This is a Questions and Answers document for a Department of Veterans Affairs solicitation regarding Underground Storage Tank (UST) and Aboveground Storage Tank (AST) inspection, testing, and repair services. The document provides technical details about the existing tank infrastructure at the facility.
The facility has 12 underground storage tanks with varying piping configurations - USTs #6-14 use suction piping while USTs #15-17 use pressurized piping. Each tank has an overfill prevention valve set at 95% capacity and a spill bucket. There are 12 containment sumps total, with under-dispenser containments located at the gas station. The facility does not utilize interstitial monitoring but conducts monthly leak tests via an automatic tank gauging (ATG) system. No sumps currently have water issues, though water infiltration varies with weather conditions. Monthly inspections following SPCC EPA protocols are required for ASTs. A potential future tank (#18) is mentioned but specifications are not yet determined. Photos of the systems were not provided due to the 400lb weight of manhole covers.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Site Visit Sign In Sheet.pdf | ||
| S02 36C25725Q0236 0002.pdf | ||
| S02 36C25725Q0236.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Item number 0001
Q: How many lines are pressurized and how many are suction?
A: UST’s #6, #7, #8, #9, #10, #11, #12, #13, and #14 are suction piping. UST’s #15, #16, and #17 are pressurized piping.
Q: How many LLD’s?
A: Annual Line leak detector testing UST’s #17, #16, #15
Q: How many containment sumps?
A: 12
Q: How many transition or intermediate sumps?
A: None
Q: How many UDC sumps?
A: Under dispenser containments located at gas station
Q: How many Fill ports? Spill Buckets equipped on fill ports?
A: Every tank has a fill port.
Q: Are there any day tanks with probes and sensors connected to the ATG’s?
A: No
Q: Are there any sensors not contained in sumps or piping connected to the ATG’s?
A: No
Item Number 0002
Q: How many monitoring systems utilize Interstitial Monitoring?
A: Not utilized
Q: Monthly interstitial monitoring must be tested on all tanks/pipes – printouts or actual testing of all sensors?
A: Not utilized. We collect monthly leak test on all underground storage tanks, that the ATG automatically generates on the system.
Q: How many sumps have water issues?
A: None.
Q: What is the average gallons of water removed on a monthly basis?
A: Varies due to inclement weather.
Item Number 0003
Q: How many Overfill prevention valves per tank?
A: One per tank overfill prevention valves, delivery shut off set at 95% capacity.
Q: How many Spill buckets?
A: There are 12 underground storage tanks and each tank has a spill bucket.
Q: Are there any spill buckets inside the containment sump?
A: No
Q: Please define standing ground water.
A: Water that enter manhole cover a er it rains.
Q: Are monthly inspec ons being required on the AST’s? If so, are we following the SPCC EPA Monthly Inspec on?
A: Yes
Q: Can the inspec on report from March of 2022 for each tank be provided?
A: Reports are on hand.
Q: Can photos of AST be provided, as well as photos of access ports to UST?
A: Photos will not be provided since each manhole is about 400lbs and more than one person can handle on his own.
Q: Will future tank #18 be UST or AST and what liquid will it store?
A: Not sure. Have not received this informa on yet.