE ALL ASPECTS OF THE SYSTEM TO THE ENGINEER &/OR
OWNER TO PROVE ALL ASSOCIATED SYSTEMS ARE OPERATIONAL.
DURING CONSTRUCTION THE CONTRACTOR SHALL MAINTAIN A SET OF AS-
BUILT REDLINED RECORD DRAWINGS AT THE PROJECT SITE. ALL CHANGES
OR DEVIATIONS IN LAYOUT, ROUTING, EQUIPMENT, COMPONENTS, &
ACCESSORIES SHALL BE RECORDED. THESE REDLINED DRAWINGS SHALL
BE GIVEN TO THE ARCHITECT / ENGINEER AFTER THE FINAL INSPECTION IN
ACCORDANCE WITH PROJECT SPECIFICATIONS.
ALL DUCT ELBOWS SHALL BE LONG RADIUS, UNLESS NOTED OTHERWISE.
VA WILL SHUT DOWN EXISTING UTILITY SYSTEM AS NECESSARY FOR
CONTRACTOR TO PERFORM REQUIRED WORK. CONTRACTOR IS
RESPONSIBLE FOR DRAINING EXISTING WET SYSTEMS, SUCH AS WATER,
CHILLED WATER, HEATING WATER ETC. AS REQUIRED TO ACCOMPLISH NEW
WORK. CONTRACTOR IS ALSO RESPONSIBLE FOR RE-FILLING SYSTEMS
INCLUDING ADDING CHEMICAL AS REQUIRED. IT IS ACCEPTABLE TO
SALVAGE EXISTING TREATED WATER IN CLEAN STORAGE CONTAINERS
APPROVED BY THE VA, AND RE-INJECT IT INTO THE SYSTEM UPON
COMPLETION OF WORK. ANY TREATED WATER NOT RE-INJECTED IS TO BE
PROPERLY DISPOSED OF.
MECHANICAL GENERAL NOTES
DUCT TO BE DEMOLISHED
Revisions: Date:
MECHANICAL SHEET INDEX
M001 MECHANICAL COVER SHEET
M002 ENERGY COMPLIANCE & MECHANICAL LOAD CALCS
M100 MECHANICAL DEMOLITION PLAN
M101 MECHANICAL NEW PLAN
M500 MECHANICAL DETAILS
M600 MECHANICAL SCHEDULES
M700 MECHANICAL CONTROLS
DEFINITIONS
NOTE: ALL DEFINITIONS MAY NOT BE USED.
INDICATED: THE TERM "INDICATED" REFERS TO GRAPHIC REPRESENTATIONS,
NOTES, OR SCHEDULES ON THE DRAWINGS, OTHER PARAGRAPHS OR
SCHEDULES IN THE SPECIFICATIONS, AND SIMILAR REQUIREMENTS IN THE
CONTRACT DOCUMENTS. WHERE TERMS SUCH AS "SHOWN", "NOTED",
"SCHEDULED", AND "SPECIFIED" ARE USED, IT IS TO HELP THE READER LOCATE
THE REFERENCE, NO LIMITATION ON LOCATION IS INTENDED.
DIRECTED: TERMS SUCH AS "DIRECTED", "REQUESTED", AUTHORIZED",
"SELECTED", "APPROVED", "REQUIRED", AND "PERMITTED" MEAN "DIRECTED BY
THE ENGINEER", "REQUESTED BY THE ENGINEER", AND SIMILAR PHRASES.
APPROVED: THE TERM "APPROVED", WHERE USED IN CONJUNCTION WITH THE
ENGINEER'S ACTION ON THE CONTRACTOR'S SUBMITTALS, APPLICATIONS, AND
REQUESTS, IS LIMITED TO THE ENGINEER'S DUTIES AND RESPONSIBILITIES AS
STATED IN GENERAL AND SUPPLEMENTARY CONDITIONS.
FURNISH: THE TERM "FURNISH" IS USED TO MEAN "SUPPLY AND DELIVER TO
THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY,
INSTALLATION, AND SIMILAR OPERATIONS."
INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT
SITE INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION,
PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING,
PROTECTING, CLEANING, AND SIMILAR OPERATIONS."
PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE
AND READY FOR THE INTENDED USE."
INSTALLER: AN "INSTALLER" IS THE CONTRACTOR OR AN ENTITY ENGAGED BY
THE CONTRACTOR, EITHER AS AN EMPLOYEE, SUBCONTRACTOR, OR SUB-
SUBCONTRACTOR, FOR PERFORMANCE OF A PARTICULAR CONSTRUCTION
ACTIVITY, INCLUDING INSTALLATION, ERECTION, APPLICATION, AND SIMILAR
OPERATIONS. INSTALLERS ARE REQUIRED TO BE EXPERIENCED IN THE
OPERATIONS THEY ARE ENGAGED TO PERFORM.
2025.03.04
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BUILDING 27
531-24-107
BOISE, ID 83702
Au to de sk
D oc s:
//2
- B oi se
V
AM
C B
IO
M
ED
/2
4- M ec h
C en tra l.r vt 3/
5/
2:
:3
PM
M002
ENERGY COMPLIANCE &
MECHANICAL LOAD CALCS
Boise VAMC BIOMED
05 MAR 2025 CLD DDL
100% CD
G07
4 4 4
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BUILDING 27
531-24-107
BOISE, ID 83702
Au to de sk
D oc s:
//2
- B oi se
V
AM
C B
IO
M
ED
/2
4- M ec h
C en tra l.r vt 3/
5/
2:
:3
PM
M100
MECHANICAL DEMOLITION PLAN Boise VAMC BIOMED
05 MAR 2025 CLD DDL
100% CD
SCALE: 1/2" = 1'-0"1 MECHANICAL DEMOLITION PLAN
SHEET KEYNOTES
1 DEMOLISH AND DISPOSE OF EXISTING FAN COIL UNIT. DEMOLISH HYDRONIC
PIPING BACK TO MAIN AND CAP. DEMOLISH ALL EXISTING CONTROL WIRING AND
ASSOCIATED ACCESSORIES.
2 DEMOLISH AND DISPOSE EXISTING FAN.
3 DEMOLISH AND DISPOSE EXISTING PTAC UNIT. PROVIDE NEW WINDOW MATCHING
EXISTING.
4 DEMOLISH EXISTING RADIANT PANEL AND ASSOCIATED HYDRONIC PIPING BACK
TO MAIN AND CAP. RETURN RADIANT PANEL AND ASSOCIATED VALVES(S),
CONTROLS/CONTROL WIRING, AND ACCESSORIES BACK TO OWNER.
NORTH
Revisions: Date:
MECHANICAL GENERAL NOTES
1. ALL EQUIPMENT TO BE SELECTED BASED OFF OF SITE INFORMATION, INCLUDING
CURBS EQUAL TO OR GREATER THAN DESIGN SNOW DEPTH. ELEVATION: SDB:
SWB: WDB:
2. THIS CONTRACTOR SHALL CLOSELY COORDINATE MECHANICAL AND PLUMBING
WITH ELECTRICAL, ARCHITECTURAL, AND BUILDING STRUCTURE.
3. ALL LOW PRESSURE RECTANGULAR DUCTWORK TO BE LINED WITH INSULATION
WITH AN R-VALUE OF R-6. ALL LOW PRESSURE ROUND DUCTWORK TO BE WRAPPED
WITH INSULATION WITH AN R-VALUE OF R-6. NO DUCT LINER IN OUTSIDE AIR
DUCTWORK OR DUCTWORK WITH IN DUCT HUMIDIFIERS.
4. ALL DUCT DIMENSIONS ARE INSIDE CLEAR DIMENSIONS.
5. GRILLES AND DUCTWORK ARE SIZED INDEPENDENTLY. THE NECK SIZE OF GRILLES
MAY NOT MATCH THE ASSOCIATED DUCT SIZE. PROVIDE TRANSITION TO GRILLES
AS NECESSARY.
6. PROVIDE BALANCING DAMPER WITH LOCKING QUADRANT IN EACH DUCT BRANCH
OF SUPPLY AND EXHAUST DUCTWORK.
7. COORDINATE EXACT THERMOSTAT LOCATIONS WITH FURNITURE AND OWNER.
FAILURE TO DO SO MAY REQUIRE MOVING THERMOSTATS AT CONTRACTORS COST.
8. ALL CONTROLS WIRING SHALL BE INSTALLED IN RACEWAYS AND BE THE
RESPONSIBILITY OF THE CONTROLS CONTRACTOR. RACEWAYS SHALL CONFORM
TO THE FOLLOWING ELECTRICAL SPECIFICATIONS; HANGERS AND SUPPORTS FOR
ELECTRICAL SYSTEMS, RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS AND
SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS.
9. CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO
ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR
CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE CONDITIONS.
10. PROVIDE FACTORY AUTHORIZED STARTUP OF ALL EQUIPMENT INCLUDING
STARTUP OF ANY FACTORY CONTROLS TO ENSURE PROPER SEQUENCING AND/OR
COMMUNICATION TO BMS.
11. PROVIDE OPERATION AND MAINTENANCE MANUALS (O&M) WITHIN 30 DAYS OF
CERTIFICATE OF OCCUPANCY FOR ALL EQUIPMENT IN DIGITAL FORMAT TO
ENGINEER FOR REVIEW. O&M'S SHALL INCLUDE DOCUMENTATION OF ALL
WARRANTIES, REPORTS AND TESTS, RECORD DRAWINGS, CONTROLS SEQUENCE
OF OPERATIONS WITH DIAGRAMS, & EQUIPMENT INFORMATION. EQUIPMENT
INFORMATION INCLUDES MAKE & MODEL, WIRING, PIPING, STARTUP, SHUTDOWN,
TROUBLE SHOOTING SYSTEM BALANCING REPORT, FINAL COMMISSIONING REPORT
AND MAINTENANCE PROCEDURES.
S
ERU-2
VRF-3
12"x6" OA
12"x6" RA
12"x6" SA 12"x6" EA
G07
L-1
L-1
D-1
CAS-17
CAS-16
CAS-18
3/4"ø CD DN
3/4"ø CD DN
1 1/2"ø V DN
1 1/2"ø V
HD
3/4"ø CD 3/4"ø CD
3/4"ø CD
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BUILDING 27
531-24-107
BOISE, ID 83702
Au to de sk
D oc s:
//2
- B oi se
V
AM
C B
IO
M
ED
/2
4- M ec h
C en tra l.r vt 3/
5/
2:
:3
PM
M101
MECHANICAL NEW PLAN Boise VAMC BIOMED
05 MAR 2025 CLD DDL
100% CD
SCALE: 1/2" = 1'-0"1 MECHANICAL NEW PLAN
NORTH
SHEET KEYNOTES
1 ALL CHILLER OR CONDENSING UNIT COILS ARE TO BE COMPLETELY PROTECTED
USING AIR INTAKE FILTRATION SCREENS SPECIFICALLY DESIGNED FOR
COTTONWOOD FILTRATION. THE SCREENS SHALL BE EASILY REMOVABLE WITH
QUARTER TURN CONNECTIONS. THE SCREEN SHALL NOT VOID THE WARRANTY
OF THE ORIGINAL EQUIPMENT MANUFACTURER. THE SCREENS SHALL HAVE A
STATIC PRESSURE DROP LESS THAN 0.1 INCHES OF WATER GAGE, BE UV
RESISTANT, FLAME RESISTANT, NON-ELECTRO STATIC, AND MOLD AND MILDEW
RESISTANT. THE FILTERS SHALL BE IN ACCORDANCE WITH THE NATIONAL AIR
FILTRATION ASSOCIATION FOR COTTONWOOD FILTERS.
2 PROVIDE 8" X 18" OPENING ON TOP OF RETURN DUCT. COVER OPENING WITH
EXPANDED METAL MESH. WITH MINIMUM 45% FREE AREA.
3 EXISTING SANITARY SEWER LINE TO REMAIN AS IS.
4 CENTRAL CONTROL PANEL.
Revisions: Date:
MECHANICAL GENERAL NOTES
1. ALL EQUIPMENT TO BE SELECTED BASED OFF OF SITE INFORMATION, INCLUDING
CURBS EQUAL TO OR GREATER THAN DESIGN SNOW DEPTH. ELEVATION: SDB:
SWB: WDB:
2. THIS CONTRACTOR SHALL CLOSELY COORDINATE MECHANICAL AND PLUMBING
WITH ELECTRICAL, ARCHITECTURAL, AND BUILDING STRUCTURE.
3. ALL LOW PRESSURE RECTANGULAR DUCTWORK TO BE LINED WITH INSULATION
WITH AN R-VALUE OF R-6. ALL LOW PRESSURE ROUND DUCTWORK TO BE WRAPPED
WITH INSULATION WITH AN R-VALUE OF R-6. NO DUCT LINER IN OUTSIDE AIR
DUCTWORK OR DUCTWORK WITH IN DUCT HUMIDIFIERS.
4. ALL DUCT DIMENSIONS ARE INSIDE CLEAR DIMENSIONS.
5. GRILLES AND DUCTWORK ARE SIZED INDEPENDENTLY. THE NECK SIZE OF GRILLES
MAY NOT MATCH THE ASSOCIATED DUCT SIZE. PROVIDE TRANSITION TO GRILLES
AS NECESSARY.
6. PROVIDE BALANCING DAMPER WITH LOCKING QUADRANT IN EACH DUCT BRANCH
OF SUPPLY AND EXHAUST DUCTWORK.
7. COORDINATE EXACT THERMOSTAT LOCATIONS WITH FURNITURE AND OWNER.
FAILURE TO DO SO MAY REQUIRE MOVING THERMOSTATS AT CONTRACTORS COST.
8. ALL CONTROLS WIRING SHALL BE INSTALLED IN RACEWAYS AND BE THE
RESPONSIBILITY OF THE CONTROLS CONTRACTOR. RACEWAYS SHALL CONFORM
TO THE FOLLOWING ELECTRICAL SPECIFICATIONS; HANGERS AND SUPPORTS FOR
ELECTRICAL SYSTEMS, RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS AND
SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS.
9. CONTRACTOR SHALL FIELD VERIFY EXISTING FIELD CONDITIONS PRIOR TO
ORDERING OR FABRICATING. ADDITIONAL COST WILL NOT BE ALLOWED FOR
CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH EXISTING SITE CONDITIONS.
10. PROVIDE FACTORY AUTHORIZED STARTUP OF ALL EQUIPMENT INCLUDING
STARTUP OF ANY FACTORY CONTROLS TO ENSURE PROPER SEQUENCING AND/OR
COMMUNICATION TO BMS.
11. PROVIDE OPERATION AND MAINTENANCE MANUALS (O&M) WITHIN 30 DAYS OF
CERTIFICATE OF OCCUPANCY FOR ALL EQUIPMENT IN DIGITAL FORMAT TO
ENGINEER FOR REVIEW. O&M'S SHALL INCLUDE DOCUMENTATION OF ALL
WARRANTIES, REPORTS AND TESTS, RECORD DRAWINGS, CONTROLS SEQUENCE
OF OPERATIONS WITH DIAGRAMS, & EQUIPMENT INFORMATION. EQUIPMENT
INFORMATION INCLUDES MAKE & MODEL, WIRING, PIPING, STARTUP, SHUTDOWN,
TROUBLE SHOOTING SYSTEM BALANCING REPORT, FINAL COMMISSIONING REPORT
AND MAINTENANCE PROCEDURES.
12) THE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND
INSTALLING ALL LOW VOLTAGE CONTROL CONDUITS AND WIRING. THE
CONTROLS CONTRACTOR IS ALSO RESPONSIBLE FOR COORDINATING ALL 120
VOLT POWER REQUIREMENTS FOR ALL CONTROLS WITH THE ELECTRICAL
CONTRACTOR WHO WILL INSTALL THE 120 VOLT POWER AND CONDUITS FOR
THE MECHANICAL CONTROLS.
THE CONTROLS CONTRACTOR IS RESONSIBLE FOR DETERMINING THE EXACT
POINT OF CONNECTION OF ALL CONTROL WIRING INTO THE EXISTING ENERGY
MANAGEMENT SYSTEM. IF AN ADDITIONAL GATEWAY IS REQUIRED, THE
CONTROLS CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND INSTALLING.
THE CONTROLS CONTRACTOR SHALL COORDINATE WITH OWNER FOR ALL WORK
TO MERGE INTO VA CAMPUS BUILDING MANAGEMENT SYSTEM.
13) SINCE WORK WILL TAKE PLACE IN A HOSPITAL, THERE IS THE POSSIBILITY OF
THE CONTRACTOR COMING IN CONTACT WITH BLOOD AND BODY FLUIDS
WHENEVER WORKING ON THE SANITARY SEWER SYSTEM. CONTRACTOR IS
REQUIRED TO PROVIDE AND USE APPROPRIATE PERSONAL PROTECTIVE
EQUIPMENT WHENEVER WORKING ON THE SANITARY SEWER SYSTEM TO
PREVENT EXPOSURE TO THEIR EMPLOYEES.
2" WIDE X10 GAUGE GI STRAP
THREADED BOTTOM 9" ABOVE
SINGLE TOP NUT WITH DOUBLE
NUT BELOW
3/8"∅ STEEL ROD ANCHORED TO
STRUCTURE WITH BEAM CLAMPS
OR EXPANSION BOLTS
R
1/6 W
1/3 W
1/2 W
VANE
RADIUS "R"
SHALL BE EQUAL
TO OR GREATER
THAN 1/6 W
VANE
RADIUS "R"
SHALL BE EQUAL
TO OR GREATER
THAN 1/3 W
R RADIUS "R"
SHALL BE EQUAL
TO OR GREATER
THAN W
LONG RADIUS ELBOWSHORT RADIUS ELBOW WITH ONE VANE SHORT RADIUS ELBOW WITH TWO VANES
1.
2.
NOTES:
ALL ELBOWS ARE LONG RADIUS UNLESS OTHERWISE NOTED ON PLANS. THE INTERIOR SURFACE OF
ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL LONG RADIUS ELBOWS SHOWN ON PLANS MAY BE MADE SHORT RADIUS ELBOWS. ALL SHORT
RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED
AS DIRECTED BY SMACNA HVAC DUCT CONSTRUCTION STANDARDS.
R
W
W W
2/3 W
1/3 W
DISTRIBUTOR
FILTER DRYER
COMBINATION SIGHT GLASS AND
MOISTURE INDICATOR
LIQUID LINE SOLENOID VALVE
THERMAL BULB
EXPANSION VALVE
HP-1
PUMPED CONDENSATE
ROUTE PUMPED CONDENSATE TO
FUNNEL DRAIN ENSURE 1" AIR GAP
CAS-17 AIR HANDLER
DISTRIBUTOR
FILTER DRYER
COMBINATION SIGHT GLASS AND
MOISTURE INDICATOR
LIQUID LINE SOLENOID VALVE
THERMAL BULB
EXPANSION VALVE
CAS-18 AIR HANDLER
DISTRIBUTOR
FILTER DRYER
COMBINATION SIGHT GLASS AND
MOISTURE INDICATOR
LIQUID LINE SOLENOID VALVE
THERMAL BULB
EXPANSION VALVE
CAS-16 AIR HANDLER
ROUTE PUMPED CONDENSATE TO
FUNNEL DRAIN ENSURE 1" AIR GAP
PUMPED CONDENSATE
FLEXIBLE CONNECTION
SHUT OFF VALVE WITH GAUGE PORT (TYP)
LIQUID LINE
SUCTION LINE
LIQUID LINE
SUCTION LINE
LIQUID LINE
SUCTION LINE
TURNING VANES
NOTES:
1. ALL TURNING VANES SHALL BE SINGLE VANE TYPE REGARDLESS OF DIMENSION.
2. ALL SINGLE VANES SHALL HAVE A 2 INCH RADIUS, 1 INCH MAXIMUM SPACE
BETWEEN VANES AND A 3/4 INCH TRAILING EDGE.
W
W1
1.
2.
3.
NOTES:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES
SHOWN SHALL APPLY
INSTALL PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS
WHEN TRANSITIONING DUCT HEIGHT AS WELL AS WIDTH, THE
LONGER LENGTH SHALL APPLY.
ECCENTRIC TRANSITION:
MAX 30° ANGLE
WHEN TRANSITIONING FROM ROUND TO FLAT OVAL,
A MAX ANGLE OF 45° IS PERMITTED
L (MIN) = (W2 - W1)/ 0.58 FOR 30°
L (MIN) = (H2 - H1)/ 0.58 FOR 30°
L (MIN) = W2 - W1 FOR 45°
L (MIN) = H2 - H1 FOR 45°
FOR ROUND DUCTWORK W=Ø
L SHALL BE GREATER OF W AND H CALCULATIONS
CONVERGING CONCENTRIC TRANSITION:
X° = 60° MAX
L (MIN) = (W2 - W1)/ 1.15
L (MIN) = (H2 - H1)/ 1.15
FOR ROUND DUCTWORK W=Ø
L SHALL BE GREATER OF W AND H CALCULATIONS
DIVERGING CONCENTRIC TRANSITION:
X° = 45° MAX
L (MIN) = (W2 - W1) / 2
L (MIN) = (H2 - H1) / 2
FOR ROUND DUCTWORK W=Ø
L SHALL BE GREATER OF W AND H CALCULATIONS
L
L
W
2AIR
FLOW
W
2AIR
FLOW W
30° X°
L
W
2 AIR
FLOWW
X°
SECURE DIFFUSER TO
DUCT WITH MINIMUM OF
8 SHEET METAL SCREWS
(2 PER SIDE)
ROUND BRANCH DUCT.
SEE PLAN FOR DUCT
SIZE
SUPPLY AIR DUCT
AS REQUIRED
NOTE:
1. CEILING DIFFUSERS IN SALES AREA
SHALL BE INSTALLED AT SAME
HEIGHT AS AREA LIGHT FIXTURES
OPPOSED BLADE
DAMPER
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BUILDING 27
531-24-107
BOISE, ID 83702
Au to de sk
D oc s:
//2
- B oi se
V
AM
C B
IO
M
ED
/2
4- M ec h
C en tra l.r vt 3/
5/
2:
:3
PM
M500
MECHANICAL DETAILS Boise VAMC BIOMED
05 MAR 2025 CLD DDL
100% CD
SCALE: NTS1 DUCT HANGER DETAIL - ROUND
SCALE: NTS2 DUCT ELBOW - ROUND DETAIL
SCALE: NTS5 MULTIPORT SPLIT SYSTEM SCHEMATIC
Revisions: Date:
SCALE: NTS6 DUCT ELBOW - SQUARE DETAIL
SCALE: NTS4 DUCT TRANSITIONS DETAIL
SCALE: NTS3 CEILING DIFFUSER (ROUND)
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BUILDING 27
531-24-107
BOISE, ID 83702
Au to de sk
D oc s:
//2
- B oi se
V
AM
C B
IO
M
ED
/2
4- M ec h
C en tra l.r vt 3/
5/
2:
:3
PM
M600
MECHANICAL SCHEDULES Boise VAMC BIOMED
05 MAR 2025 CLD DDL
100% CD
MITSUBISHI
CARRIER
(1) PROVIDE WITH MERV 8 FILTERS.
(2) PROVIDE WITH INTEGRAL CONDENSATE PUMP. ROUTE COPPER CONDENSATE PIPING TO FUNNEL DRAIN IN PLUMBING CHASE. PROVIDE FUNNEL DRAIN AS PART OF THIS PROJECT.
(3) PROVIDE SUCTION LINE FILTER WITH BYPASS ON LARGEST CAPACITY FAN COIL. AFTER
A WEEK OF USE CHECK FILTER. IF DIRTY REPLACE AND REPEAT. IF CLEAN REMOVE FILTER AND LEAVE IN BYPASS MODE.
(4) PROVIDE FACTORY AUTHORIZED STARTUP OF EQUIPMENT INCLUDING STARTUP OF ANY FACTORY CONTROLS TO ENSURE PROPER SEQUENCING AND/OR COMMUNICATION TO BMS.
(5) PROVIDE WITH SHOP PIPING AND WIRING DRAWINGS. ANY DEVIATIONS FROM SHOP DRAWING MUST BE DOCUMENTED AND PROVIDED TO ENGINEER.
(6) PROVIDE 10 YEAR WARRANTY. MUST INCLUDE COPY OF FINALIZED WARRANTY TO ENGINEER AT PROJECT CLOSEOUT.
(7) COORDINATE REFRIGERANT CHARGE AND PIPING SIZES WITH EQUIVALENT LINE LENGTH TO MINIMIZE PRESSURE DROP AND CAPACITY LOSS.
(8) PRESSURE TEST ALL REFRIGERANT PIPING. PROVIDE REPORT OF PRESSURE TESTING TO ENGINEER. PRESSURE TEST MUST BE WITNESSED BY MANUFACTURER'S REP.
PLUMB = DIVISION 22
MECH = DIVISION 23
ELEC = DIVISION 26
MNFR = MANUFACTURER
ACCEPTABLE MANUFACTURERS: REMARKS: SCHEDULE KEY:
MULTI-PORT HEAT PUMP - INDOOR UNIT SCHEDULE
LABEL TYPE
AIRFLOW
(CFM)
COOLING CAPACITY HEATING CAPACITY ELECTRICAL DISCONNECT
PROVIDED BY
(MECH/ ELEC)
SOUND
RATING
WEIGHT
(LBS) MANUFACTURER MODEL REMARKS
NOMINAL
(BTUH)
DESIGN
(BTUH)
NOMINAL
(BTUH)
DESIGN
(BTUH) VOLTS PHASE Hz MCA MOCP
EMERG
POWER
CAS-16 4-WAY CASSETTE 550 18,000 12,800 20,000 16,500 208 1 60 3 15 NO ELEC 35 36 CARRIER 45MBCAQ18XA3 ALL CAS-17 4-WAY CASSETTE 550 18,000 12,800 20,000 16,500 208 1 60 3 15 NO ELEC 35 36 CARRIER 45MBCAQ18XA3 ALL CAS-18 1-WAY CASSETTE 470 7,500 5,800 8,500 6,500 208 1 60 3 15 NO ELEC 32.5 63 CARRIER 45MCCAQ06XA3 ALL
MITSUBISHI
CARRIER
(1) PROVIDE WITH SHOP PIPING AND WIRING DRAWINGS. ANY DEVIATIONS FROM SHOP DRAWING MUST BE DOCUMENTED AND PROVIDED TO
ENGINEER.
(2) PROVIDE 10 YEAR WARRANTY. MUST INCLUDE COPY OF FINALIZED WARRANTY TO ENGINEER AT PROJECT CLOSEOUT.
(3) COORDINATE REFRIGERANT CHARGE AND PIPING SIZES WITH EQUIVALENT LINE LENGTH TO MINIMIZE PRESSURE DROP AND CAPACITY LOSS.
(4) PRESSURE TEST ALL REFRIGERANT PIPING. PROVIDE REPORT OF PRESSURE TESTING TO ENGINEER. PRESSURE TEST MUST BE WITNESSED BY
MANUFACTURER'S REP.
(5) PROVIDE WITH NEOPRENE PADS AT ALL CONNECTION POINTS.
(6) PROVIDE WITH MIRO INDUSTRIES STANCHIONED HD SUPPORT.
(7) PROVIDE BASE PAN HEATERS.
(8) PROVIDE FACTORY AUTHORIZED STARTUP OF EQUIPMENT INCLUDING STARTUP OF ANY FACTORY CONTROLS TO ENSURE PROPER SEQUENCING
AND/OR COMMUNICATION TO BMS. ENSURE DEFROST CYCLE IS ENABLED.
(9) PROVIDE WITH DIAMOND CONTROLS.
(10) ENABLE HIGH HEATING PERFORMANCE.
(11) VERIFY ALL REFRIG. PIPING SIZES AND LENGTHS W/ SITE CONDITIONS IN MANUFACTURERS SELECTIONS SOFTWARE. LENGTH SHOWN ON PLANS DO NOT
ABSOLVE CONTRACTOR FROM DOING TAKE OFFS AND COORDINATING W/ OTHER DISCIPLINES.
(12) PROVIDE WITH CENTRAL CONTROL PANEL AND REMOTE WIRELESS SENSORS. REMOTE SENSORS SHALL BE PERMANENTLY MOUNTED IN THE SPACES AS INDICATED ON THE PLANS. INSTALL CENTRAL CONTROL PANEL IN MECHANICAL ROOM, COORDINATE EXACT LOCATION WITH FMS ENGINEER.
(13) CONDENSING UNIT COILS ARE TO BE COMPLETELY PROTECTED USING AIR INTAKE FILTRATION SCREENS SPECIFICALLY DESIGNED FOR COTTONWOOD FILTRATION. THE SCREENS SHALL BE EASILY REMOVABLE WITH QUARTER TURN CONNECTIONS. THE SCREENS SHALL NOT VOID THE WARRANTY OF THE ORIGINAL EQUIPMENT MANUFACTURER. THE SCREENS SHALL HAVE A STATIC PRESSURE DROP LESS THAN 0.1 INCHES OF WATER GAGE, BE UV RESISTANT, FLAME RESISTANT, NON-ELECTRO STATIC, AND MOLD AND MILDEW RESISTANT. THE FILTER SHALL BE IN ACCORDANCE WITH THE NATIONAL AIR FILTRATION
ASSOCIATION FOR COTTONWOOD FILTERS.
PLUMB = DIVISION 22
MECH = DIVISION 23
ELEC = DIVISION 26
MNFR = MANUFACTURER
ACCEPTABLE MANUFACTURERS: REMARKS: SCHEDULE KEY
HEAT PUMP - OUTDOOR UNIT SCHEDULE
LABEL SERVES RATIO
COOLING CAPACITY HEATING CAPACITY
REFRIGERANT
TYPE
NO. OF
CONNECTIONS
ELECTRICAL DISCONNECT
PROVIDED BY
(MECH/ ELEC)
SOUND
RATING
WEIGHT
(LBS) MANUFACTURER MODEL REMARKS
NOMINAL
(BTUH)
CONNECTED
(BTUH) SEER2
NOMINAL
(BTUH)
CONNECTED
(BTUH) HSPF2 VOLTS PHASE Hz MCA MOCP
EMERG
POWER
VRF-3 BIOMED 115% 36,000 42,000 23.1 36,000 42,000 10.7 R-454B 1 208 1 60 37 40 NO ELEC 65 212 CARRIER 37MGHAQ36EA3 ALL
KRUEGER
TUTTLE & BAILEY
TITUS
PRICE
(1) PROVIDE TRANSITION AS NECESSARY.
(2) COORDINATE EXACT COLOR SELECTION WITH OWNER AND ARCHITECT.
ACCEPTABLE MANUFACTURERS: REMARKS:
REGISTER - GRILLE- DIFFUSER SCHEDULE
LABEL TYPE
MAX AIRFLOW
(CFM)
FACE
SIZE
NECK
SIZE BLOW PATTERN
PD
(IN-WC)
THROW(S)
(FT)
MAX
NC MANUFACTURER MODEL REMARKS
D-1 ROUND 3-CONE DIFFUSER 425 18" 10" ROUND 360 DEGREES 0.060 4-6-10 25 PRICE INDUSTRIES RCD ALL
RENEWAIRE
VENMAR
COOK
TRANE
ALDES
(1) PROVIDE WITH SINGLE POINT ELECTRICAL CONNECTION.
(2) PROVIDE WITH MERV 8 FILTERS, AND ECM MOTORS.
(3) PROVIDE WITH 7-DAY PROGRAMMABLE THERMOSTAT WITH REMOTE WALL MOUNTED SENSOR AND OVERRIDE SWITCH.
(4) PROVIDE WITH MANUFACTURER'S GRAVITY BACKDRAFT DAMPERS, VIBRATION ISOLATION HANGERS, AND FLEX INLET / OUTLET CONNECTIONS.
ACCEPTABLE MANUFACTURERS: REMARKS:
ENERGY RECOVERY UNIT SCHEDULE
LABEL
SUPPLY FAN EXHAUST FAN
WEIGHT
SOUND RATING
(SONES) HP VOLTAGE PHASE Hz MOCP
EMERGENCY
POWER
DISCONNECT
MANUFACTURER MODEL REMARKSCFM EXT. S.P. CFM EXT. S.P.
FURN BY
ELEC
FURN BY
MECH
ERU-2 300 0.38 300 0.38 325 3 0.5 (X2) 120 1 60 15 A NO YES NO RenewAire LLC HE1XINV ALL
CEILING
CASSETTE
UNIT
TS
AI
PROGRAMMABLE THERMOSTAT
OUTDOOR
HEAT PUMP
1. GENERAL:
THE SPACE TEMPERATURE SENSOR SHALL SIGNAL DDC CONTROLLER THE SPACE
TEMPERATURE. THE DDC SYSTEM SHALL ONLY MONITOR SPACE TEMPERATURE. A STAND
ALONE PROGRAMMABLE THERMOSTAT SHALL DETERMINE SET POINTS AND MONITOR
SPACE TEMPERATURE FOR OPERATION OF THE SYSTEM.
2. OCCUPIED MODE:
DURING THE OCCUPIED MODE THE FAN SHALL BE SET TO AUTOMATIC.
AS THE ROOM TEMPERATURE INCREASES TO THE COOLING SETPOINT THE
PROGRAMMABLE THERMOSTAT SHALL SIGNAL ON MECHANICAL COOLING.
AS THE ROOM TEMPERATURE DECREASES TO THE HEATING SETPOINT, THE
PROGRAMMABLE THERMOSTAT SHALL SIGNAL ON HEATING.
IF THE DDC ROOM TEMPERATURE SENSORS DETECTS TEMPERATURES IN EXCESS OF 80°F
(ADJUSTABLE) OR BELOW 60°F (ADJUSTABLE), THE CONTROL SYSTEM SHALL GENERATE
AN ALARM AT THE OPERATOR WORKSTATION.
3. UNOCCUPIED MODE:
DURING THE UNOCCUPIED MODE THE FAN SHALL BE STOPPED.
IF THE ROOM TEMPERATURE INCREASES TO THE SETBACK COOLING SETPOINT OF 85°F
(ADJUSTABLE), THE PROGRAMMABLE THERMOSTAT SHALL SIGNAL ON MECHANICAL
COOLING.
IF THE ROOM TEMPERATURE DECREASES TO THE SETBACK HEATING SETPOINT OF 50°F
(ADJUSTABLE), THE PROGRAMMABLE THERMOSTAT SHALL SIGNAL ON HEATING.
4. SAFETIES:
THE CONDENSATE OVERFLOW SWITCH SHALL SHUT DOWN THE UNIT WHEN CONDENSATE
BUILDS UP IN THE DRAIN PAN. THE DDC SYSTEM SHALL MONITOR THE SWITCH.
DI
TE
M
PE
R
AT
U
R E
C O
N D
EN
SA
TE
O
VE
R
FL
O
W S
EN
SO
R
HEAT
EXCHANGER
ERU
CONTROLLER
OUTSIDE AIR
EXHAUST AIR
EXHAUST AIR
SUPPLY AIR
T
AI
DP
AI
PR
ES
SU
R
E
TE
M
PE
R
AT
U
R E
AI
TE
M
PE
R
AT
U
R E
T
AI
PR
ES
SU
R
E
DP
T
AI AI
T
TE
M
PE
R
AT
U
R E
TE
M
PE
R
AT
U
R E
MOTOR
MOTOR
DI
CURRENT
SENSING
RELAY
START/STOP
CONTROL
RELAY
CURRENT
SENSING
RELAY
START/STOP
CONTROL
RELAY
DI
ST
AT
U S
ST
AT
U S
AL
AR
M S
DI
EN
AB
LE
DO
EC
O
N O
M
IZ
ER
M
O D
E
DI
1. GENERAL:
THE DDC CONTROLLER SHALL ENABLE THE ENERGY RECOVERY UNIT, CONTROL AND MONITOR THE INTAKE AND DISCHARGE DAMPERS, MONITOR FAN STATUS, FILTER DIFFERENTIAL PRESSURE, AND MONITOR THE SUPPLY AIR TEMPERATURE. THE FOLLOWING INTERNAL CONTROLS SHALL BE MONITORED REMOTELY: ALARMS AND ECONOMIZER MODE. ALL ALARMS SHALL BE
SENT TO THE OPERATOR WORKSTATION.
INTERNAL CONTROLS SHALL PROVIDE THE FROST ELIMINATION CONTROL ACROSS THE HEAT EXCHANGER.
INTERNAL CONTROLS SHALL PROVIDE ECONOMIZER CONTROL WHENEVER THE RESPECTIVE ENERGY RECOVERY UNIT GOES
INTO THE ECONOMIZER STAGE.
2. OCCUPIED MODE:
THE SUPPLY AND EXHAUST FANS SHALL START, AND THE ECONOMIZER DAMPER SHALL CYCLE PER THE INTERNAL CONTROL
REQUIREMENTS. SEE ABOVE FOR FROST AND ECONOMIZER CONTROL.
3. UNOCCUPIED MODE:
IN THE UNOCCUPIED MODE THE SUPPLY AND EXHAUST FANS SHALL STOP.
4. ALARM MODE
IF FAN MOTOR CURRENT RELAY FAILS TO SENSE CURRENT AFTER DELIVERY OF ENABLE SIGNAL, ALARM SHALL BE SENT
OPERATOR WORKSTATION.
IF FILTER DIFFERENTIAL PRESSURE EXCEEDS 0.25 IN W.C., A "DIRTY FILTER" ALARM SHALL BE SENT TO THE OPERATOR
WORKSTATION.
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BUILDING 27
531-24-107
BOISE, ID 83702
Au to de sk
D oc s:
//2
- B oi se
V
AM
C B
IO
M
ED
/2
4- M ec h
C en tra l.r vt 3/
5/
2:
:3
PM
M700
MECHANICAL CONTROLS Boise VAMC BIOMED
05 MAR 2025 CLD DDL
100% CD
Revisions: Date:
SCALE: NTS1 DUCTLESS SPLIT SYSTEM FAN COIL CONTROL SHEMATIC
SCALE: NTS2 ENERGY RECOVERY UNIT (GRAVITY BACKDRAFT DAMPER) CONTROL SCHEMATIC
800-678-7077 801-328-5151 fax: 801-328-5155 www.spectrum-engineers.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
SHEET TO BE VIEWED AND PRINTED IN COLOR
BUILDING 27
531-24-107
BOISE, ID 83702
Au to de sk
D oc s:
//2
- B oi se
V
AM
C B
IO
M
ED
/2
4- El ec C en tra l.r vt
3/ 5/
2:
:3
PM
EE001
ELECTRICAL COVER SHEET Boise VAMC BIOMED
05 MAR 2025 WNF PMS
100% CD
GENERAL ELECTRICAL NOTES
1. CLARIFICATION METHODS: AT THE TIME OF BIDDING, BIDDERS SHALL FAMILIARIZE
THEMSELVES WITH THE DRAWINGS AND SPECIFICATIONS. ANY QUESTIONS,
MISUNDERSTANDINGS, CONFLICTS, DELETIONS, DISCONTINUED PRODUCTS,
CATALOG NUMBER DISCREPANCIES, DISCREPANCIES BETWEEN THE EQUIPMENT
SUPPLIED AND THE INTENT OR FUNCTION OF THE EQUIPMENT, ETC, SHALL BE
SUBMITTED TO THE ARCHITECT/ENGINEER IN WRITING FOR CLARIFICATION PRIOR
TO ISSUANCE OF THE FINAL ADDENDUM AND BIDDING OF THE PROJECT. WHERE
DISCREPANCIES OR MULTIPLE INTERPRETATIONS OCCUR, THE MOST STRINGENT
(WHICH IS GENERALLY RECOGNIZED AS THE MOST COSTLY) THAT MEETS THE
INTENT OF THE DOCUMENTS SHALL BE ENFORCED.
2. OWNER FURNISHED ITEMS: THE OWNER WILL FURNISH MATERIAL AND
EQUIPMENT AS INDICATED IN THE CONTRACT DOCUMENTS TO BE INCORPORATED
INTO THE WORK. THESE ITEMS ARE ASSIGNED TO THE INSTALLER AND COSTS
FOR RECEIVING, HANDLING, STORAGE, IF REQUIRED, AND INSTALLATION ARE
INCLUDED IN THE CONTRACT SUM.
A. THE INSTALLER'S RESPONSIBILITIES ARE THE SAME AS IF THE INSTALLER
FURNISHED THE MATERIALS OR EQUIPMENT.
B. THE OWNER WILL ARRANGE AND PAY FOR DELIVERY OF OWNER
FURNISHED ITEMS FREIGHT ON BOARD JOB SITE AND THE INSTALLER WILL
INSPECT DELIVERIES FOR DAMAGE. IF OWNER FURNISHED ITEMS ARE
DAMAGED, DEFECTIVE OR MISSING, DOCUMENT DAMAGED ITEMS WITH
THE TRANSPORT COMPANY AND THE OWNER WILL ARRANGE
FOR REPLACEMENT. THE OWNER WILL ALSO ARRANGE FOR
MANUFACTURER'S FIELD SERVICES, AND THE DELIVERY OF
MANUFACTURER'S WARRANTIES AND BONDS TO THE INSTALLER.
C. THE INSTALLER IS RESPONSIBLE FOR DESIGNATING THE DELIVERY DATES
OF OWNER FURNISHED ITEMS AND FOR RECEIVING, UNLOADING AND
HANDLING OWNER FURNISHED ITEMS AT THE SITE.THE INSTALLER IS
RESPONSIBLE FOR PROTECTING OWNER FURNISHED ITEMS FROM
DAMAGE, INCLUDING DAMAGE FROM EXPOSURE TO THE ELEMENTS, AND
TO REPAIR OR REPLACE ITEMS DAMAGED AS A RESULT OF HIS
OPERATIONS.
DEFINITIONS
NOTE: ALL DEFINITIONS MAY NOT BE USED.
INDICATED: THE TERM "INDICATED" REFERS TO GRAPHIC REPRESENTATIONS,
NOTES, OR SCHEDULES ON THE DRAWINGS, OTHER PARAGRAPHS OR
SCHEDULES IN THE SPECIFICATIONS, AND SIMILAR REQUIREMENTS IN THE
CONTRACT DOCUMENTS. WHERE TERMS SUCH AS "SHOWN", "NOTED",
"SCHEDULED", AND "SPECIFIED" ARE USED, IT IS TO HELP THE READER LOCATE
THE REFERENCE, NO LIMITATION ON LOCATION IS INTENDED.
DIRECTED: TERMS SUCH AS "DIRECTED", "REQUESTED", AUTHORIZED",
"SELECTED", "APPROVED", "REQUIRED", AND "PERMITTED" MEAN "DIRECTED BY
THE ENGINEER", "REQUESTED BY THE ENGINEER", AND SIMILAR PHRASES.
APPROVED: THE TERM "APPROVED", WHERE USED IN CONJUNCTION WITH THE
ENGINEER'S ACTION ON THE CONTRACTOR'S SUBMITTALS, APPLICATIONS, AND
REQUESTS, IS LIMITED TO THE ENGINEER'S DUTIES AND RESPONSIBILITIES AS
STATED IN GENERAL AND SUPPLEMENTARY CONDITIONS.
FURNISH: THE TERM "FURNISH" IS USED TO MEAN "SUPPLY AND DELIVER TO
THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY,
INSTALLATION, AND SIMILAR OPERATIONS."
INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT
SITE INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION,
PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING,
CURING, PROTECTING, CLEANING, AND SIMILAR OPERATIONS."
PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE
AND READY FOR THE INTENDED USE."
INSTALLER: AN "INSTALLER" IS THE CONTRACTOR OR AN ENTITY ENGAGED BY
THE CONTRACTOR, EITHER AS AN EMPLOYEE, SUBCONTRACTOR, OR SUB-
SUBCONTRACTOR, FOR PERFORMANCE OF A PARTICULAR CONSTRUCTION
ACTIVITY, INCLUDING INSTALLATION, ERECTION, APPLICATION, AND SIMILAR
OPERATIONS. INSTALLERS ARE REQUIRED TO BE EXPERIENCED IN THE
OPERATIONS THEY ARE ENGAGED TO PERFORM.
TECHNOLOGY SYSTEMS: THE TERM "TECHNOLOGY SYSTEMS" IS USED TO
DESCRIBE ALL LOW VOLTAGE SYSTEMS GENERALLY REFERRED TO AS
"SPECIAL SYSTEMS". THESE SYSTEMS INCLUDE BUT ARE NOT NECESSARILY
LIMITED TO ALL SYSTEMS WHICH UTILIZE VOLTAGES OF LESS THAN 71 VOLTS
SUCH AS SOUND SYSTEMS, VIDEO SYSTEMS, TV SYSTEMS, SECURITY
SYSTEMS, VOICE AND DATA CABLING SYSTEMS, ETC...
ABBREVIATIONS
NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
1P SINGLE POLE
1PH SINGLE-PHASE
1WAY ONE-WAY
2/C TWO-CONDUCTOR
2WAY TWO-WAY
3/C THREE-CONDUCTOR
3WAY THREE-WAY
4OUT QUADRUPLE RECEPTACLE
OUTLET
4PDT FOUR-POLE DOUBLE THROW
4PST FOUR-POLE SINGLE THROW
4W FOUR-WIRE
4WAY FOUR-WAY
A ABOVE COUNTER
AC ARMORED CABLE
ACS ACCESS CONTROL SYSTEM
ADA AMERICANS WITH DISABILITIES
ACT
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING
CAPACITY
ALUM ALUMINUM
AMP AMPERE
ANN ANNUNCIATOR
AP ACCESS POINT (WIRELESS
DATA)
AR AS REQUIRED
ASC AMPS SHORT CIRCUIT
ATS AUTOMATIC TRANSFER
SWITCH
AV AUDIO VISUAL
AWG AMERICAN WIRE GAGE
BB
XFMR
BUCK-BOOST TRANSFORMER
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
C CEILING MOUNTED
CAT CATEGORY
CATV COMMUNITY ANTENNA
TELEVISION
CB CIRCUIT BREAKER
CCBA CUSTOM COLOR AS SELECTED
BY ARCHITECT
CCTV CLOSED CIRCUIT TELEVISION
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/
OWNER INSTALLED
CFBA CUSTOM FINISH AS SELECTED
BY ARCHITECT
CI CONTACT INDICATOR
CKT CIRCUIT
CM CONSTRUCTION MANAGER
CND CONDUIT
CO CONVENIENCE OUTLET
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CP CONTROL PANEL
CR CARD READER
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
dBA UNIT OF SOUND LEVEL
DPDT DOUBLE POLE, DOUBLE
THROW
DS DISCONNECT SWITCH
E ENHANCED
EA EACH
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENT ELECTRIC NONMETALLIC
TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ER EQUIPMENT ROOM
EX EXISTING
F FURNITURE MOUNTED
FA FIRE ALARM
FCP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPS
FMC FLEXIBLE METAL CONDUIT
FOB FREIGHT ON BOARD
FPP FIBER PATCH PANEL
FVNR FULL VOLTAGE
NON-REVERSING
FVR FULL VOLTAGE REVERSING
GEN GENERATOR
GFCI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTION
GIG GIGA HERTZ
GND GROUND
HD HEAVY DUTY
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSE POWER
HPF HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
HV HIGH VOLTAGE
HWM HORIZONTAL WIRE
MANAGEMENT
HZ HERTZ
I/O INPUT/ OUTPUT
IG ISOLATED GROUND
IMC INTERMEDIATE METAL
CONDUIT
IN/IS INSULATED/ ISOLATED
IR INFRARED
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR
LED LIGHT EMITTING DIODE
LFMC LIQUID TIGHT FLEXIBLE METAL
CONDUIT
LFNC LIQUID TIGHT FLEXIBLE
NONMETALLIC CONDUIT
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTG LIGHTING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION
SYSTEM
MAX MAXIMUM
MC METAL CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTION
MDP MAIN DISTRIBUTION PANEL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT
PROTECTION
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OCP OVER CURRENT PROTECTION
OE OWNER ELECTRONICS
OF/CI OWNER FURNISHED/
CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED/ OWNER
INSTALLED
OFP OBTAIN FROM PLANS
OH DR OVERHEAD (COILING) DOOR
OL OVERLOAD
PB PUSHBUTTON
PF POWER FACTOR
PH PHASE
PNL PANEL
PNM PLENUM
PR PAIR
PS POWER SUPPLY
PT POTENTIAL TRANSFORMER
PTZ PAN/TILT/ZOOM
PV PHOTO VOLTAIC
QTY QUANTITY
R REMOVE
RCP REFLECTED CEILING PLAN
RMC RIGID METAL CONDUIT
RNC RIGID NONMETAL CONDUIT
RO REMOTE DOOR OPEN
RPM REVOLUTIONS PER MINUTE
RPP RISER PATCH PANEL
RR REMOVE AND RELOCATE
S/S START/STOP
SCA SHORT CIRCUIT AMPS
SCBA STANDARD COLOR AS
SELECTED BY ARCHITECT
SEC SECURITY
SF SQUARE FOOT (FEET)
SFBA STANDARD FINISH AS
SELECTED BY ARCHITECT
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE, DOUBLE THROW
SPEC SPECIFICATION
SPP STATION PATCH PANEL
SPST SINGLE POLE, SINGLE THROW
ST SINGLE THROW
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TL TWIST LOCK
TP TELEPHONE POLE
TP TWISTED PAIR
TR TELECOMMMUNICATIONS
ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSER
TYP TYPICAL
UF UNDERFLOOR
UGND UNDERGROUND
UPS UNINTERRUPTIBLE POWER
SUPPLY
V VOLTS
VA VOLT AMPERE
VFC/VF
D
VARIABLE FREQUENCY MOTOR
CONTROLLER
VIC VIDEO INTERCOM SYSTEM
VSS VIDEO SURVEILLANCE SYSTEM
VWM VERTICAL WIRE MANAGEMENT
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
WPP WIRELESS PATCH PANEL
XFMR TRANSFORMER
WIRING METHODS
WIRING.
WIRING TURNED UP OR TOWARDS OBSERVER.
WIRING TURNED DOWN OR AWAY FROM OBSERVER.
BRANCH CIRCUIT HOME RUN TO PANELBOARD: NUMBER OF
ARROWS INDICATES NUMBER OF CIRCUITS. LETTER AND
NUMBER NOTATIONS IDENTIFY PANEL AND CIRCUIT NUMBERS.A-1,3,5
BRANCH CIRCUIT HOME RUN TO PANELBOARD: NUMBER OF
ARROWS INDICATES NUMBER OF CIRCUITS. LETTER AND
NUMBER NOTATIONS IDENTIFY PANEL AND CIRCUIT NUMBERS.
NUMBER IN BOX REFERS TO THE CONDUCTOR AND CONDUIT
SCHEDULE.
A-1,3,5
LOW VOLTAGE WIRING: DIVIDE, MEDIUM LINE.
CONDUIT STUB. DIMENSION RECORD DRAWINGS AND MARK.
CONDUCTOR & CONDUIT ("CC") SCHEDULE INDICATOR. REFER
TO ONE-LINE DIAGRAM.1
SYMBOL DESCRIPTION
SYMBOLS LEGEND
SYMBOL DESCRIPTION
SYMBOLS LEGEND
SINGLE BRANCH CIRCUIT HOME RUN TO PANELBOARD WITH
DEDICATED NEUTRAL CONDUCTOR. LETTER AND NUMBER
NOTATION IDENTIFY PANEL AND CIRCUIT NUMBER.A-1
3. EXPOSED STRUCTURE AREAS (EXCLUDING MECHANICAL, ELECTRICAL, AND
COMMUNICATION SPACES): INSTALL RACEWAYS BETWEEN DECK AND
STRUCTURE WHEREVER POSSIBLE IN EXPOSED STRUCTURE CEILING AREAS.
ROUTE RACEWAYS IN CONCEALED AREAS WHEREVER POSSIBLE. REFER ALL
CONDITIONS WHERE RACEWAYS MUST BE INSTALLED WHICH CANNOT COMPLY
WITH THESE REQUIREMENTS TO THE ARCHITECT.
4. SUBMITTALS: PROVIDE ORIGINAL ELECTRONIC PDF FORMAT, BOUND,
BOOKMARKED (EACH SECTION AND PRODUCT), AND HIGHLIGHTED. JOB NAME
AND SUBCONTRACTOR SHALL BE ON THE FRONT COVER. PREPARE INDEX OF
EQUIPMENT SUBMITTED IN EACH TAB.
5. REFLECTED CEILING PLANS: COORDINATE THE LOCATION OF LIGHT FIXTURES
WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. REFER ALL
DISCREPANCIES TO THE ARCHITECT AND ENGINEER.
6. ALL WORK SHALL BE DONE ACCORDING TO THE CURRENT NATIONAL ELECTRIC
CODE (NEC), IBC, NFPA, AND IFC. COMPLIANCE AND FINAL APPROVAL IS SUBJECT
TO THE ON SITE FIELD INSPECTION OF THE AHJ.
REFERENCE AND LINE SYMBOLS
DETAIL INDICATOR: A5 INDICATES DETAIL NUMBER, E-501
INDICATES DRAWING SHEET WHERE DETAIL IS SHOWN.
A5 E-501
ELEVATION OR SECTION INDICATOR, EXTERIOR: A5 INDICATES
ELEVATION OR SECTION NUMBER, E-201 INDICATES DRAWING
SHEET WHERE ELEVATION OR SECTION IS SHOWN.
A5 E-201
ELEVATION OR SECTION INDICATOR, INTERIOR: A5 INDICATES
ELEVATION OR SECTION NUMBER, E-201 INDICATES DRAWING
SHEET WHERE ELEVATION OR SECTION IS SHOWN.
A5 E-201
ROOM IDENTIFIER WITH ROOM NAME AND NUMBER.
ROOM NAME
KEYNOTE INDICATOR.1
REVISION INDICATOR.1
CU-1 EQUIPMENT INDICATOR.
BREAK, STRAIGHT: TO BREAK PARTS OF DRAWING
BREAK, ROUND
MATCH LINE INDICATOR: CENTER, EXTRA WIDE LINE.MATCH LINE
SEE XX/X-XXX
NEW LINE: MEDIUM LINE.
HIDDEN FEATURES LINE: HIDDEN, THIN LINE
EXISTING TO REMAIN LINE: THIN LINE.
DEMOLITION LINE: DASHED, MEDIUM LINE
PROPERTY LINE: DASHED, WIDE LINE.
CONTRACT LIMIT LINE: DASHDOT, WIDE LINE.
MECHANICAL EQUIPMENT INDICATOR. "X-X" INDICATES
EQUIPMENT MARK SHOWN ON EQUIPMENT SCHEDULE. "XMDP"
IDENTIFIES PANEL EQUIPMENT IS CIRCUITED TO. REFER TO
EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION.
XMDP
X-X
ELECTRICAL POWER AND DISTRIBUTION
CIRCUIT BREAKER (ONE-LINE DIAGRAM).
MOTOR.
TRANSFORMER (ONE-LINE DIAGRAM).
PANELBOARD (ONE-LINE DIAGRAM)."1H"
PANELBOARD WITH MAIN LUGS ONLY. BUS SIZE AND PHASE AS
SHOWN (ONE-LINE DIAGRAM).
225/3
"1H"
PANELBOARD WITH MAIN CIRCUIT BREAKER. SIZE AND PHASE AS
SHOWN (ONE-LINE DIAGRAM).
225/3
"1H"
DISTRIBUTION PANELBOARD, MOTOR CONTROL CENTER,
PLUG-IN BUSWAY, MEDIUM VOLTAGE SWITCHBOARD
(ONE-LINE DIAGRAM).
"1DPHA"
PANELBOARD WITH MAIN AND SUB FEED CIRCUIT BREAKER
(ONE-LINE DIAGRAM).
60/3
225/3
"1H"
DISCONNECT SWITCH, FUSED.
PANELBOARD CABINET, FLUSH MOUNTED.
PANELBOARD CABINET, SURFACE MOUNTED, 1 SECTION.
PANELBOARD CABINET, SURFACE MOUNTED, 2 SECTION.
DP#__
DISTRIBUTION PANEL OR SWITCHBOARD.
SWITCH, TOGGLE MOTOR STARTER WITH OVERLOAD
PROTECTION.ST
TRANSFORMER (SEE ONE-LINE FOR SIZE)
METER.M
DUPLEX
RECEPTACLE
DUPLEX RECEPTACLE
WALL PHONE PAY PHONE
FINISHED FLOOR
WALL BRACKET TVGENERAL USE:
NO SPECIAL
REQUIREMENTS
DEDICATED
RECEPTACLE
FOR SPECIAL
EQUIPMENT
ABOVE
COUNTER - TYPICAL
RECEPTACLES ABOVE OR BELOW COUNTER
WINDOW
OR
COMMUNICATIONS
RECEPTACLE
COMMUNICATIONS
RECEPTACLE COUNTER TOP
GROMMET
COMMUNICATIONS
RECEPTACLE
" M
AX C
O
O R
D
IN
AT
E
W
IT
H E
Q U
IP
M
EN
T
C O
O R
D
IN
AT
E
H
EI
G H
T W
IT
H
EQ
U
IP
M
EN
T
" M
AX ±4
6"
M
AX
(V
ER
IF
Y
H
EI
G H
T O
F
BA
C
KS
PL
AS
H
2' -0
16" MIN
REFER TO ARCHITECTURAL ELEVATIONS
FOR PLACEMENT OF OUTLETS
" M
IN
BOXES ON OPPOSITE SIDES OF WALL
STUD IN
BETWEEN
24"
MIN
FOR LESS THAN 24"
SEPARATION, PROVIDE LISTED
SOUND AND FIRE PUTTY PADS
GENERAL
USE: ADA
STANDARD DOOR
FINISHED FLOOR
DOOR WITH SIDELIGHT
LESS THAN 2'
DOOR WITH SIDELIGHT
GREATER THAN 2'
CABINETS
DOOR WITH NO
PLACE FOR SWITCH
AT LATCH SIDE
COMBINATION 48" MAX
PLATE FOR SWITCH AND
RECEPTACLE IN
RESIDENTIAL BATHROOM
LIGHTING
CONTROL STATION
SWITCH
LOCATION
SIDELIGHT
LESS THAN 2'
SIDELIGHT
GREATER
THAN 2'
SWITCH
LOCATION
METAL
FRAME
" M
AX
" M
AX
" M
AX
METAL
FRAME
SWITCH
LOCATION
SWITCH
LOCATION
COMMUNICATIONS
RECEPTACLE
COMMUNICATIONS
RECEPTACLE
TILE WALLSWALL BRACKET TV
DEDICATED
RECEPTACLE
FOR SPECIAL
EQUIPMENT
MIRROR
FINISHED FLOOR
NO SPECIAL REQUIREMENTS
GENERAL USE:
DUPLEX
RECEPTACLE
CENTER
IN TILE
DO NOT LOCATE
ABOVE SINK
WALLWALL
COORDINATE LOCATION
OF QUAD/ DUPLEX
OUTLET WITH EQUIPMENT
SUPPLIER
MOUNT QUAD/
DUPLEX OUTLET
BEHIND WATER
COOLER
REGULAR ADA
DRINKING FOUNTAIN - SIDE ELEVATIONSRECEPTACLES BELOW COUNTER
WINDOW
COUNTER TOP
GROMMET
DUPLEX RECEPTACLE
DUPLEX
RECEPTACLE
RECEPTACLES ABOVE COUNTER
WITH BACKSPLASHWITHOUT BACKSPLASH
COUNTER TOP
BACKSPLASH
2' -0
C O
O R
D
IN
AT
E
H
EI
G H
T W
IT
H
EQ
U
IP
M
EN
T
M
AX
M
AX
6" M
AX
6" M
AX
" M
IN
" M
IN
EQEQ
EQEQ
EQ
KING STUD/
FRAMING
(TYP)
FIRE ALARM
HORN/ STROBE
(TYP)
WALL SWITCH
(TYP)
VOLUME
CONTROL
(TYP)
ENVIRONMENTAL
CONTROLS
(THERMOSTAT)
DUPLEX
RECEPTACLE
(TYP)
DATA
RECEPTACLE
(TYP)
CARD READER
FIRE ALARM
PULL STATION
AL
IG
N (T
YP
SIGNAGE
(SEE ARCHITECTURAL
PLANS AND DETAILS
FOR LOCATIONS AND
MOUNTING HEIGHTS)
DOOR
(TYP)
AL
IG
N (T
YP
AL
IG
N (T
YP
FINISHED
FLOOR
FINISHED
FLOOR
ALIGN
(TYP) AL
IG
N
(T
YP
AL
IG
N (T
YP
SCALE: NTSE7 COMMUNICATIONS MOUNTING DETAILS
SCALE: NTS
BOX MOUNTING DETAILSF4
SCALE: NTSE3 SWITCH MOUNTING DETAILS
SCALE: NTSB3 RECEPTACLE MOUNTING DETAILS
GENERAL SHEET NOTES
SCALE: NTSF6 TYPICAL WALL MOUNTED DEVICES ALIGNMENT DETAIL
1 MOUNTING HEIGHTS OF ELECTRICAL AND ELECTRONIC EQUIPMENT IN THE
FOLLOWING ORDER OF PRIORITY:
A - ELEVATIONS (ARCHITECTURAL, ELECTRICAL, MECHANICAL, ETC).
B - EQUIPMENT SHOP DRAWINGS.
C - FIELD INSTRUCTIONS.
2 LOCATE RECEPTACLES SERVING THE SAME TYPE OF USE AT A UNIFORM HEIGHT
UNLESS DIRECTED OTHERWISE.
3 MECHANICAL, ELECTRICAL, AND COMMUNICATION ROOMS:…
This is the start of the file's text. The full file is on GovTribe.