85-GD11_MCB

General Electric Entelliguard Sensor = 1600 (LSIG) Plug = 1600 Amps LT Pickup = 0.95 (1520 Amps) LT Band = 2 ST Pickup = 7 (10640 Amps) ST Band = 4 (I^x)t = OUT Inst. Pickup = 9 (14400 Amps)

85-GD11_CBL - P

MFR6 E1 - P

OC1

Square D Sepam Series 40 CT Ratio 200:5 Extremely Inverse Time Pickup = 1.2 (0.5 - 2.4 xCT Sec) Time Dial = 0.3 3x = 3.71 s, 5x = 1.24 s, 8x = 0.471 s

T10E Inrush T10E

FUSE T10E

Cooper Bay-O-Net (High Ampere) Other 15.5 kV C04

REC 14E-5 - P

TCC

Cooper Tri-Phase

KF

Pickup = 140 (20 - 1290 Primary) Interrupting Time = 5 Cycles 3x = 0.702 s, 5x = 0.281 s, 8x = 0.121 s Clearing

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 GANG SWITCH 14E/E1 (Nom. kV=12.47, Plot Ref. kV=12.47)

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 GANG SWITCH 14E/E1 (Nom. kV=12.47, Plot Ref. kV=12.47) 2598K129.9 1K 10K 100K 1000K300 500 3K 5K 30K 300K

Amps T10E_SEC (Nom. kV=0.48, Plot Ref. kV=0.48)

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K S ec on ds

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K

S econds

ETAP Star 12.0.0C

T10E_MV

Project: ELECTRICAL SYSTEM CORR. PH 1B Location: Boise, ID Contract: 531-09-132 Engineer: Bruce G. Alward, P.E.

Filename: S:\ETAP Databases\Veterans Administration\Boise\0805

Date: 09-23-2011

SN: WOODHARBI2

Rev: Base Fault: Phase

ELECTRICAL SYSTEM CORRECTIONS, PHASE 1B

oCT E1 200/5

T10E_SEC

0.48 kV

85-GD11

0.48 kV

REC 14E-5

0 kA

1.01 kV 0 A

85-GD11_MCB

65 kA

0.48 kV 1600 A

T10E

5.69 %Z 12.47/0.48 kV 1000 kVA

FUSE T10E

2.5 kA

15.5 kV 100 A

R MFR6 E1

51P/51N

85-GD11_CBL

0.039+j0.05 ohms/1000ft

12-1/C 350

CU

45 ft

MFR6 E1 - G

OC1

Square D Sepam Series 40 CT Ratio 200:5 Extremely Inverse Time Pickup = 0.5 (0.1 - 1 xCT Sec) Time Dial = 0.26 3x = 3.22 s, 5x = 1.07 s, 8x = 0.409 s

REC 14E-5 - G

TCC

Cooper Tri-Phase

EF

Pickup = 50 (10 - 640 Primary) Interrupting Time = 5 Cycles 3x = 0.674 s, 5x = 0.271 s, 8x = 0.134 s Clearing

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 BUS 83E (Nom. kV=12.47, Plot Ref. kV=12.47)

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 BUS 83E (Nom. kV=12.47, Plot Ref. kV=12.47) 299.8K14.99 100 1K 10K 100K30 50 300 500 3K 5K 30K

Amps (Plot Ref. kV=4.16)

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K S ec on ds

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K

S econds

ETAP Star 12.0.0C

T10E_MV

Project: ELECTRICAL SYSTEM CORR. PH 1B Location: Boise, ID Contract: 531-09-132 Engineer: Bruce G. Alward, P.E.

Filename: S:\ETAP Databases\Veterans Administration\Boise\0805

Date: 09-23-2011

SN: WOODHARBI2

Rev: Base Fault: Ground

ELECTRICAL SYSTEM CORRECTIONS, PHASE 1B

oCT E1 200/5

T10E_SEC

0.48 kV

85-GD11

0.48 kV

REC 14E-5

0 kA

1.01 kV 0 A

85-GD11_MCB

65 kA

0.48 kV 1600 A

T10E

5.69 %Z 12.47/0.48 kV 1000 kVA

FUSE T10E

2.5 kA

15.5 kV 100 A

R MFR6 E1

51P/51N

85-GD11_CBL

0.039+j0.05 ohms/1000ft

12-1/C 350

45 ft

85-ND12_CBL - P

85-ND12_MCB

General Electric Entelliguard Sensor = 1600 (LSIG) Plug = 1600 Amps LT Pickup = 0.95 (1520 Amps) LT Band = 2 ST Pickup = 7 (10640 Amps) ST Band = 4 (I^x)t = OUT Inst. Pickup = 9 (14400 Amps)

MFR6 52N1 - P

OC1

Square D Sepam Series 40 CT Ratio 200:5 Extremely Inverse Time Pickup = 1.2 (0.5 - 2.4 xCT Sec) Time Dial = 0.3 3x = 3.71 s, 5x = 1.24 s, 8x = 0.471 s

T10N Inrush

REC 14N-4 - P

TCC

Cooper Tri-Phase

KF

Pickup = 140 (20 - 1290 Primary) Interrupting Time = 25 ms 3x = 0.702 s, 5x = 0.281 s, 8x = 0.121 s Clearing

T10N 1000 kVA (Secondary) 5.69 %Z Delta-Wye Solid Grd Curve Shift = 0.58

FUSE T10N

Cooper Bay-O-Net (High Ampere) Other 15.5 kV C04

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 T10N PRI. (Nom. kV=12.47, Plot Ref. kV=12.47)

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 T10N PRI. (Nom. kV=12.47, Plot Ref. kV=12.47)

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K S ec on ds

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K

S econds

ETAP Star 12.0.0C

T10N_MV

Project: ELECTRICAL SYSTEM CORR. PH 1B Location: Boise, ID Contract: 531-09-132 Engineer: Bruce G. Alward, P.E.

Filename: S:\ETAP Databases\Veterans Administration\Boise\08058_01\08058_01.OTI

Date: 09/23/2011

SN: WOODHARBI2

Rev: Base Fault: Phase

ELECTRICAL SYSTEM CORRECTIONS, PHASE 1B

oCT N1 200/5

T10N_SEC

0.48 kV

85-ND11/12

0.48 kV

85-ND12_MCB

65 kA

0.48 kV 1600 A

85-ND12_CBL

0.039+j0.05 ohms/1000ft

12-1/C 350

CU

40 ft

T10N

5.69 %Z 12.47/0.48 kV 1000 kVA

FUSE T10N

2.5 kA

15.5 kV 100 A

REC 14N-4

12 kA 15 kV 600 A

R

MFR6 52N1

51P/51N

MFR6 52N1 - G

Square D Sepam Series 40 CT Ratio 200:5 Extremely Inverse Time Pickup = 0.5 (0.1 - 1 xCT Sec) Time Dial = 0.26 3x = 3.22 s, 5x = 1.07 s, 8x = 0.409 s

REC 14N-4 - G

TCC

Cooper Tri-Phase

EF

Pickup = 50 (10 - 640 Primary) Interrupting Time = 25 ms 3x = 0.674 s, 5x = 0.271 s, 8x = 0.134 s Clearing

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 BUS 83N (Nom. kV=12.47, Plot Ref. kV=12.47)

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 BUS 83N (Nom. kV=12.47, Plot Ref. kV=12.47)

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K S ec on ds

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K

S econds

ETAP Star 12.0.0C

T10N_MV

Project: ELECTRICAL SYSTEM CORR. PH 1B Location: Boise, ID Contract: 531-09-132 Engineer: Bruce G. Alward, P.E.

Filename: S:\ETAP Databases\Veterans Administration\Boise\08058_01\08058_01.OTI

Date: 09/23/2011

SN: WOODHARBI2

Rev: Base Fault: Ground

ELECTRICAL SYSTEM CORRECTIONS, PHASE 1B

oCT N1 200/5

T10N_SEC

0.48 kV

85-ND11/12

0.48 kV

85-ND12_MCB

65 kA

0.48 kV 1600 A

T10N

5.69 %Z 12.47/0.48 kV 1000 kVA

FUSE T10N

2.5 kA

15.5 kV 100 A

REC 14N-4

12 kA 15 kV 600 A

R

MFR6 52N1

51P/51N

85-ND12_CBL

0.039+j0.05 ohms/1000ft

12-1/C 350

40 ft

67-GDG1_FDR - P

67-GDG1_CB

General Electric MVT-PM (SS,SH) Sensor = 800 (LSIG) Plug = 800 Amps LT Pickup = 1 (800 Amps) LT Band = 2 ST Pickup = 9 (7200 Amps) ST Band = Min(1) (I^x)t = OUT Inst. Pickup = 10 (8000 Amps)

MFR6 E1 - P

OC1

Square D Sepam Series 40 CT Ratio 200:5 Extremely Inverse Time Pickup = 1.2 (0.5 - 2.4 xCT Sec) Time Dial = 0.3 3x = 3.71 s, 5x = 1.24 s, 8x = 0.471 s

REC 14E-6 - P

TCC

Cooper Tri-Phase

KF

Pickup = 90 (20 - 1290 Primary) Interrupting Time = 5 Cycles 3x = 0.702 s, 5x = 0.281 s, 8x = 0.121 s Clearing

T9E 500 kVA (Secondary) 4.66 %Z Delta-Wye Solid Grd Curve Shift = 0.58

T9E Inrush

FUSE T9E

Cooper Bay-O-Net Other 15.5 kV C12

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 BUS 83E (Nom. kV=12.47, Plot Ref. kV=12.47)

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 BUS 83E (Nom. kV=12.47, Plot Ref. kV=12.47)

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K S ec on ds

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K

S econds

ETAP Star 12.0.0C

T9E_MV

Project: ELECTRICAL SYSTEM CORR. PH 1B Location: Boise, ID Contract: 531-09-132 Engineer: Bruce G. Alward, P.E.

Filename: S:\ETAP Databases\Veterans Administration\Boise\08

Date: 09-23-2011

SN: WOODHARBI2

Rev: Base Fault: Phase

ELECTRICAL SYSTEM CORRECTIONS, PHASE 1B

67-GDG1

0.48 kV oCT E1 200/5

FUSE T9E

2.5 kA

15.5 kV 50 A

T9E

4.66 %Z 12.47/0.48 kV 500 kVA

REC 14E-6

0 kA

1.01 kV 0 A

R

MFR6 E1

51P/51N

67-GDG1_FDR

0.039+j0.05 ohms/1000ft

6-1/C 350

CU

100 ft

67-GDG1_CB

65 kA

0.48 kV 800 A

MFR6 E1 - G

Square D Sepam Series 40 CT Ratio 200:5 Extremely Inverse Time Pickup = 0.5 (0.1 - 1 xCT Sec) Time Dial = 0.26 3x = 3.22 s, 5x = 1.07 s, 8x = 0.409 s

REC 14E-6 - G

TCC

Cooper Tri-Phase

EF

Pickup = 50 (10 - 640 Primary) Interrupting Time = 5 Cycles 3x = 0.674 s, 5x = 0.271 s, 8x = 0.134 s Clearing

REC 14E-6 - LG

2.059kA @ 12.47kV (Asym)

MFR6 E1 - G - LG

2.131kA @ 12.47kV (Asym)

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 BUS 83E (Nom. kV=12.47, Plot Ref. kV=12.47)

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 BUS 83E (Nom. kV=12.47, Plot Ref. kV=12.47)

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K S ec on ds

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K

S econds

ETAP Star 12.0.0C

T9E_MV

Project: ELECTRICAL SYSTEM CORR. PH 1B Location: Boise, ID Contract: 531-09-132 Engineer: Bruce G. Alward, P.E.

Filename: S:\ETAP Databases\Veterans Administration\Boise\08

Date: 09-23-2011

SN: WOODHARBI2

Rev: Base Fault: Ground

ELECTRICAL SYSTEM CORRECTIONS, PHASE 1B

67-GDG1

0.48 kV oCT E1 200/5

FUSE T9E

2.5 kA

15.5 kV 50 A

T9E

4.66 %Z 12.47/0.48 kV 500 kVA

REC 14E-6

0 kA

1.01 kV 0 A

R

MFR6 E1

51P/51N

67-GDG1_CB

65 kA

0.48 kV 800 A

67-GDG1_FDR

0.039+j0.05 ohms/1000ft

6-1/C 350

100 ft

67-NDG1_FDR - P

67-NDG1_CB

General Electric MVT-PM (SS,SH) Sensor = 800 (LSIG) Plug = 800 Amps LT Pickup = 1 (800 Amps) LT Band = 2 ST Pickup = 9 (7200 Amps) ST Band = Min(1) (I^x)t = OUT Inst. Pickup = 10 (8000 Amps)

MFR6 52N1 - P

OC1

Square D Sepam Series 40 CT Ratio 200:5 Extremely Inverse Time Pickup = 1.2 (0.5 - 2.4 xCT Sec) Time Dial = 0.3 3x = 3.71 s, 5x = 1.24 s, 8x = 0.471 s

REC 14N-3 T9N - P

TCC

Cooper Tri-Phase

KF

Pickup = 90 (20 - 1290 Primary) Interrupting Time = 5 Cycles 3x = 0.702 s, 5x = 0.281 s, 8x = 0.121 s Clearing

T9N

T9N Inrush

FUSE T9N

Cooper Bay-O-Net Other 15.5 kV C12

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 BUS 83N (Nom. kV=12.47, Plot Ref. kV=12.47)

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 BUS 83N (Nom. kV=12.47, Plot Ref. kV=12.47)

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K S ec on ds

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K

S econds

ETAP Star 12.0.0C

T9N_MV

Project: ELECTRICAL SYSTEM CORR. PH 1B Location: Boise, ID Contract: 531-09-132 Engineer: Bruce G. Alward, P.E.

Filename: S:\ETAP Databases\Veterans Administration\Boise\08

Date: 09/23/2011

SN: WOODHARBI2

Rev: Base Fault: Phase

ELECTRICAL SYSTEM CORRECTIONS, PHASE 1B

67-NDG1

0.48 kV o

CT N1

200/5

FUSE T9N

2.5 kA

15.5 kV 50 A

T9N

4.66 %Z 12.47/0.48 kV 500 kVA

REC 14N-3 T9N

0 kA

1.01 kV 0 A

R

MFR6 52N1

51P/51N

67-NDG1_FDR

0.039+j0.05 ohms/1000ft

6-1/C 350

CU

60 ft

67-NDG1_CB

65 kA

0.48 kV 800 A

REC 14N-3 T9N - G

TCC

Cooper Tri-Phase

EF

Pickup = 50 (10 - 640 Primary) Interrupting Time = 5 Cycles 3x = 0.674 s, 5x = 0.271 s, 8x = 0.134 s Clearing

MFR6 52N1 - G

OC1

Square D Sepam Series 40 CT Ratio 200:5 Extremely Inverse Time Pickup = 0.5 (0.1 - 1 xCT Sec) Time Dial = 0.26 3x = 3.22 s, 5x = 1.07 s, 8x = 0.409 s

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 GANG SWITCH 14N/N1 (Nom. kV=12.47, Plot Ref. kV=12.47)

10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

Amps X 10 GANG SWITCH 14N/N1 (Nom. kV=12.47, Plot Ref. kV=12.47)

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K S ec on ds

10K

.001

.01

.1

1K

.003

.005

.03

.05

.3

.5

3K

5K

S econds

ETAP Star 12.0.0C

T9N_MV

Project: ELECTRICAL SYSTEM CORR. PH 1B Location: Boise, ID Contract: 531-09-132 Engineer: Bruce G. Alward, P.E.

Filename: S:\ETAP Databases\Veterans Administration\Boise\08

Date: 09/23/2011

SN: WOODHARBI2

Rev: Base Fault: Ground

ELECTRICAL SYSTEM CORRECTIONS, PHASE 1B

67-NDG1

0.48 kV o

CT N1

200/5

FUSE T9N

2.5 kA

15.5 kV 50 A

T9N

4.66 %Z 12.47/0.48 kV 500 kVA

REC 14N-3 T9N

0 kA

1.01 kV 0 A

R

MFR6 52N1

51P/51N

67-NDG1_CB

65 kA

0.48 kV 800 A

67-NDG1_FDR

0.039+j0.05 ohms/1000ft

6-1/C 350

60 ft