Request For Information

1. Could you provide the electrical specs for the equipment? Voltage and amperage.

Electrical Requirements

M-Cabinet CXA 80 Supply Configuration: 3 phase, 3 wire power, neutral and ground. Wye.

or 3 phase, 3 wire power, ground. Delta.

Nominal Line Voltage: 400, 440, 460 or 480 VAC, 60 Hz Branch Power Requirement: 112.5 kVA minimum Circuit Breaker: 3 pole, 50 Amps (@ 480V) (Slow Blow) Residual Current Device to be installed depending on local regulations.