Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
Revisions: Date:
G
H
Local I.D.As-Built By:
Project Director
FIRST FLOOR AIR HANDLER SERVICE AREA AS-BUILT
MECHANICAL
FIRST FLOOR
8/31/21 - DJM
MAIN HOSPITAL
M-2
SCALE: 18" = 10'
0 10'-0" 30'-0" 70'-0"
102 103
105 106
ATTIC ACCESS HATCH
AHU #4
AHU #6
SERVED BY RADIATORS
AHU #3 AHU #5
AHU #8
AHU #21
AHU #25
AHU #26
AHU #27
AHU #28 & MAU
RTU #45
AHU
#9
AHU #11
AHU #10
AHU #9
& #10
SERVED BY SPACE HEATERS
& ERV
DENTAL MAU & FCU'S
AHU #6
AHU #4
AHU #22
AHU #24
CLC DINING RTU
SERVED BY RADIATORS
VHACHYColeE Callout Highlighted Women's Clinic area is still on Pneumatic Controls.
VHACHYColeE Polygon
VHACHYColeE Callout AHU-9 is a constant volume unit with manual dampers for balancing and thermostats that just control a re-heat coil in the supply ductwork.
VHACHYColeE Callout RTU-45 is a ventilation unit which has series fan powered VAV terminal units with return air circulation. Area has digital controls but adjustments for terminal units cannot be made at older style thermostats.
VHACHYColeE Callout Dental area - not on BAS.
VHACHYColeE Callout AHUs #27, #28, & Canteen MAU are constant volume, no VAVs.
VHACHYColeE Callout AHU #8 is a newer system with VAVs and DDC thermostats that can be plugged into.
VHACHYColeE Callout AHU #10 is a VAV system with DDC thermostats that can be plugged into.
VHACHYColeE Callout Constant volume RTU
VHACHYColeE Callout Constant volume AHU
VHACHYColeE Callout AHU #6 is a VAV system with DDC thermostats that can be plugged into.
VHACHYColeE Callout AHU #4 is a VAV system with DDC thermostats that can be plugged into with exception of the Women's Clinic.
VHACHYColeE Callout AHU #26 is a VAV system with DDC thermostats that can be plugged into.
VHACHYColeE Callout AHUs #21, #22, #24, & #25 are VAV systems with DDC thermostats that can be plugged into.
VHACHYColeE Callout AHUs #3 & 5 are VAV systems with DDC thermostats that can be plugged into.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
Revisions: Date:
G
H
Local I.D.As-Built By:
Project Director
SECOND FLOOR AIR HANDLER SERVICE AREA AS-BUILT
MECHANICAL
SECOND FLOOR
8/31/21 - DJM
MAIN HOSPITAL
M-3
SCALE: 18" = 10'
0 10'-0" 30'-0" 70'-0"
AHU
U-00
RAMPAHU
#23 AHU #3
AHU #1
AHU #2
AHU #13
AHU #15
AHU #16
RTU #17 &
MAU #17
AHU #21
AHU #18
AHU #25
AHU #24
AHU #9
AHU #14
AHU #14
AHU #8
AHU #19
VHACHYColeE Callout AHU #14 Multi-zone AHU on Pneumatic Controls. No VAVs.
VHACHYColeE Callout AHU #19 area has digital controls but adjustments for VAVs cannot be made at older style thermostats.
VHACHYColeE Callout AHU #13 is a small ventilation air unit and the system has fan powered fan coils that recirculate plenum return air. Area has digital controls but adjustments for terminal units cannot be made at older style thermostats.
VHACHYColeE Callout AHU #16 is a constant volume unit with manual dampers for balancing and thermostats that just control a re-heat coil in the supply ductwork.
VHACHYColeE Callout AHU #3 is a VAV system with DDC thermostats that can be plugged into.
VHACHYColeE Callout AHU #1 & AHU #23 are currently being replaced with a new single unit to serve both areas. System is VAV with DDC thermostats that can be plugged into.
VHACHYColeE Callout AHU #21 is a VAV system with DDC thermostats that can be plugged into.
VHACHYColeE Callout AHU #2 is a VAV system with DDC thermostats that can be plugged into.
VHACHYColeE Callout Constant volume RTU & MAU
VHACHYColeE
AHUs #15 & #18 are VAV systems with DDC thermostats that can be plugged into.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
Revisions: Date:
G
H
Local I.D.As-Built By:
Project Director
THIRD FLOOR AIR HANDLER SERVICE AREA AS-BUILT
MECHANICAL
THIRD FLOOR
8/31/21 - DJM
MAIN HOSPITAL
M-4
SCALE: 18" = 10'
0 10'-0" 30'-0" 70'-0"
AHU #6
AHU #18 AHU #20
AHU #12
AHU #15
AHU #21
AHU #23 AHU #5
AHU #3
AHU #1
AHU #7
AHU #2
AHU #4
AHU #6
AHU #16
RTU #17
MAU #17
AHU #19
VHACHYColeE Snapshot
VHACHYColeE Snapshot
VHACHYColeE Snapshot
VHACHYColeE Snapshot
VHACHYColeE Callout AHUs #15 & #18 are VAV systems with DDC thermostats that can be plugged into.
VHACHYColeE Callout AHU #20 is a constant volume unit with manual dampers for balancing and thermostats that just control a re-heat coil in the supply ductwork.
VHACHYColeE
Constant volume AHU
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
Revisions: Date:
G
H
Local I.D.As-Built By:
Project Director
FOURTH FLOOR AIR HANDLER SERVICE AREA AS-BUILT
ATTIC
MECHANICAL
FOURTH FLOOR
8/31/21 - DJM
MAIN HOSPITAL
M-5
SCALE: 18" = 10'
0 10'-0" 30'-0" 70'-0"
AHU #20
AHU #12
AHU #15
AHU #18
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
Revisions: Date:
G
H
Local I.D.As-Built By:
Project Director
BASEMENT FLOOR AIR HANDLER SERVICE AREA AS-BUILT
MECHANICAL
BASEMENT FLOOR
8/31/21 - DJM
MAIN HOSPITAL
M-6
SCALE: 18" = 10'
0 10'-0" 30'-0" 70'-0"
AHU #28
AHU #7
AHU #5
AHU #27
AHU #11
AHU #10
CANTEEN MAU
AHU #5
SERVED BY RADIATORS
VHACHYColeE Callout AHU #7 is a VAV system with DDC thermostats that can be plugged into.
VHACHYColeE
AHU #5 is a VAV system with DDC thermostats that can be plugged into.