36C25919R0092-002.pdf
PDF 26 MB Posted
- Attached to
- (CON) Restore Cooling Capability - 575 Federal contract opportunity
- Solicitation number
- 36C25919R0092
About this file
36C25919R0092 S02 575-16-104 Replace Cooling Towers Combined Sheets.pdf
View the file
Other files for this federal contract opportunity
Show all 37
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bldg # Function 18 Carport: Government Vehicles
20 Community Living Center
22 Warehouse
32 Designated Smoking Area
34 Information Tech Services
35 Recreation Therapy
36 Administrative Services
37 Pain Management &
Winter Sports Clinic
41 Patient Smoking Shelter
44 Parking Garage
45 Physical Medicine, Rehabilitation and Prosthetics
A Quality Management
B Surgeons
P:A Parking: Patients & Visitors
P:B Parking: Staff
G O
V E
R N
M E
N T
V E
H
IC
L E
P A
R K
IN
G
P R
O V
ID
E
R P
A R
K
IN
G U
P P
E R
L E
V E
L
45 P:A
P:A
P:B
P:B
P:B
Bldg # Function 1 Hospital
5 Administration
Human Resources
PIV
Home Base Patient Care
Credit Union
6 Education & Training
Computer Labs
Video Conferencing
Quality Management
7 Warehouse
8 Administrative
Engineering
9 Boiler/Chiller Plant
12 Engineering Office/Shops
13 Laundry
14 Incinerator
Property Line
North Avenue d S tre e t gas elect
B
A
N O
R
TH
PROJECT LOCATION
INDEX
1 G000T COVER
2 G100T LIFE SAFETY PLAN
3 CD101 DEMOLITION PLAN
4 CS101 SITE PLAN
5 C-500 DETAILS
6 A101T LADDER/PLATFORM PLANS/SECTIONS
7 A601T ROOF CURB LADDER/PLATFORM DETAILS
8 S001 STRUCTURAL GENERAL NOTES
9 S002 IBC INSPECTION TABLES
10 S101 FOUNDATION & SUMP PUMP LID PLANS
11 S401 STANDARD DETAILS
12 S501 DETAILS
13 M000T MECHANICAL REFERENCE SHEET
14 MD101T MECHANICAL DEMOLITION PLAN
15 M101T SITE MECHANICAL PIPING PLAN
16 M102T HYDRONIC PIPING PLAN
17 M301T SECTIONS/ELEVATIONS
18 M302T SECTIONS/ELEVATIONS
19 M303T SECTIONS/ELEVATIONS
20 M401T ENLARGED HYDRONIC PLANS
21 M501T MECHANICAL SCHEDULES
22 M601T DETAILS
23 M701T SEQUENCE OF OPERATION
24 M801T CONTROL DIAGRAMS AND POINTS LISTS
25 M802T CONTROL DIAGRAMS AND POINTS LISTS
26 M803T PIPING AND INSTRUMENTATION DIAGRAM (PID)
27 M901T HYDRONIC RISER DIAGRAMS
28 PD101T PLUMBING DEMOLITION PLAN
29 P101T PLUMBING PLANS
30 E-001T GENERAL ELECTRICAL NOTES & SYMBOLS
31 ED-100T ELECTRICAL DEMOLITION PLAN - COOLING TOWERS
32 EP-100T ELECTRICAL POWER PLANS - COOLING TOWERS
33 E-100T ELECTRICAL PANEL SCHEDULES & ONE-LINE
34 E-102T ELECTRICAL RISER DIAGRAMS
35 E-501T ELECTRICAL DETAILS
N
T
H S
T R
E E
T
N
T
H S
T R
E E
T
VICINITY MAP
NO SCALE
R
O A
D
WHITE AVENUE
MAIN
OURAY AVENUE
GRAND AVENUE
GUNNISON AVENUE
E MAIN
N
T
H S
T R
E E
T
VA WESTERN
COLORADO
HEALTH CARE
SYSTEM
N
T
H S
T R
E E
T
NORTH AVENUE
ELM AVENUE
N
R
D S
T R
E E
T
N
T
H S
T R
E E
T
GRAND VALLEY CANAL
ORCHARD AVENUE
F RD
N
T
H S
T R
E E
T N
T
H S
T R
E E
T
N
T
H S
T R
E E
T
Associate Director
Safety Officer
Chief of Staff
Information Security Officer
Associate Director of Patient Care Services
Chief, Police Service
Chief, Facilities Management
Infection Prevention Officer
Medical Center Director
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOURFOURFOURFOURFRONTFRONTFRONTFRONT
D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:CONSULTANTS:CONSULTANTS:CONSULTANTS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
575-16-104Replace Boiler Plant Cooling Towers
2226.M08
/1
/2
:5
:5
P
M
2/14/2019
COVER
G000T
1JBMK
Grand Junction, CO
CCCCOOOONNNNSSSSTTTTRRRRUUUUCCCCTTTTIIIIOOOONNNN DDDDOOOOCCCCUUUUMMMMEEEENNNNTTTTSSSS
REPLACE BOILER PLANT COOLING TOWERS
VA WESTERN COLORADO HEALTH CARE SYSTEM
2121 NORTH AVENUE
GRAND JUNCTION , CO 81501
PROJECT NO. 575-16-104
1" = 100'-0"G000T
3 VA CAMPUS - T
Albertson Engineering Inc.
3202 W. MAIN, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
605.343.9606
0 50' 100' 200'
SCALE :1" = 100'
T
DN
A A
C C
BB
Chiller Room
Water Entrance
Boiler Room
Office
Electrical
Generator
50' - 6"
58' - 4"
155' - 3" < 200'115' - 10" < 200'
2"
72"
36"
2"
36"
1"
Occ: #
Room Name
Path of travel (feet)
Egress route (# of occupants)
1-HR separation required
Fire wall
Exit occupancy load
Required egress width (inches)
Actual egress width (inches)
Direction of travel
Room number
Occupant load
Life Safety Plan Legend:
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOURFOURFOURFOURFRONTFRONTFRONTFRONT
D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:CONSULTANTS:CONSULTANTS:CONSULTANTS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
575-16-104Replace Boiler Plant Cooling Towers
2226.M08
/1
/2
:5
:0
P
M
2/14/2019
LIFE SAFETY PLAN
G100T
2JSJS
Grand Junction, CO
CCCCOOOONNNNSSSSTTTTRRRRUUUUCCCCTTTTIIIIOOOONNNN DDDDOOOOCCCCUUUUMMMMEEEENNNNTTTTSSSS
3/32" = 1'-0"G100T
1 Overall-Life Safety Plan
Occupancy Tabulation Per 2006 IBC Table 1004.12
R m
N o
N a m e
Room Occupancy A re a
S .F
P e r
P e rs o n
P e rs o n s
Level
1 Chiller Room Accessory Storage Areas, Mechanical Equipment Room 2934 SF 300 10 Level 1
2 Generator Accessory Storage Areas, Mechanical Equipment Room 344 SF 300 2 Level 1
3 Electrical Accessory Storage Areas, Mechanical Equipment Room 252 SF 300 1 Level 1
4 Office Business Areas 105 SF 100 2 Level 1
5 Boiler Room Accessory Storage Areas, Mechanical Equipment Room 2603 SF 300 9 Level 1
6 Water Entrance Accessory Storage Areas, Mechanical Equipment Room 233 SF 300 1 Level 1
Level 1 25
G
EN
ER
ATO
R
EN
C
LO
SU
R E
T
E
E
SMOKE STACK
D
D
D
S
S
T
T
REMOVE THIS SECTION OF EXISTING CHAIN
LINK FENCE DURING CONSTRUCTION ONLY.
FENCE TO BE REINSTALLED IN SAME
LOCATION FOLLOWING CONSTRUCTION.
Office of
Construction and Facilities
Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of
Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e i g h t i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t i n c h o n e f o o t o n e h a l f i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t t h r e e i n c h e s o n e f o o t
575-16-104
2/14/2019
Replace Boiler Plant
Cooling Towers
LB/AWDJ
GRAND JUNCTION, CO
ENGINEER
100% Design Submittal
AFFORDABLY CREATIVE
ENGINEERING SERVICES, INC.
324 Saint Joseph Street, Suite 200, Rapid City, SD 57701
(605) 545-1120 * Fax (605) 716-1144 www.proacesinc.com
DEMOLITON PLAN
CD101
HORIZ. SCALE: 1"=10'
10 5 0 10
LEGEND:
REMOVE AND DISPOSE CONCRETE SIDEWALK - 402 SF
REMOVE CHAIN LINK FENCE - 45 LF
(DISPOSE 43 LF, SALVAGE 2'± - SEE SHEET CS101)
T
ELECTRIC LINE (FIELD LOCATED)
WATER LINE (FIELD LOCATED)
GAS LINE (FIELD LOCATED)
FIBER OPTIC/COMMUNICATIONS LINE (FIELD LOCATED)
SANITARY SEWER MANHOLE (VA BASE FILES)
STORM WATER MANHOLE (VA BASE FILES)
WATER LINE (VA BASE FILES)
CHAIN LINK FENCE LINE (VA BASE FILES)
GAS LINE (VA BASE FILES)
STORM SEWER LINE (VA BASE FILES)
SANITARY SEWER LINE (VA BASE FILES)
EXISTING CONCRETE SIDEWALK
TRANSFORMER
F0
E
G
W
D
S
EXISTING LEGEND:
EXISTING STRUCTURAL CONCRETE
PAD TO REMAIN
REMOVE AND SALVAGE EXISTING FENCE AS
NOTED THIS SHEET - 36 LF
NOTES:
1. DO NOT DISTURB ADJACENT STRUCTURE OR UNDERGROUND UTILITIES
DURING CONSTRUCTION.
EXACT ELECTRICAL LINES ROUTING
TO/FROM ATS LOCATION IN BUILDING
AND GENERATOR ENCLOSURE, TO
BE VERIFIED BY CONTRACTOR.
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
Jay.Bauer Typewritten Text
Jay.Bauer Typewritten Text
SMOKE STACK
D
D
D
S
S
T
Office of
Construction and Facilities
Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of
Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e i g h t i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t i n c h o n e f o o t o n e h a l f i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t t h r e e i n c h e s o n e f o o t
575-16-104
2/14/2019
Replace Boiler Plant
Cooling Towers
LB/AWDJ
GRAND JUNCTION, CO
ENGINEER
100% Design Submittal
AFFORDABLY CREATIVE
ENGINEERING SERVICES, INC.
324 Saint Joseph Street, Suite 200, Rapid City, SD 57701
(605) 545-1120 * Fax (605) 716-1144 www.proacesinc.com
SITE PLAN
CS101
NOTES:
1. SIDEWALK ALONG WEST AND SOUTH EDGES OF EXISTING STRUCTURAL
CONCRETE PAD SHALL BE FLUSH WITH PAD THEN SLOPE AWAY FROM
THE CONCRETE PAD AT 2%.
LEGEND:
NEW SIDEWALK 4" THICKNESS - 490 SF
NEW 6 FT HEIGHT CHAIN LINK FENCE - 16 LF
SEE SHEET C-500.
(THREE(3) MANUAL SWING GATES IN LAYOUT)
T
ELECTRIC LINE (FIELD LOCATED)
WATER LINE (FIELD LOCATED)
GAS LINE (FIELD LOCATED)
FIBER OPTIC/COMMUNICATIONS LINE (FIELD LOCATED)
SANITARY SEWER MANHOLE (VA BASE FILES)
STORM WATER MANHOLE (VA BASE FILES)
WATER LINE (VA BASE FILES)
CHAIN LINK FENCE LINE (VA BASE FILES)
GAS LINE (VA BASE FILES)
STORM SEWER LINE (VA BASE FILES)
SANITARY SEWER LINE (VA BASE FILES)
EXISTING CONCRETE SIDEWALK
EXISTING STRUCTURAL CONCRETE PAD TO REMAIN
TRANSFORMER
F0
E
G
W
D
S
EXISTING LEGEND:
S l o p e
S l o p e
MANUAL
SWING GATE -
(3) TOTAL
PROTECT FIBER
OPTIC/COMMUNICATION
AND GAS LINES
DURING
CONSTRUCTION - SEE
STRUCTURAL SHEETS
FOR CAISSON
DETAILS
INSTALL SALVAGED CHAIN LINK FENCE
END NEW FENCE
ADJUST END POST LOCATION 2' TO
THE SOUTH TO ACCOMMODATE
NEW FENCE LOCATION
(INFILL WITH SALVAGED FENCE)
HORIZ. SCALE: 1"=10'
10 5 0 10
BOLLARD - SEE C-500 - DETAILS
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
Jay.Bauer Typewritten Text
Jay.Bauer
Office of
Construction and Facilities
Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of
Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e i g h t i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t i n c h o n e f o o t o n e h a l f i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t t h r e e i n c h e s o n e f o o t
575-16-104
2/14/2019
Replace Boiler Plant
Cooling Towers
LB/AWDJ
GRAND JUNCTION, CO
ENGINEER
100% Design Submittal
AFFORDABLY CREATIVE
ENGINEERING SERVICES, INC.
324 Saint Joseph Street, Suite 200, Rapid City, SD 57701
(605) 545-1120 * Fax (605) 716-1144 www.proacesinc.com
DETAILS
C-500
LOCKABLE MANUAL SWING
GATE WHERE SHOWN, SEE
PLANS FOR GATE LEAF
WIDTH
10"
DIA
6' HIGH CHAIN LINK FENCE
NTS
MANUAL SWING GATE DETAIL
NTS
1'-0"
DIA
T
O
T
E N
S I O
N
W I R
E
C
R O
W N
1'-0"
DIA
1'-0"
DIA
WIDTH AS
DESIGNATED
ON PLAN
M
A X
I M
U M
CAP, TYPICAL
4" O.D. END POST
OFFSET HINGES, TYPICAL
5" O.D. TERMINAL POST
3/8" TRUSS ROD
1.5" O.D. BRACE RAIL
CONCRETE FOOTING
1 5/8" O.D. TOP RAIL
CAP
STRETCHER BAR
1 5/8" O.D. POST BRACING
STRETCHER BAR BANDS
12" O.C.
5" O.D. TERMINAL POST
AT CORNER, ENDS AND
GATES
TURNBUCKLE
7 GAUGE TENSION WIRE
GALVANIZED COIL SPRING WIRE
W/ 9 GAUGE HOG RINGS AT 24"
O.C., TYPICAL
CONCRETE
FOOTING
3/8" DIA. TRUSS ROD
AT END SECTIONS
9 GA. 2" MESH
CHAIN LINK FABRIC
2 1/2" O.D. LINE POST
(10'-0" MAX SPACING)
CAP
11 GUAGE
WIRE TIES
SPACED
12" O.C., TYPICAL
NOTE:
POSTS SHALL HAVE EVEN SPACING. MINIMUM POST
SPACING 2'-0", MAXIMUM SPACING SHALL BE 8'-0".
NOTE:
GATE LOCKS TO BE PROVIDED AND
INSTALLED BY OWNER.
BOLLARD
NTS
1'-4"DIA
6" DIA. STANDARD
GALVANIZED STEEL
PIPE BOLLARD FILLED
WITH CONCRETE.
MOLD CONCRETE
CONVEX CROWN AT
TOP, TROWEL FINISH.
PAINT TOP AND STEEL
PIPE.
ASPHALT
EXPANSION JOINT
MATERIAL AND
SEALANT
BASE COURSE
SUBBASE
16" DIAMETER
CONCRETE ANCHOR
CHAIN LINK FENCE
X X
X X
X
6" CONCRETE FILLED
SCHEDULE 40 PIPE
BOLLARD. DOME
CONCRETE AT TOP OF
PIPE, TROWEL TO
CONDENSE SURFACE.
1'-0"
SECTION
PLAN
NOTE:
SEE CS101 - SITE PLAN
FOR BOLLARD LOCATIONS
Jay.Bauer Typewritten Text
Jay.Bauer
Level 1 100' - 0"
Level 2 115' - 0"
T.O. FOOTING
96' - 0"
PIT
94' - 0"
123 4
A101T
ACCESS PLATFORM
SUPPORT POST,
SEE DETAIL 4/A601T
CONCRETE PIER
SEE STRUCT.
ACCESS PLATFORM
AND RAILING SEE
DETAIL 4/A601T
ACCESS STAIR
A601T
A A
A101T
A101T
A101T
12' - 10"
A601T
GUARDRAIL, SEE DETAIL 2/A601T
A A
A101T
A101T
A101T
INSULATED MECHANICAL CURB
SEE DETAIL 1/A601T
PROVIDE LIFTING LUGS
FOR CRANE REMOVAL
AND RE-INSTALLATION
Level 1 100' - 0"
Level 2 115' - 0"
T.O. FOOTING
96' - 0"
PIT
94' - 0"
A
A101T
A101T
4' - 1"
PIT LADDER
PIT STAIR
BEYOND
COOLING TOWER
ACCESS STAIR
CONC. PIER
GUARDRAIL
A601T
A601T
5A601T
Level 1 100' - 0"
Level 2 115' - 0"
T.O. FOOTING
96' - 0"
PIT
94' - 0"
A101T
PIT ACCESS
STAIR
PIT LADDER
GUARDRAIL, SEE
DETAIL 2/A601T
REMOVABLE INSULATED CAP
INSULATED CURB
A601T
A601T
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOURFOURFOURFOURFRONTFRONTFRONTFRONT
D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:CONSULTANTS:CONSULTANTS:CONSULTANTS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
575-16-104Replace Boiler Plant Cooling Towers
2226.M08
/1
/2
:5
:4
P
M
2/14/2019
LADDER/PLATORM
PLANS/SECTIONS
A101T
6JBChecker
Grand Junction, CO
CCCCOOOONNNNSSSSTTTTRRRRUUUUCCCCTTTTIIIIOOOONNNN DDDDOOOOCCCCUUUUMMMMEEEENNNNTTTTSSSS
1/4" = 1'-0"A101T
6 PLATFORM/LADDER ELEVATION
1/4" = 1'-0"A101T
2 EQUIPMENT ACCESS PLATFOR/LADDER PLAN
1/4" = 1'-0"A101T
1 PARTIAL ROOF PLAN
1/4" = 1'-0"A101T
4 PIT ACCESS STAIR AND LADDER
1/4" = 1'-0"A101T
5 PIT ACCESS STAIR AND LADDER
NOT TO SCALEA101T
3 OPENING IN METAL DECK
MANUFACTURED ALTERNATING TREAD
DEVICE. ALL COMPONENTS OF DEVICE
SHALL BE PROVIDED AS A COMPLETE
ASSEMBLY, INCLUDING BUT NOT LIMITED
TO COLUMN, TREADS, STRINGERS,
HANDRAILS, GUARDRAILS, HARDWARE
AND LANDING. SEE SPECIFICATIONS
FOR MATERIALS AND ASSEMBLY.
Level 1 100' - 0"
Level 2 115' - 0"
MANUFACTURED ALTERNATING
TREAD DEVICE. ALL COMPONENTS
OF DEVICE SHALL BE PROVIDED AS
A COMPLETE ASSEMBLY, INCLUDING
BUT NOT LIMITED TO COLUMN,
TREADS, TRINGERS, HANDRAILS,
HARDWARE AND LANDING. SEE
SPECIFICATIONS FOR FOR
MATERIALS AND ASSEMBLY
REQUIREMENTS.
SINGLE PRE-ENGINEERED STEEL
COLUMN (BY ALTERNATING
TREAD MANUF)
18" X 18" X 3/4" STL BASE PLATE W/
(4) 3/4" DIA THREAED ROD ANCHORS
DRILL & SET W/ HILTI HIT-HY 200
EPOXY (EMBED 16") ATOP 2"
NON-SHRINK GROUT. 1/4" FILLET
WELD AROUND BASE OF COLUMN
NEW CONCRETE PIER, SEE STRUCT.
PRE-ENGINEERED STEEL COLUMN
AND PLATFORM CONNECTION
(BY ALTERNATING TREAD MANUF)
6' - 10"
Level 1 100' - 0"
Level 2 115' - 0"
MANUFACTURED ALTERNATING TREAD
DEVICE. ALL COMPONENTS OF DEVICE
SHALL BE PROVIDED AS A COMPLETE
ASSEMBLY, INCLUDING BUT NOT LIMITED
TO COLUMN, TREADS, STRINGERS,
HANDRAILS, GUARDRAILS, HARDWARE
AND LANDING. SEE SPECIFICATIONS
FOR MATERIALS AND ASSEMBLY.
PIT
94' - 0"
5/8" X 4" BENT PLATE
1 1/4"W X 1 1/2"H TEXTURED
TRACTION LADDER RUNGS,
TYPICAL
1" X 3" TUBE STEEL,
TYPICAL
T Y
P
V
IF
NOTE: ALL COMPONENTS
OF THE PIT LADDER SHALL
BE FABRICATED OUT OF
ALUMINUM AND BE MECHANICALLY
FASTENED WITH ALUMINUM
FASTENERS. THE LADDER WILL
CONINUOUSLY BE SUBMERGED IN
THE PIT.
Level 1 100' - 0"
MANUFACTURED ALTERNATING
TREAD DEVICE. ALL COMPONENTS
OF DEVICE SHALL BE PROVIDED AS
A COMPLETE ASSEMBLY, INCLUDING
BUT NOT LIMITED TO TREADS,
TRINGERS, HANDRAILS,
HARDWARE AND LANDING. SEE
SPECIFICATIONS FOR FOR
MATERIALS AND ASSEMBLY
REQUIREMENTS.
3' - 2"
1 1/2" STEEL PIPE
RAILING, PRIME
AND PAINT IN FIELD
4" X 4" X 1/4" BASE
PLATE AT UPRIGHTS.
ANCHOR TO CONCRETE
W/ (2) 1/2" STAINLESS STEEL
EXPANSION BOLT
Level 1 100' - 0"
MANUFACTURED ALTERNATING TREAD
DEVICE. ALL COMPONENTS OF DEVICE
SHALL BE PROVIDED AS A COMPLETE
ASSEMBLY, INCLUDING BUT NOT LIMITED
TO COLUMN, TREADS, STRINGERS,
HANDRAILS, GUARDRAILS, HARDWARE
AND LANDING. SEE SPECIFICATIONS
FOR MATERIALS AND ASSEMBLY.
EXISTING ROOF SYSTEM:
EXISTING EPDM ADHERED
MEMBRANE ROOFING.
EXISTING INSULATION.
EXISTING METAL DECK.
EXISTING METAL JOISTS.
TREATED WOOD BLOCKING
16 GA. 3 5/8" METAL
STUDS, 16" O.C.
FULL BATT INSULATION
VAPOR RETARDER
5/8" TYPE "X" MOISTURE
RESISTANT GYP. BD.
PERIMETER ANGLE,
SEE DETAIL 3/A1.01T
J-METAL TRIM
HOT AIR WELD
ADHERED MEMBRANE FLASHING
1/2" FIRE TREATED,
EXTERIOR RATED PLYWOOD
TERMINATION BAR
CONTINUOUS METAL FLASHING
SEALANT
REMOVABLE FASTENER, 16" O.C.
1 1/2" HSS FRAME &
INTERMEDIATES, 24" O.C. MAX.
1 1/2" METAL DECK
4" RIGID INSULATION
1/2" TREATED PLYWOOD FASTEN
TO DECK THROUGH INSULATION
18 GA. GALVANIZED STEEL CAP, CROSS BREAK FOR DRAINAGE
M
IN
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOURFOURFOURFOURFRONTFRONTFRONTFRONT
D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:ARCHITECT/ENGINEERS:CONSULTANTS:CONSULTANTS:CONSULTANTS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
575-16-104Replace Boiler Plant Cooling Towers
2226.M08
/1
/2
:5
:5
P
M
2/14/2019
ROOF CURB AND
LADDER/PLATFORM
DETAILS
A601T
7AuthorChecker
Grand Junction, CO
CCCCOOOONNNNSSSSTTTTRRRRUUUUCCCCTTTTIIIIOOOONNNN DDDDOOOOCCCCUUUUMMMMEEEENNNNTTTTSSSS
1/2" = 1'-0"A601T
3 TOWER ACCESS STAIR - PLAN VIEW
1/2" = 1'-0"A601T
4 TOWER ACCESS STAIR - SIDE ELEVATION
1/2" = 1'-0"A601T
5 TOWER ACCESS STAIR - FRONT ELEVATION
1/2" = 1'-0"A601T
7 PIT LADDER - FRONT ELEVATION
1/2" = 1'-0"A601T
6 PIT STAIR AND LADDER - SIDE ELEVATION
1" = 1'-0"A601T
2 GUARDRAIL DETAIL
1/2" = 1'-0"A601T
8 PIT STAIR - FRONT ELEVATION
NOT TO SCALEA601T
1 ROOF CURB DETAIL
ABBREVIATIONS
-AT
-AND
-ANCHOR BOLT
AB
-ALTERNATE
-ARCHITECTURAL
-BASEMENT
-BEAM
ALT
BSMT
BM
-BLOCK
-BOND BEAM
BLK
BD BM
-BUILDING
-CANTILEVER
-CLEAR
BLDG
CANT
CLR
-COMPOSITE
-CONCRETE
-CONCRETE MASONRY UNIT
-CONNECTION
COMP
CONC
CMU
CONN
-BOTTOMBOT
BRG -BEARING
-DEAD LOAD
-DEGREE
D BRG
DL
-DIAMETER
-DIMENSION
-DRAWING'S
-EACH
DIM
DWG'S
EA
-EACH FACE
-EACH WAY
-EAST
-ELECTRICAL
-ELEVATION
E F E W E
ELEC
EL
-ELEVATOR
-EQUAL
-EXTERIOR
-FINISHED FLOOR
ELEV
EQ
EXP JT
EXT
F FLR
-DECK BEARING
-EXPANSION JOINT
-DOWELDWL
-ADDITIONALADD'L
-CENTER LINECL
ARCH
-COLUMNCOL
-CONSTRUCTIONCONST
-CONTROL JOINT
-CONTINUOUSCONT
-CONTRACTORCONTR
-DETAILDET
-FOOTFT
-FOOTINGFTG
-FOUNDATIONFDN
-GALVANIZEDGALV
-GAUGEGA
-GENERAL CONTRACTORG C
-GLUED LAMINATED LUMBERGLU-LAM
-HIGH POINT
-HOOK
HS
HP
HK
-INCH
-INSULATION
-JOINT
-JOIST
IN
INSUL
JNT
JST
-JOIST BEARING
-KIPS (1,000 LBS. = 1 KIP)
-LIGHT WEIGHT
-LINTEL
-LIVE LOAD
JST BRG
k
L W
LTL
L L
-LONG LEG HORIZONTAL
-LONG LEG VERTICAL
-MASONRY OPENING
LLH
LLV
MAS
M O
-HEADED STUD
-MASONRY
-INTERIORINT
-HORIZONTALHORIZ
-MAXIMUMMAX
-MECHANICALMECH
-MICRO LAMINATED LUMBERML
-MINIMUMMIN
-MISCELLANEOUSMISC
-NORTHN
-NOMINAL
-NOT TO SCALE
NEC
NOM
NTS
-ON CENTER
-OPENING
-PER
-PLANK
OC
OPNG
PLK
-PLATE
-POST TENSION
-POUND
-POUNDS PER SQUARE FOOT
-POUNDS PER SQUARE INCH
P
PT
PSF
PSI
-PRECAST
-REINFORCE
-REVERSE
-ROOF DRAIN
P/C
REINF
REQ'D
REV
RD
-NECESSARY
-REQUIRED
-OPPOSITEOPP
-NUMBER#
-SCHEDULESCHED
-SECTIONSEC
-SHEETSHT
-SIMILARSIM
-CENTER TO CENTERCC
-HOLLOW CORE PLANKH/C
-MOMENTM
LVL -LAMINATED VENEER LUMBER
-SOUTHS
-SQUARESQ
-STEEL
-TEMPERATURE
STD
STL
TEMP
-TONGUE AND GROOVE
-TOP AND BOTTOM
-TOP OF PIER
-TOP OF STEEL
T&G T&B
TOP
TOS
-TYPICAL
-UNLESS NOTED OTHERWISE
-VERTICAL
-WELDED WIRE FABRIC
-WEST
TYP
UNO
VERT
WWF
W
-STANDARD
-TOP OF FOOTINGTOFTG
-THROUGHTHRU
-SPECIFICATIONSPEC
-TOP OF BEAMTOB
-TOP OF CONCRETETOC
(E) -EXISTING
-ROUGH SAWNRS
-DEMOLITIONDEMO
-NOT IN CONTRACTNIC
-TOP OF MASONRYTOM
-FIELD VERIFYFV
-GYPSUM BOARDGYP BD
-BOARDBD
-AMERICAN PLYWOODAPA
ASSOCIATION
-CHANNELC
-CAST IN PLACECIP
CONTR J
GT -GIRDER TRUSS
-HOLLOW STRUCTURAL SECTIONHSS
-MANUFACTURERMANF
-OVER HEADOH
-POWDER ACTUATED FASTENERPAF
-PLYWOODPW
-RADIUSR
-TOP OF WALLTOW
-STRUCT ENGINEER OF RECORDSER
-STAINLESS STEELSS
-WITH
-WOOD
W/
WD
-PLUS OR MINUS±
-TRANSVERSETRANS
BIT -BITUMINOUS
-BLOCKINGBLKG
-LONGITUDINALLONGIT
-DRILLED PIERD P
MAT'S -MATERIALS
MM/DD/YY
E
NI
G N
ON
A L
G N. O
R E
A
T O
H KAD
E
RP
RR
E
D
G I S
T E
S O
U
R E
T
E
SS IEFO
FRIED
LUCAS G.
13166
Albertson Engineering Inc.
3202 W. MAIN, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
605.343.9606
517 7th street rapid city sd 57701 p 605.342.9470 f 605.342.2377 www.4front.biz
FOUR FRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg. of
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
Department of
Veterans Affairs
1 2 3 4 5 6 7 8 9 10
F
E
D
C
B
A o n e e ig h t in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h t in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
/1
/2
:1
:0
A
M
AEI #: 2017-449
02/14/2019
STRUCTURAL GENERAL
NOTES
S001
Replace Boiler Plant Cooling Towers
KNRLGF
GRAND JUNCTION, CO
ENGINEER
CONSRUCTION DOCUMENTS
02/14/2019
GENERAL NOTES:
1. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB
SPECIFICATIONS AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND
SITE DRAWINGS. CONSULT THESE DRAWINGS FOR SLEEVES, DEPRESSIONS AND
OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS.
2. ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. ANY
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE VA PROJECT
ENGINEER OF RECORD BEFORE PROCEEDING WITH THE AFFECTED PART OF THE
WORK.
3. THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE
BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO
DETERMINE ERECTION PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE
BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION
OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING (AND ACCOMPANYING
FOOTINGS), GUYS OR TIE-DOWNS.
4. ADDITIONAL OBSERVATIONS AS A RESULT OF REJECTION OF WORK COMPLETED
AND/OR ADDITIONAL OBSERVATIONS DUE TO THE DEFICIENCIES IN WORK OBSERVED
WILL BE AT THE EXPENSE OF THE CONTRACTOR.
5. ALL STRUCTURAL SHOP DRAWINGS TO BE REVIEWED BY JOB SUPERINTENDENT IN
ADDITION TO ALL PERSONNEL DEEMED NECESSARY BY CONTRACTOR PRIOR TO
SUBMITTAL TO ENGINEER OF RECORD FOR APPROVAL.
6. ALL SHOP DRAWINGS TO BE REVIEWED BY ENGINEER OF RECORD SHALL HAVE
ELECTRONIC COPIES PROVIDED TO ENGINEER OF RECORD FOR REVIEW. AN
ELECTRONIC MARKED SET OF THOSE DRAWINGS WILL BE RETURNED TO THE
CONTRACTOR. NO ADDITIONAL HARD COPIES OF THE SHOP DRAWINGS NEED TO BE
PROVIDED TO THE ENGINEER OF RECORD, ALTHOUGH OTHER PARTIES MAY REQUIRE
HARD COPIES OF THE MARKED UP DRAWINGS. THESE REQUIREMENTS ARE IN
ADDITION TO THE TYPICAL PROJECT SHOP DRAWING SUBMITTAL REQUIREMENTS
STATED IN THE PROJECT SPECIFICATIONS.
7. THE DESIGN OF THE STRUCTURE SHOWN IN THESE CONSTRUCTION DOCUMENTS IS
FOR THE ONE-TIME USE AT THE SPECIFIC SITE REFERENCED IN THESE
CONSTRUCTION DOCUMENTS.
DESIGN CODES:
• 2018 INTERNATIONAL BUILDING CODE.
• ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND
COMMENTARY.
• ACI 350 CODE REQUIREMENTS FOR ENVIRONMENTAL ENGINEERING CONCRETE
STRUCTURES AND COMMENTARY.
• AISC 360-10 SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS.
• H-18-8 SEISMIC DESIGN REQUIREMENTS.
DESIGN LOADS:
THE STRUCTURAL SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED WITH THE
FOLLOWING SUPERIMPOSED LOADINGS:
FLOOR:
LIVE LOAD 50 PSF
MECH. EQUIPMENT 20 PSF
WIND:
BASIC WIND SPEED 115 MPH (ULTIMATE)
EXPOSURE CATEGORY C
IMPORTANCE FACTOR 1.0
SEISMIC:
RISK CATEGORY II
SEISMIC DESIGN CATEGORY B
SITE CLASSIFICATION D
SEISMIC IMPORTANCE FACTOR 1.0
MAPPED SPECTRAL RESPONSE COEFFICIENTS
Ss = 0.233g S1 = 0.069g
FOUNDATIONS:
1. SEE THE FOLLOWING REPORT FOR COMPLETE GEOTECHNICAL RECOMMENDATIONS
AND INSTALLATION PROCEDURES. SITE PREPARATION AND FOUNDATION SHALL
COMPLY WITH THE FOLLOWING:
PREPARED BY: HUDDLESTON-BERRY ENGINEERING & TESTING, LLC
TITLE: GEOTECHNICAL INVESTIGATION
NEW COOLING TOWER
VA HOSPITAL AND MEDICAL CENTER
GRAND JUNCTION, COLORADO
PROJECT # 01878-0001
DATE: JANUARY 10, 2019
TITLE: ALTERNATIVE FOUNDATION RECOMMENDATIONS
NEW COOLING TOWER
VA HOSPITAL AND MEDICAL CENTER
GRAND JUNCTION, COLORADO
PROJECT #01878-0001
DATE: JANUARY 24, 2019
2. GEOTECHNICAL RECOMMENDATIONS WERE PREPARED WITH SPECIFIC KNOWLEDGE
OF THE SPECIFIC BUILDING TYPE, CONSTRUCTION TYPE, AND LIKELY LOADS SHOWN
ON THE CONSTRUCTION DOCUMENTS. DETERMINING THE AMOUNT OF SETTLEMENT
ACCEPTABLE FOR THE BUILDING TYPE IS THE RESPONSIBILITY OF THE
GEOTECHNICAL ENGINEER. ALL STRUCTURAL DESIGNS WERE BASED UPON STAYING
WITHIN THE LIMITS GIVEN WITHIN THE GEOTECHNICAL REPORT FOR THE LOADS
PRESCRIBED BY THE BUILDING CODE REFERENCED IN THE DESIGN CODES SECTION
OF THESE STRUCTURAL NOTES.
3. DESIGNS BASED UPON AN ALLOWABLE BEARING CAPACITY OF 2,000 PSF. SEE
GEOTECHNICAL REPORTAND RECOMMENDATIONS FOR ALL REQUIREMENTS
RELATED TO THE CONSTRUCTION OF THE SLAB AND FOOTING ON GRANULAR
ENGINEERED FILL MATERIAL.
4. DESIGN OF DRILLED PIERS BASED UPON AN ALLOWABLE END BEARING CAPACITY OF
15,000 PSF. ALLOWABLE SKIN FRICKTION SHALL BE ASSUMED TO BE 0 PSF FOR THE
ENTIRE LENGTH OF THE PIERS. SEE GEOTECHNICAL REPORT, MEMO, AND
RECOMMENDATIONS FOR ALL REQUIREMENTS RELATED TO THE CONSTRUCTION OF
THE DRILLED PIERS.
PLUMBING SLEEVES:
MINIMUM SLEEVE SPACING SHALL BE TWO DIAMETERS CENTER TO CENTER TO THE
LARGER SLEEVE OR 6" CLEAR BETWEEN SLEEVES, WHICHEVER IS GREATER. PRIOR TO
CONSTRUCTION SLEEVE LOCATIONS AND SIZES SHALL BE APPROVED BY THE
STRUCTURAL ENGINEER OF RECORD.
CHEMICAL ANCHORS:
SHALL BE A POLYMER INJECTION SYSTEM SUCH AS "HILTI-HIGH STRENGTH EPOXY" OR
APPROVED EQUAL, INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
INSTRUCTIONS. INSTALLERS SHALL BE TRAINED BY THE MANUFACTURER'S
REPRESENTATIVE.
ANCHOR BOLTS:
1. SHALL BE A36 THREADED ROD. PROVIDE HOT DIP GALVANIZE FINISH ON ALL
ANCHOR BOLTS PERMANENTLY EXPOSED TO EXTERIOR OR IN CONTACT WITH
PRESSURE TREATED LUMBER.
2. THREADED ROD EMBEDMENT DEPTH SPECIFIED IN THE DRAWINGS SHALL BE FROM
TOP OF CONCRETE TO TOP OF DOUBLE NUT.
CONCRETE TESTING:
1. CONCRETE TESTING SHALL BE PAID FOR BY THE CONTRACTOR, AND RESULTS GIVEN
TO VA. TESTING LABORATORY SHALL PERFORM THE FOLLOWING TEST ON CAST-IN-
PLACE CONCRETE:
A. ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OF PORTLAND CEMENT
CONCRETE."
B. ASTM C39 - "STANDARD TEST METHOD FOR COMPRESSIVE STRENGTH OF
CYLINDRICAL CONCRETE SPECIMENS. A SEPARATE TEST SHALL BE CONDUCTED
FOR EACH CLASS, FOR EVERY 50 CUBIC YARDS (OR FRACTION THEREOF), PLACED
PER DAY. REQUIRED CYLINDER(S) QUANTITIES AND TEST AGE AS FOLLOWS:
a. AT 7 DAYS
b. AT 28 DAYS
C. PROVIDE ONE ADDITIONAL RESERVE CYLINDER TO BE TESTED UNDER THE
DIRECTION OF THE ENGINEER OF RECORD, IF REQUIRED. IF 28 DAY STRENGTH IS
ACHIEVED, THE ADDITIONAL CYLINDER(S) MAY BE DISCARDED.
PENETRATIONS:
NO PENETRATIONS SHALL BE MADE IN ANY STRUCTURAL MEMBERS OTHER THAN THOSE
LOCATED ON THESE DRAWINGS WITHOUT PREVIOUS APPROVAL OF THE ENGINEER OF
RECORD.
CONCRETE MIX DESIGN:
1. SHALL BE MIX DESIGNED BY A RECOGNIZED TESTING LABORATORY TO ACHIEVE A
STRENGTH AT 28 DAYS AS LISTED BELOW WITH A PLASTIC AND WORKABLE MIX:
1. 4,000 PSI - ALL CONCRETE
2. SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELD CYLINDER OR LAB TESTS FOR
REVIEW PRIOR TO USE. MIX SHALL BE UNIQUELY IDENTIFIED BY MIX NUMBER OR OTHER
POSITIVE IDENTIFICATION. CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS
OF ASTM STANDARD C94 FOR MEASURING, MIXING, TRANSPORTING, ETC. CONCRETE
TICKETS SHALL BE TIME STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME
ALLOWED FROM THE TIME THE MIXING WATER IS ADDED UNTIL IT IS DEPOSITED IN ITS
FINAL POSITION SHALL NOT EXCEED ONE AND ONE HALF (1-1/2) HOURS. IF FOR ANY
REASON THERE IS A LONGER DELAY THAN STATED ABOVE, THE CONCRETE SHALL BE
DISCARDED AT THE CONTRACTORS EXPENSE. IT SHALL BE THE RESPONSIBILITY OF THE
TESTING LAB TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF
ANY NONCOMPLIANCE WITH THE ABOVE. ALL SLABS SHALL BE CURED USING CURING
COMPOUND MEETING ASTM STANDARD C309 TYPE 1 AND SHALL HAVE A FUGITIVE DYE.
THE COMPOUND SHALL BE PLACED AS SOON AS THE FINISHING IS COMPLETED OR AS
SOON AS THE WATER HAS LEFT THE UNFINISHED CONCRETE. ALL SCUFFED OR
BROKEN AREAS IN THE CURING MEMBRANE SHALL BE RECOATED DAILY. CALCIUM
CHLORIDES SHALL NOT BE UTILIZED; OTHER ADMIXTURES MAY BE USED ONLY WITH THE
APPROVAL OF THE ENGINEER.
3. CONCRETE SHALL UTILIZE TYPE I/II CEMENT.
4. COARSE AND FINE AGGREGATES SHALL COMPLY WITH ASTM C33 AND ACI 302.1,
CURRENT VERSIONS.
a. COMPLIANCE WITH THE NON-REACTIVE REQUIREMENTS OF ACI 302.1 SHALL NOT BE
PROVIDED FOR BY THE PROVISION OF ACI 302.1 (SUBSECTION 7.3) THAT EXCLUDES
THE AGGREGATES BEING CLASSIFIED AS DELETERIOUSLY REACTIVE WITH ALKALIES
IF THE AGGREGATE HAS A SATISFACTORY SERVICE RECORD EVALUATION OR WITH
THE ADDITION OF A MATERIAL THAT HAS SHOWN TO PREVENT HARMFUL EXPANSION
DUE TO ALKALI-AGGREGATE REACTION.
b. CONCRETE MIX DESIGN SHALL INCLUDE TEST RECORDS OF THE COMPLIANCE OF
THE AGGREGATE MEETING THE REQUIREMENTS OF ASTM C1260, AND THAT THE
EXPANSION OF THE MORTAR SAMPLE SHALL NOT EXCEED 0.10% WHEN TESTED IN
ACCORDANCE WITH ASTM C1260 AT 14 DAYS. USE OF ADMIXTURES THAT MITIGATE
THE EFFECT OF THE REACTIVE AGGREGATE TO BE PROPOSED IN CONCRETE MIX
SHOP DRAWING MAY BE AN APPROVED APPROACH BY THE ENGINEER OF RECORD
TO ALLOW FOR THE USE OF OTHERWISE REACTIVE AGGREGATES. IF SUCH
MITIGATING MEASURES ARE PROPOSED, THEY MUST BE INCLUDED WITHIN MIX
DESIGN SUBMITTAL. THE ENGINEER OF RECORD IS GIVEN DISCRETION AS TO
WHETHER OR NOT TO ACCEPT MITIGATING MEASURES OR TO MAINTAIN
REQUIREMENTS THAT NONREACTIVE AGGREGATES MUST BE USED. AT A MINIMUM,
SUCH DOCUMENTATION MUST SHOW THAT REACTIVE AGGREGATES USED IN
COMBINATION WITH A GIVEN AMOUNT OF ADMIXTURE RESULTS IN THE EXPANSION
OF THE MORTAR SAMPLE BEING LESS THAN 0.10% WHEN TESTED IN ACCORDANCE
WITH ASTM C1567 AT 14 DAYS. LIABILITY OF THE PERFORMANCE OF THE CONCRETE
MIX REMAINS SOLELY WITH GENERAL CONTRACTOR.
c. IF CONCRETE MIXES ARE APPROVED BY THE ENGINEER OF RECORD THAT CONTAIN
EITHER FINE OR COARSE AGGREGATE, THAT EITHER SEPARATELY OR IN
COMBINATION EXCEED THE 0.10% EXPANSION WHEN TESTED ACCORDING TO ASTM
C1260, SPECIAL CONSIDERATIONS MUST BE GIVEN TO SLAB CURING (SLABS ON
GRADE AND ELEVATED SLABS). IN SUCH INSTANCES SLABS SHALL BE CURED USING
EITHER A WET BURLAP OR CONTINUOUS WETTING/FOGGING METHOD FOR SLABS
FOR AT LEAST 10 DAYS. USE OF CURING AND/OR SEALING COMPOUNDS IS NOT
ACCEPTABLE UNTIL THE SLAB HAS CURED A MINIMUM OF 28 DAYS AND THE
CONDITIONS FOR THE APPLICATION OF THE CURING COMPOUND ON THE CONCRETE
SLAB SET BY THE MANUFACTURER’S RECOMMENDATIONS HAVE BEEN MET.
d. VA PROJECT ENGINEER OF RECORD HAS SOLE DISCRETION IN DETERMINING
ACCEPTABILITY OF A CONCRETE SLAB THAT IS EXHIBITING ALKALI-SILICA REACTION.
FOR SLABS SHOWING AN ALKALI SILICA REACTION SOLELY WITHIN THE FINE
AGGREGATE: A SLAB SHOWING AN AVERAGE DENSITY OF POPOUTS GREATER THAN
1 PER 8 SQUARE FEET OVER ANY CONTIGUOUS AREA OF 100 SQUARE FEET OR
LARGER, OR ANY AREA WITH A DENSITY OF 1 POPOUTS PER 2 SQUARE FEET WITHIN
ANY AREA UP TO 100 SQUARE FEET WOULD BE CONSIDERED AS A BASIS FOR THE
REJECTION OF THE SLAB FROM WHICH THOSE SAMPLE AREAS ARE INCLUDED. FOR
A ALKALI SILICA REACTION WITHIN THE COARSE AGGREGATE: THE POPOUT
DENSITIES CONSIDERED FOR REJECTION OF THE CONCRETE SLAB SHALL BE ½ OF
THE DENSITIES GIVEN FOR FINE AGGREGATE. THE EXTENT OF REJECTED SLAB TO
BE DETERMINED BY ENGINEER. THE TIME FRAME FOR OBSERVATION OF ALKALI
SILICA REACTIONS AND DETERMINATION OF REJECTION OF THE CONCRETE SLAB
SHALL BE AT LEAST 56 DAYS FROM THE DATE OF POUR.
e. CONCRETE MIXES UTILIZING CRUSHED LIMESTONE AS COARSE AGGREGATE AND
CONTAINING AT LEAST 25% CLASS F FLY ASH AND HAVING A SATISFACTORY
SERVICE RECORD PER ACI 302.1 IS CONSIDERED AN ACCEPTABLE ALTERNATIVE
APPROACH TO THE COMPLIANCE REQUIREMENTS OUTLINED IN PROVISIONS 4a THROUGH 4d ABOVE.
5. THE CONCRETE STRENGTHS SHOWN IN THE SECTION ABOVE AND IN THE
SPECIFICATIONS ARE MINIMUM COMPRESSIVE STRENGTHS. THE ENGINEER OF RECORD
SHALL DETERMINE IF THE CONCRETE IS ACCEPTABLE, OR TO BE REMOVED, OR TO
RECEIVE SPECIAL CURING IF THE COMPRESSIVE STRENGTHS ARE LESS THAN
SPECIFIED.
6. ALL CONCRETE EXPOSED TO WEATHER OR EARTH SHALL BE AIR ENTRAINED TO 5%
TO 7%.
7. WATER REDUCING AGENTS MAY BE USED IF THE CONCRETE MIX. PLASTICIZERS AND
SUPER-PLASTICIZERS MAY BE USED ONLY WHEN WRITTEN PERMISSION OF THE
ENGINEER IS GIVEN.
8. NO SALTS OF ANY KIND MAY BE USED IN CONCRETE BEFORE OBTAINING THE
ENGINEER'S WRITTEN PERMISSION FOR THEIR USE.
9. AIR CONTENT OF TROWEL FINISHED FLOOR SLABS SHALL NOT EXCEED 3%.
10. MAXIMUM WATER TO CEMENTITIOUS MATERIAL FOR ALL CONCRETE SHALL NOT
EXCEED 0.45 UNLESS NOTED OTHERWISE.
11. ALL CONCRETE USED FOR CONSTRUCTION OF POOL, TANKS, OR TANK LIDS SHALL HAVE
WATERPROOF ADMIXTURE XYPEX C-1000 OR APPROVED EQUAL.
12. CONCRETE USED FOR THE SUMP PIT WALLS TO HAVE A MAXIMUM WATER CEMENT
RATIO OF 0.40.
FORMWORK AND SHORING:
NO STRUCTURAL CONCRETE SHALL BE STRIPPED UNTIL IT HAS REACHED AT LEAST TWO-
THIRDS OF THE 28 DAY DESIGN STRENGTH. DESIGN, ERECTION AND REMOVAL OF ALL
FORMWORK, SHORES AND RESHORES SHALL MEET THE REQUIREMENTS SET FORTH IN
ACI STANDARDS 301 AND 347.
STRUCTURAL STEEL:
1. STEEL SHALL CONFORM TO ASTM A992 (Fy=50 KSI) FOR ALL W-SHAPES, AND ASTM A36 (Fy=36 KSI) FOR ALL OTHER MISCELLANEOUS SHAPES AND PLATES.
STRUCTURAL TUBING SHALL CONFORM TO ASTM A500, GRADE B (Fy=46 KSI).
STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, GRADE B, TYPE "E" OR "S" (Fy=35
KSI).
2. STEEL SHALL CONFORM TO THE LATEST EDITION OF AISC SPECIFICATIONS FOR
STRUCTURAL STEEL BUILDINGS.
3. ALL SHOP CONNECTIONS TO BE WELDED (UTILIZING E70XX ELECTRODES) AND FIELD
CONNECTIONS TO BE BOLTED, UNLESS OTHERWISE NOTED. STEEL TO RECEIVE ONE
SHOP COAT AND ONE FIELD TOUCH UP COAT OF APPROVED PAINT, EXCEPT WHERE
GALVANIZED IS INDICATED ON THE DRAWINGS.
4. WELDS FOR ALL EXPOSED STRUCTURAL STEEL SHALL BE GROUND SMOOTH UNLESS
NOTED OTHERWISE.
5. ALL BOLTED CONNECTIONS SHALL CONSIST OF 3/4" DIA. (MIN.) ASTM A325 HIGH
STRENGTH BOLTS, UNLESS NOTED OTHERWISE. BEAM CONNECTIONS SHALL BE
DESIGNED BY THE FABRICATOR TO SUPPORT AN END REACTION OF Wc/2L KIPS IN
ACCORDANCE WITH PART 2 - "BEAM AND GIRDER DESIGN" OF THE MANUAL OF STEEL
CONSTRUCTION (9th EDITION), BUT CONNECTIONS SHALL NOT HAVE LESS THAN 2
ROWS OF BOLTS. SEE ALSO DOUBLE ANGLE AND SHEAR TAB CONNECTION
SCHEDULE(S) WHERE APPLICABLE.
6. CONTRACTOR SHALL MAINTAIN ERECTION TOLERANCES OF STRUCTURAL STEEL AND
ARCHITECTURALLY EXPOSED STRUCTURAL STEEL WITHIN AISC'S CODE OF
STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES.
7. ANCHOR BOLT HOLES IN STRUCTURAL STEEL SHALL BE OVERSIZED NO MORE THAN
1/8" MAX, UNLESS NOTED OTHERWISE.
SHEAR STUD CONNECTORS:
1. SHEAR STUD CONNECTORS SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE
WITH AWS D1.1, "STRUCTURAL WELDING CODE", SECTION 7 - STUD WELDING. STUDS
SHALL BE TYPE "B", HEADED STUDS, HAVING A MINIMUM TENSILE STRENGTH OF 60,000
PSI, AND SHALL BE OF LENGTH AND DIAMETER SHOWN ON THE DRAWINGS.
SPECIAL INSPECTION AND TESTING:
1. SEE DETAILED INSPECTION AND TESTING REQUIREMENTS AS INDICATED ON SHEET
S002.
CONCRETE AND REINFORCING PLACEMENT:
1. ALL CONCRETE SHALL BE PLACED IN ACCORDANCE WITH ACI 301 AND ACI 117
EXCEPT AS MODIFIED BELOW:
A. ACI 117 ITEM 4.3.1.1 ELEVATIONS OF SLABS-ON-GRADE TOP OF SLAB ELEVATION
SHALL BE WITHIN A 3/8" ENVELOPE EITHER SIDE OF THE THEORETICAL DESIGN
SURFACE.
B. ACI 117 ITEM 4.5.7 FLOOR FINISH TOLERANCES AS MEASURED BY PLACING A
FREESTANDING (UNLEVELED) 10 FT. STRAIGHTEDGE ANYWHERE ON THE SLAB
AND ALLOWING IT TO REST UPON TWO HIGH SPOTS WITHIN 28 DAYS AFTER
SLAB CONCRETE PLACEMENT. THE GAP AT ANY POINT BETWEEN THE
STRAIGHT EDGE AND THE FLOOR SHALL NOT EXCEED 1/4".
2. ALL REINFORCING STEEL TO BE ASTM A615, GRADE 60 (#4 AND LARGER), EXCEPT
WHERE NOTED OTHERWISE. REINFORCING SHALL NOT BE WELDED.
3. WELDED WIRE FABRIC TO CONFORM TO ASTM A185 AND SHALL BE FREE FROM OIL,
SCALE, AND RUST. PLACE WWF IN ACCORDANCE WITH THE TYPICAL PLACING
DETAILS OF ACI STANDARDS AND THE SPECIFICATIONS. MINIMUM LAPS SHALL BE
ONE SPACE PLUS 2".
4. ALL REINFORCING STEEL BARS TO BE DETAILED AND PLACED IN ACCORDANCE
WITH THE LATEST ACI MANUALS.
5. LAP ALL REINFORCING SPLICES IN CONCRETE A MINIMUM OF 48 BAR DIAMETERS
OR 24 INCHES, WHICHEVER IS GREATER, UNLESS NOTED OTHERWISE ON
DRAWINGS (CLASS B SPLICE).
6. PROVIDE CORNER BARS OF SAME BAR DIAMETER AS SPECIFIED FOR THE WALL,
BEAM OR FOOTING. PROVIDE MINIMUM OF 40 BAR DIAMETER LAP FOR ALL CORNER
BARS, UNLESS NOTE OTHERWISE.
7. PROVIDE FOUNDATION DOWELS AS SHOWN. MINIMUM SIZE DOWELS TO BE #4,
UNLESS OTHERWISE NOTED. ALL VERTICAL REINFORCING STEEL IN COLUMNS AND
PIERS, OR VERTICAL REINFORCING IN WALLS, SHALL BE DOWELED INTO THE
FOOTINGS WITH SAME SIZE AND QUANTITY DOWEL AS THE VERTICAL
REINFORCING.
8. WHERE SHOWN ON THE DRAWINGS, PROVIDE WELD PLATES, WELDMENTS, OR
CONCRETE INSERTS FOR FASTENING AND SECURING OTHER COMPONENTS.
CONCRETE INSERTS SHALL BE FURNISHED BY THE CONTRACTOR REQUIRING
THEM AND INSTALLED BY THE CONTRACTOR CASTING THE CONCRETE AROUND
THEM. CLIP ANGLES SHALL BE FURNISHED BY THE CONTRACTOR REQUIRING
THEM.
9. REINFORCING STEEL SHALL RECEIVE CONCRETE COVER AS FOLLOWS:
DESCRIPTION MINIMUM COVER
CAST AGAINST & PERMANENTLY 3"
EXPOSED TO EARTH
EXPOSED TO EARTH OR WEATHER
#6 THROUGH #18 BARS 2"
#5 BARS OR SMALLER 1 1/2"
NOT EXPOSED TO EARTH OR WEATHER
OR IN CONTACT WITH THE GROUND, SLABS
AND WALLS
#11 BARS OR SMALLER 3/4"
#14 AND #18 1 1/2"
BEAMS AND COLUMNS 1 1/2"
SHELLS, FOLDED PLATE MEMBERS:
NO. 6 BAR AND LARGER 3/4"
NO. 5 BAR, W31 OR D31 WIRE AND SMALLER 1/2"
10. PROVIDE TWO (2) #5'S, ONE AT EACH FACE, UNLESS NOTED OTHERWISE, AROUND
ALL OPENINGS GREATER THAN 12"x12" IN CAST-IN-PLACE CONCRETE. EXTEND
REINFORCING 2'-0" BEYOND OPENING IN BOTH DIRECTIONS. CONTACT ENGINEER
OF RECORD FOR ALL OPENINGS GREATER THAN 12"x12" FOR DESIGN.
11. COLD WEATHER AND HOT WEATHER PROVISIONS OF ACI 306 AND 305 (CURRENT
EDITIONS), RESPECTIVELY, SHALL BE MAINTAINED.
12. UNLESS NOTED OTHERWISE ALL UNDER SLAB VAPOR RETARDERS SHALL
CONFORM TO THE REQUIREMENTS OF ASTM 1745 CLASS A AND SHALL BE
INSTALLED AS PER MANUFACTURER'S RECOMMENDATIONS.
13. CONTRACTOR IS RESPONSIBLE FOR ESTIMATING CONCRETE QUANTITIES ON
ELEVATED SLABS AND SHALL ACCOUNT FOR DEFLECTIONS IN THE FLOOR
STRUCTURE.
14. CONTRACTOR SHALL MAINTAIN A CONSTANT THICKNESS OVER THE ENTIRE
ELEVATED SLAB. ELEVATED SLAB THICKNESS SHALL NOT BE 3/8" GREATER THAN
OR 1/4" LESS THAN THE SPECIFIED THICKNESS.
15. LASER SCREED OR OTHER SIMILARLY FUNCTIONING EQUIPMENT SHALL NOT BE
PERMITTED FOR ELEVATED SLABS UNLESS AUTHORIZED BY ENGINEER OF
RECORD.
GENERAL NOTES
Jay.Bauer Typewritten Text
Jay.Bauer
IBC 2018 TABLE 1705.3 REQUIRED SPECIAL INSPECTION
AND TEST OF CONCRETE CONSTRUCTION
NO
4. INSPECTION OF ANCHORS POST-INSTALLED IN HARDENED CONCRETE
MEMBERS.
10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.
A. APPLICATION OF PRESTRESSING FORCES.
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND
TECHNIQUES.
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE.
7. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER
APPLICATION TECHNIQUES
ACI 318: CH. 26.9
ACI 318: 26.10
ACI 318: 26.5.3-26.5.5
ACI 318: 26.5
ASTM C 172, ASTM C 31,
ACI 318: 26.5, 26.12
ACI 318: 17.8.2.4,
ACI 318: 17.8.2
X
X
X
X
X
X
X
ACI 318: 26.11.2
1908.9
1908.6, 1908.7, 1908.8
1908.10
YES
YES
YES
NO
NO
3. INSPECTION OF ANCHORS CAST IN CONCRETE.
2. REINFORCING BAR WELDING:
1. INSPECTION REINFORCEMENT, INCLUDING PRESTRESSING
TENDONS, AND VERIFY PLACEMENT
TYPE
ACI 318 CH 20, 25.2,
25.3, 26.6.1-26.6.3
REFERENCED
STANDARD
CONTINUOUS
SPECIAL
INSPECTION
PERIODIC
SPECIAL
INSPECTION
X
AWS D1.4,
ACI 318: 26.6.4
IBC REFERENCE
1908.4 YES
YES
NO
REQD ON
PROJECT
X
ACI 318: 17.8.2
5. VERIFYING USE OF REQUIRED DESIGN MIX. ACI 318: CH. 19,
26.4.3, 26.4.4
X
1904.1, 1904.2, 1908.2, 1908.3 YES
12. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS
OF THE CONCRETE MEMBER BEING FORMED. ACI 318: 26.11.1.2(b)X YES
NO
9. INSPECT OF PRESTRESSED CONCRETE:
B. GROUTING OF BONDED PRESTRESSING TENDONS.
11. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF
TENDONS IN POST-TENSIONED CONCRETE & PRIOR TO REMOVAL OF
SHORES & FORMS FROM BEAMS & STRUCTURAL SLABS.
XA. CERIFFY WELDABILITY OF REINFORCING BARS OTHER THAN
ASTM A706.
X
B. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16".
C. INSPECT ALL OTHER WELDS
A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR
UPWARDLLY INCLINED ORIENTATIONS TO RESIST SUSTAINED
TENSION LOADS.
B. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT
DEFINED IN 4A.
X
X
X
YES
a. WHERE APPLICABLE, SEE SECTION 1705.12, SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE.
b. SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSEUD BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 IN ACI 318, OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL PRIOR TO THE COMMENCEMENT OF THE WORK.
WELDING OR REINFORCING BARS.
SPECIAL INSPECTIONS OF WELDING AND QUALIFICATIONS OF SPECIAL INSPECTORS FOR REINFORCING BARS SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF AWS D1.4 FOR
SPECIAL INSPECTION AND AWS D1.4 FOR SPECIAL INSPECTOR QUALIFICATION.
MATERIAL TESTS.
IN THE ABSENCE OF SUFFICIENT DATA OR DOCUMENTATION PROVIDING EVIDENCE OF CONFORMANCE TO QUALITY STANDARDS FOR MATERIALS IN CHAPTERS 19 AND 20 OF ACI 318, THE BUILDING OFFICIAL SHALL REQUIRE TESTING OF MATERIALS IN ACCORDANCE WITH THE APPROPRIATE SYANDARDS AND CRITERIA FOR THE MATERIAL IN CHAPTERS 19 AND 20 OF ACI 318.
TABLE N5.4-1
INSPECTION TASKS PRIOR TO WELDING
TABLE N5.4-2
INSPECTION TASKS DURING WELDING
AISC 360-10 TABLE N5.4-3
INSPECTION TASKS AFTER WELDING
AISC 360-10 TABLE N5.6-1
INSPECTION TASKS PRIOR TO BOLTING
AISC 360-10 TABLE N5.6-2
INSPECTION TASKS DURING BOLTING
AISC 360-10 TABLE N5.6-3
INSPECTION TASKS AFTER BOLTING
INSPECTION TASKS PRIOR TO WELDING
WELDER QUALIFICATION RECORDS AND CONTINUITY RECORDS
MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE
MATERIAL IDENTIFICATION (TYPE/GRADE)
WELDER IDENTIFICATION SYSTEM
FIT-UP OF CJP GROOVE WELDS OF HSS T-, Y- AND K-JOINTS WITHOUT BACKING
• JOINT PREPARATION
• DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)
• CLEANLINESS (CONDITION OF STEEL SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
CONFIGURATION AND FINISH OF ACCESS HOLES
FIT-UP OF FILLET WELDS
• DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
• CLEANLINESS (CONDITION OF STEEL SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
CHECK WELDING EQUIPMENT
INSPECTION
INTERVAL
REQUIRED ON
PROJECT
USE OF QUALIFIED WELDERS
CONTROL AND HANDLING OF WELDING CONSUMABLES
• PACKAGING
• EXPOSURE CONTROL
NO WELDING OVER CRACKED TACK WELDS
ENVIRONMENTAL CONDITIONS
• WIND SPEED WITHIN LIMITS
• PRECIPITATION AND TEMPERATURE
WPS FOLLOWED
• SETTINGS ON WELDING EQUIPMENT
• TRAVEL SPEED
• SELECTED WELDING MATERIALS
• SHIELDING GAS TYPE/FLOW RATE
• PREHEAT APPLIED
• INTERPASS TEMPERATURE MAINTAINED (MIN/MAX)
• PROPER POSITION (F, V, H, OH)
WELDING TECHNIQUES
• INTERPASS AND FINAL CLEANING
• EACH PASS WITHIN PROFILE LIMITATIONS
• EACH PASS MEETS QUALITY REQUIREMENTS
THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY WHICH A WELDER WHO HAS WELDED A JOINT OR
MEMBER CAN BE IDENTIFIED. STAMPS, IF USED, SHALL BE THE LOW-STRESS TYPE.
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
P
P
O
O
P
O
O
O
O
O
O
O
O
O
WELDS CLEANED
SIZE, LENGTH AND LOCATION OF WELDS
WELDS MEET VISUAL ACCEPTANCE CRITERIA:
• CRACK PROHIBITION
• WELD/BASE-METAL FUSION
• CRATER CROSS SECTION
• WELD PROFILES
• WELD SIZE
• UNDERCUT
• POROSITY
ARC STRIKES
k-AREA
BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED)
REPAIR ACTIVITIES
DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER
YES
YES
YES
YES
YES
YES
YES
YES
O
P
P
P
P
P
O
O
(a)WHEN WELDING OF DOUBLE PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN PERFORMED IN THE k-AREA, VISUALLY INSPECT THE WEB k-AREA FOR CRACKS WITHIN 3" (75 mm) OF THE WELD.
(b) AFTER ROLLED HEAVY SHAPES (SEE SECTION A3.1c) AND BUILT-UP HEAVY SHAPES (SEE SECTION A3.1d) ARE WELDED, VISUALLY INSPECT
THE WELD ACCESS HOLE FOR CRACKS.
INSPECTION TASKS PRIOR TO BOLTING
MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTENER MATERIALS
INSPECTION
INTERVAL
REQUIRED ON PROJECT
FASTENER ASSEMBLIES PLACED IN ALL HOLES AND
WASHERS AND NUTS ARE POSITIONED AS REQUIRED
YESO
O
O
O
O
P
O
O
O
O
O
DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS P
FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS
CORRECT FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT
LENGTH IF THREADS ARE TO EXCLUDED FROM SHEAR PLANE)
CORRECT BOLTING PROCEDURE SELECTED FOR JOINT DETAIL
CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE CONDITION AND
HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE REQUIREMENTS
PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION PERSONNEL
OBSERVED AND DOCUMENTED FOR FASTENER ASSEMBLIES AND METHODS USED
PRTECTED STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS AND OTHER
FASTENER COMPONENTS
JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THE PRETENSIONING
OPERATION
FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM
ROTATING
FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RCSC SPECIFICATION,
PROGRESSING SYSTEMATICALLY FROM THE MOST RIGID POINT TOWARD THE FREE
EDGES
• O-OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS.
P-PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER.
• OBSERVATION OF WELDING OPERATIONS AND VISUAL INSPECTION OF IN-PROCESS AND COMPLETED WELDS SHALL BE THE PRIMARY METHOD TO CONFIRM THAT THE MATERIALS, PROCEDURES AND WORKMANSHIP ARE IN CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
• FOR STRUCTURES IN RISK CATEGORY III/IV (ASCE/SEI 7, TABLE 1.5-1), ULTRASONIC TESTING SHALL BE PERFORMED ON ALL COMPLETE-JOINT- PENETRATION GROOVE WELDS SUBJECT TO TRANSVERSELY APPLIED TENSION LOADING IN BUTT, T- AND CORNER JOINTS, IN MATERIALS 5/16" (8 MM)
THICK OR GREATER.
• FOR STRUCTURES IN RISK CATEGORY II (ASCE/SEI 7, TABLE 1.5-1), ULTRASONIC TESTING SHALL BE PERFORMED ON 10% OF COMPLETE-JOINT- PENETRATION GROOVE WELDS SUBJECT TO TRANSVERSELY APPLIED TENSION LOADING IN BUTT, T- AND CORNER JOINTS, IN MATERIALS 5/16" (8 MM)
THICK OR GREATER.
• ALL NONDESTRUCTIVE TESTING OF WELDED JOINTS SHALL BE DOCUMENTED.
• SEE AISC360-16 CHAPTER N FOR ADDITIONAL WELD INSPECTION REQUIREMENTS.
• SEE AISC360-16 CHAPTER N FOR ADDITIONAL BOLT INSPECTION REQUIREMENTS.
• EXPOSED CUT SURFACES OF GALVANIZED STRUCTURAL STEEL MAIN MEMBERS AND EXPOSED CORNERS OF RECTANGULAR HSS SHALL BE VISUALLY
INSPECTED FOR CRACKS SUBSEQUENT TO GALVANIZING.
• INSPECTION SHALL OCCUR DURING THE PLACEMENT OF ANCHOR RODS AND OTHER EMBEDMENTS SUPPORTING STRUCTURAL STEEL FOR COMPLIANCE WITH THE CONSTRUCTION DOCUMENTS, INCLUDING DIAMETER, GRADE, TYPE AND LENGTH OF THE ANCHOR ROD OR EMBEDDED ITEM, AND THE EXTENT OR DEPTH OF EMBEDMENT INTO THE CONCRETE.
• FABRICATED STEEL AND ERECTED STEEL FRAMES, AS APPROPRIATE, SHALL BE INSPECTED FOR COMPLIANCE WITH THE DETAILS SHOWN ON THE CONSTRUCTION DOCUMENTS, INCLUDING BRACES, STIFFENERS, MEMBER LOCATIONS AND PROPER JOINT DETAIL APPLICATION.
INSPECTION TASKS DURING BOLTING INSPECTION INTERVAL
REQUIRED ON THIS
PROJECT
INSPECTION TASKS AFTER BOLTING INSPECTION INTERVAL REQUIRED ON PROJECT
INSPECTION TASKS DURING WELDING INSPECTION INTERVAL
REQUIRED ON
THIS PROJECT
INSPECTION TASKS AFTER WELDING INSPECTION INTERVAL REQUIRED ON PROJECT
STEEL CONSTRUCTION
WELDING PROCEDURE SPECIFICATIONS (WPSs) AVAILABLE YESP
FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY)
• JOINT PREPARATION
• DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)
• CLEANLINESS (CONDITION OF STEEL SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
YESO
PLACEMENT AND INSTALLATION OF STEEL HEADED STUD ANCHORS YESP
NO PROHIBITED WELDS HAVE BEEN ADDED WITHOUT THE APPROVAL OF THE EOR YESO
WELD ACCESS HOLES IN ROLLED HEAVY SHAPES AND BUILT-UP HEAVY SHAPES(b) YESP
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
IBC 2018 TABLE 1705.6 REQUIRED
VERIFICATION AND INSPECTION OF SOILS
VERIFICATION AND INSPECTION TASKS
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE
ADEQUATE TO ACHIEVE THE DESIGN BEARING CAPACITY.
CONTINUOUS SPECIAL
INSPECTION
PERIODICALLY SPECIAL
INSPECTION
X
X
X
X
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH
AND HAVE REACHED PROPER MATERIAL.
3. PERFORM CLASSIFICATION AND TESTING OF
COMPACTED FILL MATERIALS.
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT
THICKNESSES DURING PLACEMENT AND COMPACTION OF
COMPACTED FILL.
REQUIRED
ON PROJECT
YES
YES
YES
YES
YES
FREQUENCY OF INSPECTION
X
PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE
AND VARIFY THAT SITE HAS BEEN PREPARED PROPERLY.
SPECIAL INSPECTION AND TESTING:
1. SPECIAL INSPECTION AND MINIMUM TESTING SHALL BE PERFORMED IN ACCORDANCE WITH 2018 IBC AND ALL REFERENCED MATERIALS AND TABLES.
2. INSPECTION SHALL BE PROVIDED BY AN INDEPENDENT TESTING AGENCY HIRED AT THE CONTRACTOR'S EXPENSE. AGENCY INSPECTION PERSONNEL SHALL MEET THE INSPECTOR
QUALIFICATIONS FOR EACH MATERIAL ITEM AS INDICATED IN THE SPECIFICATIONS.
3. ANY MATERIAL OR PLACEMENT DEVIATIONS FROM MINIMUMS SHOWN ON THE DRAWINGS OR IN SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER OF RECORD.
4. IN ADDITION TO THE IBC INSPECTION TABLES, THE INSPECTOR SHALL VERIFY THAT ALL STEEL MAINTAIN ERECTION TOLERANCE OF STRUCTURAL STEEL AND ARCHITECTURALLY EXPOSED STRUCTURAL STEEL WITHIN AISC'S CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES.
5. IN ADDITION TO THE CONCRETE AND MASONRY IBC INSPECTION TABLES, THE INSPECTOR SHALL VERIFY THAT ALL CONCRETE AND MASONRY MAINTAIN TOLERANCES SPECIFIED IN ACI 117-90
STANDARD SPECIFICATIONS FOR…
This is the start of the file's text. The full file is on GovTribe.