1. Question and Answer Document.docx
DOCX document 24 KB Posted
- Attached to
- J045--Replace Domestic Hot Water Skid
- Solicitation number
- 36C25726Q0544
About this file
This is a Question and Answer Document for VA solicitation 36C25726Q0544, addressing contractor inquiries regarding a domestic hot water skid replacement project at a VA medical campus. The project scope involves replacing three existing Spirax Sarco S9A-IG10-16 domestic hot water skids with new Spirax EasiHeat DHW package skids. Site access is restricted to the Engineering Canopy with crane placement limited to the medical helicopter pad and no dedicated project staging areas. The work is tax-exempt and classified as ICRA Class 2, requiring all on-site workers to complete OSHA safety training plus facility-specific safety and infection prevention training. No hazardous materials (asbestos, lead, or mold) are present in the work area.
Technical requirements include integrating the new skids with the VA's existing Andover Controls BAS system through the facility's preferred control contractor, Entech, with the awarded contractor responsible for hiring Entech for system programming and verification. Contractors must reuse existing electrical feeds, disconnects, and related infrastructure while adhering to AWWA standards for domestic water flushing, disinfection, bacteriological testing, and legionella procedures before placing each skid into service. Each skid must be individually commissioned and accepted before proceeding to the next unit. A two-week utility shutdown window is required to minimize patient care impact, with coordination through the Contracting Officer Representative and VA Maintenance and Operations. The one-year maintenance period begins after substantial completion and must follow the manufacturer's recommended maintenance plan. As-built drawings and existing equipment specifications have been provided to support contractor planning and submission development.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 3. Domestic Hot Water Flow Diagram.pdf | ||
| 36C25726Q0544 0001_1.docx | DOCX document | |
| 36C25726Q0544 0001.docx | DOCX document | |
| 2. Sign-In Sheet from Site Visit.pdf | ||
| Service Contract Act WD 2015-5253 Rev 29.pdf | ||
| 36C25726Q0544_1.docx | DOCX document | |
| RFQ - 36C25726Q0544.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Question and Answer Document 36C25726Q0544 - STX - Replace Domestic Hot Water Skid
1. What are the site access, staging, and crane placement limitations at the medical campus?
a. Answer: Access will be via Engineering Canopy, there will be no project specific staging areas, and the crane is limited to the medical helicopter pad near the site.
2. Is this project tax exempt?
a. Answer: Yes
3. Are there any known hazardous materials (asbestos, lead, mold) in the work area?
a. Answer: There are no hazardous asbestos, lead or mold related to replacing the hot water skids and pumps
4. Can the VA provide existing as-built drawings for the domestic hot water skids, piping, controls, and BAS integration points?
a. Answer: Please see the attached drawing 14_110_Domestic HW_Drawings_2015Apr21_MEP_4.pdf
5. Can the VA provide the complete manufacturer and model information for the existing skids?
a. Answer: Spirax Sarco S9A-IG10-16
6. Is the contractor required to use the VA's existing controls vendor for integration?
a. Answer: Yes. The Vendor is Entech
7. What Infection Control Risk Assessment (ICRA) classification will apply to this project?
a. Answer: This will be an IRCA Class 2
8. Who is the controls contractor at the facility?
a. Answer: VA M&O maintains the controls
9. Please confirm whether the scope is correctly described as domestic hot water skid replacement. The RFQ title uses STX - Replace Domestic Hot Water Skid, while the SOW heading says Replace Domestic Hot Work Skids.
a. Answer: A portion of this project is intended to replace three (3) domestic hot water skids type Spirax Sarco S9A-IG10-16
10. Please confirm whether VAAR 852.219-75 should be completed under Services, General Construction, or Special Trade Construction. The solicitation NAICS is 238220 and the work appears to be mechanical/special trade construction, but the Services box is checked in the certification.
a. Answer: It will be under Services
11. Please provide any available drawings, mechanical plans, equipment schedules, controls diagrams, shutdown diagrams, details, or specifications for the existing and replacement domestic hot water skid work.
a. Answer: Please see the attached Drawing 14_110_Domestic HW_Drawings_2015Apr21_MEP.pdf
12. Please identify any required basis-of-design manufacturer, approved equal criteria, submittal review criteria, or minimum feature requirements for the new domestic hot water package skids.
a. Answer: Spirax EasiHeat™ DHW
13. Please confirm required utility shutdown notice periods, allowable shutdown windows, VA coordination requirements, and whether written utility shutdown plans are required before work.
a. Answer: Shutdown period that will impact patient care 2 weeks, Coordination with the COR and VA M&O, Utility shutdown plans is required for energized work.
14. Please provide required BAS integration points, monitoring points, control points, graphics, alarms, trends, naming conventions, network requirements, and whether VA requires use of a specific Andover Controls vendor.
a. Answer: please get with the VA’s Current Vendor Entech
15. Please confirm whether the contractor must replace, modify, or reuse existing electrical feeds, disconnects, breakers, starters, VFDs, conduit, wiring, controls power, or motor controls for the new booster and return pumps and skid controls.
a. Answer: The Contractor will be allowed to reuse existing electrical feeds
16. Please clarify the required one-year maintenance scope, including visit frequency, emergency response requirements, included parts/consumables, reporting requirements, manufacturer maintenance plan requirements, and whether maintenance begins at substantial completion, final acceptance, or after commissioning.
a. Answer: Maintenance period will start after Substantial completion and must follow the manufacture’s recommended maintenance plan for the first year.
17. Please clarify whether each skid must be commissioned and accepted before moving to the next skid, or whether all three skids are commissioned only after final inspection. The SOW appears to contain both requirements.
18. Answer: Each Skid must be commissioned and accepted before moving to the next
19. skid.
20. Please confirm whether domestic water flushing, disinfection, bacteriological testing, temperature verification, legionella-related procedures, or water quality testing are required before placing each skid into service.
a. Answer: Please install equipment base on AWWA standards
21. Please identify the three entry points requiring 6 mil reinforced fire-retardant poly ICRA barriers and provide any project-specific ICRA permit, barrier, negative air, HEPA filtration, or infection control requirements.
a. Answer: The work area will not need ICRA barrier while working in the Pump Room.
22. Please confirm staging, loading dock, parking, elevator, crane/rigging access, after-hours access, material delivery procedures, and removal path for existing skids.
23. Answer: Access to the site is limited to the Engineering Canopy
24. Please clarify the 40-hour training requirement, including required attendees, class size, training schedule, curriculum, documentation, video/recording requirements, and whether training may be split between classroom and hands-on instruction.
a. Answer: All worker on site much have OSHA safety training. Also site specific safety and Infection prevention training must be done at the facility.
25. Will the VA's existing BAS contractor be involved in the integration, or is the awarded contractor solely responsible for all programming, integration, and verification with the Andover Controls system?
a. Answer: The contractor will be required to hire the VA’s preferred control contractor to connect the system into Andover Controls.