36C25619Q1485-0002001.docx

DOCX document 18 KB Posted

Attached to
Copy of Copy of 564-20-1-561-0004 Fire Alarm Inspection & Repair Services (VA-19-00088192)
Solicitation number
36C25619Q1485
Issued by

About this file

36C25619Q1485 0002 QA 09-18-2019 Answer .docx

View the file

Other files

File Type Posted
36C25620C0020-000.docx DOCX document
36C25619Q1485-0002000.docx DOCX document
36C25619Q1485-0002001.docx DOCX document
36C25619Q1485-0002000.docx DOCX document
36C25619Q1485-0001001.docx DOCX document
36C25619Q1485-0001000.docx DOCX document
36C25619Q1485-0001000.docx DOCX document
36C25619Q1485-0001001.docx DOCX document
36C25619Q1485-000.docx DOCX document
36C25619Q1485-000.docx DOCX document
36C25619Q1485-003.pdf PDF
36C25619Q1485-002.pdf PDF
36C25619Q1485-001.docx DOCX document
36C25619Q1485-003.pdf PDF
36C25619Q1485-002.pdf PDF
36C25619Q1485-001.docx DOCX document
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 According to TJC/VA/NFPA guidelines for electric fire pump NFPA 25-2017 section 8.3.1.2 has fire pump runs being performed Monthly and not weekly. Can you please confirm the frequency? Government response 1: Frequency must be weekly for all pumps.

2 Can you confirm that parts will be furnished by the VHSO as listed in the SOW Section Q.1? Government response 2: Yes. Parts as listed in the SOW Section II. Q.1. “All fire alarm replacement part(s) will be furnished by VHSO; however, Contractor must include labor to install the part(s).”

3 Can you confirm the estimated number of sprinkler gauges to be replaced under SOW Section Q.3? Government response 3: Please see SOW Section III, a. and b. including Device List.

4 How many kitchen hoods are to be tested? Government response 4: For Base Period and Option Years 1, 2, and 3 there are a total of 4 (4) kitchen hoods. For Option year 4 there are a total of six (6) kitchen hoods. Must be verified by Contractor. How many tanks? Government response 4: One tank per each kitchen hood.

5 According to TJC/VA/NFPA Guidelines for Fire Department Notification (NFPA 72-2016 Table 14.4.3.2 (4)) is only required to be inspected annually. Can you please verify the frequency? Government response 5: In accordance with SOW Section II.I.3.a) frequency must be Quarterly.

6 According to TJC/VA/NFPA Guidelines for Waterflows/Tamper (NFPA 72-2016 Table 14.4.3.2 (17)j)1)k) are only required to be inspected semi-annually. Can you please verify the frequency? Government response 6: In accordance with SOW Section II.J.3.a) frequency must be Quarterly.

7 Can you confirm that any improper installation, water damage of the fire alarm system in the parking garage will not be responsibility of the contractor? Government response 7: Contractor must be responsible for Building 18 “Parking Garage” fire alarm system; since, the fire alarm installation deficiencies have been corrected.

8 Is the cost of the elevator contractor coming out to provide access to elevator shaft/pit to be covered by the VA or contractor? Government response 8: VA shall engage a third party to furnish Contractor access to the elevator shaft/pit as required.

9 Can the contract billing be changed to 12 equal monthly payments? It will be base on your unit price in the RFQ.

10 Section II - Scope of Work; Letter J Water Based Systems - Question: Can you please provide a copy of the previous years inspection report so that our company can get essential information on sprinkler systems? The report is from another contractor and is not public knowledge.

Clarification questions:

Answer 6 - The SOW states to test IAW the current version of NFPA 72/25 and Joint Commission. As it relates to Tamper Switches and Waterflow Switches the current NFPA code/Joint Commission Standard states they are only to be tested Semi-Annually. There are a number of factors for code being changed a number of years ago. One of the main reason was that it has been found that introduction of fresh water is the primary cause of MIC which it was causes pipe corrosion. So testing more frequently is actually causing harm to the fire sprinkler system. It was also my understanding that if a VA wants to over test a system they need to get approval from the AHJ which is the VA Fire Protection Engineers from CEOSH. Can you confirm the frequency of inspections for the tampers/waterflows? Our answer for 6 remains the same “Government response 6: In accordance with SOW Section II.J.3.a) frequency must be Quarterly.” NOTE: Frequency is for inspections. Can you confirm that VA acknowledgement of the risk of additional flow switch testing? No; since, this is not applicable. Can the VA confirm the AHJ Approval of testing frequencies? No; since, this is not applicable.

Answer 7 - If the conduit & fire alarm system was compromised by water can VA confirm devices and wiring were replaced and system was blown out with compressor? Our answer for 7 remains the same “Government response 7: Contractor must be responsible for Building 18 “Parking Garage” fire alarm system; since, the fire alarm installation deficiencies have been corrected.” Water damage to devices can sometimes cause pre-mature device failure.

Answer 9 - So if our unit price was $12,000 we would invoice $1,000 monthly? If the total amount is $12,000 for a year, yes the $1,000 monthly is correct.