Question and Answer
36C25723Q0488 – Chiller Water Pump Replacement
1. The existing pumps do not have drain pans under the pump housing itself. Do the new pumps required a drain pan under the pump housing itself.
Answer: NO
2. Please confirm if new pump motors need to be rated for a VFD with shaft grounding ring or just on/off application?
Answer: On/off application
3. Please confirm if any pump discharge balancing valves are not to be replaced?
Answer: YES
4. Does the government want to add these services to the statement of work?
- Test and Balance NO
- Chemical flush NO
5. Were the HOA switches for the pumps?
Answer: They are located on the MCC panel.
6. Does the government want to replace HOA Switches?
Answer: NO
7. Please confirm all not asbestos is in the work area of the pumps.
Answer: No asbestos present
8. Can the contractor remove all three pumps at same time?
Answer: NO
9. Where is the HOA switch?
Answer: They are located on the MCC panel.
10. Do you want to replace HOA?
Answer: NO