36C25919R0092-003.pdf
PDF 26 MB Posted
- Attached to
- (CON) Restore Cooling Capability - 575 Federal contract opportunity
- Solicitation number
- 36C25919R0092
About this file
36C25919R0092 S02 575-18-109 Restore Cooling Capability Combined Sheets.pdf
View the file
Other files for this federal contract opportunity
Show all 37
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N O
R
TH
Bldg # Function 18 Carport: Government Vehicles
20 Community Living Center
22 Warehouse
32 Designated Smoking Area
34 Information Tech Services
35 Recreation Therapy
36 Administrative Services
37 Pain Management &
Winter Sports Clinic
41 Patient Smoking Shelter
44 Parking Garage
45 Physical Medicine, Rehabilitation and Prosthetics
A Quality Management
B Surgeons
P:A Parking: Patients & Visitors
P:B Parking: Staff
G O
V E
R N
M E
N T
V E
H
IC
L E
P A
R K
IN
G
P R
O V
ID
E
R P
A R
K
IN
G U
P P
E R
L E
V E
L
45 P:A
P:A
P:B
P:B
P:B
Bldg # Function 1 Hospital
5 Administration
Human Resources
PIV
Home Base Patient Care
Credit Union
6 Education & Training
Computer Labs
Video Conferencing
Quality Management
7 Warehouse
8 Administrative
Engineering
9 Boiler/Chiller Plant
12 Engineering Office/Shops
13 Laundry
14 Incinerator
Property Line
North Avenue d S tre e t gas elect
B
A
N
T
H S
T R
E E
T
N
T
H S
T R
E E
T
VICINITY MAP
NO SCALE
R
O A
D
WHITE AVENUE
MAIN
OURAY AVENUE
GRAND AVENUE
GUNNISON AVENUE
E MAIN
N
T
H S
T R
E E
T
VA WESTERN
COLORADO
HEALTH CARE
SYSTEM
N
T
H S
T R
E E
T
NORTH AVENUE
ELM AVENUE
N
R
D S
T R
E E
T
N
T
H S
T R
E E
T
GRAND VALLEY CANAL
ORCHARD AVENUE
F RD
N
T
H S
T R
E E
T N
T
H S
T R
E E
T
N
T
H S
T R
E E
T
PROJECT LOCATION
INDEX
1 G000C COVER
2 G100C LIFE SAFETY PLAN
3 S001 STRUCTURAL GENERAL NOTES
4 S002 IBC INSPECTION TABLES
5 S101 FOUNDATION PLAN
6 S401 STANDARD DETAILS
7 M000C MECHANICAL REFERENCE SHEET
8 MD101C SITE MECHANICAL DEMOLITION PLAN
9 MD102C MECHANICAL DEMOLITION PLAN
10 M101C SITE MECHANICAL PIPING PLAN
11 M102C HYDRONIC PIPING PLAN
12 M301C SECTIONS/ELEVATIONS
13 M302C SECTIONS/ELEVATIONS
14 M401C ENLARGED HYDRONIC PLANS
15 M501C MECHANICAL SCHEDULES
16 M502C MECHANICAL SCHEDULES
17 M601C DETAILS
18 M701C SEQUENCE OF OPERATION
19 M803C PIPING AND INSTRUMENTATION DIAGRAM (PID)
20 M901C HYDRONIC RISER DIAGRAMS
21 E-001C GENERAL ELECTRICAL NOTES
22 ES-100C CHILLER SITE PLAN
23 ED-100C ELECTRICAL DEMOLITION PLAN - CHILLERS
24 EP-100C ELECTRICAL POWER PLAN - CHILLERS
25 E-100C ELECTRICAL PANEL SCHEDULE
26 E-102C ELECTRICAL RISER DIAGRAMS - CHILLERS
27 E-501C ELECTRIC DETAILS
Associate Director
Safety Officer
Chief of Staff
Information Security Officer
Associate Director of Patient Care Services
Chief, Police Service
Chief, Facilities Management
Infection Prevention Officer
Medical Center Director
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOURFOURFOURFOURFRONTFRONTFRONTFRONT
D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:CONSULTANTS:CONSULTANTS:CONSULTANTS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
575-18-109Restore Facility Cooling Capability
2226.M09
/1
/2
:3
:1
P
M
2/14/2019
COVER
G000C
1JBMK
Grand Junction, CO
CCCCOOOONNNNSSSSTTTTRRRRUUUUCCCCTTTTIIIIOOOONNNN DDDDOOOOCCCCUUUUMMMMEEEENNNNTTTTSSSS
RESTORE FACILITY COOLING CAPABILITY
VA WESTERN COLORADO HEALTH CARE SYSTEM
2121 NORTH AVENUE
GRAND JUNCTION , CO 81501
PROJECT NO. 575-18-109
1" = 100'-0"G000C
1 VA CAMPUS
Albertson Engineering Inc.
3202 W. MAIN, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
605.343.9606
0 50' 100' 200'
SCALE :1" = 100'
T
T T
DN
A A
C C
BB
50' - 6"
58' - 4"
155' - 3"115' - 10"
2"
72"
36"
1"
36"
2"
Generator
Boiler Room
Electrical
Office
Chiller Room
Water Entrance
Occ: #
Room Name
Path of travel (feet)
Egress route (# of occupants)
1-HR separation required
Fire wall
Exit occupancy load
Required egress width (inches)
Actual egress width (inches)
Direction of travel
Room number
Occupant load
Life Safety Plan Legend:
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOURFOURFOURFOURFRONTFRONTFRONTFRONT
D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:CONSULTANTS:CONSULTANTS:CONSULTANTS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
575-18-109Restore Facility Cooling Capability
2226.M09
/1
/2
:3
:3
P
M
2/14/2019
LIFE SAFETY PLAN
G100C
2AuthorJS
Grand Junction, CO
CCCCOOOONNNNSSSSTTTTRRRRUUUUCCCCTTTTIIIIOOOONNNN DDDDOOOOCCCCUUUUMMMMEEEENNNNTTTTSSSS
3/32" = 1'-0"G100C
1 Overall-Life Safety Plan
Occupancy Tabulation Per 2006 IBC Table 1004.12_
R m
N o
N a m e
Room Occupancy A re a
S .F
P e r
P e rs o n
P e rs o n s
Level
1 Chiller Room Accessory Storage Areas, Mechanical Equipment Room 2934 SF 300 10 Level 1
2 Generator Accessory Storage Areas, Mechanical Equipment Room 344 SF 300 2 Level 1
3 Electrical Accessory Storage Areas, Mechanical Equipment Room 252 SF 300 1 Level 1
4 Office Business Areas 105 SF 100 2 Level 1
5 Boiler Room Accessory Storage Areas, Mechanical Equipment Room 2603 SF 300 9 Level 1
6 Water Entrance Accessory Storage Areas, Mechanical Equipment Room 233 SF 300 1 Level 1
Level 1 25
MM/DD/YY
E
NI
G N
ON
A L
G N. O
R E
A
T O
H KAD
E
RP
RR
E
D
G I S
T E
S O
U
R E
T
E
SS IEFO
FRIED
LUCAS G.
13166
Albertson Engineering Inc.
3202 W. MAIN, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
605.343.9606
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOUR FRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of
Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
/1
/2
:3
:0
A
M
AEI #: 2017-449
02/14/2019
STRUCTURAL GENERAL
NOTES
S001
Replace Boiler Plant Chiller Pads
KNRLGF
GRAND JUNCTION, CO
ENGINEER
CONSRUCTION DOCUMENTS
02/14/2019
GENERAL NOTES:
1. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB
SPECIFICATIONS AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND
SITE DRAWINGS. CONSULT THESE DRAWINGS FOR SLEEVES, DEPRESSIONS AND
OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS.
2. ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. ANY
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE VA PROJECT
ENGINEER BEFORE PROCEEDING WITH THE AFFECTED PART OF THE WORK.
3. THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE
BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO
DETERMINE ERECTION PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE
BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION
OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING (AND ACCOMPANYING
FOOTINGS), GUYS OR TIE-DOWNS.
4. ADDITIONAL OBSERVATIONS AS A RESULT OF REJECTION OF WORK COMPLETED
AND/OR ADDITIONAL OBSERVATIONS DUE TO THE DEFICIENCIES IN WORK OBSERVED
WILL BE AT THE EXPENSE OF THE CONTRACTOR.
5. ALL STRUCTURAL SHOP DRAWINGS TO BE REVIEWED BY JOB SUPERINTENDENT IN
ADDITION TO ALL PERSONNEL DEEMED NECESSARY BY CONTRACTOR PRIOR TO
SUBMITTAL TO ENGINEER FOR APPROVAL.
6. ALL SHOP DRAWINGS TO BE REVIEWED BY ENGINEER OF RECORD SHALL HAVE
ELECTRONIC COPIES PROVIDED TO THE ENGINEER OF RECORD FOR REVIEW. AN
ELECTRONIC MARKED SET OF THOSE DRAWINGS WILL BE RETURNED TO THE
CONTRACTOR. NO ADDITIONAL HARD COPIES OF THE SHOP DRAWINGS NEED TO BE
PROVIDED TO THE ENGINEER OF RECORD, ALTHOUGH OTHER PARTIES MAY REQUIRE
HARD COPIES OF THE MARKED UP DRAWINGS. THESE REQUIREMENTS ARE IN
ADDITION TO THE TYPICAL PROJECT SHOP DRAWING SUBMITTAL REQUIREMENTS
STATED IN THE PROJECT SPECIFICATIONS.
7. THE DESIGN OF THE STRUCTURE SHOWN IN THESE CONSTRUCTION DOCUMENTS IS
FOR THE ONE-TIME USE AT THE SPECIFIC SITE REFERENCED IN THE GEOTECHNICAL
REPORT.
DESIGN CODES:
• 2018 INTERNATIONAL BUILDING CODE.
• ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND
COMMENTARY.
• AISC 360-10 SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS.
• H-18-8 SEISMIC DESIGN REQUIREMENTS.
DESIGN LOADS:
THE STRUCTURAL SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED WITH THE
FOLLOWING SUPERIMPOSED LOADINGS:
FLOOR:
LIVE LOAD 100 PSF
MECH. EQUIPMENT 20 PSF
SEISMIC:
RISK CATEGORY II
SEISMIC DESIGN CATEGORY B
SITE CLASSIFICATION D
SEISMIC IMPORTANCE FACTOR 1.0
MAPPED SPECTRAL RESPONSE COEFFICIENTS
Ss = 0.233g S1 = 0.069g
PLUMBING SLEEVES:
MINIMUM SLEEVE SPACING SHALL BE TWO DIAMETERS CENTER TO CENTER TO THE
LARGER SLEEVE OR 6" CLEAR BETWEEN SLEEVES, WHICHEVER IS GREATER. PRIOR TO
CONSTRUCTION SLEEVE LOCATIONS AND SIZES SHALL BE APPROVED BY THE
STRUCTURAL ENGINEER OF RECORD.
CHEMICAL ANCHORS:
SHALL BE A POLYMER INJECTION SYSTEM SUCH AS RAMSET "EPCON", MOLLY
"PARAMOUNT HVC", SIKA "SIKADUR INJECTION SEL", "HILTI-HIGH STRENGTH EPOXY", OR
APPROVED EQUAL, INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS
INSTRUCTIONS. INSTALLERS SHALL BE TRAINED BY THE MANUFACTURER'S
REPRESENTATIVE.
ANCHOR BOLTS:
1. SHALL BE A36 THREADED ROD. PROVIDE HOT DIP GALVANIZE FINISH ON ALL
ANCHOR BOLTS PERMANENTLY EXPOSED TO EXTERIOR OR IN CONTACT WITH
PRESSURE TREATED LUMBER.
2. THREADED ROD EMBEDMENT DEPTH SPECIFIED IN THE DRAWINGS SHALL BE FROM
TOP OF CONCRETE TO TOP OF DOUBLE NUT.
CONCRETE TESTING:
1. CONCRETE TESTING SHALL BE PAID FOR BY THE CONTRACTOR, AND RESULTS GIVEN
TO VA. TESTING LABORATORY SHALL PERFORM THE FOLLOWING TEST ON CAST-IN-
PLACE CONCRETE:
A. ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OF PORTLAND CEMENT
CONCRETE."
B. ASTM C39 - "STANDARD TEST METHOD FOR COMPRESSIVE STRENGTH OF
CYLINDRICAL CONCRETE SPECIMENS. A SEPARATE TEST SHALL BE CONDUCTED
FOR EACH CLASS, FOR EVERY 50 CUBIC YARDS (OR FRACTION THEREOF), PLACED
PER DAY. REQUIRED CYLINDER(S) QUANTITIES AND TEST AGE AS FOLLOWS:
a. AT 7 DAYS
b. AT 28 DAYS
C. PROVIDE ONE ADDITIONAL RESERVE CYLINDER TO BE TESTED UNDER THE
DIRECTION OF THE ENGINEER OF RECORD, IF REQUIRED. IF 28 DAY STRENGTH IS
ACHIEVED, THE ADDITIONAL CYLINDER(S) MAY BE DISCARDED.
PENETRATIONS:
NO PENETRATIONS SHALL BE MADE IN ANY STRUCTURAL MEMBERS OTHER THAN THOSE
LOCATED ON THESE DRAWINGS WITHOUT PREVIOUS APPROVAL OF THE ENGINEER.
CONCRETE MIX DESIGN:
1. SHALL BE MIX DESIGNED BY A RECOGNIZED TESTING LABORATORY TO ACHIEVE A
STRENGTH AT 28 DAYS AS LISTED BELOW WITH A PLASTIC AND WORKABLE MIX:
1. 4,000 PSI - INTERIOR SLABS-ON-GRADE
2. 4,000 PSI - ALL OTHER CONCRETE
2. SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELD CYLINDER OR LAB TESTS FOR
REVIEW PRIOR TO USE. MIX SHALL BE UNIQUELY IDENTIFIED BY MIX NUMBER OR
OTHER POSITIVE IDENTIFICATION. CONCRETE SHALL COMPLY WITH ALL THE
REQUIREMENTS OF ASTM STANDARD C94 FOR MEASURING, MIXING,
TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE TIME STAMPED WHEN
CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM THE TIME THE MIXING
WATER IS ADDED UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED
ONE AND ONE HALF (1-1/2) HOURS. IF FOR ANY REASON THERE IS A LONGER DELAY
THAN STATED ABOVE, THE CONCRETE SHALL BE DISCARDED AT THE
CONTRACTOR'S EXPENSE. IT SHALL BE THE RESPONSIBILITY OF THE TESTING LAB
TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY
NONCOMPLIANCE WITH THE ABOVE. ALL SLABS SHALL BE CURED USING CURING
COMPOUND MEETING ASTM STANDARD C309 TYPE 1 AND SHALL HAVE A FUGITIVE
DYE. THE COMPOUND SHALL BE PLACED AS SOON AS THE FINISHING IS COMPLETED
OR AS SOON AS THE WATER HAS LEFT THE UNFINISHED CONCRETE. ALL SCUFFED
OR BROKEN AREAS IN THE CURING MEMBRANE SHALL BE RECOATED DAILY.
CALCIUM CHLORIDES SHALL NOT BE UTILIZED; OTHER ADMIXTURES MAY BE USED
ONLY WITH THE APPROVAL OF THE ENGINEER.
3. CONCRETE SHALL UTILIZE TYPE I/II CEMENT.
4. COARSE AND FINE AGGREGATES SHALL COMPLY WITH ASTM C33 AND ACI 302.1,
CURRENT VERSIONS.
5. THE CONCRETE STRENGTHS SHOWN IN THE SECTION ABOVE AND IN THE
SPECIFICATIONS ARE MINIMUM COMPRESSIVE STRENGTHS. THE ENGINEER OF
RECORD SHALL DETERMINE IF THE CONCRETE IS ACCEPTABLE, OR TO BE
REMOVED, OR TO RECEIVE SPECIAL CURING IF THE COMPRESSIVE STRENGTHS ARE
LESS THAN SPECIFIED.
6. ALL CONCRETE EXPOSED TO WEATHER OR EARTH SHALL BE AIR ENTRAINED TO 5%
TO 7%.
7. WATER REDUCING AGENTS MAY BE USED IF THE CONCRETE MIX. PLASTICIZERS
AND SUPER-PLASTICIZERS MAY BE USED ONLY WHEN WRITTEN PERMISSION OF THE
ENGINEER IS GIVEN.
8. NO SALTS OF ANY KIND MAY BE USED IN CONCRETE BEFORE OBTAINING THE
ENGINEER'S WRITTEN PERMISSION FOR THEIR USE.
9. AIR CONTENT OF TROWEL FINISHED FLOOR SLABS SHALL NOT EXCEED 3%.
10. MAXIMUM WATER TO CEMENTITIOUS MATERIAL FOR ALL CONCRETE SHALL NOT
EXCEED 0.5 UNLESS NOTED OTHERWISE.
SPECIAL INSPECTION AND TESTING:
1. SEE DETAILED INSPECTION AND TESTING REQUIREMENTS AS INDICATED ON
SHEET S002.
CONCRETE AND REINFORCING PLACEMENT:
1. ALL CONCRETE SHALL BE PLACED IN ACCORDANCE WITH ACI 301 AND ACI 117.
2. ALL REINFORCING STEEL TO BE ASTM A615, GRADE 60 (#4 AND LARGER), EXCEPT
WHERE NOTED OTHERWISE. REINFORCING SHALL NOT BE WELDED.
3. ALL REINFORCING STEEL BARS TO BE DETAILED AND PLACED IN ACCORDANCE
WITH THE LATEST ACI MANUALS.
4. LAP ALL REINFORCING SPLICES IN CONCRETE A MINIMUM OF 48 BAR DIAMETERS
OR 24 INCHES, WHICHEVER IS GREATER, UNLESS NOTED OTHERWISE ON
DRAWINGS (CLASS B SPLICE).
5. WHERE SHOWN ON THE DRAWINGS, PROVIDE WELD PLATES, WELDMENTS, OR
CONCRETE INSERTS FOR FASTENING AND SECURING OTHER COMPONENTS.
CONCRETE INSERTS SHALL BE FURNISHED BY THE CONTRACTOR REQUIRING
THEM AND INSTALLED BY THE CONTRACTOR CASTING THE CONCRETE AROUND
THEM. CLIP ANGLES SHALL BE FURNISHED BY THE CONTRACTOR REQUIRING
THEM.
6. REINFORCING STEEL SHALL RECEIVE CONCRETE COVER AS FOLLOWS:
DESCRIPTION MINIMUM COVER
CAST AGAINST & PERMANENTLY 3"
EXPOSED TO EARTH
EXPOSED TO EARTH OR WEATHER
#6 THROUGH #18 BARS 2"
#5 BARS OR SMALLER 1 1/2"
NOT EXPOSED TO EARTH OR WEATHER
OR IN CONTACT WITH THE GROUND, SLABS
AND WALLS
#11 BARS OR SMALLER 3/4"
#14 AND #18 1 1/2"
BEAMS AND COLUMNS 1 1/2"
SHELLS, FOLDED PLATE MEMBERS:
NO. 6 BAR AND LARGER 3/4"
NO. 5 BAR, W31 OR D31 WIRE AND SMALLER 1/2"
7. PROVIDE TWO (2) #5'S, ONE AT EACH FACE, UNLESS NOTED OTHERWISE, AROUND
ALL OPENINGS GREATER THAN 12"x12" IN CAST-IN-PLACE CONCRETE. EXTEND
REINFORCING 2'-0" BEYOND OPENING IN BOTH DIRECTIONS. CONTACT ENGINEER
OF RECORD FOR ALL OPENINGS GREATER THAN 12"x12" FOR DESIGN.
8. COLD WEATHER AND HOT WEATHER PROVISIONS OF ACI 306 AND 305 (CURRENT
EDITIONS), RESPECTIVELY, SHALL BE MAINTAINED.
9. UNLESS NOTED OTHERWISE ALL UNDER SLAB VAPOR RETARDERS SHALL
CONFORM TO THE REQUIREMENTS OF ASTM 1745 CLASS A AND SHALL BE
INSTALLED AS PER MANUFACTURER'S RECOMMENDATIONS.
AEI #: 2018-318
GENERAL NOTES
FOUNDATIONS:
1. SEE THE FOLLOWING REPORT FOR COMPLETE GEOTECHNICAL RECOMMENDATIONS
AND INSTALLATION PROCEDURES. SITE PREPARATION AND FOUNDATION SHALL
COMPLY WITH THE FOLLOWING:
PREPARED BY: HUDDLESTON-BERRY ENGINEERING & TESTING, LLC
TITLE: GEOTECHNICAL INVESTIGATION
NEW COOLING TOWER
VA HOSPITAL AND MEDICAL CENTER
GRAND JUNCTION, COLORADO
PROJECT # 01878-0001
DATE: JANUARY 10, 2019
TITLE: ALTERNATIVE FOUNDATION RECOMMENDATIONS
NEW COOLING TOWER
VA HOSPITAL AND MEDICAL CENTER
GRAND JUNCTION, COLORADO
PROJECT #01878-0001
DATE: JANUARY 24, 2019
2. GEOTECHNICAL RECOMMENDATIONS WERE PREPARED WITH SPECIFIC KNOWLEDGE
OF THE SPECIFIC BUILDING TYPE, CONSTRUCTION TYPE, AND LIKELY LOADS SHOWN
ON THE CONSTRUCTION DOCUMENTS. DETERMINING THE AMOUNT OF SETTLEMENT
ACCEPTABLE FOR THE BUILDING TYPE IS THE RESPONSIBILITY OF THE
GEOTECHNICAL ENGINEER. ALL STRUCTURAL DESIGNS WERE BASED UPON STAYING
WITHIN THE LIMITS GIVEN WITHIN THE GEOTECHNICAL REPORT FOR THE LOADS
PRESCRIBED BY THE BUILDING CODE REFERENCED IN THE DESIGN CODES SECTION
OF THESE STRUCTURAL NOTES.
3. DESIGNS BASED UPON AN ALLOWABLE BEARING CAPACITY OF 2,000 PSF. SEE
GEOTECHNICAL REPORT FOR AND RECOMMENDATIONS ALL REQUIREMENTS
RELATED TO THE CONSTRUCTION OF THE SLAB AND FOOTING ON GRANULAR
ENGINEERED FILL MATERIAL.
Jay.Bauer Typewritten Text
Jay.Bauer Typewritten Text
IBC 2018 TABLE 1705.3 REQUIRED SPECIAL INSPECTION
AND TEST OF CONCRETE CONSTRUCTION
NO
4. INSPECTION OF ANCHORS POST-INSTALLED IN HARDENED
CONCRETE MEMBERS.
10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.
A. APPLICATION OF PRESTRESSING FORCES.
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND
TECHNIQUES.
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH
TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE
TEMPERATURE OF THE CONCRETE.
7. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER
APPLICATION TECHNIQUES
ACI 318: CH. 26.9
ACI 318: 26.10
ACI 318: 26.5.3-26.5.5
ACI 318: 26.5
ASTM C 172, ASTM C 31,
ACI 318: 26.5, 26.12
ACI 318: 17.8.2.4,
ACI 318: 17.8.2
X
X
X
X
X
X
X
ACI 318: 26.11.2
1908.9
1908.6, 1908.7, 1908.8
1908.10
YES
YES
YES
YES
NO
3. INSPECTION OF ANCHORS CAST IN CONCRETE.
2. REINFORCING BAR WELDING:
1. INSPECTION REINFORCEMENT, INCLUDING PRESTRESSING
TENDONS, AND VERIFY PLACEMENT
TYPE
ACI 318 CH 20, 25.2,
25.3, 26.6.1-26.6.3
REFERENCED
STANDARD
CONTINUOUS
SPECIAL
INSPECTION
PERIODIC
SPECIAL
INSPECTION
X
AWS D1.4,
ACI 318: 26.6.4
IBC REFERENCE
1908.4 YES
YES
NO
REQD ON
PROJECT
X
ACI 318: 17.8.2
5. VERIFYING USE OF REQUIRED DESIGN MIX. ACI 318: CH. 19,
26.4.3, 26.4.4
X
1904.1, 1904.2, 1908.2, 1908.3 YES
12. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS
OF THE CONCRETE MEMBER BEING FORMED.
ACI 318: 26.11.1.2(b)X YES
YES
9. INSPECT OF PRESTRESSED CONCRETE:
B. GROUTING OF BONDED PRESTRESSING TENDONS.
11. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF
TENDONS IN POST-TENSIONED CONCRETE & PRIOR TO REMOVAL OF
SHORES & FORMS FROM BEAMS & STRUCTURAL SLABS.
XA. CERIFFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706.
X
B. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16".
C. INSPECT ALL OTHER WELDS
A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLLY
INCLINED ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS.
B. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4A.
X
X
X
NO
a. WHERE APPLICABLE, SEE SECTION 1705.12, SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE.
b. SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSEUD BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 IN ACI 318, OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL PRIOR TO THE COMMENCEMENT OF THE WORK.
WELDING OR REINFORCING BARS.
SPECIAL INSPECTIONS OF WELDING AND QUALIFICATIONS OF SPECIAL INSPECTORS FOR REINFORCING BARS SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF AWS D1.4 FOR
SPECIAL INSPECTION AND AWS D1.4 FOR SPECIAL INSPECTOR QUALIFICATION.
MATERIAL TESTS.
IN THE ABSENCE OF SUFFICIENT DATA OR DOCUMENTATION PROVIDING EVIDENCE OF CONFORMANCE TO QUALITY STANDARDS FOR MATERIALS IN CHAPTERS 19 AND 20 OF ACI 318, THE BUILDING OFFICIAL SHALL REQUIRE TESTING OF MATERIALS IN ACCORDANCE WITH THE APPROPRIATE SYANDARDS AND CRITERIA FOR THE MATERIAL IN CHAPTERS 19 AND 20 OF ACI 318.
IBC 2018 TABLE 1705.6
REQUIRED VERIFICATION AND INSPECTION OF SOILS
VERIFICATION AND INSPECTION TASKS
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE
TO ACHIEVE THE DESIGN BEARING CAPACITY.
CONTINUOUS SPECIAL
INSPECTION
PERIODICALLY SPECIAL
INSPECTION
X
X
X
X
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE
REACHED PROPER MATERIAL.
3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL
MATERIALS.
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES
DURING PLACEMENT AND COMPACTION OF COMPACTED FILL.
REQUIRED
ON PROJECT
YES
YES
YES
YES
YES
FREQUENCY OF INSPECTION
XPRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND
VARIFY THAT SITE HAS BEEN PREPARED PROPERLY.
SPECIAL INSPECTION AND TESTING:
1. SPECIAL INSPECTION AND MINIMUM TESTING SHALL BE PERFORMED IN ACCORDANCE WITH
2018 IBC AND ALL REFERENCED MATERIALS AND TABLES.
2. INSPECTION SHALL BE PROVIDED BY AN INDEPENDENT TESTING AGENCY HIRED AT THE
CONTRACTOR'S EXPENSE. AGENCY INSPECTION PERSONNEL SHALL MEET THE INSPECTOR
QUALIFICATIONS FOR EACH MATERIAL ITEM AS INDICATED IN THE SPECIFICATIONS.
3. ANY MATERIAL OR PLACEMENT DEVIATIONS FROM MINIMUMS SHOWN ON THE DRAWINGS OR
IN SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER.
4. IN ADDITION TO THE IBC INSPECTION TABLES, THE INSPECTOR SHALL VERIFY THAT ALL STEEL
MAINTAIN ERECTION TOLERANCE OF STRUCTURAL STEEL AND ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL WITHIN AISC'S CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS
AND BRIDGES.
5. IN ADDITION TO THE CONCRETE AND MASONRY IBC INSPECTION TABLES, THE INSPECTOR
SHALL VERIFY THAT ALL CONCRETE AND MASONRY MAINTAIN TOLERANCES SPECIFIED IN ACI
117-90 STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION AND
MATERIALS.
6. TESTING - ANY FAILED FIELD TEST SHALL BE REPORTED TO ALBERTSON ENGINEERING INC
IMMEDIATELY.
MM/DD/YY
E
NI
G N
ON
A L
G N. O
R E
A
T O
H KAD
E
RP
RR
E
D
G I S
T E
S O
U
R E
T
E
SS IEFO
FRIED
LUCAS G.
13166
Albertson Engineering Inc.
3202 W. MAIN, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
605.343.9606
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOUR FRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of
Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
/1
/2
:3
:1
A
M
AEI #: 2017-449
02/14/2019
IBC INSPECTION TABLES
S002
Replace Boiler Plant Chiller Pads
KNRLGF
GRAND JUNCTION, CO
ENGINEER
CONSRUCTION DOCUMENTS
02/14/2019
IBC TESTING SCHEDULE
AEI #: 2018-318
Jay.Bauer Typewritten Text
Jay.Bauer
FOUNDATION & FLOOR SLAB PLAN NOTES
• SEE SHEET S001 FOR STRUCTURAL NOTES.
• VERIFY ALL DIMENSIONS & ELEVATIONS WITH ARCHITECTURAL AND MECHANICAL
DRAWINGS BEFORE CONSTRUCTION COMMENCES.
• ELEVATIONS ON THE STRUCTURAL DRAWINGS REFER TO THE TOP OF
CONCRETE REFERENCE ELEVATION SET AT 100'-0" (MAIN FLOOR) = CIVIL
ELEVATION 4612.75'.
• SLAB ON GRADE CONTROL JOINTS SHALL BE TOOLED OR SAWCUT. THE JOINT
PATTERN SHALL BE APPROXIMATELY SQUARE AND LIMITED TO AN AREA NOT TO
EXCEED 225 S.F. JOINTS SHALL BE CUT WITHIN 8 HRS OF POURING THE SLAB.
• PROVIDE #4x18" DOWELS @ 12" C.C. ALONG ALL SLAB CONSTRUCTION JOINTS.
DOWELS MUST BE DRILLED INTO (E) SLAB W/ 8" EMBED DEPTH (GREASE ONE
END).
• SEE ARCHITECTURAL & MECHANICAL DRAWINGS FOR SLOPES, DROPS, AND
DRAIN LOCATIONS IN FLOOR SLAB.
• SEE SHEET S401 FOR TYPICAL FOUNDATION RELATED DETAILS INCLUDING BUT
NOT LIMITED TO TYPICAL PIPE CROSSING DETAIL, AND TYPICAL EQUIPMENT PAD
DETAILS.
• COORDINATE WITH MECHANICAL DRAWINGS FOR ALL DEDUCT ALTERNATES FOR
VARIOUS PIECES OF MECHANICAL EQUIPMENT AND CORRESPONDING
EQUIPMENT PADS SHOWN ON THIS SHEET.
• ALL EQUIPMENT / HOUSEKEEPING PAD SIZES AND LOCATIONS SHOWN ON THIS
SHEET ARE APPROXIMATE AND SHALL BE USED FOR BIDDING PURPOSES ONLY.
• ALL EQUIPMENT / HOUSEKEEPING PAD SIZES SHALL BE VERIFIED AND FINALIZED
AFTER FINAL EQUIPMENT CUT SHEETS HAVE BEEN APPROVED.
A A
B B
C C
2.2
2.2
62' - 8"
9' - 9" 17' - 4" 14' - 8" 1' - 4" 19' - 7"
DEMO (E) RAISED CONC
PUMP PADS AFTER (E)
PUMPS ARE REMOVED
7'
3' - 5" 3' - 6" 3' - 3" 3' - 6" 1' - 0"
3'-6" x 7'-6" x 6" THICK
MECH EQUIPMENT PAD
8'
8'
4' - 7 1/2" 2' - 0" 13' - 0" 2' - 0"
2'-0" x 8'-0" x 6" THICK
MECH EQUIPMENT PAD
6'
9'
0"
4 1/2" 2' - 8" 11' - 10" 2' - 8"
DEMO (E) RAISED CONC
EQUIPMENT PAD AFTER
(E) CHILLER IS REMOVED
2'-8" x 6'-4" x 6"
THICK MECH
EQUIPMENT PAD
2'-8" x 6'-4" x 6"
THICK MECH
EQUIPMENT PAD
8'
7'
2 1/4"
2' - 0" 13' - 0" 2' - 0"
2'-0" x 8'-0" x 6" THICK
MECH EQUIPMENT PAD
4" 7'
2'
7'
8'
7'
4" 4' - 10"4'-10" x 7'-4" x 6" THICK
MECH EQUIPMENT PAD
3'-6" x 7-6" x 6"
THICK MECH
EQUIPMENT PAD
DEMO (E) SLAB BELOW MECH
PADS. REPLACE W/ NEW 5" CONC
SLAB ON GRADE, REINFORCED
W/ #4 REBAR @ 12" C.C. EA WAY
DEMO (E) SLAB BELOW MECH
PADS. REPLACE W/ NEW 5" CONC
SLAB ON GRADE, REINFORCED
W/ #4 REBAR @ 12" C.C. EA WAY
DEMO (E) RAISED CONC
PUMP PADS AFTER (E)
PUMPS ARE REMOVED
8' - 7 1/2" 3' - 6" 2' - 6 1/2"
(E) CONC SLAB ON
CONC, TYP UNO
(E) EQUIPMENT PAD
TO REMAIN, TYP UNO
(E) CONC FND WALLS & FTGS,
TYP UNO
(E) PILE CAP,
TYP UNO
(E ) P
IP
E 4 x
STRONG
(E ) P
IP
E 4
S
TD (E) PIPE 4 STD
(E ) P
IP
E 5
S
TD
(E ) P
IP
E 5
S
TD
(E ) P
IP
E 4
S
TD
(E) CMU WALL
MM/DD/YY
E
NI
G N
ON
A L
G N. O
R E
A
T O
H KAD
E
RP
RR
E
D
G I S
T E
S O
U
R E
T
E
SS IEFO
FRIED
LUCAS G.
13166
Albertson Engineering Inc.
3202 W. MAIN, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
605.343.9606
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOUR FRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of
Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
/1
/2
:3
:1
A
M
AEI #: 2017-449
02/14/2019
FOUNDATION PLAN
S101
Replace Boiler Plant Chiller Pads
KNRLGF
GRAND JUNCTION, CO
ENGINEER
CONSRUCTION DOCUMENTS
02/14/2019
SCALE: 1/4" = 1'-0"S101
1 FOUNDATION & FLOOR SLAB PLAN
STRUCTURAL SHEET NOTES
PROJECT
NORTH
TRUE
NORTH
AEI #: 2018-318
Jay.Bauer Typewritten Text
Jay.Bauer
6" CONC SLAB, REINF W/
#4 REBAR @ 18" C.C. EACH
WAY CENTERED IN THE SLAB
TYP UNO
EDGE OF EQUIPMENT
EXISTING CONC SLAB ON GRADE REFER TO EQUIP SHOP
DWGS FOR SIZE, LOCATION
& PROJECTION OF EQUIP
ANCHOR BOLTS
NOTE:
SEE MECH & ELECT DWGS
FOR PADS REQUIRED
FLOORS SHALL BE ROUGHENED
BELOW THE NEW PAD AREA.
EXISTING CONC
SLAB ON GRADE
NEW 5" CONC SLAB ON GRADE,
SEE PLAN & NOTES
1/2" ISOLATION JOINT & CAULK
#4x18" REBAR DOWEL @ 12"
C.C. DRILL INTO (E) SLAB (8"
MIN EMBED) GREASE ONE END
GRANULAR SUB-BASE MATERIAL
AS APPROVED BY
GEOTECHNICAL ENGINEER
PREPARE SLAB SUBGRADE AS
PER GEOTECHNICAL
ENGINEER'S RECOMMENDATION
FV
TO FTG
EXISTING CONT CONC FTG
(FIELD VERIFY)
COMPACTED SUBGRADE
FLOWABLE CONC FILL
WIDTH TO BE EQUAL TO
FTG WIDTH PLUS 2x THE
PIPE BURY DEPTH
BELOW SLAB PIPE
SEE MECH DWGS
ACTUALLY FURNISHED
PAD SIZE TO BE BASE ON EQUIPMENT
#4 REBAR @ 12" C.C.
EA WAY T&B
EDGE OF EQUIPMENT
ALL SIDES
6" MIN
C
LR3"SLAB ON GRADE OR
FINISHED GRADE
REFER TO EQUIP SHOP
DWGS FOR SIZE, LOCATION
& PROJECTION OF EQUIP
ANCHOR BOLTS
1'
2" C
LR
2" CLR
MM/DD/YY
E
NI
G N
ON
A L
G N. O
R E
A
T O
H KAD
E
RP
RR
E
D
G I S
T E
S O
U
R E
T
E
SS IEFO
FRIED
LUCAS G.
13166
Albertson Engineering Inc.
3202 W. MAIN, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
605.343.9606
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOUR FRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of
Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
/1
/2
:3
:1
A
M
AEI #: 2017-449
02/14/2019
STANDARD DETAILS
S401
Replace Boiler Plant Chiller Pads
KNRLGF
GRAND JUNCTION, CO
ENGINEER
CONSRUCTION DOCUMENTS
02/14/2019
SCALE: 3/4" = 1'-0"S401
B1 TYP EQUIP PAD - INTERIOR
SCALE: 3/4" = 1'-0"S401
B4 TYP SLAB REPLACEMENT DETAIL
AEI #: 2018-318
SCALE: 3/4" = 1'-0"S401
B6 TYP PIPE BLW FTG
AEI #: 2018-318
SCALE: 3/4" = 1'-0"S401
B8 TYP EQUIP PAD - ON GRADE
Jay.Bauer Typewritten Text
Jay.Bauer
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN
THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT
BE USED IN THIS SET OF DRAWINGS.
CWS
CA
CD
CDR-H
CR
CS
CW
HW
HW-R
HWR
HWS
G
PD
V
SS
STM-HP
SD
OSD
(E)
CWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
COMPRESSED AIR
CONDENSATE DRAINAGE
CONDENSATE RETURN - HP
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
DOMESTIC COLD WATER
HOT WATER
HOT WATER RECIRCULATION
HEATING WATER RETURN
HEATING WATER SUPPLY
NATURAL GAS
PUMP DISCHARGE
SANITARY VENT
SANITARY SEWER
HIGH PRESSURE STEAM
STORM DRAINAGE
OVERFLOW STORM DRAINAGE
2"
CAP
PLUG
2"
4"
4" 4"
PLUMBING AND PIPING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
EXISTING PIPE TAG
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
PIPING BEING DEMOLISHED
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
PIPE RISE
PIPE DROP
PIPE TEE REDUCING 45
DEGREE TEE
45 DEGREE TEE
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
PG PROPANE GAS
INVERT: -10' - 1"
1/8" / 12" SLOPE
ABBREVIATIONS
AC AIR CONDITIONING UNIT
ACC AIR COOLED CONDENSER
ACCU AIR COOLING CONDENSING UNIT
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CH CHILLER
CT COOLING TOWER
CUH CABINET UNIT HEATER
CWP CONDENSER WATER PUMP
CHWP CHILLED WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DC DUCT MOUNTED COIL
DCP DOMESTIC WATER CIRCULATING PUMP
EF EXHAUST FAN
EDC ELECTRIC DUCT COIL
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
FCU FAN COIL UNIT
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF VENTILATOR
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
HRU HEAT RECOVERY UNIT
PRV POWER ROOF VENTILATOR
RE RETURN/EXHAUST FAN
RTU ROOFTOP UNIT
SEP SEWAGE EJECTOR PUMP
SF SUPPLY FAN
SP SUMP PUMP
UH UNIT HEATER
WH WATER HEATER
EQUIPMENT ABBREVIATIONS
PIPE ACCESSORY TAGS
DOMESTIC WATER METER
CHECK VALVE
PRESSURE REDUCING VALVE
23-30
POINT WHERE DEMO DISCONNECTS FROM EXISTING
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BHP BRAKE HORSE POWER
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CO CONTRACTING OFFICER
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FL FLOOR
FLA FULL LOAD AMPS
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
H2O WATER
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
KW KILOWATT
LBS POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MOPD MAXIMUM OVERCURRENT
PROTECTION DEVICE
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RLA RUNNING LOAD AMPERES
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
GENERAL HYDRONIC SYMBOLS
Room
MEDIUM PRESSURE STEAM
CONDENSATE RETURN - MP
STM-MP
CDR-M
DEDUCT ALTERNATE BORDER
THIS PROJECT IS NOT INTENDED TO BE PHASED. HOWEVER, THERE IS A DEFINED AND
ANTICIPATED SEQUENCE OF WORK. THIS IS GENERAL INFORMATION ABOUT THE PROJECT
AND AN ATTEMPT TO CLEARLY DEFINE THE SEQUENCE OF WORK DURING CONSTRUCTION.
THE SUCCESSFUL CONTRACTOR SHALL ULTIMATELY VERIFY EXISTING CONDITIONS AND
COORDINATE CLOSELY WITH THE COR TO SCHEDULE AND CONDUCT ALL CONSTRUCTION FOR
THIS PROJECT.
THE ANTICIPATED SEQUENCE IS AS FOLLOWS:
1. ALL SUBMITTALS SHALL BE APPROVED BEFORE MOBILIZATION OR CONSTRUCTION
CAN BEGIN.
2. ELECTRICAL CONTRACTOR PREPARE EXISTING 1,600 AMPERE DISTRIBUTION PANEL
FOR TIE-IN TO NEW 500 TON RENTAL CHILLER AND CORRESPONDING PUMP PACKAGE
AT AND INSIDE BUILDING 9. SEE ELECTRICAL PLANS FOR DETAILS. THIS SCOPE OF
WORK IS REMOVED FROM THE PROJECT AS A PART OF DEDUCT ALTERNATE # 1.
3. ELECTRICAL CONTRACTOR TO PREPARE OTHER 2 REMOTE CHILLER AND
CORRESPONDING PUMP PACKAGE LOCATIONS FOR NEW 120 TON RENTAL CHILLERS
TO BE INSTALLED AT EACH LOCATION. EACH LOCATION IS EQUIPPED WITH AN
EXISTING 200 AMP PANEL FOR SERVING THE RENTAL CHILLER. THIS SCOPE OF
WORK IS REMOVED FROM THE PROJECT AS A PART OF DEDUCT ALTERNATE # 1.
4. MECHANICAL OR GENERAL CONTRACTOR TO PROVIDE A 500 TON RENTAL CHILLER
WITH CORRESPONDING PUMP SKID. ENTIRE SYSTEM SHALL BE HOUSED ON A SEMI
TRACTOR TRAILER THROUGHOUT CONSTRUCTION AND ACCORDING TO THE SITE
PLANS. SEE CIVIL, MECHANICAL, AND ELECTRICAL PLANS FOR DETAILS. THIS SCOPE
OF WORK IS REMOVED FROM THE PROJECT AS A PART OF DEDUCT ALTERNATE # 1.
THIS CHILLER IS ONLY NEEDED IF CONSTRUCTION EXTENDS TO APRIL 15 OR
BEYOND.
5. MECHANICAL OR GENERAL CONTRACTOR TO PROVIDE (2) 120 TON RENTAL CHILLERS
WITH CORRESPONDING PUMP SKIDS AT THE OTHER REMOTE LOCATIONS. SEE
MECHANICAL SITE PLANS FOR DETAILS. THIS SCOPE OF WORK IS REMOVED FROM
THE PROJECT AS A PART OF DEDUCT ALTERNATE # 1.
6. SITE UTILITY CONTRACTOR SHALL BEGIN EXCAVATION WORK WHERE THE 8 INCH
CHILLED WATER SUPPLY AND RETURN MAINS TIE TO THE CAMPUS 12 INCH MAINS AT
APPROXIMATELY 30 FEET FROM THE EAST EXTERIOR WALL OF BUILDING 9.
7. MECHANICAL CONTRACTOR TO DISCONNECT 8 INCH CHILLED WATER SUPPLY AND
RETURN PIPING FROM 12 INCH PIPING APPROXIMATELY 30 FEET FROM BUILDING 9
EAST EXTERIOR WALL AND AFTER HOURS OR DURING AN OFF PEAK COOLING
DEMAND PERIOD. THIS WORK IS NOT PART OF DEDUCT #1. M.C. TO PROVIDE AND
CONNECT TEMPORARY CHILLED WATER PIPING FROM THE 500 TON RENTAL CHILLER
TO THE 12 INCH SUPPLY AND RETURN MAINS. M.C. SHALL ALSO CONNECT THE
OTHER (2) 120 TON CHILLERS TO THE CHILLED WATER SUPPLY AND RETURN PIPING
LOOPS AS REQUIRED. COORDINATE WITH COR FOR EXACT SCHEDULING AND TIE-IN
REQUIREMENTS. SEE MECHANICAL AND SITE PLANS FOR DETAILS. AT THE SAME
TIME THE ELECTRICAL CONTRACTOR SHALL DISCONNECT PLANT LOADS FROM THE
EXISTING 1,600 AMPERE DISTRIBUTION PANEL AND CONNECT TO THE NEW 500 TON
RENTAL CHILLER AND CORRESPONDING PUMP PACKAGE AFTER HOURS OR DURING
AN OFF PEAK COOLING DEMAND PERIOD. THIS IS ONLY REQUIRED IF WORK HAS NOT
BEEN COMPLETED BY APRIL 15. COORDINATE WITH COR FOR EXACT SCHEDULING
AND TIE-IN REQUIREMENTS. SEE ELECTRICAL PLANS FOR DETAILS. THIS SCOPE OF
WORK IS REMOVED FROM THE PROJECT AS A PART OF DEDUCT ALTERNATE # 1.
8. ALL DISCIPLINES SHALL COORDINATE WITH EACH OTHER AND WITH THE COR FOR
STARTUP AND COMMISSIONING OF ALL NEW RENTAL CHILLERS AND PUMP SYSTEM.
COORDINATE ON SCHEDULE AND VERIFY FULL LOAD CAPACITY AND OPERATION
BEFORE FINAL SHUT DOWN OF EXISTING CHILLER PLANT. THIS SCOPE OF WORK IS
REMOVED FROM THE PROJECT AS A PART OF DEDUCT ALTERNATE # 1.
9. SHUT DOWN THE CHILLER PLANT FOR CONSTRUCTION. ONLY AFTER THE
TEMPORARY COOLING SYSTEM IS COMPLETELY OPERATIONAL AND MAXIMUM
CAPACITY IS VERIFIED CAN THE CHILLER PLANT BE SHUT DOWN FOR
CONSTRUCTION.
10. THE RENTAL CHILLERS SHALL BE SHUT DOWN AND DISCONNECTED ONLY AFTER ALL
WORK HAS BEEN COMPLETED TO REPLACE THE CHILLERS, ACCESSORIES, AND ALL
CHILLED WATER PIPING SYSTEMS WITHIN THE PLANT. THIS WORK SHALL BE DONE
AFTER HOURS. THE ENTIRE CHILLED WATER PLANT SHALL BE COMMISSIONED AND
FULL CAPACITY SHALL BE VERIFIED BEFORE ANY RENTAL CHILLER SYSTEMS ARE
REMOVED FROM THE SITE.
SCOPE AND SEQUENCE OF WORK SUMMARY
DEDUCT ALTERNATE # 1 – NEW 500 TON AIR COOLED RENTAL CHILLER AND CORRESPONDING
PUMP SKID AS WELL AS (2) 120 TON AIR COOLED RENTAL CHILLERS, ALL ASSOCIATED PIPING, COOROSP[ONDING PUMP PACKAGES, AND ALL ACCESSORIES SHALL BE REMOVED FROM
PROJECT SCOPE. 500 TON CHILLER TO BE USED ONLY IF THE CONSTRUCTION PERIOD
EXTENDS PAST MAY 1. IF USED, HAVE THE CHILLER ON SITE BY APRIL 15. ELECTRICAL
PORION IS NOT PART OF THIS DEDUCT.
DEDUCT ALTERNATE # 2 – NEW CHILLER 9-CCU-2, ALL ASSOCIATED PIPING, AND ALL
ACCESSORIES SHALL BE REMOVED FROM THE PROJECT SCOPE.
DEDUCT ALTERNATE # 3 – NEW PLATE AND FRAME HEAT EXCHANGER 9-HX-1, ALL ASSOCIATED
PIPING, AND ALL ACCESSORIES SHALL BE REMOVED FROM THE PROJECT SCOPE.
DEDUCT ALTERNATE # 4 – NEW FILTRATION SKID FS-2, ALL ASSOCIATED PIPING, AND ALL
ACCESSORIES SHALL BE REMOVED FROM THE PROJECT SCOPE.
DEDUCT ALTERNATE # 5 – 10 YEAR PARTS AND LABOR WARRANTY FOR ALL EQUIPMENT SHALL
BE REMOVED FROM THE PROJECT SCOPE.
DEDUCT ALTERNATE # 6 – NEW PRIMARY PUMP 9-P-2, ALL ASSOCIATED PIPING, AND ALL
ACCESSORIES SHALL BE REMOVED FROM THE PROJECT SCOPE.
DEDUCT ALTERNATE # 7 – NEW SECONDARY PUMP 9-P-8, ALL ASSOCIATED PIPING, AND ALL
ACCESSORIES SHALL BE REMOVED FROM THE PROJECT SCOPE.
DEDUCT ALTERNATE SUMMARY
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE REQUIREMENTS OF THE
INTERNATIONAL BUILDING CODE (IBC), INTERNATIONAL MECHANICAL CODE (IMC),
INTERNATIONAL PLUMBING CODE (IPC), INTERNATIONAL FUEL GAS CODE (IFGC), NFPA 101
LIFE SAFETY CODE, AND ANY AUTHORITY HAVING JURISDICTION. THIS IS A FEDERAL
PROJECT. AS SUCH ALL CODE REQUIREMENTS ARE REQUIRED AND ENFORCED BY THE
UNITED STATES DEPARTMENT OF VETERANS AFFAIRS.
2. ALL EQUIPMENT, MATERIALS, AND ARTICLES INCORPORATED IN THE WORK SHALL BE NEW
AND OF COMPARABLE QUALITY AS SPECIFIED. ALL WORKMANSHIP SHALL BE FIRST-CLASS
AND SHALL BE PERFORMED BY MECHANICS SKILLED AND REGULARLY EMPLOYED IN THEIR
RESPECTIVE TRADES.
3. ALL WORK SHALL BE COORDINATED WITH ALL AFFECTED TRADES PRIOR TO STARTING
WORK. REWORK REQUIRED DUE TO COORDINATION ISSUES SHALL BE DONE BY THE
INSTALLATION CONTRACTOR WITHOUT INCREASED COST TO THE OWNER.
4. THESE DRAWINGS ARE GENERAL IN NATURE. ALTHOUGH EVERY ATTEMPT HAS BEEN
MADE TO INDICATE THE EXACT ROUTING AND LOCATION OF PROPOSED SYSTEMS, NOT
ALL OFFSETS, REQUIRED FITTINGS AND/OR CONDITIONS CAN BE SHOWN. THE
CONTRACTOR SHALL COORDINATE WORK AND MAKE REQUIRED CHANGES TO THE
ROUTING IN ORDER TO AVOID CONFLICTS WITHOUT ANY INCREASED COST TO THE
OWNER.
5. SYSTEMS DESIGNATED TO BE PROVIDED AND INSTALLED WITHIN THESE CONTRACT
DOCUMENTS ARE INTENDED TO BE COMPLETE AND OPERATIONAL. PROVIDE EVERYTHING
ESSENTIAL FOR THE COMPLETION OF THE WORK TO MAKE THE SYSTEM READY FOR
NORMAL AND PROPER OPERATION, INCLUDING ALL WORK OR MATERIALS NOT DIRECTLY
SHOWN ON THE DRAWINGS OR IN THE SPECIFICATIONS, BUT NECESSARY FOR THE
PROPER OPERATION OF THE SYSTEM.
6. HVAC CONTRACTOR IS RESPONSIBLE FOR ENSURING PROPER MAINTENANCE
CLEARANCES ARE MAINTAINED. COORDINATE CLOSELY WITH ALL TRADES.
7. ALL EXPOSED PIPING WITHIN THE CHILLER PLANT EXTENDING 6 FEET AFF OR BELOW,
WHERE SUBJECT TO ABRASION OR INCIDENTAL PEDESTRIAN CONTACT SHALL BE
INSULATED WITH ALUMINUM PROTECTIVE JACKET.
8. ALL NEW CHILLED WATER PIPING IS INTENDED TO BE INSULATED, THREADED SCHEDULE 40
BLACK IRON FOR SIZES 2 INCH AND SMALLER. ALL NEW CHILLED WATER PIPING LARGER
THAN 2 INCH IS INTENDED TO BE INSULATED, WELDED SCHEDULE 40 BLACK IRON. SEE
SPECIFICATIONS FOR MATERIALS AND METHODS. PROVIDE MANUAL AIR VENTS AT ALL
HIGH POINTS OF NEW CHILLED WATER PIPING.
9. REFER TO THE PIPING AND INSTRUMENTATION DIAGRAM SHEET M803C OR HYDRONIC
RISER DIAGRAMS SHEET M901C FOR PIPE SIZES NOT SHOWN ON TOP VIEW FLOOR PLANS.
10. ALL NEW STEAM PIPING SHALL BE INSTALLED ACCORDING TO THE ASME 31.1 POWER
PIPING CODE AND THE ASME BOILER AND PRESSURE VESSEL CODE. ALL NEW HIGH
PRESSURE STEAM PIPING IS INTENDED TO BE INSULATED, SCHEDULE 40, BLACK STEEL.
CONDENSATE RETURN PIPING IS INTENDED TO BE INSULATED, SCHEDULE 80, BLACK
STEEL. SEE SPECIFICATIONS FOR MATERIALS AND METHODS.
11. ALL STEAM PIPING SHALL PITCH A MINIMUM 1/2 INCH PER 50 FEET OF PIPE IN THE
DIRECTION OF FLOW. PROVIDE MAIN DRIPS AT ALL HIGH POINT OF PIPING RUNS WITH
MANUAL AIR VENT AND TRAPS PIPED TO NEAREST CONDENSATE RETURN POINTS. VERIFY
ELEVATIONS AND ROUTING PRIOR TO STARTING WORK.
12. ALL STEAM TRAPS SHALL BE FLOAT AND THERMOSTATIC TYPE 9F&T) AND SHALL BE
SELECTED FOR THE FULL CONDENSATE LOAD OF THE ABSORPTION CHILLER. ALL DRIP
LINES AHEAD OF CONTROL VALVES AND MAIN DRIPS AT LOW POINTS SHALL BE 3/4" F&T
TRAPS. WHERE LIFTING CONDENSATE AT DROPS, PROVIDE CHECK VALVE WITH UNION
AND GATE VALVE UP STREAM OF THE CHECK VALVE.
13. IF TEMPORARY CHILLER MALFUNCTIONS: TECHNICIAN IS TO RESPOND WITHIN 1 HOUR. IF
THE TEMPORARY CHILLER IS NOT FULLY FUNCTIONAL WITHIN 2 HOURS, A REPLACEMENT
MUST BE DISPATCHED. THERE MUST BE AN AVAILABLE BACKUP CHILLER AT ALL TIMES
WITHIN 4 HOUR DRIVING DISTANCE.
MECHANICAL GENERAL NOTES
A
DP
FLANGES OR UNION
PRESSURE GAUGE
TEMPERATURE GAUGE
TEMPERATURE SENSOR
DIFFERENTIAL PRESSURE
SENSOR
PRESSURE SENSOR
2 POSITION CONTROL VALVE
2-WAY MODULATING
CONTROL VALVE
3-WAY MODULATING
CONTROL VALVE
MANUAL BUTTERFLY VALVE
STRAINER WITH BALL VALVE
AND DRAIN
BALL VALVE
BALANCING VALVE
SUCTION DIFFUSER
TRIPLE DUTY VALVE
FLEXIBLE CONNECTION
Ts
Ps
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOURFOURFOURFOURFRONTFRONTFRONTFRONT
D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:CONSULTANTS:CONSULTANTS:CONSULTANTS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
575-18-109Restore Facility Cooling Capability
2226.M09
/1
/2
:3
:3
P
M
2/14/2019
MECHANICAL REFERENCE
SHEET
M000C
7JBMK
Grand Junction, CO
CCCCOOOONNNNSSSSTTTTRRRRUUUUCCCCTTTTIIIIOOOONNNN DDDDOOOOCCCCUUUUMMMMEEEENNNNTTTTSSSS
PROJECT GENERAL NOTES
1 REMOVE ALL UNUSED PIPING, DUCTWORK AND ACCESSORIES. VA TO GET CREDIT FOR ALL
SALVAGED EQUIPMENT, PIPE, AND ACCESSORIES. CONTRACTOR TO REMOVE ALL SALVAGED
AND DEMOLISHED MATERIALS.
2 THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING, PRIOR TO
FINAL BID, ALL EXISTING CONDITIONS FOR PLUMBING AND MECHANICAL SYSTEMS WITHIN
SPACE AND WITHIN CLOSE PROXIMITY OF SPACE.
3 THE MECHANICAL CONTRACTOR SHALL PERFORM SERVICE AND REPAIR ON THE EXISTING
EQUIPMENT AND ITS ACCESSORIES AS FOLLOWS: CLEAN ALL COILS, REPLACE THE FILTERS
AND BELTS, INSPECT, REPAIR, OR REPLACE THE ECONOMIZERS, DRIVES AND FAN BEARINGS,
MOTORS, CONTROL COMPONENTS, VALVES AND ANY OTHER ITEM NECESSARY FOR A
COMPLETE AND PROPER OPERATING SYSTEM. THIS CONTRACTOR SHALL ALSO VISIT THE SITE,
PRIOR TO FINAL BIDDING, AND VERIFY ALL EXISTING SITE CONDITIONS. PROVIDE ALL MATERIAL
AND COMPONENTS AS NEEDED TO BRING THE UNITS TO FULL COMPLIANCE OF THE
GOVERNMENT'S CRITERIA AND AUTHORITY HAVING JURISDICTION.
4 WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF CONSTRUCTION, PREVENT
CONSTRUCTION DEBRIS FROM ENTERING DRAIN BODY BY SEALING DRAIN OPENING PRIOR TO
START OF WORK.
5 COORDINATE INSTALLATION OF PIPING, DUCTWORK, CONDUIT, LIGHTS, CABLE TRAY,
STRUCTURE, AND EQUIPMENT TO PREVENT CONFLICTS.
6 THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE CONDITIONS BOTH EXISTING AND THOSE
ILLUSTRATED BY THESE DOCUMENTS AS WELL AS THOSE WHICH CAN BE REASONABLY
ANTICIPATED INCLUDING, BUT NOT LIMITED TO ARCHITECTURAL, ELECTRICAL, VENTILATION, AND OTHER SYSTEMS INVOLVED ON THIS PROJECT.
7 FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING SYSTEM, AND SHALL CONFORM TO
ALL REQUIREMENTS OF APPLICABLE FEDERAL, STATE, AND LOCAL CODES, INCLUDING BUT NOT
LIMITED TO THE INTERNATIONAL BUILDING CODE AND INTERNATIONAL MECHANICAL CODE.
8 LOCATE EQUIPMENT REQUIRING ACCESS 2'-0" MAXIMUM ABOVE CEILING.
9 ALL ROOF MOUNTED EQUIPMENT SHALL BE A MINIMUM 10'-0" FROM EDGE OF ROOF.
10 LOCATE DUCTWORK, PIPING AND MECHANICAL EQUIPMENT AWAY FROM THE SPACE ABOVE
ELECTRICAL PANELS. TRANSFORMERS AND OTHER ELECTRICAL EQUIPMENT.
11 FIRE SEAL AROUND DUCT AND PIPING PENETRATIONS OF FIRE RATED WALLS. REFER TO
SPECIFICATION.
12 PROVIDE SLEEVES AND/OR OPENINGS TO RUN PIPES AND DUCTS THROUGH FOUNDATIONS,
FLOORS, WALLS, AND ROOF.
13 ADJUST PIPING AND DUCTWORK SIZES TO PROPERLY CONNECT TO MECHANICAL EQUIPMENT.
14 PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL ANOTHER SIZE IS
SHOWN.
15 FOR DETAILS, EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT SHOWN ON THE SEGMENTS,
REFER TO DETAILS, SCHEDULES, AND SPECIFICATIONS.
16 INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE RESPECTIVE MANUFACTURER'S WRITTEN
INSTALLATION INSTRUCTIONS, AT A LEVEL OF QUALITY AND WORKMANSHIP CONSISTENT WITH
THE SPECIFICATIONS.
17 LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT AS INDICATED ON THE DRAWING, ARE
APPROXIMATE AND SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. WORK SHALL BE
COORDINATED WITH ALL OTHER TRADES TO AVOID INTERFERENCE IN THE FIELD.
18 INSTALL EXPOSED PIPING AND DUCTWORK AS HIGH AS PRACTICAL IN ROOMS WITHOUT
CEILINGS.
CHILLER MECHANICAL SHEET INDEX
G000C COVER
G100C LIFE SAFETY PLAN
M000C MECHANICAL REFERENCE SHEET
MD101C SITE MECHANICAL DEMOLITION PLAN
MD102C MECHANICAL DEMOLITION PLAN
M101C SITE MECHANICAL PIPING PLAN
M102C HYDRONIC PIPING PLAN
M301C SECTIONS/ELEVATIONS
M302C SECTIONS/ELEVATIONS
M401C ENLARGED HYDRONIC PLANS
M501C MECHANICAL SCHEDULES
M502C MECHANICAL SCHEDULES
M601C DETAILS
M701C SEQUENCE OF OPERATION
M803C PIPING AND INSTRUMENTATION DIAGRAM (PID)
M901C HYDRONIC RISER DIAGRAMS
p
D co co
D
Y
H co co
D
D
D
D
D
D
D
S
S
S
S
D
S
D
D
D
D
D
D D
D
SS
Sewer
Sewer
Drain
Sewer Sewer
Drain
Sewer
Sewer
Sewer
Steam
Steam
Drain
Drain
Sewer
Signal
Steam
Sewer Signal
Sewer
Electric
Electric
Sewer
Electric
Storm
Electric
Chilled Water
Drain
Water
Sewer
Sewer
Sewer
Sewer
Sewer
Electric
Sewer
Signal
STOP
STOP
STOP
STOP
ONLY
V−101
V−105
V−106
V−107
V−113
V−112 V−115
V−118
V−129
V−139
V−138
V−135
V−124
V−136
V−102
V−103 V−109
V−125 V−126
V−127
V−134 V−119
V−128V−133
V−131
V−116
V−111
V−117
V−121
V−122
1 CORNER
SMOKE STACK
TRANSFORMER
G E
N E
R A
T O
R E
N C
L O
S U
R E
G E
N E
R A
T O
R
GENERATOR TRANSFORMER
TRANSFORMER
SPOT LIGHTS
WATER RISER
2IN COPPER
WATER RISER
3INCH COPPER
LIGHTED SIGN
LIGHTED SIGN
TELEPHONE VAULT
O2
ENCLOSURE
VAULT
VAULT
WATER
TOWER
CREDIT UNION
CARPORT
CARPORT
SHED
SMOKE
SHACK
PARKING
GARAGE
CARPORT
DN
T
T
SD
SD
SD
FM
FM
BUILDING 9
G
W W
W
W
STM
SAN
W
G
W
STM
SAN
FENCE
XFMR
G
W
W W
SA
N
STM
W
W
E
FO
E
HPS
MD101C
23-6523-65
23-66
(E) 12" CWS
(E) 12" CWR
(E) 8" CWR
(E) 8" CWS
REMOVE SECTION OF EXISTING PIPES AND
PREPARE FOR CONNECTION OF NEW 12"
CHILLED WATER PIPES FROM BUILDING TO
EXISTING 12" CHILLED WATER PIPES.
EXISTING 8" CHILLED WATER PIPE TO BE
CAPPED AND ABANDONED IN PLACE.
VERIFY IN FIELD ACTUAL LOCATION OF
8" TO 12" PIPE TRANSITIONS.
23-65
23-65
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOURFOURFOURFOURFRONTFRONTFRONTFRONT
D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:CONSULTANTS:CONSULTANTS:CONSULTANTS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
575-18-109Restore Facility Cooling Capability
2226.M09
/1
/2
:3
:4
P
M
2/14/2019
SITE MECHANICAL
DEMOLITION PLAN
MD101C
8JBMK
Grand Junction, CO
CCCCOOOONNNNSSSSTTTTRRRRUUUUCCCCTTTTIIIIOOOONNNN DDDDOOOOCCCCUUUUMMMMEEEENNNNTTTTSSSS
0 25' 50' 100'
SCALE :1" = 50'
1/4" = 1'-0"MD101C
2 PIPE DEMOLITION DETAIL
TRUE
NORTH
0 2' 4' 8'
SCALE :1/4" = 1'-0"
KEYNOTES
23-65 CAP AND ABANDON EXISTING 8 INCH CHILLED WATER SUPPLY AND RETURN PIPING BELOW GRADE. FIELD
VERIFY EXACT LOCATION OF 8 TO 12 INCH CHILLED WATER TRANSITION.
23-66 VA TO GET CREDIT FOR SCRAP OF EXISTING CHILLERS, PIPING, AND ANY OTHER METALS. CONTRACTOR TO
HANDLE REMOVAL OF ALL MATERIALS.
DN
SD
SD
SD
F M
A A
C C
BB
23-10 23-10 23-10
23-1023-10
23-1023-1023-10
23-51
23-55
23-53
23-53
23-52
23-5423-5423-54
23-5423-5423-54 DEDUCT
ALTERNATE #3
DEDUCT
ALTERNATE #2
(E) 6"
(E) 5"
(E) 8"(E) 8"
(E) 10"
(E) 8"
(E) 6"(E) 6"
(E) 6"
(E) 8"
(E) 6"(E) 6"
(E) 1" STM-MP
(E) 1" CDR-M(E) 2 1/2"
(E) 1 1/4"
(E) 12" CR
(E) 14" CS
(E) 12" CS
(E) 12" CR
23-6523-65
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOURFOURFOURFOURFRONTFRONTFRONTFRONT
D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:CONSULTANTS:CONSULTANTS:CONSULTANTS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C